TE-H.2.22 Fire Systems.xlsx
XLSX spreadsheet 93 KB Posted
- Attached to
- Ft Carson BASOPS (Base Operations Services)
- Solicitation number
- W5168W-24-R-0009
- Issued by
-
Department of the Army
About this file
This document is a detailed spreadsheet listing 724 fire sprinkler systems for buildings located at Fort Carson, Colorado. The spreadsheet provides information on each system, including the building number, system type, annual inspection due date, system size, and installation date. The systems include wet, dry, pre-action, and fire pump systems of varying sizes, ranging from 1.25-inch to 8-inch. Many of the systems have backflow protectors installed. This information appears to be related to a federal contract opportunity for Base Operations Support Services at Fort Carson, which includes facility maintenance and utilities services.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Systems
| Fort Carson Fire Sprinkler Systems TE-H.2.22 | |||||||||
| Month: Jan 2022 | Total Systems: | ||||||||
| Revised: 1-1-22 | 724 | ||||||||
| System No. | Bldg #. | System Type | Month Due for Annual | Location | Comments | System Sizes | Install Date | ||
| 1 | 238 | FS238-1 | Dry | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2000 | |
| 2 | 239 | FS239-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 2.5" | 2001 | |
| 3 | 307 | FS307-1 | Dry | Annual/ May | West Mech. Rm. | No Backflow | 6" | 1662 | |
| 4 | 319 | FS319-1 | Pre-Action | Annual/ May | Comm. Bldg. | Has Backflow | 1.5" | 1994 | |
| 5 | 320 | FS320-1 | Wet | Annual/ May | SW Corner of Bldg. | Has Backflow | 6" | 2000 | |
| 6 | 330 | FS330-1 | Wet | Annual/ Oct | Mech. Rm. | One Backflow Protects all Systems | #1) 6" | 1999 | |
| 7 | 330 | FS330-2 | Wet | Annual/ Oct | Overhead | #2) 6" Overhead | 1999 | ||
| 8 | 330 | FS330-3 | Wet | Annual/ Oct | Overhead | #3) 6" Overhead | 1999 | ||
| 9 | 330 | FS330-4 | Wet | Annual/ Oct | Mech. Rm. | #4) 6" | 1999 | ||
| 10 | 330 | FS330-5 | Wet | Annual/ Oct | Rack Storage | #5) 6" Racks | 1999 | ||
| 11 | 330 | FS330-6 | Wet | Annual/ Oct | Rack Storage | #6) 6" Racks | 1999 | ||
| 12 | 330 | FS330-7 | Wet | Annual/ Oct | Fire Hose Valve System | #7) 6" FHV | 1999 | ||
| 13 | 330 | FS330-8 | Wet | Annual/ Oct | Mech. Rm. | #8) 6" | 2015 | ||
| 14 | 344 | FS344-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 6" | 2017 | |
| 15 | 350 | FS350-1 | Wet | Annual/ May | Mech. Rm. | One Backflow Protects all Systems | #3) 2.5" offices | 1991 | |
| 16 | 350 | FS350-2 | Pre-Action | Annual/ May | Mech. Rm. | #1) 6" | 1991 | ||
| 17 | 350 | FS350-3 | Pre-Action | Annual/ May | Mech. Rm. | #2) 6" | 1991 | ||
| 18 | 405 | FS405-1 | Wet | Annual/ Feb | Mech. Rm. | Has Backflow | 3" | 2011 | |
| 19 | 407 | FS407-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 4" | 2001 | |
| 20 | 501 | FS501-1 | Wet/Fire Pump | Annual/ May | Admin Area | One Backflow Protects all Systems | 6" | 2020 | |
| 21 | 501 | FS501-2 | Dry/Nitrogen | Annual/ May | North System | #1) 6" | 2020 | ||
| 22 | 501 | FS501-3 | Dry/Nitrogen | Annual/ May | South System | #2) 6" | 2020 | ||
| 23 | 510 | FS510-1 | Wet/Fire Pump | Annual/ May | Fire Pump House | No Backflow | 1.5" | 2010 | |
| 24 | 510 | FS510-2 | Wet | Annual/ May | Fire Riser Rm. | One Backflow Protects all Systems | 4" | 2010 | |
