GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

PANELBOARD SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

350mm TO CENTER OF THE ENCL

MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL

3.

4.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

7.

5.

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT

THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING

TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.

DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT

F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

SCOPE OF WORKS

LEGEND, GENERAL NOTES AND

E-1

12.

13.

14.

10.

11.

8.

9.

15.

SINGLE POLE TOGGLE SWITCH, 15A-125V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

S

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

T

J

THERMOSTAT (UNDER MECH. ITEM)

JUNCTION BOX

SYMBOL

SYMBOL

F FAN MOTOR (UNDER MECH. ITEM)

SAFETY SWITCH

C CONTROL CIRCUIT

3-WAY SWITCH, 15A-125V

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

CABNET TYPE, RATED WATT ON LTG SCHEDULE

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER

ON LTG SCHEDULE, WET LOCATION

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

FAULT PROTECTED TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

PANELBOARD

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

FIXTURE A MINIMUM DISTANCE OF 458mm.

FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING

FMCP

FTR

AUXILIARY

DESCRIPTIONSYMBOL

STROBES

WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL

BUILDING TRANSMITTER UNIT FOR FIRE ALARM

SYSTEM

L

WP

FAULT PROTECTED TYPE, WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED

TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING

L

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

L

W/EMERGENCY UNIT TYPE

QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

UNITS.

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

16.

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING

THE MANUFACTURER AND MODEL OF NEW BUILDING TRANSMITTER EQUIPMENT

IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE TESTED WITH THE RECEIVING SYSTEM(D21)

SHALL BE COORDINATED WITH THE CENTRAL FIRE DEPARTMENT.

RECEPTACLE

AND WALL

WIRING CONCEALED OR EXPOSED IN/ON THE CEILING

CEILING OR CONCEALED IN NEW WALL.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

SCOPE OF WORK

1.

A. REPAIR/MAINTENANCE ( K )

4.

2.

6.

5.

3.

7.

3S

WITH NEW.

RECEPTACLES W/COVER PLATES ASSOCIATED WIRING & CONDUITS

REPLACE EXISTING PANELBOARDS, WATTHOUR METER W/CT'S,

AND ASSOCIATED WIRING AND CONDUIT.

75 CANDELA), MICROPHONE, SPEAKER (WATTAGE AS REQ'D) DEVICE

BUILDING TRANSMITTER, ANTENNA, VISUAL/SIGNAL STROBES (15 OR

PANEL, MANUAL PULL STATION, SMOKE DETECTOR & RELAY MODULE,

ADDRESSABLE FIRE ALARM CONTROL AND MASS NOTIFICATION SYSTEM

REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH NEW

AND ACCESSORIES WITH NEW.

REPLACE EXISTING EXTERIOR UNDERGROUND TELECOMMUNICATION LINE

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

SYSTEMS AND ROLL-UP DOORS WITH NEW.

JUNCTION BOXES, CONTROL/POWER WIRES AND CONDUITS FOR MECHANICAL

REPLACE DETERIORATED EXISTING SAFETY SWTICH, MOTOR CONTROLLERS,

UNDERGROUND EXTERIOR SECONDARY LINE AND ACCESSORIES WITH NEW.

REPLACE EXISTING PAD MOUNTED TRANSFORMER, OVERHEAD &

& CONDUIT WITH NEW.

PLATES, TERMINAL BLOCKS, EQUIPMENT CABINET AND ASSOCIATED WIRE

TELEPHONE TERMINAL CABINET, TELEPHONE/DATA OUTLETS W/COVER

REPLACE DETERIORATED EXISTING TELEPHONE SYSTEM INCLUDING

AND CONDUITS WITH NEW.

LIGHTS, EXTERIOR LIGHTS, TOGGLE SWITCHES, 3-WAY SWITCHES, WIRES

REPLACE DETERIORATED EXISTING INTERIOR LIGHTING FIXTURES, EXIT

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING

TYPE WITH PLUG

SINGLE RECEPTACLE, 2P-3W-20A-125/250V, GROUNDING

30L

FIRE ALARM & MNSCONTROL PANEL

F

F/M

FIRE ALARM & MNS CIRCUIT

T LAN/TEL LINE

2372A

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-2

SCALE: 1/300

W/BUILT-IN PROTECTIVE DEVICES (15A FUSE)

3PH, 11.4KV-120/208V(DELTA-WYE), 60HZ, 300KVA

DEAD-FRONT TYPE, LOAD BREAK SW,

METAL ENCL, OIL-FILLED, SELF-COOLED,

RADIAL TYPE TRANSFORMER

EXIST O/H SEC. LINE

EXIST O/H SEC. LINE

EXIST O/H PRI. LINE

NEW U/G SEC. LINE

3-1/C, #1, 24KV, "XLP" AND 1/C, #1, 600V, "XLP"

NEW U/G PRIM. LINE

ACCESSORIES.

EXIST SECONDARY LINE WITH NEW ASSOCIATED

RECONNECT NEW SECONDARY LINE TO

P

P

P S

S

S

S

S

S

S O /H

O /H

O /H

O /H

O /H

10m2.5m0

SCALE: 1:300

5m

EXIST O/H PRI. LINE

EXIST/NEW EXTERIOR POWER LINE DISTRIBUTION PLAN

NEW ENTRANCE CAP AND SEC. RACK

O/ H

S

O/ H

S

S

EXIST ELECTRIC POLE (TYP.)

REPLACE WITH NEW PAD MOUNTED

W H

MAND SERVICE ENTRANCE.

REMOVE EXISTING SERVICE SECONDARY LINE

NEW WATT HOUR METER AND CT'S

NEW O/H SEC. LINE 4-AWG#4"WP"(TYP.)

2 SETS OF 4-250MCM IN 103C

/TURN-IN EXIST PAD MOUNTED TRANSFOMER TO DPW

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUIDLING S-2399)

ELECRICAL

DISTRIBUTION PLAN

EXIST/NEW EXTERIOR POWER LINE

"P"

NEW 4-AWG#2 &1#8(G) IN 35C

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-3

10m2.5m0

SCALE: 1:300

5m

SCALE: 1/300

C O

U R

T B

A S

K E

T B

A L

L

F

MH7

MH7-2

MH7-1-A

C

C

C

C

C

P

P

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

NOTES

TO FIX NEW TELECOM CABLES WHEN ACROSSING

CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS

SEE SHEET NO. E-1.

