AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA
FAR (48 CFR) 53.243
NES 066 Fairbanks Satellite Operations Facility
a. The above numbered solicitation is hereby amended to provide additional Offeror Questions and Answ ers; update the Project Table of Contents; and update the Finishes Information. The specific changes are identif ied on Page 2, Summary of Changes.
b. The date for receipt of Proposals remains unchanged on 17 February 2009 at 4:00 PM Alaska Standard Time.
c. Point of Contact for this amendment is Michael Suprenant at 907-753-2555.
d. All other aspects of this solicitation remain unchanged.
1. CONTRACT ID CODE PAGE OF PAGES
1 6
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 06-Feb-2009
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W911KB-09-R-0006
X 9B. DATED (SEE ITEM 11)
23-Dec-2008
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning 1 copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
06-Feb-2009
CODE
U.S. ARMY ENGINEER DISTRICT, AK
CEPOA-CT (W911KB)
PO BOX 6898
ELMENDORF AFB AK 99506-0898
W911KB 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W911KB-09-R-0006
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
1. Additional Offeror Questions and Answers are listed below.
2. Revised Project Table of Contents; and Revised Finishes Information are attached.
(End of Summary of Changes)
Questions and Answers During Solicitation
Project: NES066
Q22. Sheet C4.02 notes that the new 8” fire protection water line is to be provided with a 2” recirculation line.
Sheet FP2.01 does not show a recirculation line and there is no requirement for a recirculation pump, although a pump will be necessary. To where does this recirculation line recirculate? Is the water being recirculated back into the existing 8” water line?
A22. Yes there will be a recirculation line on the fire water line. It will tie in to the recirculation line on the existing 8" line.
Q24. Sheet C5.04 shows no heat trace channel for the 2” recirculation pipe. Please confirm that no heat trace system is required for the 2” recirculation pipes and the 1-1/2” domestic water service. (Reference specification 33 61 14.00-2.6.)
A24. There is no heat trace in the recirculation line.
Q27. Hello Michael, when we talked on the phone I mentioned some products required for the project are discontinued. These products are all the Nora rubber flooring colors, and Daltile SN05, SN01. Another question I have is the accent colors. I need a diagram or a description as to how these colors are accents such as a border or placed every third tile, etc. to determine how much order.
A27. All Nora products are still available. We recommend referring to the Nora site for additional verification. The Daltile products required some substitutions by our interior designers...D317 (biscuit) replaces D317 (white), CP85 (mountain) replaces SN05 (silver smoke), and CP80 (beach) replaces SN01 (antique white).
Q30. Notice:
If you are using MasterFormat 2004 Edition, the proper section number to use is “Section 09 69 00, Access Flooring”, which appears below.
If you are continuing to use MasterFormat 1995 Edition, the proper section number to use is “Section 10270, Access Flooring”. Please change the section number below if required.
SECTION 09 69 00
ACCESS FLOORING
A30. Regardless of numbering preference, the information is available. Numbering will remain as is. Follow specification provided, unless amended. Refer to following Q/A instances for additional information regarding access flooring.
Q31. 1) SUBJECT: Floor Panels
DRAWING/SPEC: Section 09 69 13 DESCRIPTION: Per Section 096913. paragraph. 2.1.2.1 to 3 What type of floor panel is required?
Steel Panels?
Cement Filled Panels?
Wood Core Panels?
A31. Metal
Q32. 2) SUBJECT: Room Finish Schedule / Specifications
DRAWING/SPEC: A7.02/Sections 09 65 00 and Section 09 69 13
DESCRIPTION: Room finish schedule shown Rooms 112 to have EMI floor covering and Room 114 to have
RF1/RF2/RF3.
Section 09 69 13, 2.1.3, 2.1.3.1 - Room 112 and Room 114 is scheduled to have raised access flooring with anti-static Vinyl Composition Tile. Supplier’s option to provide 12” x 12” or 24” x 24” goods.
A32. Follow Room Finish Schedule regarding finishes. Please refer to Q27 (above) for additional finishes info. A revised Room Finish Schedule will be provided to reflect current materials.
