GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
350mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
3.
4.
6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
7.
5.
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT
THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING
TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.
DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT
F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SCOPE OF WORKS
LEGEND, GENERAL NOTES AND
E-1
12.
13.
14.
10.
11.
8.
9.
15.
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
T
J
THERMOSTAT (UNDER MECH. ITEM)
JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
SAFETY SWITCH
C CONTROL CIRCUIT
3-WAY SWITCH, 15A-125V
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
CABNET TYPE, RATED WATT ON LTG SCHEDULE
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER
ON LTG SCHEDULE, WET LOCATION
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
FAULT PROTECTED TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
FIXTURE A MINIMUM DISTANCE OF 458mm.
FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING
FMCP
FTR
AUXILIARY
DESCRIPTIONSYMBOL
STROBES
WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL
BUILDING TRANSMITTER UNIT FOR FIRE ALARM
SYSTEM
L
WP
FAULT PROTECTED TYPE, WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
TYPE
SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING
L
L
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
L
W/EMERGENCY UNIT TYPE
QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
16.
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
THE MANUFACTURER AND MODEL OF NEW BUILDING TRANSMITTER EQUIPMENT
IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE TESTED WITH THE RECEIVING SYSTEM(D21)
SHALL BE COORDINATED WITH THE CENTRAL FIRE DEPARTMENT.
RECEPTACLE
AND WALL
WIRING CONCEALED OR EXPOSED IN/ON THE CEILING
CEILING OR CONCEALED IN NEW WALL.
ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS
SCOPE OF WORK
1.
A. REPAIR/MAINTENANCE ( K )
4.
2.
6.
5.
3.
7.
3S
WITH NEW.
RECEPTACLES W/COVER PLATES ASSOCIATED WIRING & CONDUITS
REPLACE EXISTING PANELBOARDS, WATTHOUR METER W/CT'S,
AND ASSOCIATED WIRING AND CONDUIT.
75 CANDELA), MICROPHONE, SPEAKER (WATTAGE AS REQ'D) DEVICE
BUILDING TRANSMITTER, ANTENNA, VISUAL/SIGNAL STROBES (15 OR
PANEL, MANUAL PULL STATION, SMOKE DETECTOR & RELAY MODULE,
ADDRESSABLE FIRE ALARM CONTROL AND MASS NOTIFICATION SYSTEM
REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH NEW
AND ACCESSORIES WITH NEW.
REPLACE EXISTING EXTERIOR UNDERGROUND TELECOMMUNICATION LINE
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
SYSTEMS AND ROLL-UP DOORS WITH NEW.
JUNCTION BOXES, CONTROL/POWER WIRES AND CONDUITS FOR MECHANICAL
REPLACE DETERIORATED EXISTING SAFETY SWTICH, MOTOR CONTROLLERS,
UNDERGROUND EXTERIOR SECONDARY LINE AND ACCESSORIES WITH NEW.
REPLACE EXISTING PAD MOUNTED TRANSFORMER, OVERHEAD &
& CONDUIT WITH NEW.
PLATES, TERMINAL BLOCKS, EQUIPMENT CABINET AND ASSOCIATED WIRE
TELEPHONE TERMINAL CABINET, TELEPHONE/DATA OUTLETS W/COVER
REPLACE DETERIORATED EXISTING TELEPHONE SYSTEM INCLUDING
AND CONDUITS WITH NEW.
LIGHTS, EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY SWITCHES, WIRES
REPLACE DETERIORATED EXISTING INTERIOR LIGHTING FIXTURES, EXIT
TYPE WITH PLUG
SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING
TYPE WITH PLUG
SINGLE RECEPTACLE, 2P-3W-20A-125/250V, GROUNDING
30L
FIRE ALARM & MNSCONTROL PANEL
F
F/M
FIRE ALARM & MNS CIRCUIT
T LAN/TEL LINE
2372A
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-2
SCALE: 1/300
W/BUILT-IN PROTECTIVE DEVICES (15A FUSE)
3PH, 11.4KV-120/208V(DELTA-WYE), 60HZ, 300KVA
DEAD-FRONT TYPE, LOAD BREAK SW,
METAL ENCL, OIL-FILLED, SELF-COOLED,
RADIAL TYPE TRANSFORMER
EXIST O/H SEC. LINE
EXIST O/H SEC. LINE
EXIST O/H PRI. LINE
NEW U/G SEC. LINE
3-1/C, #1, 24KV, "XLP" AND 1/C, #1, 600V, "XLP"
NEW U/G PRIM. LINE
ACCESSORIES.
EXIST SECONDARY LINE WITH NEW ASSOCIATED
RECONNECT NEW SECONDARY LINE TO
P
P
P S
S
S
S
S
S
S O /H
O /H
O /H
O /H
O /H
10m2.5m0
SCALE: 1:300
5m
EXIST O/H PRI. LINE
EXIST/NEW EXTERIOR POWER LINE DISTRIBUTION PLAN
NEW ENTRANCE CAP AND SEC. RACK
O/ H
S
O/ H
S
S
EXIST ELECTRIC POLE (TYP.)
REPLACE WITH NEW PAD MOUNTED
W H
MAND SERVICE ENTRANCE.
REMOVE EXISTING SERVICE SECONDARY LINE
NEW WATT HOUR METER AND CT'S
NEW O/H SEC. LINE 4-AWG#4"WP"(TYP.)
2 SETS OF 4-250MCM IN 103C
/TURN-IN EXIST PAD MOUNTED TRANSFOMER TO DPW
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUIDLING S-2399)
ELECRICAL
DISTRIBUTION PLAN
EXIST/NEW EXTERIOR POWER LINE
"P"
NEW 4-AWG#2 &1#8(G) IN 35C
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-3
10m2.5m0
SCALE: 1:300
5m
SCALE: 1/300
C O
U R
T B
A S
K E
T B
A L
L
F
MH7
MH7-2
MH7-1-A
C
C
C
C
C
P
P
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
NOTES
TO FIX NEW TELECOM CABLES WHEN ACROSSING
CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS
SEE SHEET NO. E-1.
