7)_Drawing__MECH_2388.pdf
PDF 1 MB Posted
- Attached to
- Repair Building 2399 & 2388 CP Casey
- Solicitation number
- W90VN819R0037
About this file
Drawing 7 Mechanical - B2388
View the file
Other files
| File | Type | Posted |
|---|---|---|
| W90VN8-19-R-0037.pdf | ||
| 1)_Drawing_files___Title.pdf | ||
| Submittal_Register.pdf | ||
| 2)_Drawing__ARCH_2388.pdf | ||
| 8)_Drawing__MECH_2399.pdf | ||
| W90VN8-19-R-0037.pdf | ||
| 6)_Drawing__ELEC_2399.pdf | ||
| 5)_Drawing__ELEC_2388.pdf | ||
| 3)_Drawing__ARCH_2399.pdf | ||
| 4)_Drawing__CIVIL.PDF |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
15.
14.
13.
12.
11.
10.
9.
8.
7.
6.
5.
4.
3.
2.
1.
PIPING SYSTEMS SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS
AND FLUSHED UNTIL ALL WATER BEING FLUSHED IS CLEAR AS TAP WATER.
RA & EA DUCT SHALL BE PRESSURE CLASS -50mm AQ.
ALL AIR DUCT DIMENSION SHOWN ARE INDICATED AS ACTUAL INSIDE DIMENSIONS.
DUCTWORK SHALL BE PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREAS.
TO SMACNA STATIC PRESSURE CLASS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS
ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING
OF SEAL CLASS C.
CONNECT TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE
THE EXISTING EQUIPMENT ANY EQUIPMENT, DUCT WORK, PIPING ETC. DAMAGED DUE TO
THE WORK PERFORMED UNDER THIS CONTRACT SHALL BE REPAIRED OR REPLACED BY
THE CONTRACTOR SHALL VISIT THE SITE AND SHALL FAMILIARIZE HIMSELF WITH
THE EXISTING CONDITIONS, EQUIPMENT, FINISHES, ETC., PRIOR TO START OF WORK.
IF ANY DISCREPANCY IS DETECTED, IT SHOULD BE BROUGHT TO THE CONTRACTING OFFICER'S
REPRESENTATIVE ATTENTION WITH RECOMMENDATIONS FOR PROPER CORRECTIONS FOR
LOCATION AND SIZES OF EXISTING EQUIPMENT, DUCTWORK, PIPING, ETC. APPROXIMATE
SHOP DRAWING SHALL NOT BE THE EXACT DUPLICATION OF THE CONTRACT DRAWING.
NO MECHANICAL WORK CAN BE STARTED WITHOUT AN APPROVED SHOP DRAWINGS.
ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
ALL WALL/FLOOR/ROOF OPENINGS RESULTED FROM THE REMOVAL OF PIPING AND
CONTRACTING OFFICER'S APPROVAL.
AND SHALL BE VERIFIED AT THE JOB SITE.
THIS CONTRACTOR.
GENERAL NOTES
PATCHED OR RESTORED TO MATCH ADJACENT SURFACE OR AREA.
ANY OPENING RESULT FROM THE REMOVAL WORK THAT'S NOT TO BE RE-USED SHALL BE
ALL HVAC PIPING/DUCTWORK TO BE REMOVED SHALL INCLUDE ALL IT'S ACCESSORIES
SUCH AS ANCHORS, HANGERS/SUPPORT, ETC.
SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACTLY
FIELD CONDITIONS. SUCH DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR
ACCORDING TO ACTUAL FIELD CONDITIONS AND SUBMITTED TO THE
CONTRACTING OFFICER FOR APPROVAL.
THE EXIST DUCTWORK AND INSTALL NEW DUCTWORK AND MAKE ALL NECESSARY DUCT
IF THE EXIST DUCT ELEVATION IS CONFLICTED WITH NEW PIPING INSTALLATION, REMOVE
THE EXIST DUCTWORK AND PIPING ELEVATION/LOCATION.
PRIOR TO INSTALL NEW HVAC AND PLUMBING PIPING CONTRACTOR MUST COORDINATE WITH
CONNECTION TO FUNCTION AS ORIGINALLY INTENDED.
CONCRETE REMOVAL AND RESTORATION SHALL CONFORM TO SPEC.
SCOPE OF WORK
CONDITIONING UNITS, CONTROLS AND ASSOCIATED PIPING WITH NEW PACKAGED
M-1
HEAT PUMP UNITS, CONTROLS AND ASSOCIATED PIPING.
ASSOCIATED PIPING WITH NEW.
3. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED DOMESTIC C.W, H.W, SEWER
3. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ELECTRIC WALL HEATER WITH NEW.
SCOPE OF WORK
GENERAL NOTES &
2. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED ROOF EXHAUST FAN,
4. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED DOMESTIC HOT WATER CIRC. PUMP
AND VENT PIPING INCLUDING WATER HAMMER ARRESTORS WITH NEW.
REPAIR AND MAINTENANCE WORK(K-WORK)
A. HVAC
B. PLUMBING
1. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED WINDOW TYPE AIR
AND ASSOCIATED DUCTWORK WITH ACCESSORIES WITH NEW.
HEATER WITH ELECTRIC HOT WATER HEATER AND ASSOCIATED PIPING WITH NEW.
1. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED OIL TYPE DOMESTIC HOT WATER
2. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED PLUMBING FIXTURES AND
DOMESTIC HOT WATER RE-CIRC. PUMP AND ASSOCIATED PIPING WITH NEW.
5. REPAIR BY REPLACEMENT OF EXISTING DETERIORATED DOMESTIC HOT WATER STORAGE
TANK AND ASSOCIATED PIPING WITH NEW.
(BLDG S-2388)
MECHANICAL
CAMP CASEY
REPAIR BUILDING S-2399,
CHONG, ST
160851
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING
ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENT REQUIREMENTS.
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY,
GENERAL NOTE
M E C H A N I C A L E Q U I P M E N T S C H E D U L E
1,7251/238.90.38
DOMESTIC HOT WATER
RECIRC PUMP INLINE CENTRIFUGAL TYPE
PIPE MOUNTED
115/1/60
1,7251/438.90.32
P
DOMESTIC HOT WATER
CIRC PUMP INLINE CENTRIFUGAL TYPE
PIPE MOUNTED
115/1/60
REMARKSRPM
HP
HEAD(kPa)
(LPS)
CAPACITY
TYPESERVICE
PUMPS
Q'TYITEM NO
VOLT/PH/HZ
MOTOR
P
NO
ITEM
DOMESTIC HOT WATER STORAGE TANK
Q'TY SERVICE
TANK CAPACITY
TYPE
STORAGE TANK
TANK SIZE
(LITS) (mm DIAx mm LONG)
DT
VERTICAL TYPESTORAGE TANK
STL. ROUNDBUILDING D.H.W.
MAX. WORKING
PRESSURE
(KPa)
2,271 1,219 x 2,057
REMARK
(600 GALS)
PROVIDED W/CEMENT LINING
AND SUPPORT SADDLE
EWH
ELECTRIC HOT WATER HEATER
1 MECH RM.
QTYITEM NO SERVICE
(LITS) VOLT/PH/HZ (DEG. C)KW
LOWER :10.0 KW
473.2 208/3/60
REMARKS
ELEMENT CAPACITY
T Y P E
CAPACITY
STORAGE SUPPLY
TEMP.
MOUNTED TYPE
UPPER :10.0 KW
TOTAL :20 KW
ELECTRIC VERTICAL FLOOR 43.3 C
NOTES:
1 2
HP
PACKAGED HEAT PUMP UNIT
ITEM
NO QTY. SERVICE T Y P E
(KW)
COOLING
(KW)
HEATING
(KW)
POWER INPUT
COOLING
(KW)
POWER INPUT
HEATING
TYPE
REFRIGERANT
VOLT/PH/HZ REMARKS
WALL MOUNT TYPE
PACKAGED
INSTALLED AS PER MANUFACTURER RECOMMENDATIONS.
ALL HEAT PUMP UNITS REFRIGERANT PIPING SHALL BE
3.0 3.8 0.82 0.96 R-410A 220/1/60 3 4
COOLING CAPACITY SHALL BE BASED ON 35 DEG C.
HEATING CAPACITY SHALL BE BASED ON 7 DEG C.
3 LG MODEL SW07B9JWAS OR APPROVED EQUAL. 4 POWER PLUG-INCODE
CORRIDOR(101), DRYROOM(103)
ELECTRIC WALL HEATER
SERVICE T Y P E
WALL MTD
ELEMENT CAPACITY
120/1/601,000
TOTAL
VOLT/PH/HZ
REMARKS
EH
(WATTS) AMPERAGE
8.4
UNITS SHALL BE PROVIDED WITH DISCONNECT
SWITCH AND INTEGRAL THERMOSTAT.