Q33. In the Finish Schedule A7.01; Room 112, does this get the same finish as Rm114?
A33a. Please, follow what is indicated in the Room Finish Schedule.
In the Finish Schedule A7.01; Room 114, Please explain RF1/RF2/RF3. are there color zones in the floor? If so, what sqft of area gets what color? Can you provide a floor covering drawing? This has an impact on pricing.
A33b. The varying RF finishes are to create a patterning. An electronic file is to be provided with this response for reference, indicating patterning.
Q35. 1) There is a spec section for the Mobile Shelving Units (106810). However on the drawings Sheet A2.02 there is a note that states “NIC” for the “file storage system”. Please verify that this is one and the same and not in this contract.
A35. The Mobile Shelving Unit was intended to be provided in the furniture purchase. Follow drawings and disregard specification mention of the Mobile Shelving Units
Q36. 2) Sheet C5.02 has a detail for “Bollards”. However there are no bollards called out on the civil drawings.
Please verify that there are no bollards on the Civil.
A36. Follow Architectural plans/details regarding bollards.
Q37. In Division 10, section 10 68 10, Mobile Shelving Storage – Powered; I can tell by the drawing that the moveable unit should be about 16’ wide on a track about 36’ long but there is no indication as to how tall the unit should be, how many shelves you require per unit and the number of file supports you would like to have per shelf.
Will you please let me know these requirements?
A37. Refer to response to Q35 (above)
Q45. The published hardware specification does not support the requirements of an access control system (prox readers, mag contacts and electric strikes) as shown on drawings E4.01, E4.02, and E7.06.
Please provide the appropriate hardware schedule if these items are required.
A45. Revision to the hardware specifications and the door schedule (possibly) will have to be made to reflect the inclusion of electronic components. Electronic components will be required.
Q46-Q49. I’m having some issues getting answers to a less than complete spec for Div 9, Section 09 69 13, rigid grid access flooring.
1.) The finish schedule does not inform us of what is called out for floor finish for the access floor, for flooring type or color A46. (1). Flooring finish in this room is indicated within the Room Finish Schedule. Additional info from the Interior Designer will be provided in order to indicate patterning.
2.) Section 096913, 1.2, submittals, SD-03, specifically prohibits zinc electro plated anti-corrosion coatings. Please clarify and explain.?
A46 (2). Due to prior USACE encounters, Zinc plating has been prohibited. Follow specification as is. This is a USACE standard requirement. Please, elaborate as to why this is of concern.
3.) No reflective floor plan is laid out for the access panel floors. This in itself is not a huge problem, but layout items, such as electrical cutouts, size of boxes, number of boxes, mechanical diffusers, etc. should be laid out to make sure its all correct. Please clarify.
A46 (3). Please follow electrical and mechanical plans for the additional information mentioned.
4.) Section 096913, 1.3, system description, specifically states “ access flooring must be installed at the location and elevation and in the arrangement shown on the drawings.” Please clarify. We have not found any drawings to work from.
A46 (4a). A flooring pattern will be provided, indicating pattern.
Plus:
b.) requires equi-potential plane grounding. Please clarify.
A46 (4b). Stringer system shall be electrically continuous per spec 09_69_13 para 1.3.b. Stringer system shall be grounded per 09_69_13 para 1.3.9 and drawings E5.01 and detail 3 on drawing E7.04.
c.)Submit certifications for: compliance with ICC-ES AC300 – please clarify.
A46 (4c). Per spec submit systems manufacturer's proof of compliance with AC300.
Q50. Under Part 2 products, 2.1.2, panel construction, calls out three types of floor panels. Hollow formed, metal clad cementitious, or metal clad wood. However, the specs do not specify what the govt. wants for this project.
Please clarify.
A50 (a). Provide metal panels. Cementitious or wood are not permitted.
The floor covering 2.1.3, states the flooring materials must be firmly bonded with waterproof adhesive, but the flooring finish is not specified. Please clarify.