1.

2.

UNDER THE BRIDGE.

3.

THE CONTRACTOR SHALL VERIFY EXISTING4.

UNDERGROUND TELECOMM LINE'S ACTUAL

CONDITION PRIOR TO WORK.

NEW SINGLE MODE FIBER OPTIC CABLE

AND TELEPHONE CABLE SHALL BE INSTALLED

ON THE EXISTING/NEW MANHOLES AND TYPE OF

SPLICE KITS SHALL BE COORDINATED WITH

BASE SIGNAL COMPANY.

FIBER OPTIC CABLE IN EXIST U/G DUCT

NEW 1-12 CORE STRAND SINGLE MODE

MH7-1-B

1WAY: FABRIC MESH 3" 3CELL(1PACK)

2EA: SPARE WITH PULL WIRE

FIBER OPTIC CABLE

INNER DUCT

1EA: 1-12 STRAND SINGLE MODE

NEW 2WAY OF 103mm PVC CONDUIT IN NEW U/G CONC. DUCT

1WAY: EMPTY CONDUIT W/ PULLING WIRE

SPLICE TELECOMMUNICATION CABLE WITH

NEW SPLICE KIT FOR 1-12 CORE

FIBER OPTIC CABLE

INNER DUCT

1WAY: FABRIC MESH 3" 3CELL(1PACK)

2EA: SPARE WITH PULL WIRE

FIBER OPTIC CABLE

1WAY: 1-25 PAIR AWG#24 TELEPHONE CABLE

1EA: 1-12 STRAND SINGLE MODE

IN NEW U/G CONC. DUCT

NEW 2WAY OF 103mm PVC CONDUIT

DRAWINGS

(SMALL), SEE 2014 OMA STANDARD DETAIL

NEW TELECOMMUNICATION MANHOLE

NEW PULLBOX "WP"

SPLICE 1-25PAIR TELEPHONE CABLE

EXIST TELEPHONE PEDESTAL/

IN NEW 103C

NEW U/G 1-25 PAIR TELEPHONE CABLE

OFFICE

SHOP CONTROL

TERMINAL CABINBET FOR TELEPHONE CABLE.

FIBER OPTIC CABLE AND TERMINATE AT TELEPHONE

AT FIBER OPTIC PATCH PANEL IN NEW LAN CABINET FOR

1-25 PAIR TELEPHONE CABLE IN 54 C./ TEMINATE

NEW 1-12 CORE FIBER OPTIC CABLE IN 54 C. AND

EXIST TELECOMMUNICATION CABLE

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUIDLING S-2399)

ELECRICAL

LINE DISTRIBUTION PLAN

EXIST/NEW EXTERIOR TELECOMMUNICATION

EXIST/NEW EXTERIOR TELECOMMUNICATION DISTRIBUTION LINE PLAN

SHOP AREA

MECH ROOM

S /S

EWC

LATRINE

WOMEN'S

LATRINE

MEN'S

VEST

J/C

TOOL ROOM

ROOM

LAUNDRY

OFFICE

INSPECTOR

OFFICE

FOREMAN

OFFICE

SHOP CONTROL

BB

STORAGE

EQUIPMENT

FEC

E-4

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

LL L

L

L

L

L

L

L

L

LL

LL

LL

L

L

L

LL

L

L

L L

L

S S

S S

S

S

S S

S S

S

S S

S

S S

S

S S

S

S

S

EP

EP

EP

S

L

LL

L

S S

L L L L

L L L L

L

L L

L

L

SCALE:

NEW GROUND FLOOR LIGHTING PLAN

S

"PC"

"PA"

"PB"

EP

EF-1J

EF-1J

JEF-1

S

PA-1

PA-2

PB-1

PB-2

PB-3

PB-4

PA-3

PA-4

L

L

L

L

L

L

L

L

L

L

L

L

L

L L

L

L

L

L

L

L

L

L

L

L

L

L

(TYP OF 5)

EXISTING EXTERIOR BAY LIGHT TO REMAIN

(TYP OF 3)

NEW EXTERIOR BAY LIGHT TYPE "NS-10"

EXISTING BAY FLOOD LIGHT TO REMAIN

(TYP OF 21)

NEW BAY FLOOD LIGHT TYPE"NS-9"

(TYP OF 4)

(TYP OF 5)

EXIST EXTERIOR LIGHT

(TYP OF 4)

EXIST EMERGENCY LIGHT

1/100

NOTE.

1.

LIGHTING FIXTURES TO MEET THE SITE CONDITION.

CONDITION AND PROVIDE NEW WIRING TO NEW AND EXISTING

CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY EXISTING SITE

L L

L L

J J

J J

EPEP

EPEP

PROOF TYPE (TYP)

JUNCTION BOX EXPLOSION NEW LED PIT LIGHT TYPE "NS-4" /

(TYP OF 4EA)

TO MATCH WITH EXSTING WALL CONDITION

REPAIR CONCRETE WALL AFTER INSTALLATION

(UNDER MECH ITEM)

(UNDER MECH ITEM)

(UNDER MECH ITEM)

EXH. FAN-1, 120V, 80W

EXH. FAN-1, 120V, 80W

EXH. FAN-1, 120V, 80W

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

NEW GROUND FLOOR LIGHTING PLAN

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-5

CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)

NS-10

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND

ACCESSORIES AS REQUIRED, (NS-6a) & EM UNIT(NS-6b)

415 415

CEILING PENDANT MOUNTED LED LIGHT FIXTURE,

ACCESSORIES

LUMINOUS EFFICACY 110L/W, WITH CONVERTER &

13,200LM, 5700K, IP RATING 65, 430 X 273(H)mm, 3.5KG

1PH, 120V, 120W LED LAMP,

DIODE(LED) EXIT LIGHT FIXTURE 1PH, 120V, 4.99W

WALL SURFACE MOUNTED LIGHT EMITTING

NS-7

NS-6a & 6b

NS-8

100 WALL

245mm

254mm

NS-5a & 5b

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,

CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED) FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES

WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

WET LOCATION SHOWER LIGHT TRIM, UL LISTED POWER UNIT

AS REQUIRED, UL LISTED POWER UNIT

WALL MOUNTED LIGHT EMITTING DIODE(LED) LIGHT

FIXTURE, 1PH, 120V, 50W, UL LISTED, WITH CONVERTER &

ACCESSORIES, (NS-5a) & WITH EM UNIT (NS-5b) AS REQUIRED

NS-3

(MAX. INPUT), BATTERY BACK-UP WITH BATTERY CHARGER

WET LOCATIONS TYPE(IP66), UL LISTED

FIXTURE, 1PH, 120V, 60 WATT, CONVERTER AND ACCESSORIES

NS-4

NS-9

21dia (100LG)

STEEL CONDUIT

UNION, 21dia

EXPLOSION PROOF TYPE (CLASS 1, DIVISION 1)

STEEL CONDUIT

21dia (100LG)

RIGID SUPPORT

UNION, 16dia

WIRE GUARD

LIGHT

LED LIGHTING FIXTURE, 1PH, 120V

28WATT LAMP W/WIRE GUARD AND SUPPORT HOOK

JUNCTION BOX "EF"

CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

LIGHTING FIXTURE DETAILS

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-6

REMARKSMOUNTING METHODQ'TY

NO

SHT

WATTSTYPE

LAMP

NAME

ROOM

TYPE

LIGHT FIXTURE SCHEDULE

OCE STD DET 40-06-04

NO

LED 4-

3-

1-

18 1-

NS-6b

2-

1-

- 2

45 1NS-4b

NS-4a

1-

2-

109 45 1-

1-

1 W/"EM" UNIT-

45 1-

NS-10 3- WALL MOUNTED60

ABOVE THE DOOR TOPWALL MOUNTED4.99NS-3

EXTERIOR

EXIT

50 6-

ABOVE THE MIRROR TOP

W/"EM" UNIT

W/"EM" UNIT

W/"EM" UNIT

W/"EM" UNIT

W/"EM" UNIT

W/"EM" UNIT

W/"EM" UNIT

W/"EM" UNIT

CEILING SURFACE

NS-5b

NS-5a 50

NS-5b

NS-5b

NS-5a

NS-5b

1-

1-

1-

WALL MOUNTED

SHOP AREA

OFFICE

INSPECTOR

LATRINE

WOMEN'S

LATRINE

MEN'S

VEST

J/C

OFFICE

SHOP CONTROL

OFFICE

FOREMAN

TOOL ROOM

MECH ROOM

STORAGE

EQUIPMENT

ROOM

LAUNDRY

120 CEILING PENDANT NS-9

CEILING SURFACE

CEILING SURFACE

NS-8

CEILING SURFACE

CEILING SURFACE

WALL MOUNTED ABOVE THE MIRROR TOP

NS-8

NS-7

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

CEILING SURFACE

NS-6b 45 1- CEILING SURFACE

NS-6a

W/"EM" UNIT

CEILING SURFACE

CEILING SURFACE

NS-6a

NS-6b 45

CEILING SURFACE

CEILING SURFACE

NS-6b

NS-6a

CEILING SURFACE

CEILING SURFACE

NS-6b

NS-6a

CEILING SURFACE

CEILING SURFACE

ABOVE THE BAY DOOR TOP

NS-4 50 4- WALL MOUNTED IN INSPECTION PIT

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

LIGHT FIXTURE SCHEDULE

MECH ROOM

S /S

LATRINE

WOMEN'S

LATRINE

MEN'S

VEST

J/C

TOOL ROOM

ROOM

LAUNDRY

OFFICE

INSPECTOR

OFFICE

FOREMAN

OFFICE

SHOP CONTROL

L/S

W WD

STORAGE

EQUIPMENT

D

E-7

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

EP

SCALE:

1/100

W H

M

"MP"

30 30

"PA"

"PB"

PA-8

EP

CT'S

PA-5

PA-6

PA-7

"WP"

"WP"

"WP"

"WP"

"WP" "WP"

PA-9

PA-10

PA-12

PA-13

PA-14

PA-15

PA-16

PA-22

PA-18

PA-21

PA-20

PB-5

PB-6

PB-7

PB-8

PB-10

PB-11

PB-15

"PC"

PA-19

PB-14

PB-13

PB-12

NEW GROUND FLOOR POWER PLAN

J

PB-19

A

PB-18

PB-17

J A

PB-16

J

A J

PB-20

J

PB-21

A

PB-22

A

J

A

J

J

PA-11

PA-17

PB-9

"WP"

NOTE.

1.

TO MEET THE SITE CONDITION.

CONDITION AND PROVIDE NEW WIRING TO NEW RECEPTACLES

CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY EXISTING SITE

2.

DEVICES BY COORDINATING WITH DPW.

CONTRACTOR SHALL REMOVE ABANDONED OR UNUSED ELECTRIC

A A

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

NEW GROUND FLOOR POWER PLAN

3-AWG#10 & 1#10(G) IN 21C (TYPICAL)

ROLL-UP DOOR, 1PH, 208V, 1HP

W/ PUCH BUTTON SWITCH

(ARCH ITEM) (TYP. OF 8)

(TYPICAL FOR DRYERS)

2-AWG#10 & 1#10(G) IN 21C

MOUNTING HEIGHT: 1150mm(TYP OF 10)

SINGLE RECEPTACLE, 3P, 4W, 240V

"WP"

MECH ROOM

FEC

S /S

LATRINE

WOMEN'S

LATRINE

MEN'S

VEST

J/C

TOOL ROOM

ROOM

LAUNDRY OFFICE

INSPECTOR

OFFICE

FOREMAN

OFFICE

SHOP CONTROL

STORAGE

EQUIPMENT

D

FEC

"PA"

"PB"

E-8

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

SCALE:

1/100

(UNDER MECH ITEM)JHR

J HR

PC-5

A

3PH-208V-4.5KW

(UNDER MECH ITEM)

NEW ELECTRICAL HOT

WATER HEATER

WAF

(TYP. OF 3)