QTYITEM
NO
RECESSED TYPE
BATHROOM(102)
CENTRIFUGAL FAN
ROOF MOUNTED BELT DRIVE
330.3 62.2 700 1/4 115/1/60
EF
ITEM NO Q'TY
FANS
SERVICE TYPE
AIR CAP
(LPS)
FAN MOTORESP
(Pa) RPM
HP VOLT/PH/HZ REMARKS
NOTE :
1 DISCONNECT SWITCH
MANUAL BACKDRAFT DAMPER3
2 BIRDSCREEN
1 2 3
BATHROOM(102)
SHOWERROMM(104)
CENTRIFUGAL FAN
ROOF MOUNTED BELT DRIVE
93.4 990 1/4 115/1/60
EF
1 2 3FOR MECH RM(105) 189 4 PREFABRICA ROOF CURB
M-2
(BLDG S-2388)
MECHANICAL
AND GENERAL NOTE
MECHANICAL EQUIPMENT SCHEDULE
CAMP CASEY
REPAIR BUILDING S-2399,
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SPECIFIC NOTES
EXISTING/REMOVAL PLAN(GROUND FLOOR)
1 2
REMAIN EXISTING ELECTRIC UNIUT HEATER.
REMOVE EXISTING MECHANICAL EQUIPMENTS(WAF, DOMESTIC HOT WATER HEATER, STORAGE TANK, REMOVE EXISTING ALL PLUMBING FIXTURES AND ASSOCIATED PIPING.
EXHAUST FANS, ETC) AND ASSOCIATED DUCTS AND PIPING.
REMOVE EXISTING ALL PLUMBING PIPING(HW,CW,SEWER AND VENT PIPING) AND
ASSOCIATED ACCESSORIES.
SCALE : 1 / 50
M-3
(BLDG S-2388)
MECHANICAL
AND SPECIFIC NOTES
EXISTING/REMOVAL PLAN(GROUND FLOOR)
M16
CAMP CASEY
REPAIR BUILDING S-2399,
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
1 GROUND FL HVAC PLAN
CORRIDOR
BATHROOM
DRYROOM
SHOWER ROOM
MECH ROOM
S S
PTDWR
T
T
HP
HP
HP
HP
ELEC. WALL
HEATER 1
EH
ELEC. WALL
HEATER
EH
VD VD
EA EA
E-1:250x250
70.8LPS
E-1:250x250
70.8LPS
2x
300x150
E-1:200x200
47.2LPS
x2
250x150
250x150
VD
VD
250x200
VD
VD
EF
300x200
ROOF EXH. FAN
CONC. PADCONC. PAD
CONDENSATE DRAIN
SPILL ON GROUND 25mm
CONDENSATE DRAIN
SPILL ON GROUND 25mm
ROOF EXH. FAN
EF
SCALE : 1 / 50
M-4
(BLDG S-2388)
MECHANICAL
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2.
OF EQUIPMENTS IN FIELD(TYP)
PRIOR TO EQUIPMENTS INSTALLATION.
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR EQUIPMENTS.
GROUND FL HVAC PLAN AND NOTES
M17
CAMP CASEY
REPAIR BUILDING S-2399,
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
103 104
105CORRIDOR
BATHROOM
DRYROOM SHOWER ROOM
MECH ROOM
S S
WALL MOUNTED STAINLESS STEEL TYPE
FLOOR MOUNTED TYPE
151P-8 4015 75
MODEL KSAJ-515-24 OR APPROVED EQUAL.
W/AERATOR SHALL BE KOSDO INC
COUNTER TOP.
4 WATER CLOSET
LAVATORY
F I X T U R E
SYMBOL
P-5
P-1
QTY.
REQUIREMENTS.
NOTES :
C.W.
1. QUANTITIES ARE SHOWN FOR ESTIMATION PURPOSE ONLY, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON THE CONTRACT DOCUMENTS
R E M A R K S
BACK
VENTH.W.
PIPE CONNECTION
15 40
WASTE
FLUSH TANK,
SERVICE SINK
156 SHOWERP-10 4015 75
FLUSH VALVE, WALL HUNG.15URINALP-3 - 40 504
S.D
W/AERATOR SHALL BE KOSDO INC
MODEL KSAJ-100 OR APPROVED EQUAL.