A50 (b). Flooring finish is provided. Please, refer to Room Finish Schedule (A 7.02)
Q51. Under 1.4 delivery, storage and handling, it states, “store all materials in safe, dry and clean location….panels must be stored between 40 degrees and 90 degrees F and 20%to 70% humidity. However, under Products, 2.7, Cutouts, it states, “ cutting of panels must be performed outside of building”. Please clarify how you anticipate unloading and storage in mid winter and how you anticipate the cutting operation if not allowed in the building in mid winter. Please clarify.
A51. There are numerous ways to accommodate these requirements simultaneously. Due to liability issues, we cannot provide solutions at this time. Please, consult the site supervisor for coordination.
Q52. Under Part 3, Execution, 3.1.1, call for structural concrete floor systems to be thoroughly cleaned. Also, floor coatings required for dust and vapor control must be provided prior to pedestal installation. However, if the coating and pedestal adhesive are not compatible, then the floor coating goes on after the pedestal installation. Please clarify what product goes on as a sealer, who supplies and installs it and who does the cleaning and application of the sealer product.
A52. We do not provide this information. This is typical of contractor responsibilities.
Q53. 3.2 Field tests – please describe the procedures for acceptance tests.
3.4 Fire safety – calls out for an automatic detection system installed below the raised floor. Please verify what is required and whom is responsible for this spec call out.
There are numerous other details that need to be addressed in this spec section that offer background but not defined requirements. Also, the finished flooring product is not specified, i.e., high pressure laminate, color or type, or vinyl tile, or carpet, etc. Please clarify.
A53 (c). Flooring finishes are provided. Refer to Room finish Schedule (A 7.02)
Complete and accurate drawings of what the govt. expects and wants, inclusive of mechanical and electrical requirements are needed to accurately and cost effectively bid this segment of the work. We look forward to your prompt response to the questions outlined above and getting definitive answers PRIOR to quoting on this project.
Q66. Drawing A2.02 states; File Storage System as indicated by dashed linetype is for reference only and will be provided under seperate contract (NIC). What is the purpose for specification 10 68 10? Is this storage system to provided under this contract?
A66. This item is not to be included in this contract. Please, refer to the response to Q35
Q108. 1. Sheet 7.02 Finish Schedule is very specific about the products to be used in this project. The specifications seem to contradict the finish schedule in places. My question is this, are the products on the finish schedule the products you wish to have installed on this project. Is there any provisions for an alternate “or equal” product.
A108. Please, follow the finishes listed in the Room Finish Schedule.
Q109. 2. In the color and material Legend under Rubber Flooring, in the remarks section, there is reference to a “logo color cut on floor” Is there a logo to be color cut on the floor? Is there artwork to be associated with this Logo?
A109. There is a logo that has been provided by the interior design contractor. This will be provided for reference.
Q110. 3. In stair 102 and 113 the finish schedule calls for Rubber Tile, do you wish to have rubber treads and risers as well? Or is it just rubber tile on the landings.
A110. Rubber treads and risers are the correct material.
Q111. 4. In Mechanical room 208 the finish schedule calls for carpet, Mechanical rooms with floor drains typically do not have carpet, is this in error, or do you wish to have carpet installed as stated on the finish schedule.
A111. This was in error by our interior design contractor. A revised Room Finish Schedule will be provided, indicating proper finish.
Q113. I did not see the casework specification addressed in the addendum 2 on 1/20/09, nor since. Is the casework solid hardwood frames with hardwood plywood exposed surfaces, or is it frameless with laminate exposed surfaces as per my question on 1/15/09? Will my question below be addressed prior to bid?