JHR

J HR

HPU

-1

HPU

-4

HPU

-3

HPU

-3

HPU

-5

J J J JEF-2 EF-2 EF-2 EF-2

CF-1J CF-1JCF-1J

PC-10

J

HPU

-2

(TYP. OF 4EA)

(UNDER MECH ITEM)

CEILING EXH. FAN, 120V, 20W

EH

EH

PC-4

B

B B

B B

B

MECH ROOM

WAF

J

EWHJ

T V

EF-3

EUH

AC

(UNDER MECH ITEM)

ROOF EXH. FAN, 120V, 1/4HP

(TYP. OF 4)

"MP"

"PC"

PC-1

PC-2

PC-3

PC-6

PC-7

PC-8

PC-11

PC-12

PC-13

PC-14

PC-15

SCALE:

MP-6

MP-8

MP-7

MP-5

MP-4J

T

T

T

T

NEW MECHANICAL ROOM POWER/CONTOL PLAN

1/50

FOR MECHANICAL EQUIPMENT

NEW GROUND FLOOR POWER & CONTROL PLAN

(TYP. OF 6)

(UNDER MECH ITEM)

HEAT PUMP UNIT, 1PH, 220V, 0.96KW

(UNDER MECH ITEM)

HEAT PUMP UNIT, 1PH, 220V, 1.15KW

(UNDER MECH ITEM)

HEAT PUMP UNIT, 1PH, 220V, 1.44KW

(UNDER MECH ITEM)

HEAT PUMP UNIT, 1PH, 220V, 1.74KW

(UNDER MECH ITEM)

HEAT PUMP UNIT, 1PH, 220V, 2.25KW

NON-FUSIBLE, NEMA 3R ENCL.

(TYPICAL)

3#12 & 1#12(G) IN 16C

(TYPICAL)

3#12 & 1#12(G) IN 16C

3#10 & 1#10(G) IN 21C

2#10 & 1#10(G) IN 21C

NON-FUSIBLE, NEMA 3R ENCL.

HOSE REEL W/ EXHAUST FAN, 3PH, 200V,1/3HP

PC-9

(UNDER MECH ITEM)

EXH. FAN, 120V, 1/4HP

JMP-8 P

SAFETY SWITCH-B, DPST, 240VAC, 30A, C

SAFETY SWITCH-C, 3PST, 240VAC, 30A,

B A

B A

A A

(MECH ITEM)

CEILING FAN CONTROLLER

POWER /CONTROL PLAN

SEE NEW MECHANICAL ROOM

NEW PANELBOARD "PA"

NEW PANELBOARD "PB"

NEW PANELBOARD "PC"

B B

COIL VOLTAGE 120V, NEMA 1 ENCL. (TYP.)

120V, NEMA SIZE 0, "H-O-A" SEL. SWITCHES, PILOT LIGHTS,

MAGNETIC MOTOR STATRER W/O.L RELAYS, 2P,

COIL VOLTAGE 120V, NEMA 1 ENCL. (TYP.)

240V, NEMA SIZE 0, "H-O-A" SEL. SWITCHES, PILOT LIGHTS,

COMBINATION TYPE MOTOR STATRER W/O.L RELAYS, 3P,

(UNDER MECH ITEM)

ELECTRIC WATER HEATER, 1PH,

220V, 4.5KW(UNDER MECH ITEM)

PUMP, 1PH, 120V, 1/6HP

HOT WATER CIRCULATION

(UNDER MECH ITEM)

ELECTRIC UNIT HEATER, 1PH, 208V, 3KW

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

PLAN FOR MECHANICAL EQUIPMENT

NEW GROUND FLOOR POWER & CONTROL

EXIST WARM AIR FURNACE,

3PH, 208V, 2HP

500AT

600AF

225AF

3P

3P

225AF

3P

CONDUCTOR, #2(G) IN 21C

NEW GROUNDING

3PH, 4W, 120/208V, 60HZ

SYSTEM, NEMA 1 ENCL

CU BUS, 400A

42,000AIC SYM

G

S/NGND

MAIN PANELBOARD "MP"

WHM

TR TYPE, W/CT'S 500/5Ax3EA

120/208V, 60Hz SYSTEM, NEMA 3R ENCL.

AND 15MIN DEMAND REGISTER FOR 3PH, 4W,

WITH NEW ADVANCED DIGITAL WATTHOUR METER,

321 5

"PB"

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES1.

NOTES

EXIST/NEW POWER ONE-LINE DIAGRAM

NOT TO SCALE

1#6(G)

IN 53C

REPLACE THE DETERIORATED EXISTING WHM

NEW U/G SEC LINE,

SPARE

101101

120AT

4#1 &

1#6(G)

IN 41C

100AF

3P

100AF

3P

100AF

3P

20AT

"PA"

NEW SEC LINE,

G

W/WELDING CONNECTION

NEW GROUND ROD, COPPER

CLAD STEEL, 19diax3000LG

(TYPICAL)

TOTAL DEMAND LOAD ; 138,720(VA)

TOTAL LOAD 176012 59428 58978

LOAD

TOTAL

MAIN PANELBOARD "MP" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MAIN 3P-600AF-500AT CIRCUIT BREAKER

MTD TYPE, NEMA 1 ENCL.

60HZ, SN & GND, SURFACE

3PHASE ,4WIRE, 120/208V,

57606

PANELBOARD "PA"

3 42000225

PANELBOARD "PB"

4#1&1#6(G)120

5583 5283 5774

SEE SHEET NO. E-1.