1.
2.
UNDER THE BRIDGE.
3.
THE CONTRACTOR SHALL VERIFY EXISTING4.
UNDERGROUND TELECOMM LINE'S ACTUAL
CONDITION PRIOR TO WORK.
NEW SINGLE MODE FIBER OPTIC CABLE
AND TELEPHONE CABLE SHALL BE INSTALLED
ON THE EXISTING/NEW MANHOLES AND TYPE OF
SPLICE KITS SHALL BE COORDINATED WITH
BASE SIGNAL COMPANY.
FIBER OPTIC CABLE IN EXIST U/G DUCT
NEW 1-12 CORE STRAND SINGLE MODE
MH7-1-B
1WAY: FABRIC MESH 3" 3CELL(1PACK)
2EA: SPARE WITH PULL WIRE
FIBER OPTIC CABLE
INNER DUCT
1EA: 1-12 STRAND SINGLE MODE
NEW 2WAY OF 103mm PVC CONDUIT IN NEW U/G CONC. DUCT
1WAY: EMPTY CONDUIT W/ PULLING WIRE
SPLICE TELECOMMUNICATION CABLE WITH
NEW SPLICE KIT FOR 1-12 CORE
FIBER OPTIC CABLE
INNER DUCT
1WAY: FABRIC MESH 3" 3CELL(1PACK)
2EA: SPARE WITH PULL WIRE
FIBER OPTIC CABLE
1WAY: 1-25 PAIR AWG#24 TELEPHONE CABLE
1EA: 1-12 STRAND SINGLE MODE
IN NEW U/G CONC. DUCT
NEW 2WAY OF 103mm PVC CONDUIT
DRAWINGS
(SMALL), SEE 2014 OMA STANDARD DETAIL
NEW TELECOMMUNICATION MANHOLE
NEW PULLBOX "WP"
SPLICE 1-25PAIR TELEPHONE CABLE
EXIST TELEPHONE PEDESTAL/
IN NEW 103C
NEW U/G 1-25 PAIR TELEPHONE CABLE
OFFICE
SHOP CONTROL
TERMINAL CABINBET FOR TELEPHONE CABLE.
FIBER OPTIC CABLE AND TERMINATE AT TELEPHONE
AT FIBER OPTIC PATCH PANEL IN NEW LAN CABINET FOR
1-25 PAIR TELEPHONE CABLE IN 54 C./ TEMINATE
NEW 1-12 CORE FIBER OPTIC CABLE IN 54 C. AND
EXIST TELECOMMUNICATION CABLE
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUIDLING S-2399)
ELECRICAL
LINE DISTRIBUTION PLAN
EXIST/NEW EXTERIOR TELECOMMUNICATION
EXIST/NEW EXTERIOR TELECOMMUNICATION DISTRIBUTION LINE PLAN
SHOP AREA
MECH ROOM
S /S
EWC
LATRINE
WOMEN'S
LATRINE
MEN'S
VEST
J/C
TOOL ROOM
ROOM
LAUNDRY
OFFICE
INSPECTOR
OFFICE
FOREMAN
OFFICE
SHOP CONTROL
BB
STORAGE
EQUIPMENT
FEC
E-4
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
LL L
L
L
L
L
L
L
L
LL
LL
LL
L
L
L
LL
L
L
L L
L
S S
S S
S
S
S S
S S
S
S S
S
S S
S
S S
S
S
S
EP
EP
EP
S
L
LL
L
S S
L L L L
L L L L
L
L L
L
L
SCALE:
NEW GROUND FLOOR LIGHTING PLAN
S
"PC"
"PA"
"PB"
EP
EF-1J
EF-1J
JEF-1
S
PA-1
PA-2
PB-1
PB-2
PB-3
PB-4
PA-3
PA-4
L
L
L
L
L
L
L
L
L
L
L
L
L
L L
L
L
L
L
L
L
L
L
L
L
L
L
(TYP OF 5)
EXISTING EXTERIOR BAY LIGHT TO REMAIN
(TYP OF 3)
NEW EXTERIOR BAY LIGHT TYPE "NS-10"
EXISTING BAY FLOOD LIGHT TO REMAIN
(TYP OF 21)
NEW BAY FLOOD LIGHT TYPE"NS-9"
(TYP OF 4)
(TYP OF 5)
EXIST EXTERIOR LIGHT
(TYP OF 4)
EXIST EMERGENCY LIGHT
1/100
NOTE.
1.
LIGHTING FIXTURES TO MEET THE SITE CONDITION.