PLUMBING FIXTURE SCHEDULE
DWH
P
50mm C.W PIPING (E)
P-1
P-1
P-1
P-1
P-5
P-5
P-5
P-3
P-3
P-3
P-3
P-8
P-10 X 6
(PDI:"A" TYP)
WATER HAMMER ARRESTOR x 2
WATER HAMMER ARRESTOR x 2
(PDI:"A" TYP)
(PDI:"A" TYP)
(PDI:"C" TYP)
20202020
CONC. PAD
P
DOMESTIC HOT
WATER CIRC. PUMP
DOMESTIC HOT WATER
RE-CIRC. PUMP
DT
DOMESTIC HOT WATER
STORAGE TANK
CONC. PAD
WATER HAMMER ARRESTOR
(PDI:"A" TYP)
WATER HAMMER ARRESTOR
WATER HAMMER ARRESTOR
WATER HAMMER ARRESTOR
(PDI:"B" TYP)
103 104
CORRIDOR
BATHROOM
DRYROOM SHOWER ROOM
MECH ROOM
S S
P-1
P-1
P-1
P-1
P-5
P-5
P-5
P-3
P-3
P-3
P-3
P-8
DOMESTIC HOT
WATER HEATER
S
EXACT SIZE & LOCATION
SHALL BE VERIFY IN FIELD
S
150 FCO
75 FD
75 FD
75 FD
75 FD
75 FD
100 FCO
100 FCO
80 VTR
V
V
SCALE : 1 / 50
HOT & COLD WATER PIPING SEWER & VENT PIPING
1 GROUND FL PLUMBING PIPING PLAN
M-5
(BLDG S-2388)
MECHANICAL
1.
NOTES:
CONTRACTOR SHALL VERIFY EXACT LOCATION, SIZE AND DIRECTION
2.
OF PLUMBING PIPING IN FIELD(TYP)
CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING PIPING.
PRIOR TO PLUMBING PIPING INSTALLATION.
FIXTURE SCH. AND NOTES
GROUND PLUMBING PIPING PLAN,
M18
CAMP CASEY
REPAIR BUILDING S-2399,
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
MECHANICAL
"C"
"A"
"B"
TYPE
33-60128 125
WATER HAMMER ARRESTOR
94 81
115 81
HEIGHT DIAMETER
1-11
12-32
CAPACITY
FIXTURE UNIT
FIXTURE
TO LAST
THREADED PLUG
FROM BRANCH
SUPPLY
AND SIZE
20 OR 25 SEE
DWGS FOR LOCATION
PRESSURE PNEUMATIC
STAINLESS STEELSHELL
STAINLESS STEEL
ORIFICE
FLOW CONTROL
H E
IG
H
T DISPLACEMENT
ADAPTER
FLUID
BELLOWS
HYDRAULIC
CUSHION
DISPLACEMENT
DIAMETER
M22-
M-6
CAMP CASEY
REPAIR BUILDING S-2399,
CHONG, ST
160851
DIVISION 7 WORK
BACKDRAFT MOTORIZED
INSULATED ROOF CURVE,
EXHAUST DUCT WORK
POWER ROOF VENTILATOR
POWER ROOF VENTILATOR
MIN. 2 EACH SIDE
BY FAN MFR.,
RECOMMENDED
LAGBOLTS AS
CURB HT.
300 MIN.
SEE ARCH. DWGS.
WOOD BLOCKING,
SEE ARCH. DWGS.
ROOF CONSTR.
SEE ARCH. DWGS.
WOOD NAILER
ALL AROUND
GASKET SEAL
(SPECIFIED IN DIVISION 7)
FLASHING
UNIT HOOD
M
DAMPER
MOTOR
DAMPER
- M21
TYPICAL IN LINE PUMP PIPING DETAIL
DISCHARGE
SUCTION
CALIBRATED BALANCING
PRESSURE GAUGE
(TYP)
SHUT-OFF COCK
PROVIDE CHECK VALVE
DOMESTIC HOT WATER
RECIRULATION PUMP
IN DISCHARGES
VALVE
- M35
NOTES : 1.WATER-PROOF MEMBRANE ARE NOT REQUIRED IN SLAB ON GRADE.
PLUG Y-BRANCH
WHEN NOT THRU RUN
1/8 BEND
LEAD CAULKING
JUTE PACKING, SEE NOTE-2
FINISH FLOOR
NEOPRENE GASKET
2.CHROMIUM-PLATED BRONZE, NICKEL BRONZE,NICKEL BRASS OR
STAINLESS STEEL FLUSH TYPE ACCESS COVER PLATE
FLOOR CLEANOUT
CAST IRON
PIPE
Y-BRANCH
SCORIATED COVER
SEE NOTE-2
TWO PIECE THREADED
ADJUSTABLE HOUSING
WATER-PROOF MEMBRANE
- M35
DETAILS
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M1 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M2 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M3 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M4 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M5 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M6 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M7 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M8 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M9 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M10 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M11 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M12 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M13 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M14 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M15 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M16 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M17 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M18 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M19 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M20 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M21 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M22 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M23 |
| 160851_Repair Bldg S-2399(TMP), Cp Casey_M24 |
File details come from the government source that posted it.