GENERAL NOTES
PANEL IS RESET.
CYCLES AS OUTLINED IN NFPA 720 5.8.6.5 DISTINCTIVE SIGNAL. THE EVACUATION SIGNAL TO CONTINUE UNTIL THE
BETWEEN TWO SETS OF MESSAGES AND BEFORE THE MESSAGES ARE REPEATED USE A TEMPORAL CODE TONE FOR THREE
EXIT." PROVIDE A 2 SECOND PAUSE "MAY I HAVE YOUR ATTENTION PLEASE..." (REPEAT THE MESSAGE).
HAS BEEN DETECTED IN THE BUILDING, WHILE THIS IS BEING VERIFIED. PLEASE LEAVE THE BUILDING BY THE NEAREST
IN A FEMALE VOICE "MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION PLEASE. CARBON MONOXIDE
PRIORITY OVER A CARBON MONOXIDE ALARM.
SHALL TAKE PRIORITY OVER SUPERVISORY AND TROUBLE SIGNALS. THE ACTIVATION OF THE FIRE ALARM SHALL TAKE
FIRE ALARM STROBES WITH A DISTINCTIVE VOICE MESSAGE LISTED BELOW. THE PRIORITY OF CARBON MONOXIDE ALARMS
AS CARBON MONOXIDE ALARM. CARBON MONOXIDE ALARM WILL INITIATE A BUILDING EVACUATION ALARM UTILIZING THE
11.UPON ACTIVATION OF A CARBON MONOXIDE DETECTOR THE FIRE ALARM SYSTEM SHALL TRANSMIT AN ALARM INDICATED
UNTIL THE PANEL IS RESET.
AS OUTLINED IN NFPA 72 18.4.2 & 18.4.2.1, DISTINCTIVE EVACUATION SIGNAL. THE EVACUATION SIGNAL TO CONTINUE
REPEATED TWICE AND BEFORE THE MESSAGES ARE REPEATED AGAIN USE A TEMPORAL CODE, THREE TONE FOR THREE CYCLES
"MAY I HAVE YOUR ATTENTION PLEASE..." (REPEAT THE MESSAGE). NOTE: AFTER THE VOICE FIRE ALARM MESSAGES ARE
BEEN REPORTED IN THE BUILDING. PLEASE LEAVE THE BUILDING BY THE NEAREST EXIT. PROVIDE A 2 SECOND PAUSE
THE FOLLOWING: "MAY I HAVE YOUR ATTENTION PLEASE. MAY I HAVE YOUR ATTENTION PLEASE. A FIRE EMERGENCY HAS
12.FIRE ALARM SYSTEM SHALL USE A VOICE EVACUATION MESSAGE. THE MESSAGE SHALL USE A FEMALE VOICE AND STATE
MXX
FXX
RED FIRE ALARM STROBE W/ CLEAR LENS. XX=CANDELA RATING FOR STROBES.
P
MXX
FIRE ALARM CONTROL PANEL
WHITE MASS NOTIFICATION STROBE WITH AMBER LENS. XX=CANDELA RATING FOR STROBES.
F
M
M
FAP
XCV
ATI
LOC
CEILING, WALL OR DUCT PHOTOELECTRIC SMOKE DETECTOR.
FIRE ALARM ANTENNA
MASS NOTIFICATION ANTENNA
SPRINKLER WATER FLOW SWITCH
W
DOC
FIRE ALARM / MASS NOT. PLAN
JUNCTION BOX COVERS, PULLING EL COVERS AND DEVICES SHALL BE RED IN COLOR.
6. FIRE ALARM CIRCUITS SHALL CONSIST OF 600 VOLT, COPPER, NPFLP CABLES INSTALLED IN 1/2" EMT.
5. NOTIFICATION APPLIANCE CIRCUITS SHALL BE STYLE Z AS DEFINED BY NFPA 72.
4. FLOW SWITCH ASSOCIATED WITH SPRINKLER SYSTEM SHALL BE CONNECTED TO BUILDING FIRE ALARM SYSTEM.
3. SYCHRONIZE ALL STROBES.
2. CONCEAL FIRE ALARM CIRCUITS INSIDE FINISHED WALLS AND ABOVE FINISHED CEILINGS WHERE PRACTICABLE.
WALL MOUNTED IN LOCATION INDICATED.