| 25 | 510 | FS510-3 | Glycerin | Annual/ May | Back of Restaurant | 1 1/4" | 2010 | ||
| 26 | 515 | FS515-1 | Wet/Fire Pump | Annual/ May | Mech. Rm. | One Backflow Protects all Systems | #1) 4" | 2008 | |
| 27 | 515 | FS515-2 | Dry | Annual/ May | South Secure Rm. | #2) 4" | 2008 | ||
| 28 | 517 | FS517-1 | Wet/Fire Pump | Annual/ Apr | Mech. Rm. | One Backflow Protects all Systems | #1) 4" | 2010 | |
| 29 | 517 | FS517-2 | Dry | Annual/ Apr | Mech. Rm. | #2) 4" | 2010 | ||
| 30 | 520 | FS520-1 | Wet | Annual/ Oct | Rack Storage | One Backflow Protects all Systems | #1 Rack) 6" | 2001 | |
| 31 | 520 | FS520-2 | Wet | Annual/ Oct | Overhead | #2 Overhead) 6" | 2001 | ||
| 32 | 702 | FS702-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 6" | 2010 | |
| 33 | 703 | FS703-1 | Dry | Annual/ Mar | Fire Riser Rm. | System Feed from Bldg. 704 | 4" | 2010 | |
| 34 | 704 | FS704-1 | Wet/Fire Pump | Annual/ Mar | Mech. Rm. | One Backflow Protects all Systems | 6" | 2010 | |
| 35 | 704 | FS704-2 | Dry | Annual/ Mar | Supply Cage | 4" | 2010 | ||
| 36 | 749 | FS749-1 | Dry/Fire Pump | Annual/ May | Fire Pump House | Has Backflow | 6", New 8" Fire Pump 2019 | 1968 | |
| 37 | 750 | FS750-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 4" | 1998 | |
| 38 | 754 | FS754-1 | Wet | Annual/ Oct | North Mech. Rm. | Has Backflow | 4" | 1997 | |
| 39 | 754 | FS754-2 | Wet | Annual/ Oct | South Mech. Rm. | Has Backflow | 4" | 1997 | |
| 40 | 756 | FS756-1 | Wet | Annual/ Oct | 1st Floor | One Backflow Protects all Systems | #1 Mech Rm.) 4" | 1997 | |
| 41 | 756 | FS756-2 | Wet | Annual/ Oct | Mainflow & Mezz | #2 Mezz.) 4" | 1997 | ||
| 42 | 756 | FS756-3 | Wet | Annual/ Oct | 1st Floor North | # 3 1st N.) 2" | 1997 | ||
| 43 | 756 | FS756-4 | Wet | Annual/ Oct | 2nd Floor North | #4 2nd N.) 2" | 1997 | ||
| 44 | 756 | FS756-5 | Wet | Annual/ Oct | 3rd Floor North | #5 3rd N.) 2" | 1997 | ||
| 45 | 756 | FS756-6 | Wet | Annual/ Oct | 1st Floor South | #6 1st S.) 2" | 1997 | ||
| 46 | 756 | FS756-7 | Wet | Annual/ Oct | 2nd Floor South | #7 2nd S.) 2" | 1997 | ||
| 47 | 756 | FS756-8 | Wet | Annual/ Oct | 3rd Floor South | #8 3rd S.) 2" | 1997 | ||
| 48 | 758 | FS758-1 | Wet | Annual/ Oct | 1st Floor | One Backflow Protects all Systems | #1 Mech Rm.) 4" | 1996 | |
| 49 | 758 | FS758-2 | Wet | Annual/ Oct | Mainflow & Mezz | #2 Mezz.) 4" | 1996 | ||
| 50 | 758 | FS758-3 | Wet | Annual/ Oct | 1st Floor North | # 3 1st N.) 2" | 1996 | ||
| 51 | 758 | FS758-4 | Wet | Annual/ Oct | 2nd Floor North | #4 2nd N.) 2" | 1996 | ||
| 52 | 758 | FS758-5 | Wet | Annual/ Oct | 3rd Floor North | #5 3rd N.) 2" | 1996 | ||
| 53 | 758 | FS758-6 | Wet | Annual/ Oct | 1st Floor South | #6 1st S.) 2" | 1996 | ||
| 54 | 758 | FS758-7 | Wet | Annual/ Oct | 2nd Floor South | #7 2nd S.) 2" | 1996 | ||
| 55 | 758 | FS758-8 | Wet | Annual/ Oct | 3rd Floor South | #8 3rd S.) 2" | 1996 | ||
| 56 | 840 | FS840-1 | Wet | Annual/ Dec | 1st Floor & Elevator | One Backflow Protects all Systems | #1) 4" & Elevator Mech. | 2012 | |
| 57 | 840 | FS840-2 | Wet | Annual/ Dec | 2nd Floor & Elevator | #2) 4" & Elevator Shaft | 2012 | ||
| 58 | 842 | FS842-1 | Wet | Annual/ Nov | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 3" & Elevator Mech. | 2011 | |