16640

ELECTRIC HOT WATER HEATER

SPARE

2500 833 834

4#4&1#8(G)

SPACE

SPACE

150AT

225AF

3P

100AF

2P

30AT

100AF

1P

20AT

100AF

20AT

2P

2#10 &

IN 16C

EWH

W/BUILT-IN CONTROLLER

J

1PH-208V-4.5KW

ELECTRIC HOT WATER HEATER

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-9

NEW PAD MOUNTED TRANSFORMER,

NEW GROUND ROD, COPPER

NEW GROUND ROD, COPPER

PANELBOARD "PC"

EXH FAN 1/4HPx1

WARM AIR FURNACE, 2HP

AIR COMPRESSOR, 5HP

53311 17233 16522 19556

38231 13319 12308 12604

800 800

1243 1244

ELECTRIC UNIT HEATER 3000

HOT WATER CIR. PUMP 800

1500 1500

50000 16667 16667 16666

SPARE

SPARE

11 12

SPACE SPACE

SPACE1000

4500 2250 2250

LEAK DETECTOR 500

70AT 20AT 150AT

"PC"

4#4 &

1#8(G)

EXTC

W.A.F

J

EXT

J J

100AF

20AT

1P

100AF

20AT

1P

100AF

20AT

1P

100AF

20AT

1P

J

P

J

EF EUH

110 110 110

AC

W/BUILT-IN CONTROLLER

W/BUILT-IN CONTROLLER

(EXISTING MECH ITEM)

EXISTING WARM AIR FURNACE

(EXISTING MECH ITEM)

GAS LEAK DETECTOR CONTROL PANEL

SPARE SPARE

IN 21C

3#10 &

3#10&1#10(G)

3#12&1#12(G)

1#10(G)

IN 16C

3#12 &

1#12(G) 1#10(G)

NON-FUSIBLE, NEMA 3R ENCL

3PH-208V-2HP

AIR COMPRESSOR

3PH-208V-5HP

(MECH ITEM)

(MECH ITEM)

(MECH ITEM)

EXHAUST FAN

1PH-120V-1/4HP

(MECH ITEM)

ELECTRIC UNIT HEATER,

1PH-208V-3KW

(MECH ITEM)

ELECTRIC UNIT HEATER,

1PH-208V-3KW

SAFETY SWITCH-C, 3PST, 240V, 30A

4#1/0 &

2 SETS OF 4-250KCMIL & #2(G) IN 103dia C.

2SET-4-250KCMIL & #2(G) IN 103C

IN 354C

2 SETS OF (4#250KCMIL)

4#1/0&1#6(G)

2#10&1#10(G)

2#12&1#12(G)

2#12&1#12(G)

2#12&1#12(G)

2#12&1#12(G)

FOR EXIST CONNECTED LOADS

RECONNECT TO EXIST SECONDARY LINE

7#12 IN 21C

1#6 IN 16C

NEW GROUNDING WIRE, 1#3/0 "BC" IN 27C.

CONNECTION

STEEL, 19dia x 3000LG WITH WELDING

NEW GROUND ROD, COPPER CLAD

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

MAIN PANELBOARD "MP" LOAD SCHEDULE

EXIST/NEW POWER ONE-LINE DIAGRAM &

RE-CONNECT TO EXIST U/G PRI LINE W/ ASSOCIATED DEVICES

PROTECTIVE DEVICES(RE-USE EXIST CONCRETE PAD)

OIL-FILLED, SELF-COOLED, LOAD BREAK SW. W/BUILT-IN

3PH, 11.4KV-120/208V, 60HZ, 300KVA, METAL ENCL. RADIAL TYPE,

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

E-10

TOTAL LOAD 53311

LOAD

TOTAL

PANELBOARD "PA" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MAIN 3P-225AF-150AT CIRCUIT BREAKER

751 751

1 10000100 2#12&1#12(G)

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

5 6

1200 1200

720 720

RCPTS 180VAx5 900

240 240

720 720 7 8

SPARE

TOTAL DEMAND LOAD ; 43,363(VA)

22Wx3, 4.99Wx1, FAN 80Wx1

LIGHT, LED 45Wx10, 50W x3, LIGHT, LED 120Wx10

LIGHT, LED 60Wx4

RCPTS 180VAx4

RCPTS 180VAx4

WASHER 600Wx1

WASHER 600Wx1

RCPTS 180VAx5

DRYER 5400Wx1

DRYER 5400Wx1

RCPTS 360VAx2

RCPTS 180VAx2

RCPTS 360VAx2

RCPTS 5000VAx1

RCPTS 5000VAx1

RCPTS 360VAx2

RCPTS 5000VAx1

RCPTS 5000VAx1

27002700

360 360

360 360

1667 1666

1667 1667 1666

1667 1667 1666

1667 1667 1666

1667 1667 1666

720 360 360

5000 1667 1667 1666

RCPTS 180VAx2

RCPTS 5000VAx1

RCPTS 5000VAx1

SPARE

SPARE 1000

2#10&1#10(G)

2#12&1#12(G)

3#10&1#10(G)

2#12&1#12(G)

2#12&1#12(G)

3#10&1#10(G)

4#1 & 1#6(G)

TOTAL LOAD 38231

LOAD

TOTAL

PANELBOARD "PB" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

MAIN 3P-225AF-120AT CIRCUIT BREAKER

951 951

1 10000100 2#12&1#12(G)20

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

5 6

1080 1080

720 720

720 720

540 540 7 8

2#12&1#12(G)

3#10&1#10(G)

SPARE

22W x2, 4.99W x2, EXH FAN 45W x2

RCPTS 180VAx5

RCPTS 180VAx4

RCPTS 180VAx4

ELECTRIC WALL HEATER-1.0KW

TOTAL DEMAND LOAD ; 31,235(VA)

SPARE

RCPTS 360VAx1

LIGHT, LED 45Wx 3, 50Wx12,18Wx4, LIGHT, LED 120W x9

LIGHT, LED 120W x6

LIGHT, LED 60W x4

RCPTS 180VAx3

LAN/TEL

RCPTS 5000VAx1

RCPTS 5000VAx1

RCPTS 5000VAx1

RCPTS 5000VAx1

ROLL-UP DOOR

ROLL-UP DOOR

ROLL-UP DOOR

ROLL-UP DOOR

ROLL-UP DOOR

ROLL-UP DOOR

ROLL-UP DOOR

ROLL-UP DOOR

1667 1667 1666

5000 1667 1667 1666

5000 1667 1667 1666

5000 1667 1667 1666

1000 500 500

1000 500500

1000 500 500

1000 500 500

SPARE

500 500

500 500

1000 1000

500 500

4#4 & 1#8(G)

TOTAL LOAD 16640

LOAD

TOTAL

PANELBOARD "PC" LOAD SCHEDULE

LOAD DESCRIPTION

NO.