1. FOR CLARITY, SOME SYMBOLS WHICH COINCIDE WITH OTHER SYMBOLS ARE SHOWN AWAY FROM WALL BUT ARE ACTUALLY
W ALARM
WATER FLOW
CO
ALARM AND MNS. XX=CANDELA RATING FOR STROBES.
WHITE MASS NOTIFICATION STROBE WITH AMBER LENS AND 4" SPEAKER. SPEAKER USED FOR FIRE
TRANSCEIVER.
RADIO TRANSCEIVERS: FIRE ALARM TO BE MONACO TRANSCEIVER. MASS NOTIFICATION TO BE ATI
DEVICE.
ADA COMPLIANT, DUAL ACTION MANUAL FIRE ALARM PULL STATION. INSTALL AT 48" TO TOP OF
OPERATOR CONSOLE.
SAFEPATH SP4-LOC (OR APPROVED EQUAL) REMOTE MICROPHONE AND MASS NOTIFICATION LOCAL
COOPER WHEELOCK MASS NOTIFICATION CONTROL PANEL
GENERAL NOTES (CONTINUED)
CALCULATIONS FOR THE APPLIANCE USED.
10. THE MAXIMUM NUMBER OF NOTIFICATION APPLIANCES ON A CIRCUIT SHALL BE DETERMINED BASED ON
SHALL BE INSTALLED IN SEPARATE CONDUITS.
PLACE ALL INDICATING DEVICES ON ONE CIRCUIT OF THE ADDRESSABLE SYSTEM. NOTIFICATION APPLIANCE CIRCUITS
9. THE SIGNALING LINE CIRCUIT (SEE SHEET E2) IS SEPARATED INTO ZONES FOR CLARITY. THE CONTRACTOR MAY
SHALL BE RUN IN SEPARATE CONDUITS.
8. THE INSTALLATION SHALL COMPLY WITH NFPA 72 FOR A CLASS B ADDRESSABLE SYSTEM. ALL IDC AND NAC CIRCUITS
WITH THE SIGNAGE PLAN SHOWN ON THE ARCHITECTURAL SHEETS.
7. THE CONTRACTOR SHALL LABEL THE FIRE ALARM DEVICE ADDRESSES BY ROOM NUMBER AND/OR FUNCTION IN ACCORDANCE
K
168048
S C A L E I N F E E T
NORTH
LEGEND
X C
V X
C V
A T I
F A
P D
O C
F
MP
M15
F15
PP
P
P
P
M
F135M135
M
M135F135
M
M
M110 F110
M
M
M110 F110
M
M
M110 F110
M
M
LOC
LOC M34
F34
DOC
XCV
XCV
ATI
FAP
S C A L E I N F E E T
844 2
ENLARGED MECH. RM. LAYOUT
X C
V X
C V
A T I
F A
P D
O C
MECHANICAL ROOM LAYOUT
REFER TO ENLARGED
K
CONTRACT INSPECTION BRANCH.
AND TURN OVER TO DPW
(KNOX) BOX IN THIS ROOM
REMOVE EXISTING KEY ACCESS
SHOWN.
AND DOCUMENT CABINET ARE
ONLY PANELS, NEW KNOX BOX
M
SWITCHES.
EMERGENCY SERVICES. KNOX BOX SHALL BE MONITORED BY THE FIRE ALARM PANEL VIA TWO TAMPER
21. FIRE DEPARTMENT KEY ACCESS (KNOX) BOX SHALL BE MOUNTED AND KEYED PER FORT LEONARD WOOD
20. DUCT SMOKE DETECTOR SHALL BE FACTORY PROVIDED BY RTU MANUFACTURER.
EXIT DOORWAY OPENING.