CONDITION AND PROVIDE NEW WIRING TO NEW AND EXISTING
CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY EXISTING SITE
L L
L L
J J
J J
EPEP
EPEP
PROOF TYPE (TYP)
JUNCTION BOX EXPLOSION NEW LED PIT LIGHT TYPE "NS-4" /
(TYP OF 4EA)
TO MATCH WITH EXSTING WALL CONDITION
REPAIR CONCRETE WALL AFTER INSTALLATION
(UNDER MECH ITEM)
(UNDER MECH ITEM)
(UNDER MECH ITEM)
EXH. FAN-1, 120V, 80W
EXH. FAN-1, 120V, 80W
EXH. FAN-1, 120V, 80W
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
NEW GROUND FLOOR LIGHTING PLAN
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-5
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
NS-10
FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND
ACCESSORIES AS REQUIRED, (NS-6a) & EM UNIT(NS-6b)
415 415
CEILING PENDANT MOUNTED LED LIGHT FIXTURE,
ACCESSORIES
LUMINOUS EFFICACY 110L/W, WITH CONVERTER &
13,200LM, 5700K, IP RATING 65, 430 X 273(H)mm, 3.5KG
1PH, 120V, 120W LED LAMP,
DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W
WALL SURFACE MOUNTED LIGHT EMITTING
NS-7
NS-6a & 6b
NS-8
100 WALL
245mm
254mm
NS-5a & 5b
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED) FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES
WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
WET LOCATION SHOWER LIGHT TRIM, UL LISTED POWER UNIT
AS REQUIRED, UL LISTED POWER UNIT
WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT
FIXTURE, 1PH, 120V, 50W, UL LISTED, WITH CONVERTER &
ACCESSORIES, (NS-5a) & WITH EM UNIT (NS-5b) AS REQUIRED
NS-3
(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER
WET LOCATIONS TYPE(IP66), UL LISTED
FIXTURE, 1PH, 120V, 60 WATT, CONVERTER AND ACCESSORIES
NS-4
NS-9
21dia (100LG)
STEEL CONDUIT
UNION, 21dia
EXPLOSION PROOF TYPE (CLASS 1, DIVISION 1)
STEEL CONDUIT
21dia (100LG)
RIGID SUPPORT
UNION, 16dia
WIRE GUARD
LIGHT
LED LIGHTING FIXTURE, 1PH, 120V
28WATT LAMP W/WIRE GUARD AND SUPPORT HOOK
JUNCTION BOX "EF"
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
LIGHTING FIXTURE DETAILS
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-6
REMARKSMOUNTING METHODQ'TY
NO
SHT
WATTSTYPE
LAMP
NAME
ROOM
TYPE
LIGHT FIXTURE SCHEDULE
OCE STD DET 40-06-04
NO
LED 4-
3-
1-
18 1-
NS-6b
2-
1-
- 2
45 1NS-4b
NS-4a
1-
2-
109 45 1-
1-
1 W/"EM" UNIT-
45 1-
NS-10 3- WALL MOUNTED60
ABOVE THE DOOR TOPWALL MOUNTED4.99NS-3
EXTERIOR
EXIT
50 6-
ABOVE THE MIRROR TOP
W/"EM" UNIT
W/"EM" UNIT
W/"EM" UNIT
W/"EM" UNIT
W/"EM" UNIT
W/"EM" UNIT
W/"EM" UNIT
W/"EM" UNIT
CEILING SURFACE
NS-5b
NS-5a 50
NS-5b
NS-5b
NS-5a
NS-5b
1-
1-
1-
WALL MOUNTED
SHOP AREA
OFFICE
INSPECTOR
LATRINE
WOMEN'S
LATRINE
MEN'S
VEST
J/C
OFFICE
SHOP CONTROL
OFFICE
FOREMAN
TOOL ROOM
MECH ROOM
STORAGE
EQUIPMENT
ROOM
LAUNDRY
120 CEILING PENDANT NS-9
CEILING SURFACE
CEILING SURFACE
NS-8
CEILING SURFACE
CEILING SURFACE
WALL MOUNTED ABOVE THE MIRROR TOP
NS-8
NS-7
CEILING SURFACE
CEILING SURFACE
CEILING SURFACE
CEILING SURFACE
NS-6b 45 1- CEILING SURFACE
NS-6a
W/"EM" UNIT
CEILING SURFACE
CEILING SURFACE
NS-6a
NS-6b 45
CEILING SURFACE
CEILING SURFACE
NS-6b
NS-6a
CEILING SURFACE
CEILING SURFACE
NS-6b
NS-6a
CEILING SURFACE
CEILING SURFACE
ABOVE THE BAY DOOR TOP
NS-4 50 4- WALL MOUNTED IN INSPECTION PIT
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
LIGHT FIXTURE SCHEDULE
MECH ROOM
S /S
LATRINE
WOMEN'S
LATRINE
MEN'S
VEST
J/C
TOOL ROOM
ROOM
LAUNDRY
OFFICE
INSPECTOR
OFFICE
FOREMAN
OFFICE
SHOP CONTROL
L/S
W WD
STORAGE
EQUIPMENT
D
E-7
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
EP
SCALE:
1/100
W H
M
"MP"
30 30
"PA"
"PB"
PA-8
EP
CT'S
PA-5
PA-6
PA-7
"WP"
"WP"
"WP"
"WP"
"WP" "WP"
PA-9
PA-10
PA-12
PA-13
PA-14
PA-15
PA-16
PA-22
PA-18
PA-21
PA-20
PB-5
PB-6
PB-7
PB-8
PB-10
PB-11
PB-15
"PC"
PA-19
PB-14
PB-13
PB-12
NEW GROUND FLOOR POWER PLAN
J
PB-19
A
PB-18
PB-17
J A
PB-16
J
A J
PB-20
J
PB-21
A
PB-22
A
J
A
J
J
PA-11
PA-17
PB-9
"WP"
NOTE.
1.
TO MEET THE SITE CONDITION.
CONDITION AND PROVIDE NEW WIRING TO NEW RECEPTACLES
CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY EXISTING SITE
2.
DEVICES BY COORDINATING WITH DPW.