1. ProSteel, Inc FAX –in
A113. Refer to the specifications (062000, section 2.4.2)
R0004 FAIRBANKS SATELLITE OPERATIONS FAC. NES066
FOX, ALASKA
08 11 16 ALUMINUM DOORS AND FRAMES
08 14 00 WOOD DOORS
08 36 13 SECTIONAL OVERHEAD DOOR
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 06 90 COLOR PAGES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 00 CERAMIC TILE
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 68 00 CARPET
09 69 13 RIGID GRID ACCESS FLOORING
09 90 00.00 40 PAINTING AND COATING
DIVISION 10 - SPECIALTIES
10 14 02 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 26 13 WALL CORNER GUARDS
10 28 13 TOILET AND JANITOR CLOSET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
AM#4...DELETE TEX T...AM#4
DIVISION 12 - FURNISHINGS
12 21 00 WINDOW BLINDS
12 93 00 SITE FURNISHINGS
DIVISION 13 - SPECIAL CONSTRUCTION
13 34 19 PREENGINEERED METAL BUILDINGS
13 48 00.00 10 SEISMIC PROTECTION FOR MECHANICAL EQUIPMENT
13 48 00 SEISMIC PROTECTION FOR MISCELLANEOUS EQUIPMENT
DIVISION 14 - CONVEYING EQUIPMENT
14 24 00 HYDRAULIC ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 13 18.00 10 PREACTION SPRINKLER SYSTEMS, FIRE PROTECTION
21 21 00.00 40 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 31 00 WATER SOFTENERS, CATION-EXCHANGE (SODIUM CYCLE)
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 05 93.00 10 TESTING, ADJUSTING, AND BALANCING OF HVAC SYSTEMS
PROJECT TABLE OF CONTENTS Page 2 admin/office finishes
Carpet:
mfg: Karastan line: hypnotizing color: Flirt 67412
Wall Color:
mfg: sherwin williams color: Heavenly White, SW6553
Wall Base:
mfg: roppe color: burnt umber P194 ceiling:
mfg: suspended acoustical color: white bathroom finishes flooring:
mfg: daltile line: porcelain floor tile, shadow stone color: antique white, sn01 18"x 18"
Wall Color:
mfg: sherwin williams color: alabaster, sw7008 accent wall color:
mfg: sherwin williams color: virtual taupe, sw7039
Wall Base tile:
mfg: daltile line: porcelain floor tile, shadow stone color: silver smoke, sno5 12"x 12" accent tiles:
mfg: daltile line: porcelain floor tile, shadow stone color: silver smoke, sno5 12"x12" mfg: daltile line: mosaics unglazed, keystones color: white, d317 2"x2" partitons: mfg: global partitons line: Global stainless steel color: #4 satin finish ceiling:
color: alabaster, sw7008 break room finishes mfg: zaxxon line: ionique color: coffee ebony W3453
Wall Color:
mfg: sherwin williams color: heavenly white, SW6553
Wall Base:
mfg: roppe color: green beige P109 cabinetry:
mfg: wilsonart color:asian sand 7952−38 counter top:
mfg: lg line: hi−macs color: tundra quartz g65 ceiling:
mfg: tbd color: tbd conference room finishes
Carpet:
mfg: lees line: i−spy color: random order 451
Wall Color:
mfg: sherwin williams color: Heavenly White, SW6553
Wall Base:
carpet base acoustic panel:
mfg: tbd color: tbd ceiling:
mfg: tbd color: tbd lobby finishes mfg: zaxxon (see description in sustainability narratives tab) line: ionique color: effervescence S3176 grey limestone S3476 tundra S3151
Wall Color:
mfg: sherwin williams color: heavenly white, SW6553 color: rock candy, SW6231
Wall Base:
mfg: roppe color: canvas P149
Acoustic Panel:
mfg:tbd color:tbd ceiling:
mfg:tbd color:tbd operations/ logistics floor finishes mfg: nora line: noraplan, environcare (tate approved finish) color: lapis 2939 siberian iris 2937 lace vine 2945 driftwood 2787
Wall Color:
mfg: sherwin williams color: heavenly white, SW6553 color: rainstorm, SW6230
Wall Base:
mfg: roppe color: blue P187
Acoustic Panel:
mfg:tbd color:tbd ceiling:
mfg: suspended acoustical color:white
| NES066 Finishes Info AM4.pdf |
| Finishes Info.pdf |
| NES066-044-A7-02 A7.pdf |
| First Floor |
| Second Floor |
| #2 FLOOR LOGO copy |
| admin |
| bathrooms |
| break |
| conference |
| lobby |
| ops |
| admin-office |
| bathrooms |
| break room |
| conference room |
| lobby |
| operations-logistics |
File details come from the government source that posted it. Updated .