19. ALL MANUAL FIRE ALARM PULL STATIONS ARE TO BE INSTALLED WITHIN 5 FEET FROM EDGE OF AN
WIRE NUTS IN FIRE PROTECTION, FIRE ALARM, AND MASS NOTIFICATION SYSTEMS IS PROHIBITED.
18. WIRING SHALL BE THHN OR TFFN STRANDED WITH CRIMP ON TERMINAL ENDS AFFIXED. THE USE OF
17. ALL AC AND DC POWER WIRING SHALL BE RUN IN SEPARATE 3/4" CONDUIT.
WITH ENGRAVED OR MACHINE PRINTED LABELS BY THE ZONE AND CIRCUIT THAT IT CONTAINS.
16. ALL JUNCTION, TERMINAL AND PULLING BOX COVERS SHALL BE PAINTED RED AND SHALL BE IDENTIFIED
15. ALL SYSTEM WIRING SHALL BE IN 3/4" OR LARGER EMT CONDUIT.
COMPLIANT INSTALLATION OF A FULLY FUNCTIONAL AND OPERATIONAL SYSTEM.
14. ALL INSTALLATION MATERIALS SHALL BE PROVIDED AS REQUIRED IN ORDER TO PROVIDE A CODE
EDITION), NFPA 720, (2015 EDITION) AND NFPA 72 (2016 EDITION).
13. PROVIDE FIRE ALARM EQUIPMENT AND INSTALLATION METHODS IN COMPLIANCE WITH NFPA 70 (2014
DETECTOR
DUCT SMOKE
CO
MASS NOTIFICATION 15 WATT HORN SPEAKER. EXTERIOR DEVICES SHALL BE WET LOCATION RATED.
AT 60" ABOVE STOOP.
EXTERIOR, WET LOCATION RATED RED WATER FLOW ALARM WITH HORN AND WHITE STROBE. INSTALL
AT 60" FROM STOOP TO TOP OF DEVICE.
FIRE ALARM FIRE DEPARTMENT KEY ACCESS (KNOX) BOX WITH DUAL TAMPER SWITCHES. INSTALL
THE FIRE DEPT.
INDICATION (SEE NOTES, THIS SHEET) TO RESULT IN BUILDING EVACUATION AND AN ALARM TO
PROVIDE IN ACCORDANCE WITH NFPA 720. ACTIVATION SHALL PRODUCE A UNIQUE VOICE AND VISUAL
CEILING MOUNTED CARBON MONOXIDE DETECTOR, LISTED FOR USE WITH PROVIDED FIRE ALARM PANEL.
PERMANENTLY SCREENED IN WHITE INK LETTERS 1" HIGH AND READING "FIRE ALARM DOCUMENTS".
WALL MOUNTED FIRE ALARM DOCUMENTS CABINET, 12" X 15" X 2-1/4" DEEP. CABINET SHALL BE
K
DETECTOR
DUCT SMOKE
A P
P R
D M
A D
E
D I
R E
C T
O R
A T
E
O F
U
B L I
R K
S
F O
R
L
O N
A
D
O
I
S S
O U
R I
D E
S C
R I
P T I
O N
R E
V I
S I
O N
S
D A
T E
G A
Y
B E
R
S
E D
B
A P
P R
O V
E D
D A
T E
S U
B M I
T T
E D
C H
E C
K E
D
D R
A W
N
D E
S I
G N
E D
C O
O R
D I
N A
T I
O N
D A
T E
D A
T E
D A
T E
SCALE
DATE
PROJECT NO:
DRAWING NO:
OFSHEET
AS SHOWN
C.0004125
DPW 02645-5J
E6
F
N T
R A
L
I
S S
U E
A D
D I
T I
N
B
I
L D I
N G
M A
T I
F I
C A
T I
A N
F I
A
A
G
G G
A R
G
G G
A R
E L
L
C8030.22
22 OCT 15