CKT

GND

S/N

DIAGRAM

CONNECTION

CIRCUIT BREAKER

PHASE LOAD

A B PC AT

SIZE

AF AIC

B CA N G

REMARK

1440 720

2 10000100 2#12&1#12(G)20

MTD TYPE, NEMA 1 ENCL.

3PHASE ,4WIRE, 120/208V,

1440 720

2250 1125

2#12&1#12(G)

5583 5283 5774

TOTAL DEMAND LOAD ; 14,340(VA)

SPACE

SPACE

SPACE

SPACE

0.96KW

HEAT PUMP UNIT, 1PH, 220V,

1.15KW

HEAT PUMP UNIT, 1PH, 220V,

1.44KW

HEAT PUMP UNIT, 1PH, 220V,

1.74KW

HEAT PUMP UNIT, 1PH, 220V,

2.25KW

HEAT PUMP UNIT, 1PH, 220V,

ELECTRIC WALL HEATER-1.0KW

1/3HP

HOSE REEL W/ EXHAUST FAN,

1/3HP

HOSE REEL W/ EXHAUST FAN,

ROOF EXH FAN 1/4HPx2

CEILING FAN 20Wx3

1/3HP

HOSE REEL W/ EXHAUST FAN,

1/3HP

HOSE REEL W/ EXHAUST FAN,

1.44KW

HEAT PUMP UNIT, 1PH, 220V,

500 167 167 166

167 167 166500

ROOF EXH FAN 1/4HPx2 800 800

500 167

167 167

167 166

480480

870870

575 575

SPARE

SPARE

2#12&1#12(G)

2#12&1#12(G)

3#12&1#12(G)

SPACE - - - -

SPACE

SPACESPACE

SPACE

SPACE

SPACE

17233 16522 19556 13319 12308 12604

MAIN 3P-100AF-70AT CIRCUIT BREAKER

60HZ, SN & GND, SURFACE

60HZ, SN & GND, SURFACE 60HZ, SN & GND, SURFACE

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

LOAD SCHEDULE

NEW PANELBOARD "PA", "PB" & "PC"

4#1/0 & 1#6(G)

MECH ROOM

FEC

S

S

LATRINE

WOMEN'S

LATRINE

MEN'S

VEST

J/C

TOOL ROOM

ROOM

LAUNDRY

OFFICE

INSPECTOR

OFFICE

FOREMAN

OFFICE

SHOP CONTROL

L/S

W WD BB

STORAGE

EQUIPMENT

D

E-11

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

F

M F

F

F

F

F

M F

F M

C P

F T

R

TS TS

J

PSTS

J

TS

J

J

TS

CO

SCALE:

1/100

COMBINED ADDRESSABLE FIRE ALARM/

FTR BUILDING TRANSMITTER W/BATTERY &

BATTERY CHARGER, NEMA 1 ENCL

W/MOUNTING BARCKET

OMNI-DIRECTION TYPE

FIRE ALARM ANTENNA

DIGITAL VOICE PANEL W/AMPLIFIER & BACK

SYNCHRONIZATION CONTROL MODULE,

24VDC, BUILT-IN ADDRESSABLE POINTS

UP AMPLIFIER (AS REQ'D) & MICROPHONE,

POWER MODULES PANEL(AS REQ'D) AND

MICROPHONE, BATTERY, BATTERY CHAREGER,

MODULE & RELAYS LCD ANNUNCIATOR,

MODULES AS REQ'D, PROGRAMMABLE

MASS NOTIFICATION CONTROL PANEL,

POWER SUPPLY, DIGITAL VOICE MODULE,

FMCP

W/WORDS "FIRE" + MNS-AMBER STROBE

AS REQ'D)/COMBO. (FA-CLEAR STROBE

WALL MOUNTED SPEAKER (WATTAGE

WP

F ADDRESSABLE MANUAL PULL STATION

SPEAKER (WATTAGE AS REQ'D)

FIRE ALARM/MASS NOTIFICATION

WALL MOUNTED "WP" TYPE,

* ADDITIONAL LEGEND (THIS SHEET ONLY)

(15 CANDELA MINIMUM, AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

SHALL BE DE-RATED AS REQUIRED)

TAMPER SWITCH

(UNDER MECH ITEM) (TYPICAL)

FOR SPRINKLER SYSTEM

W/ADDRESSABLE MODULE

PS

J

TS

J

(UNDER MECH ITEM)

FOR SPRINKLER SYSTEM

W/ADDRESSABLE MODULE

PRESSURE SWITCH

ADDRESSABLE SMOKE DETECTOR

NOTES

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES,1.

3.

EXTERIOR AESTHETICALLY.

2. FIRE ALARM AND MASS NOTIFICATION SYSTEM LAYOUT

IS CONCEPTUAL. FINAL DESIGNER SHALL COMPLETE

DESIGN IN ACCORDANCE WITH THE APPLICABLE CODE,

SPECIFICATIONS AND MANUFACTURER'S EQUIPMENT

LISTING.

SEE SHEET NO. E-1.

FOR THE LOCATION OF OUTDOOR FIRE ALARM & MNS

DEVICES, IT SHALL BE COORDINATED WITH THE BUILDING

NEMA 1 ENCL, (SEMI-FLUSH MOUNTED)

M F

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

NEW GROUND FLOOR FIRE ALARM/MASS NOTIFICATION PLAN

NOTIFICATION PLAN

NEW GROUND FLOOR FIRE ALARM/MASS

D T

D ADDRESSABLE DUCT SMOKE DETECTOR

T

CO ADDRESSABLE CARBON MONOXIDE DETECTOR

DUCT SMOKE DETECTOR TEST

ACTIVATION OF A CARBON MONOXIDE DETECTOR MUST

SEND A SEPARATE "CARBON MONOXIDE DETECTOR" ALARM

SIGNAL TO THE FIRE ALARM REPORTING SYSTEM (BUILDING

TRANSMITTER).

4.

FOR EMERGENCY SHUT-DOWN

CONNECT TO W.A.F CONTROLLER

F

F

F

FFF

F

F

F

F

F

F F

F

F /M

F/MF/MF/M

F/M

F /M

F/M

F/M

F /M

F /M

F/M F/M

F /M

F/M

F /M

/M

FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM

NOT TO SCALE

NOTES:

NFPA 72, 2013 EDITION.

PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT

CONTRACTOR SUBMITS SHOP DRAWINGS.

THE VOLTAGE DROP AND POWER SUPPLY CALCULATION

SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE

4.

(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.

ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE

MANUFACTURER'S EQUIPMENT LISTING.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION

MANUFACTURER'S LISTED INSTALLATION

2.

CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL

13.

12.

11.

9.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT

PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION

VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL

ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED

ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT

COORDINATE THE EXACT DEVICE LOCATIONS WITH

SWITCHES AND NON-ADDRESSABLE INITIATION

ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE

PROHIBITED FOR ALL IDC, NAC AND SLC.

ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.

7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE

SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL

10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN

3.

5.

6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE

ALARM CIRCUIT AND ROOM LOCATION OF PANEL

LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED

FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED

THE FIRE ALARM/MASS NOTIFICATION SYSTEM

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING

FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,

WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE

POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.

SHALL BE INDICATED ON THE FIRE ALARM/MASS

BUILDING TRANSMITTER AND ANTENNA.

AND 305mm VERTICALLY.

DEVICES SHALL BE PROVIDED WITH CLASS "B"

THE SYSTEM FOR READY TO USE. THE NUMBER OF

DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE

FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE

DEVICE LOCATIONS IN ACCORDANCE WITH THE

AND BUILDING ARCHITECTURAL FEATURES.

OR FM APPROVED.

SPECIFICATION SECTION 28.31.76.00.31 (FA) AND

HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES

PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.

18.

19.

20.

PER UFC 4-021-01.

17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE

NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED

AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE

MANUFACTURER'S EQUIPMENT LISTING.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION

THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT

LEAST FOR THE FOLLOWING ITEMS.

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

STROBES FOR MASS NOTIFICATION SHALL BE MARKED

STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"

"ALERT" IN RED LETTER AND W/AMBER LENS.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

1.

AND W/CLEAR LENS.

15.

CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2

& 24.4.1.8.2.

THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE

ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM

ON THE PANEL BY SWITCH.

THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED

MASS MESSAGE IS REQUIRED TO BE ANNOUNCED

IMMEDIATELY UNTIL SHUTDOWN MANUALLY.

SPECIFICATION SECTION 28.31.76.00.31 (MNS)

THE CONTRACTOR SHALL PROVIDE THE REQUIRED

TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS

16.

DEVICE LOCATIONS IN ACCORDANCE WITH THE

MANUFACTURER'S LISTED INSTALLATION

AND NFPA 72, 2013 EDITION.

APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY

ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION

MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.

ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.

23.

MASS VISUAL APPLIANCE LOCATION REQUIREMENTS

AS SHOP DRAWING SUBMITTALS.

CONTRACT DRAWINGS SHALL NOT BE SUBMITTED

ARMY AND AIR FORCE PROJECTS.

WITH ANY FIRE ALARM VISUAL APPLIANCES ON

MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.

25.

22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE

AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM

ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.

SHALL BE SYNCHRONIZED.

VOICE EVACUATION SPEAKERS, NEPA 72.

AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD

TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES

USED.

26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL

EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.

SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND

ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.

SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS

REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.

BOTH KOREAN AND ENGLISH.

THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.

APPLICABLE CODE, SPECIFICATIONS AND

REQUIREMENTS AND WIRE COUNT.

ALARM AND DETECTION SYSTEM.

NOTIFICATION CONTROL PANEL COVER.

MODULES.

SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO

REQUIRED.

WITH THE APPLICABLE CODE, SPECIFICATIONS AND

REQUIREMENTS AND WIRE COUNT.

OF 20% SPARE ADDRESSES FOR FUTURE USE.

FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.

SEE SHEET NO. E-1.

2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING

1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING

3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING

6) "ALL CLEAR" MESSAGE

TEST8)

THE BUILDING

CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)

THE LOCAL AREA

5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR

NORMAL MAIN ENTRANCE/EXIT

4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

SYSTEM DIAGRAM

FIRE ALARM/MASS NOTIFICATION

E-12

24VDC, BUILT-IN ADDRESSABLE POINTS MODULES AS REQ'D,

(AS REQ'D) & MICROPHONE. NEMA 1 ENCL

DIGITAL VOICE PANEL W/AMPLIFIER & BACK UP AMPLIFIER

BATTERY CHAREGER, POWER MODULES PANEL (AS REQ'D) AND

SYNCHRONIZATION CONTROL MODULE, POWER SUPPLY,

PROGRAMMABLE MODULE & RELAYS, LCD ANNUNCIATOR,

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL (FMCP),

COMBINED ADDRESSABLE

DIGITAL VOICE MODULE, MICROPHONE, BATTERY,

FIRE ALARM/MASS NOTIFICATION

CONTROL PANEL (FMCP)

1st FL.

FTR

16#14 IN 21C(FOR SIGNAL)

2#12 IN 16C(FOR POWER)

(PROGRAM OF D-21 MONACO

BUILDING TRANSMITTER

BT-XM AT LEAST 16 ZONES)

#6 "BC" IN 21C

GROUND CONDUCTOR

COAXIAL CABLE

W/CONNECTORS IN 16C

OMNI-DIRECTION TYPE

FIRE ALARM ANTENNA

W/MOUNTING BRACKET

GROUND ROD, COPPER CLAD

WITH WELDING CONNECTION

STEEL, 19mmdia x 3000mmLG

"EM"SG

G ~

G

CONTROL PANEL & BOOSTER PANEL)

(INSTALLED BESIDE FIRE ALARM

(RATED AS REQ'D) (TYPICAL)

SURGE PROTECTOR

2#12 & 1#12(G) IN 16C

GROUND ROD, COPPER CLAD

GROUNDING SYSTEM #6, "BC" IN 21C

CONN TO BLDG ELECTRODE

STEEL, 19mmdiax3000mmLG

WITH WELDING CONNECTION AND

ENCLOSURE

LIGHTNING ARRESTER

W/WEATHER-PROOF

F

F M

EXT

WP

101 108

W/BATTERY & BATTERY

CHARGER, NEMA 1 ENCL

VISUAL SIGNAL STROBES (75 CANDELA

MINIMUM, AMBER STROBE SHALL BE

MNS-AMBER STROBE W/WORDS "ALERT")

(FA-CLEAR STROBE W/WORDS "FIRE" +

DE-RATED AS REQUIRED) (TYPICAL)

WALL MOUNTED COMBO.