| 59 | 842 | FS842-2 | Wet | Annual/ Nov | 2nd Floor | #2 2nd floor) 3" | 2011 | ||
| 60 | 842 | FS842-3 | Wet | Annual/ Nov | 3rd Floor | #3 3rd floor) 3" | 2011 | ||
| 61 | 1000 | FS1000-1 | Wet | Annual/ Jan | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 2.5" | 2009 | |
| 62 | 1000 | FS1000-2 | Wet | Annual/ Jan | 2nd Floor | #2 2nd floor) 2" | 2009 | ||
| 63 | 1000 | FS1000-3 | Wet | Annual/ Jan | 3rd Floor | #3 3rd floor) 2" | 2009 | ||
| 64 | 1005 | FS1005-1 | Wet | Annual/ Mar | 1st Floor | One Backflow Protects all Systems | #1) 6" | 2009 | |
| 65 | 1005 | FS1005-2 | Wet | Annual/ Mar | 2nd Floor | #2) 3" | 2009 | ||
| 66 | 1005 | FS1005-3 | Wet | Annual/ Mar | 3rd Floor | #3) 3" | 2009 | ||
| 67 | 1011 | FS1011-1 | Wet | Annual/ Oct | Basement Mech. Rm. | One Backflow Protects all Systems | #1 Basement) 4" | 1998 | |
| 68 | 1011 | FS1011-2 | Wet | Annual/ Oct | 1st Floor | #2 1st floor) 4" | 1998 | ||
| 69 | 1011 | FS1011-3 | Wet | Annual/ Oct | 2nd Floor | #3 2nd floor) 4" | 1998 | ||
| 70 | 1011 | FS1011-4 | Wet | Annual/ Oct | 3rd Floor | #4 3rd floor) 4", 3rd Elev & Hall) 1.25" | 1998 | ||
| 71 | 1014 | FS1014-1 | Pre-Action | Annual/ Jan | Comm. Bldg. | Has Backflow | 1.5" | 1997 | |
| 72 | 1040 | FS1040-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | 4" | 2010 | |
| 73 | 1042 | FS1042-1 | Wet | Annual/ Aug | Basement Riser Rm. | One Backflow Protects all Systems | #1 Basement) 6" | 2004 | |
| 74 | 1042 | FS1042-2 | Wet | Annual/ Aug | 1st Floor | #2 1st floor)4" | 2004 | ||
| 75 | 1042 | FS1042-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 4" | 2004 | ||
| 76 | 1042 | FS1042-4 | Wet | Annual/ Aug | 3rd Floor & Elevator | #4 3rd floor) 4" | 2004 | ||
| 77 | 1043 | FS1043-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 78 | 1043 | FS1043-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 79 | 1043 | FS1043-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 80 | 1043 | FS1043-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 81 | 1044 | FS1044-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 82 | 1044 | FS1044-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 83 | 1044 | FS1044-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 84 | 1044 | FS1044-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 85 | 1046 | FS1046-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 86 | 1046 | FS1046-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 87 | 1046 | FS1046-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 88 | 1046 | FS1046-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 89 | 1047 | FS1047-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 90 | 1047 | FS1047-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 91 | 1047 | FS1047-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 92 | 1047 | FS1047-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 93 | 1117 | FS1117-1 | Wet/Fire Pump | Annual/ Nov | Basement Mech. Rm. | One Backflow Protects all Systems | #1 Basement) 4" | 7/3/20 | Installed by Arapahoe Fire |
| 94 | 1117 | FS1117-2 | Dry Nitrogen | Annual/ Nov | Fire Riser Rm. | #2 Elevator Pit) 1" | 7/3/20 | ||
| 95 | 1117 | FS1117-3 | Dry Nitrogen | Annual/ Nov | Fire Riser Rm. | #3 Elevator Mech.) 1" | 7/3/20 | ||