CONTRACTOR SHALL REMOVE ABANDONED OR UNUSED ELECTRIC
A A
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
NEW GROUND FLOOR POWER PLAN
3-AWG#10 & 1#10(G) IN 21C (TYPICAL)
ROLL-UP DOOR, 1PH, 208V, 1HP
W/ PUCH BUTTON SWITCH
(ARCH ITEM) (TYP. OF 8)
(TYPICAL FOR DRYERS)
2-AWG#10 & 1#10(G) IN 21C
MOUNTING HEIGHT: 1150mm(TYP OF 10)
SINGLE RECEPTACLE, 3P, 4W, 240V
"WP"
MECH ROOM
FEC
S /S
LATRINE
WOMEN'S
LATRINE
MEN'S
VEST
J/C
TOOL ROOM
ROOM
LAUNDRY OFFICE
INSPECTOR
OFFICE
FOREMAN
OFFICE
SHOP CONTROL
STORAGE
EQUIPMENT
D
FEC
"PA"
"PB"
E-8
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SCALE:
1/100
(UNDER MECH ITEM)JHR
J HR
PC-5
A
3PH-208V-4.5KW
(UNDER MECH ITEM)
NEW ELECTRICAL HOT
WATER HEATER
WAF
(TYP. OF 3)
JHR
J HR
HPU
-1
HPU
-4
HPU
-3
HPU
-3
HPU
-5
J J J JEF-2 EF-2 EF-2 EF-2
CF-1J CF-1JCF-1J
PC-10
J
HPU
-2
(TYP. OF 4EA)
(UNDER MECH ITEM)
CEILING EXH. FAN, 120V, 20W
EH
EH
PC-4
B
B B
B B
B
MECH ROOM
WAF
J
EWHJ
T V
EF-3
EUH
AC
(UNDER MECH ITEM)
ROOF EXH. FAN, 120V, 1/4HP
(TYP. OF 4)
"MP"
"PC"
PC-1
PC-2
PC-3
PC-6
PC-7
PC-8
PC-11
PC-12
PC-13
PC-14
PC-15
SCALE:
MP-6
MP-8
MP-7
MP-5
MP-4J
T
T
T
T
NEW MECHANICAL ROOM POWER/CONTOL PLAN
1/50
FOR MECHANICAL EQUIPMENT
NEW GROUND FLOOR POWER & CONTROL PLAN
(TYP. OF 6)
(UNDER MECH ITEM)
HEAT PUMP UNIT, 1PH, 220V, 0.96KW
(UNDER MECH ITEM)
HEAT PUMP UNIT, 1PH, 220V, 1.15KW
(UNDER MECH ITEM)
HEAT PUMP UNIT, 1PH, 220V, 1.44KW
(UNDER MECH ITEM)
HEAT PUMP UNIT, 1PH, 220V, 1.74KW
(UNDER MECH ITEM)
HEAT PUMP UNIT, 1PH, 220V, 2.25KW
NON-FUSIBLE, NEMA 3R ENCL.
(TYPICAL)
3#12 & 1#12(G) IN 16C
(TYPICAL)
3#12 & 1#12(G) IN 16C
3#10 & 1#10(G) IN 21C
2#10 & 1#10(G) IN 21C
NON-FUSIBLE, NEMA 3R ENCL.
HOSE REEL W/ EXHAUST FAN, 3PH, 200V,1/3HP
PC-9
(UNDER MECH ITEM)
EXH. FAN, 120V, 1/4HP
JMP-8 P
SAFETY SWITCH-B, DPST, 240VAC, 30A, C
SAFETY SWITCH-C, 3PST, 240VAC, 30A,
B A
B A
A A
(MECH ITEM)
CEILING FAN CONTROLLER
POWER /CONTROL PLAN
SEE NEW MECHANICAL ROOM
NEW PANELBOARD "PA"
NEW PANELBOARD "PB"
NEW PANELBOARD "PC"
B B
COIL VOLTAGE 120V, NEMA 1 ENCL. (TYP.)
120V, NEMA SIZE 0, "H-O-A" SEL. SWITCHES, PILOT LIGHTS,
MAGNETIC MOTOR STATRER W/O.L RELAYS, 2P,
COIL VOLTAGE 120V, NEMA 1 ENCL. (TYP.)
240V, NEMA SIZE 0, "H-O-A" SEL. SWITCHES, PILOT LIGHTS,
COMBINATION TYPE MOTOR STATRER W/O.L RELAYS, 3P,
(UNDER MECH ITEM)
ELECTRIC WATER HEATER, 1PH,
220V, 4.5KW(UNDER MECH ITEM)
PUMP, 1PH, 120V, 1/6HP
HOT WATER CIRCULATION
(UNDER MECH ITEM)
ELECTRIC UNIT HEATER, 1PH, 208V, 3KW
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
PLAN FOR MECHANICAL EQUIPMENT
NEW GROUND FLOOR POWER & CONTROL
EXIST WARM AIR FURNACE,
3PH, 208V, 2HP
500AT
600AF
225AF
3P
3P
225AF
3P
CONDUCTOR, #2(G) IN 21C
NEW GROUNDING
3PH, 4W, 120/208V, 60HZ
SYSTEM, NEMA 1 ENCL
CU BUS, 400A
42,000AIC SYM
G
S/NGND
MAIN PANELBOARD "MP"
WHM
TR TYPE, W/CT'S 500/5Ax3EA
120/208V, 60Hz SYSTEM, NEMA 3R ENCL.
AND 15MIN DEMAND REGISTER FOR 3PH, 4W,
WITH NEW ADVANCED DIGITAL WATTHOUR METER,
321 5
"PB"
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES1.
NOTES
EXIST/NEW POWER ONE-LINE DIAGRAM
NOT TO SCALE
1#6(G)
IN 53C
REPLACE THE DETERIORATED EXISTING WHM
NEW U/G SEC LINE,
SPARE
101101
120AT
4#1 &
1#6(G)
IN 41C
100AF
3P
100AF
3P
100AF
3P
20AT
"PA"
NEW SEC LINE,
G
W/WELDING CONNECTION
NEW GROUND ROD, COPPER
CLAD STEEL, 19diax3000LG
(TYPICAL)
TOTAL DEMAND LOAD ; 138,720(VA)
TOTAL LOAD 176012 59428 58978
LOAD
TOTAL
MAIN PANELBOARD "MP" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MAIN 3P-600AF-500AT CIRCUIT BREAKER
MTD TYPE, NEMA 1 ENCL.
60HZ, SN & GND, SURFACE
3PHASE ,4WIRE, 120/208V,
57606
PANELBOARD "PA"
3 42000225
PANELBOARD "PB"
4#1&1#6(G)120
5583 5283 5774
SEE SHEET NO. E-1.