W/WORDS "FIRE" + MNS-AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

AS REQ'D)/COMBO. (FA-CLEAR STROBE

WALL MOUNTED SPEAKER (WATTAGE

ADDRESSABLE MANUAL

PULL STATION (TYPICAL)

WALL MOUNTED "WP" TYPE,

NOTIFICATION SPEAKER

FIRE ALARM/MASS

(WATTAGE AS REQ'D) (TYPICAL)

SHALL BE DE-RATED AS REQUIRED) (TYPICAL)

ADDRESSABLE SMOKE

DETECTOR

TS

J

TS

J

TS

J

PS

J

110 110 110

TAMPER SWITCH

(UNDER MECH ITEM) (TYPICAL)

FOR SPRINKLER SYSTEM

W/ADDRESSABLE MODULE

(UNDER MECH ITEM)

FOR SPRINKLER SYSTEM

W/ADDRESSABLE MODULE

PRESSURE SWITCH

F

F 101110

F

ROOF FL.

F M

EXT

WP

101 101

102107 101

(15 or 75 CANDELA MINIMUM, AMBER STROBE

109 112

104 103

F 110 110

F M

EXT

WP

F M

EXT

WP

CARBON MONOXIDE

CO

MODULE

DETECTOR W/ADDRESSABLE

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

D

T

ADDRESSABLE DUCT SMOKE

DETECTOR W/TEST

MECH ROOM

FEC

FEC

S

S

EWC

LATRINE

WOMEN'S

LATRINE

MEN'S

VEST

J/C

TOOL ROOM

D3

ROOM

LAUNDRY

OFFICE

INSPECTOR

OFFICE

FOREMAN

OFFICE

SHOP CONTROL

L/S

W WD BB

STORAGE

EQUIPMENT

D

FEC

FEC

E-13

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

TTC

L A

N

T

T

T

T

T T

T

T

T

T

T

T

T

2-4PAIR, #24AWG, CAT-6

TEL WIRE IN 16C

PATCH PANELS

TO BE TERMINATED AT

(TYP)

1-TEL/1-LAN OUTLET, CAT6

W/ RACK MOUNTED 6-SINGLE

REAR RECEPTACLE, ON-OFF

SWITCH & CORD, 2P-3W-20A-125V

POWER SURGE PROTECTION

SCALE:

1/100

NEW GROUND FLOOR LAN/TEL SYTEM PLAN

WALL MOUNTED EQUIPMENT CABINET

NEW TELEPHONE TERMINAL CABINET ("TTC")

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

NEW GROUND FLOOR LAN/TEL SYTEM PLAN

EXOTHERMIC WELDING, LISTED COMPRESSION TWO-

1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR

TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE

HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE

"MP" GROUNDING BUS BAR

1#6 "BC" IN 21C

CONN TO MAIN PANELBOARD

TEL SYSTEM DIAGRAM

NOT TO SCALE

STAMP FACING OUT" TO ENSURE THAT THEY CAN BE

3. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT

REVISION OF THE ANSI/TIA/EIA-568.

4. LABEL ALL DROPS IAW TIA/EIA-606-A.

5. LABEL ALL GROUNDS IAW I3A.

LUGS ARE PREFERRED.

FIELD VERIFIED.

TO TELEPHONE PATCH PANEL

TGB

CONN TO TMGB

1#6 "BC" IN 27C

(100mm x 450mmLG x 6.4mmTHK)

GROUND BUS BAR(TGB)

TMGB

G

(TYPICAL)

CABLE SUPPORT

G

110TYPE TERMINAL BLOCK

(2-100PAIR) FOR TEL

(TYPICAL)

CROSS CONNECTION CORD AS REQ'D

PLUS 25% SPARES TO BE FURNISHED BY THE

1#6 "BC" IN 16C

G

FOR TELEPHONE

1-24PORT PATCH PANEL

TO EACH DATA OUTLET AS REQ'D

TO EACH TEL OUTLET AS REQ'D

AS REQ'D

PROVIDE PATCH CORDS

HUB(N.I.C)

1-24PORT PATCH PANEL

FOR DATA

W/ RACK MOUNTED 6-SINGLE

REAR RECEPTACLE, ON-OFF

SWITCH & CORD, 2P-3W-20A-125V

GROUND BUS BAR(TGB)

TELECOMMUNICATION

TELECOMMUNICATION MAIN

PTB

CONTRACTOR

RECEPTACLES

(1-100PAIR)

ENTRANCE TERMINAL BLOCK

110 TYPE PROTECTED

G

2. "PLYWOOD WILL BE INSTALLED WITH FIRE RATED

NOTE.

SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.

SYSTEM AND WIRING FOR GOVERNMENT APPROVAL. TELECOMMUNCATION WORK

6. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAILED TELECOMMUNICATION

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

TEL SYSTEM DIAGRAM

E-14

TELEPHONE TERMINAL CABINET ("TTC")

WALL MOUNTED EQUIPMENT CABINET

1-12CORE, FIBER OPTIC CABLE IN 53C.

1-25PAIR, #24AWG TEL CABLE IN 53C.

PATCH PANEL W/"SC" CONNECTOR

1-12 STRAND FIBER OPTIC

PB-9

QUAD-PLEX RECEPTACLE

2P-3W-125V-20A GND TYPE

WITH DEDICATED CIRCUIT

107SHOP CONTROL OFFICE

(WI/ FIRE RATED PLTWOOD)

CP CASEY

REPAIR BUILDING S-2399,

TAK, YS

160851

(BUILDING S-2399)

ELECTRICAL

(24"(W)x36"(H)x30"(D)

POWER SURGE PROTECTION

E-1
E-2
E-3
E-4
E-5
E-6
E-7
E-8
E-9
E-10
E-11
E-12
E-13
E-14