| 96 | 1117 | FS1117-4 | Wet | Annual/ Nov | 1st Floor West | #4 1st floor West) 4" | 7/3/20 | ||
| 97 | 1117 | FS1117-5 | Wet | Annual/ Nov | 2nd Floor West | #5 2nd floor West) 3" | 7/3/20 | ||
| 98 | 1117 | FS1117-6 | Wet | Annual/ Nov | 3rd Floor West | #6 3rd floor West) 4" | 7/3/20 | ||
| 99 | 1118 | FS1118-1 | Wet | Annual/ Dec | Basement Mech. Rm. | One Backflow Protects all Systems | 4" | 2006 | |
| 100 | 1118 | FS1118-2 | Wet | Annual/ Dec | 1st Floor East | 3" | 2006 | ||
| 101 | 1118 | FS1118-3 | Wet | Annual/ Dec | Elevators | 1.25" | 2006 | ||
| 102 | 1118 | FS1118-4 | Wet | Annual/ Dec | 1st Floor West | 3" | 2006 | ||
| 103 | 1118 | FS1118-5 | Wet | Annual/ Dec | 2nd Floor East | 4" | 2006 | ||
| 104 | 1118 | FS1118-6 | Wet | Annual/ Dec | 2nd Floor West | 4" | 2006 | ||
| 105 | 1118 | FS1118-7 | Wet | Annual/ Dec | 3rd Floor East | 3" | 2006 | ||
| 106 | 1118 | FS1118-8 | Wet | Annual/ Dec | 3rd Floor West | 3" | 2006 | ||
| 107 | 1161 | FS1161-1 | Wet | Annual/ Aug | Mech. Rm. | Has Backflow | 2" | 2007 | |
| 108 | 1187 | FS1187-1 | Wet | Annual/ Nov | Janitors Closet | Has Backflow | 6" | 2004 | |
| 109 | 1200 | FS1200-1 | Wet | Annual/ Dec | CQ Area | Has Backflow | 3" | 2010 | |
| 110 | 1210 | FS1210-1 | Wet/Fire Pump | Annual/ Mar | East Admin | One Backflow Protects all Systems | #1 East) 6" | 2009 | |
| 111 | 1210 | FS1210-2 | Wet | Annual/ Mar | West Admin | #2 West) 6" | 2009 | ||
| 112 | 1210 | FS1210-3 | Dry | Annual/ Mar | East Canopy | #3 East Canopy) 4" | 2009 | ||
| 113 | 1210 | FS1210-4 | Dry | Annual/ Mar | West Canopy | #4 West Canopy) 4" | 2009 | ||
| 114 | 1219 | FS1219-1 | Wet | Annual/ May | Basement Mech. Rm. | One Backflow Protects all Systems | #1 Basement) 3" | 2011 | |
| 115 | 1219 | FS1219-2 | Wet | Annual/ May | 1st Floor North & Elevator | #2 1st floor) 4" | 2011 | ||
| 116 | 1219 | FS1219-3 | Wet | Annual/ May | 2nd Floor North | #3 2nd floor) 4" | 2011 | ||
| 117 | 1219 | FS1219-4 | Wet | Annual/ May | 3rd Floor North | #4 3rd floor) 4" | 2011 | ||
| 118 | 1219 | FS1219-5 | Dry | Annual/ May | 2nd Floor Center | #5) 1.5" | 2011 | ||
| 119 | 1220 | FS1220-1 | Wet | Annual/ Apr | Elevators | One Backflow Protects all Systems | #1 1st floor) 1.5" | 2005 | |
| 120 | 1220 | FS1220-2 | Wet | Annual/ Apr | 2nd Floor | #2 2nd floor) 4" | 2005 | ||
| 121 | 1220 | FS1220-3 | Wet | Annual/ Apr | 3rd Floor | #3 3rd floor) 4" | 2005 | ||
| 122 | 1230 | FS1230-1 | Wet | Annual/ Dec | Center East Warehouse | Has Backflow | 6" | 1996 | |
| 123 | 1280 | FS1280-1 | Wet | Annual/ Jul | Mech. Rm. | One Backflow Protects all Systems | #1) 6" | 2012 | |
| 124 | 1280 | FS1280-2 | Dry | Annual/ Jul | Mod 2 | #2) 6" | 2012 | ||
| 125 | 1282 | FS1282-1 | Wet | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 2012 | |
| 126 | 1283 | FS1283-1 | Dry | Annual/ Jul | Fire Riser Rm. | Has Backflow | 4" | 2013 | |
| 127 | 1355 | FS1355-1 | Wet | Annual/ Sep | Mech. Rm. | Has Backflow | 4" | 2009 | |