16640
ELECTRIC HOT WATER HEATER
SPARE
2500 833 834
4#4&1#8(G)
SPACE
SPACE
150AT
225AF
3P
100AF
2P
30AT
100AF
1P
20AT
100AF
20AT
2P
2#10 &
IN 16C
EWH
W/BUILT-IN CONTROLLER
J
1PH-208V-4.5KW
ELECTRIC HOT WATER HEATER
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-9
NEW PAD MOUNTED TRANSFORMER,
NEW GROUND ROD, COPPER
NEW GROUND ROD, COPPER
PANELBOARD "PC"
EXH FAN 1/4HPx1
WARM AIR FURNACE, 2HP
AIR COMPRESSOR, 5HP
53311 17233 16522 19556
38231 13319 12308 12604
800 800
1243 1244
ELECTRIC UNIT HEATER 3000
HOT WATER CIR. PUMP 800
1500 1500
50000 16667 16667 16666
SPARE
SPARE
11 12
SPACE SPACE
SPACE1000
4500 2250 2250
LEAK DETECTOR 500
70AT 20AT 150AT
"PC"
4#4 &
1#8(G)
EXTC
W.A.F
J
EXT
J J
100AF
20AT
1P
100AF
20AT
1P
100AF
20AT
1P
100AF
20AT
1P
J
P
J
EF EUH
110 110 110
AC
W/BUILT-IN CONTROLLER
W/BUILT-IN CONTROLLER
(EXISTING MECH ITEM)
EXISTING WARM AIR FURNACE
(EXISTING MECH ITEM)
GAS LEAK DETECTOR CONTROL PANEL
SPARE SPARE
IN 21C
3#10 &
3#10&1#10(G)
3#12&1#12(G)
1#10(G)
IN 16C
3#12 &
1#12(G) 1#10(G)
NON-FUSIBLE, NEMA 3R ENCL
3PH-208V-2HP
AIR COMPRESSOR
3PH-208V-5HP
(MECH ITEM)
(MECH ITEM)
(MECH ITEM)
EXHAUST FAN
1PH-120V-1/4HP
(MECH ITEM)
ELECTRIC UNIT HEATER,
1PH-208V-3KW
(MECH ITEM)
ELECTRIC UNIT HEATER,
1PH-208V-3KW
SAFETY SWITCH-C, 3PST, 240V, 30A
4#1/0 &
2 SETS OF 4-250KCMIL & #2(G) IN 103dia C.
2SET-4-250KCMIL & #2(G) IN 103C
IN 354C
2 SETS OF (4#250KCMIL)
4#1/0&1#6(G)
2#10&1#10(G)
2#12&1#12(G)
2#12&1#12(G)
2#12&1#12(G)
2#12&1#12(G)
FOR EXIST CONNECTED LOADS
RECONNECT TO EXIST SECONDARY LINE
7#12 IN 21C
1#6 IN 16C
NEW GROUNDING WIRE, 1#3/0 "BC" IN 27C.
CONNECTION
STEEL, 19dia x 3000LG WITH WELDING
NEW GROUND ROD, COPPER CLAD
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
MAIN PANELBOARD "MP" LOAD SCHEDULE
EXIST/NEW POWER ONE-LINE DIAGRAM &
RE-CONNECT TO EXIST U/G PRI LINE W/ ASSOCIATED DEVICES
PROTECTIVE DEVICES(RE-USE EXIST CONCRETE PAD)
OIL-FILLED, SELF-COOLED, LOAD BREAK SW. W/BUILT-IN
3PH, 11.4KV-120/208V, 60HZ, 300KVA, METAL ENCL. RADIAL TYPE,
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-10
TOTAL LOAD 53311
LOAD
TOTAL
PANELBOARD "PA" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MAIN 3P-225AF-150AT CIRCUIT BREAKER
751 751
1 10000100 2#12&1#12(G)
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
5 6
1200 1200
720 720
RCPTS 180VAx5 900
240 240
720 720 7 8
SPARE
TOTAL DEMAND LOAD ; 43,363(VA)
22Wx3, 4.99Wx1, FAN 80Wx1
LIGHT, LED 45Wx10, 50W x3, LIGHT, LED 120Wx10
LIGHT, LED 60Wx4
RCPTS 180VAx4
RCPTS 180VAx4
WASHER 600Wx1
WASHER 600Wx1
RCPTS 180VAx5
DRYER 5400Wx1
DRYER 5400Wx1
RCPTS 360VAx2
RCPTS 180VAx2
RCPTS 360VAx2
RCPTS 5000VAx1
RCPTS 5000VAx1
RCPTS 360VAx2
RCPTS 5000VAx1
RCPTS 5000VAx1
27002700
360 360
360 360
1667 1666
1667 1667 1666
1667 1667 1666
1667 1667 1666
1667 1667 1666
720 360 360
5000 1667 1667 1666
RCPTS 180VAx2
RCPTS 5000VAx1
RCPTS 5000VAx1
SPARE
SPARE 1000
2#10&1#10(G)
2#12&1#12(G)
3#10&1#10(G)
2#12&1#12(G)
2#12&1#12(G)
3#10&1#10(G)
4#1 & 1#6(G)
TOTAL LOAD 38231
LOAD
TOTAL
PANELBOARD "PB" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MAIN 3P-225AF-120AT CIRCUIT BREAKER
951 951
1 10000100 2#12&1#12(G)20
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
5 6
1080 1080
720 720
720 720
540 540 7 8
2#12&1#12(G)
3#10&1#10(G)
SPARE
22W x2, 4.99W x2, EXH FAN 45W x2
RCPTS 180VAx5
RCPTS 180VAx4
RCPTS 180VAx4
ELECTRIC WALL HEATER-1.0KW
TOTAL DEMAND LOAD ; 31,235(VA)
SPARE
RCPTS 360VAx1
LIGHT, LED 45Wx 3, 50Wx12,18Wx4, LIGHT, LED 120W x9
LIGHT, LED 120W x6
LIGHT, LED 60W x4
RCPTS 180VAx3
LAN/TEL
RCPTS 5000VAx1
RCPTS 5000VAx1
RCPTS 5000VAx1
RCPTS 5000VAx1
ROLL-UP DOOR
ROLL-UP DOOR
ROLL-UP DOOR
ROLL-UP DOOR
ROLL-UP DOOR
ROLL-UP DOOR
ROLL-UP DOOR
ROLL-UP DOOR
1667 1667 1666
5000 1667 1667 1666
5000 1667 1667 1666
5000 1667 1667 1666
1000 500 500
1000 500500
1000 500 500
1000 500 500
SPARE
500 500
500 500
1000 1000
500 500
4#4 & 1#8(G)
TOTAL LOAD 16640
LOAD
TOTAL
PANELBOARD "PC" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
1440 720
2 10000100 2#12&1#12(G)20
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
1440 720
2250 1125
2#12&1#12(G)
5583 5283 5774
TOTAL DEMAND LOAD ; 14,340(VA)
SPACE
SPACE
SPACE
SPACE
0.96KW
HEAT PUMP UNIT, 1PH, 220V,
1.15KW
HEAT PUMP UNIT, 1PH, 220V,
1.44KW
HEAT PUMP UNIT, 1PH, 220V,
1.74KW
HEAT PUMP UNIT, 1PH, 220V,
2.25KW
HEAT PUMP UNIT, 1PH, 220V,
ELECTRIC WALL HEATER-1.0KW
1/3HP
HOSE REEL W/ EXHAUST FAN,
1/3HP
HOSE REEL W/ EXHAUST FAN,
ROOF EXH FAN 1/4HPx2
CEILING FAN 20Wx3
1/3HP
HOSE REEL W/ EXHAUST FAN,
1/3HP
HOSE REEL W/ EXHAUST FAN,
1.44KW
HEAT PUMP UNIT, 1PH, 220V,
500 167 167 166
167 167 166500
ROOF EXH FAN 1/4HPx2 800 800
500 167
167 167
167 166
480480
870870
575 575
SPARE
SPARE
2#12&1#12(G)
2#12&1#12(G)
3#12&1#12(G)
SPACE - - - -
SPACE
SPACESPACE
SPACE
SPACE
SPACE
17233 16522 19556 13319 12308 12604
MAIN 3P-100AF-70AT CIRCUIT BREAKER
60HZ, SN & GND, SURFACE
60HZ, SN & GND, SURFACE 60HZ, SN & GND, SURFACE
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
LOAD SCHEDULE
NEW PANELBOARD "PA", "PB" & "PC"
4#1/0 & 1#6(G)
MECH ROOM
FEC
S
S
LATRINE
WOMEN'S
LATRINE
MEN'S
VEST
J/C
TOOL ROOM
ROOM
LAUNDRY
OFFICE
INSPECTOR
OFFICE
FOREMAN
OFFICE
SHOP CONTROL
L/S
W WD BB
STORAGE
EQUIPMENT
D
E-11
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
F
M F
F
F
F
F
M F
F M
C P
F T
R
TS TS
J
PSTS
J
TS
J
J
TS
CO
SCALE:
1/100
COMBINED ADDRESSABLE FIRE ALARM/
FTR BUILDING TRANSMITTER W/BATTERY &
BATTERY CHARGER, NEMA 1 ENCL
W/MOUNTING BARCKET
OMNI-DIRECTION TYPE
FIRE ALARM ANTENNA
DIGITAL VOICE PANEL W/AMPLIFIER & BACK
SYNCHRONIZATION CONTROL MODULE,
24VDC, BUILT-IN ADDRESSABLE POINTS
UP AMPLIFIER (AS REQ'D) & MICROPHONE,
POWER MODULES PANEL(AS REQ'D) AND
MICROPHONE, BATTERY, BATTERY CHAREGER,
MODULE & RELAYS LCD ANNUNCIATOR,
MODULES AS REQ'D, PROGRAMMABLE
MASS NOTIFICATION CONTROL PANEL,
POWER SUPPLY, DIGITAL VOICE MODULE,
FMCP
W/WORDS "FIRE" + MNS-AMBER STROBE
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
WP
F ADDRESSABLE MANUAL PULL STATION
SPEAKER (WATTAGE AS REQ'D)
FIRE ALARM/MASS NOTIFICATION
WALL MOUNTED "WP" TYPE,
* ADDITIONAL LEGEND (THIS SHEET ONLY)
(15 CANDELA MINIMUM, AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
SHALL BE DE-RATED AS REQUIRED)
TAMPER SWITCH
(UNDER MECH ITEM) (TYPICAL)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
PS
J
TS
J
(UNDER MECH ITEM)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
PRESSURE SWITCH
ADDRESSABLE SMOKE DETECTOR
NOTES
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES,1.
3.
EXTERIOR AESTHETICALLY.
2. FIRE ALARM AND MASS NOTIFICATION SYSTEM LAYOUT
IS CONCEPTUAL. FINAL DESIGNER SHALL COMPLETE
DESIGN IN ACCORDANCE WITH THE APPLICABLE CODE,
SPECIFICATIONS AND MANUFACTURER'S EQUIPMENT
LISTING.
SEE SHEET NO. E-1.
FOR THE LOCATION OF OUTDOOR FIRE ALARM & MNS
DEVICES, IT SHALL BE COORDINATED WITH THE BUILDING
NEMA 1 ENCL, (SEMI-FLUSH MOUNTED)
M F
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
NEW GROUND FLOOR FIRE ALARM/MASS NOTIFICATION PLAN
NOTIFICATION PLAN
NEW GROUND FLOOR FIRE ALARM/MASS
D T
D ADDRESSABLE DUCT SMOKE DETECTOR
T
CO ADDRESSABLE CARBON MONOXIDE DETECTOR
DUCT SMOKE DETECTOR TEST
ACTIVATION OF A CARBON MONOXIDE DETECTOR MUST
SEND A SEPARATE "CARBON MONOXIDE DETECTOR" ALARM
SIGNAL TO THE FIRE ALARM REPORTING SYSTEM (BUILDING
TRANSMITTER).
4.
FOR EMERGENCY SHUT-DOWN
CONNECT TO W.A.F CONTROLLER
F
F
F
FFF
F
F
F
F
F
F F
F
F /M
F/MF/MF/M
F/M
F /M
F/M
F/M
F /M
F /M
F/M F/M
F /M
F/M
F /M
/M
FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM
NOT TO SCALE
NOTES:
NFPA 72, 2013 EDITION.
PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT
CONTRACTOR SUBMITS SHOP DRAWINGS.
THE VOLTAGE DROP AND POWER SUPPLY CALCULATION
SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE
4.
(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.
ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
MANUFACTURER'S LISTED INSTALLATION
2.
CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL
13.
12.
11.
9.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT
PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION
VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL
ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED
ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT
COORDINATE THE EXACT DEVICE LOCATIONS WITH
SWITCHES AND NON-ADDRESSABLE INITIATION
ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE
PROHIBITED FOR ALL IDC, NAC AND SLC.
ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.
7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE
SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL
10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN
3.
5.
6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE
ALARM CIRCUIT AND ROOM LOCATION OF PANEL
LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED
FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED
THE FIRE ALARM/MASS NOTIFICATION SYSTEM
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,
WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE
POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.
SHALL BE INDICATED ON THE FIRE ALARM/MASS
BUILDING TRANSMITTER AND ANTENNA.
AND 305mm VERTICALLY.
DEVICES SHALL BE PROVIDED WITH CLASS "B"
THE SYSTEM FOR READY TO USE. THE NUMBER OF
DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE
FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE
DEVICE LOCATIONS IN ACCORDANCE WITH THE
AND BUILDING ARCHITECTURAL FEATURES.
OR FM APPROVED.
SPECIFICATION SECTION 28.31.76.00.31 (FA) AND
HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES
PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.
18.
19.
20.
PER UFC 4-021-01.
17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE
NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED
AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT
LEAST FOR THE FOLLOWING ITEMS.
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
STROBES FOR MASS NOTIFICATION SHALL BE MARKED
STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"
"ALERT" IN RED LETTER AND W/AMBER LENS.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
1.
AND W/CLEAR LENS.
15.
CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2
& 24.4.1.8.2.
THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE
ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM
ON THE PANEL BY SWITCH.
THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED
MASS MESSAGE IS REQUIRED TO BE ANNOUNCED
IMMEDIATELY UNTIL SHUTDOWN MANUALLY.
SPECIFICATION SECTION 28.31.76.00.31 (MNS)
THE CONTRACTOR SHALL PROVIDE THE REQUIRED
TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS
16.
DEVICE LOCATIONS IN ACCORDANCE WITH THE
MANUFACTURER'S LISTED INSTALLATION
AND NFPA 72, 2013 EDITION.
APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY
ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION
MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.
ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.
23.
MASS VISUAL APPLIANCE LOCATION REQUIREMENTS
AS SHOP DRAWING SUBMITTALS.
CONTRACT DRAWINGS SHALL NOT BE SUBMITTED
ARMY AND AIR FORCE PROJECTS.
WITH ANY FIRE ALARM VISUAL APPLIANCES ON
MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.
25.
22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE
AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM
ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.
SHALL BE SYNCHRONIZED.
VOICE EVACUATION SPEAKERS, NEPA 72.
AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD
TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES
USED.
26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL
EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.
SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND
ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.
SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS
REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.
BOTH KOREAN AND ENGLISH.
THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.
APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
ALARM AND DETECTION SYSTEM.
NOTIFICATION CONTROL PANEL COVER.
MODULES.
SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO
REQUIRED.
WITH THE APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
OF 20% SPARE ADDRESSES FOR FUTURE USE.
FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.
SEE SHEET NO. E-1.
2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING
1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING
3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING
6) "ALL CLEAR" MESSAGE
TEST8)
THE BUILDING
CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)
THE LOCAL AREA
5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR
NORMAL MAIN ENTRANCE/EXIT
4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SYSTEM DIAGRAM
FIRE ALARM/MASS NOTIFICATION
E-12
24VDC, BUILT-IN ADDRESSABLE POINTS MODULES AS REQ'D,
(AS REQ'D) & MICROPHONE. NEMA 1 ENCL
DIGITAL VOICE PANEL W/AMPLIFIER & BACK UP AMPLIFIER
BATTERY CHAREGER, POWER MODULES PANEL (AS REQ'D) AND
SYNCHRONIZATION CONTROL MODULE, POWER SUPPLY,
PROGRAMMABLE MODULE & RELAYS, LCD ANNUNCIATOR,
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL (FMCP),
COMBINED ADDRESSABLE
DIGITAL VOICE MODULE, MICROPHONE, BATTERY,
FIRE ALARM/MASS NOTIFICATION
CONTROL PANEL (FMCP)
1st FL.
FTR
16#14 IN 21C(FOR SIGNAL)
2#12 IN 16C(FOR POWER)
(PROGRAM OF D-21 MONACO
BUILDING TRANSMITTER
BT-XM AT LEAST 16 ZONES)
#6 "BC" IN 21C
GROUND CONDUCTOR
COAXIAL CABLE
W/CONNECTORS IN 16C
OMNI-DIRECTION TYPE
FIRE ALARM ANTENNA
W/MOUNTING BRACKET
GROUND ROD, COPPER CLAD
WITH WELDING CONNECTION
STEEL, 19mmdia x 3000mmLG
"EM"SG
G ~
G
CONTROL PANEL & BOOSTER PANEL)
(INSTALLED BESIDE FIRE ALARM
(RATED AS REQ'D) (TYPICAL)
SURGE PROTECTOR
2#12 & 1#12(G) IN 16C
GROUND ROD, COPPER CLAD
GROUNDING SYSTEM #6, "BC" IN 21C
CONN TO BLDG ELECTRODE
STEEL, 19mmdiax3000mmLG
WITH WELDING CONNECTION AND
ENCLOSURE
LIGHTNING ARRESTER
W/WEATHER-PROOF
F
F M
EXT
WP
101 108
W/BATTERY & BATTERY
CHARGER, NEMA 1 ENCL
VISUAL SIGNAL STROBES (75 CANDELA
MINIMUM, AMBER STROBE SHALL BE
MNS-AMBER STROBE W/WORDS "ALERT")
(FA-CLEAR STROBE W/WORDS "FIRE" +
DE-RATED AS REQUIRED) (TYPICAL)
WALL MOUNTED COMBO.