| 128 | 1363 | FS1363-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 129 | 1363 | FS1363-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 130 | 1363 | FS1363-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 131 | 1363 | FS1363-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 132 | 1364 | FS1364-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 133 | 1364 | FS1364-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 134 | 1364 | FS1364-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 135 | 1364 | FS1364-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 136 | 1365 | FS1365-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 137 | 1365 | FS1365-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 138 | 1365 | FS1365-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 139 | 1365 | FS1365-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 140 | 1366 | FS1366-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 141 | 1366 | FS1366-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 142 | 1366 | FS1366-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 143 | 1366 | FS1366-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 144 | 1367 | FS1367-1 | Glycol | Annual/ Aug | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 145 | 1367 | FS1367-2 | Wet | Annual/ Aug | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 146 | 1367 | FS1367-3 | Wet | Annual/ Aug | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 147 | 1367 | FS1367-4 | Wet | Annual/ Aug | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 148 | 1392 | FS1392-1 | Dry | Annual/ Jul | South Mech. Rm. | Has Backflow | 6" | 1964 | |
| 149 | 1435 | FS1435-1 | Wet/Fire Pump | Annual/ May | 1st Floor North | One Backflow Protects all Systems | #1 1st N.) 4" | 2007 | |
| 150 | 1435 | FS1435-2 | Wet | Annual/ May | 2nd Floor | #2 2nd N.) 4" | 2007 | ||
| 151 | 1435 | FS1435-3 | Wet | Annual/ May | 3rd Floor | #3 3rd N.) 4" | 2007 | ||
| 152 | 1435 | FS1435-4 | Wet | Annual/ May | 1st Floor South | #4 1st S.) 4" | 2007 | ||
| 153 | 1435 | FS1435-5 | Wet | Annual/ May | 2nd Floor South | #5 2nd S.) 4" | 2007 | ||
| 154 | 1444 | FS1444-1 | Wet | Annual/ Apr | Mech. Rm. | Has Backflow | 6" | 2003 | |
| 155 | 1445 | FS1445-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 3" | 2008 | |
| 156 | 1447 | FS1447-1 | Wet/Fire Pump | Annual/ May | Under Mezz. | One Backflow Protects all Systems | #1) 4" | 2008 | |
| 157 | 1447 | FS1447-2 | Wet | Annual/ May | Mech. Rm. | #2) 2.5" | 2008 | ||
| 158 | 1447 | FS1447-3 | Dry | Annual/ May | Hard Stand | #3) 6" | 2008 | ||
| 159 | 1447 | FS1447-4 | Wet | Annual/ May | Readiness Area | #4) 6" | 2008 | ||
| 160 | 1447 | FS1447-5 | Wet | Annual/ May | Admin Area | #5) 4" | 2008 | ||
| 161 | 1449 | FS1449-1 | Wet | Annual/ Dec | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | 2008 | |
| 162 | 1449 | FS1449-2 | Wet | Annual/ Dec | 2nd Floor | #2 2nd floor) 4" | 2008 | ||
| 163 | 1449 | FS1449-3 | Wet | Annual/ Dec | 3rd Floor | #3 3rd floor) 4" | 2008 | ||
| 164 | 1450 | FS1450-1 | Wet | Annual/ Mar | North Mech. Rm. | Has Backflow | 4" | 1975 | |
| 165 | 1450 | FS1450-2 | Wet | Annual/ Mar | West Mech. Rm. | Has Backflow | 2.5" | 2011 | |
| 166 | 1454 | FS1454-1 | Wet | Annual/ Mar | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | 2003 | |
| 167 | 1454 | FS1454-2 | Wet | Annual/ Mar | 2nd Floor | #2 2nd floor) 4" | 2003 | ||
| 168 | 1456 | FS1456-1 | Wet | Annual/ Mar | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | 2001 | |
| 169 | 1456 | FS1456-2 | Wet | Annual/ Mar | 2nd Floor | #2 2nd floor) 4" | 2001 | ||