W/WORDS "FIRE" + MNS-AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
ADDRESSABLE MANUAL
PULL STATION (TYPICAL)
WALL MOUNTED "WP" TYPE,
NOTIFICATION SPEAKER
FIRE ALARM/MASS
(WATTAGE AS REQ'D) (TYPICAL)
SHALL BE DE-RATED AS REQUIRED) (TYPICAL)
ADDRESSABLE SMOKE
DETECTOR
TS
J
TS
J
TS
J
PS
J
110 110 110
TAMPER SWITCH
(UNDER MECH ITEM) (TYPICAL)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
(UNDER MECH ITEM)
FOR SPRINKLER SYSTEM
W/ADDRESSABLE MODULE
PRESSURE SWITCH
F
F 101110
F
ROOF FL.
F M
EXT
WP
101 101
102107 101
(15 or 75 CANDELA MINIMUM, AMBER STROBE
109 112
104 103
F 110 110
F M
EXT
WP
F M
EXT
WP
CARBON MONOXIDE
CO
MODULE
DETECTOR W/ADDRESSABLE
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
D
T
ADDRESSABLE DUCT SMOKE
DETECTOR W/TEST
MECH ROOM
FEC
FEC
S
S
EWC
LATRINE
WOMEN'S
LATRINE
MEN'S
VEST
J/C
TOOL ROOM
D3
ROOM
LAUNDRY
OFFICE
INSPECTOR
OFFICE
FOREMAN
OFFICE
SHOP CONTROL
L/S
W WD BB
STORAGE
EQUIPMENT
D
FEC
FEC
E-13
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
TTC
L A
N
T
T
T
T
T T
T
T
T
T
T
T
T
2-4PAIR, #24AWG, CAT-6
TEL WIRE IN 16C
PATCH PANELS
TO BE TERMINATED AT
(TYP)
1-TEL/1-LAN OUTLET, CAT6
W/ RACK MOUNTED 6-SINGLE
REAR RECEPTACLE, ON-OFF
SWITCH & CORD, 2P-3W-20A-125V
POWER SURGE PROTECTION
SCALE:
1/100
NEW GROUND FLOOR LAN/TEL SYTEM PLAN
WALL MOUNTED EQUIPMENT CABINET
NEW TELEPHONE TERMINAL CABINET ("TTC")
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
NEW GROUND FLOOR LAN/TEL SYTEM PLAN
EXOTHERMIC WELDING, LISTED COMPRESSION TWO-
1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR
TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE
HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE
"MP" GROUNDING BUS BAR
1#6 "BC" IN 21C
CONN TO MAIN PANELBOARD
TEL SYSTEM DIAGRAM
NOT TO SCALE
STAMP FACING OUT" TO ENSURE THAT THEY CAN BE
3. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT
REVISION OF THE ANSI/TIA/EIA-568.
4. LABEL ALL DROPS IAW TIA/EIA-606-A.
5. LABEL ALL GROUNDS IAW I3A.
LUGS ARE PREFERRED.
FIELD VERIFIED.
TO TELEPHONE PATCH PANEL
TGB
CONN TO TMGB
1#6 "BC" IN 27C
(100mm x 450mmLG x 6.4mmTHK)
GROUND BUS BAR(TGB)
TMGB
G
(TYPICAL)
CABLE SUPPORT
G
110TYPE TERMINAL BLOCK
(2-100PAIR) FOR TEL
(TYPICAL)
CROSS CONNECTION CORD AS REQ'D
PLUS 25% SPARES TO BE FURNISHED BY THE
1#6 "BC" IN 16C
G
FOR TELEPHONE
1-24PORT PATCH PANEL
TO EACH DATA OUTLET AS REQ'D
TO EACH TEL OUTLET AS REQ'D
AS REQ'D
PROVIDE PATCH CORDS
HUB(N.I.C)
1-24PORT PATCH PANEL
FOR DATA
W/ RACK MOUNTED 6-SINGLE
REAR RECEPTACLE, ON-OFF
SWITCH & CORD, 2P-3W-20A-125V
GROUND BUS BAR(TGB)
TELECOMMUNICATION
TELECOMMUNICATION MAIN
PTB
CONTRACTOR
RECEPTACLES
(1-100PAIR)
ENTRANCE TERMINAL BLOCK
110 TYPE PROTECTED
G
2. "PLYWOOD WILL BE INSTALLED WITH FIRE RATED
NOTE.
SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.
SYSTEM AND WIRING FOR GOVERNMENT APPROVAL. TELECOMMUNCATION WORK
6. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAILED TELECOMMUNICATION
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
TEL SYSTEM DIAGRAM
E-14
TELEPHONE TERMINAL CABINET ("TTC")
WALL MOUNTED EQUIPMENT CABINET
1-12CORE, FIBER OPTIC CABLE IN 53C.
1-25PAIR, #24AWG TEL CABLE IN 53C.
PATCH PANEL W/"SC" CONNECTOR
1-12 STRAND FIBER OPTIC
PB-9
QUAD-PLEX RECEPTACLE
2P-3W-125V-20A GND TYPE
WITH DEDICATED CIRCUIT
107SHOP CONTROL OFFICE
(WI/ FIRE RATED PLTWOOD)
CP CASEY
REPAIR BUILDING S-2399,
TAK, YS
160851
(BUILDING S-2399)
ELECTRICAL
(24"(W)x36"(H)x30"(D)
POWER SURGE PROTECTION
| E-1 |
| E-2 |
| E-3 |
| E-4 |
| E-5 |
| E-6 |
| E-7 |
| E-8 |
| E-9 |
| E-10 |
| E-11 |
| E-12 |
| E-13 |
| E-14 |