| 170 | 1500 | FS1500-1 | Wet/Fire Pump | Annual/ Mar | Basement Mech. Rm. | Has Backflow | 4" | 1998 | |
| 171 | 1510 | FS1510-1 | Wet | Annual/ Apr | Basement Mech. Rm. | Has Backflow | 8" | ||
| 172 | 1510 | FS1510-2 | Wet | Annual/ Apr | NE Warehouse | Has Backflow | 6" | 1974 | |
| 173 | 1511 | FS1511-1 | Dry | Annual/ Jun | Maintenance Shop | Has Backflow | 6" | 1965 | |
| 174 | 1517 | FS1517-1 | Wet | Annual/ Dec | SW Corner of Bldg. | Has Backflow | 8" | 2018 | |
| 175 | 1525 | FS1525-1 | Wet | Annual/ Jun | North CIF Area | One Backflow Protects all Systems | #1) 6" | 1995 | |
| 176 | 1525 | FS1525-2 | Wet | Annual/ Jun | North Center | #2) 6" | 1995 | ||
| 177 | 1525 | FS1525-3 | Wet | Annual/ Jun | South Center | #6) 3" | 2013 | ||
| 178 | 1525 | FS1525-4 | Wet | Annual/ Jun | South Area | One Backflow Protects all Systems | #3) 6" | 1995 | |
| 179 | 1525 | FS1525-5 | Dry | Annual/ Jun | West Canopy | #4) 6" | 1995 | ||
| 180 | 1525 | FS1525-6 | Dry | Annual/ Jun | North Canopy | #5) 3" | 1995 | ||
| 181 | 1532 | FS1532-1 | Wet | Annual/ Apr | Mech. Rm. | Has Backflow | 6" | 2009 | |
| 182 | 1534 | FS1534-1 | Wet | Annual/ Nov | Mech. Rm. | One Backflow Protects all Systems | #1 Wet) 6" | 2011 | |
| 183 | 1534 | FS1534-2 | Glycerin | Annual/ Nov | Mech. Rm. | #2 Glycerin) 1.5" | 2011 | ||
| 184 | 1550 | FS1550-1 | Wet | Annual/ Jun | 2nd Floor | One Backflow Protects all Systems | #1) 6" | 1995 | |
| 185 | 1550 | FS1550-2 | Dry | Annual/ Jun | East Canopy | #2) 4" | 1995 | ||
| 186 | 1550 | FS1550-3 | Dry | Annual/ Jun | Generator Rm. | #3) 2" | 1995 | ||
| 187 | 1550 | FS1550-4 | Wet | Annual/ Jun | 1st Floor | #4) 4" | 1995 | ||
| 188 | 1550 | FS1550-5 | Wet | Annual/ Jun | 1st Floor | #5) 4" | 1995 | ||
| 189 | 1550 | FS1550-6 | Wet | Annual/ Jun | High Bays | #6) 6" | 1995 | ||
| 190 | 1551 | FS1551-1 | Wet | Annual/ Jun | Mech. Rm. | Has Backflow | 4" | 1992 | |
| 191 | 1552 | FS1552-1 | Wet | Annual/ Mar | 1st Floor | One Backflow Protects all Systems | #1 1st Floor Main) 4" | 2003 | |
| 192 | 1552 | FS1552-10 | Wet | Annual/ Mar | 3rd Floor North | #10 3rd N) 3" | 2003 | ||
| 193 | 1552 | FS1552-11 | Wet | Annual/ Mar | 3rd Floor South | #11 3rd S) 3" | 2003 | ||
| 194 | 1552 | FS1552-2 | Wet | Annual/ Mar | 1st Floor Center | #2 1st Center) 4" | 2003 | ||
| 195 | 1552 | FS1552-3 | Wet | Annual/ Mar | 1st Floor North | #3 1st N.) 2.5" | 2003 | ||
| 196 | 1552 | FS1552-4 | Wet | Annual/ Mar | 1st Floor South | #4 1st S.) 2.5" | 2003 | ||
| 197 | 1552 | FS1552-5 | Wet | Annual/ Mar | 2nd Floor | #5 2nd Floor Main) 4" | 2003 | ||
| 198 | 1552 | FS1552-6 | Wet | Annual/ Mar | 2nd Floor North | #6 2nd N.) 3" | 2003 | ||
| 199 | 1552 | FS1552-7 | Wet | Annual/ Mar | 2nd Floor South | #7 2nd S) 3" | 2003 | ||
| 200 | 1552 | FS1552-8 | Wet | Annual/ Mar | 2nd Floor Center | #8 2nd Center) 4" | 2003 | ||
| 201 | 1552 | FS1552-9 | Wet | Annual/ Mar | 3rd Floor | #9 3rd Floor Main) 4" | 2003 | ||
| 202 | 1554 | FS1554-1 | Wet | Annual/ Mar | 1st Floor | One Backflow Protects all Systems | #1 1st Floor Main) 4" | 2003 | |
| 203 | 1554 | FS1554-10 | Wet | Annual/ Mar | 3rd Floor North | #10 3rd N) 3" | 2003 | ||
| 204 | 1554 | FS1554-11 | Wet | Annual/ Mar | 3rd Floor South | #11 3rd S) 3" | 2003 | ||
| 205 | 1554 | FS1554-2 | Wet | Annual/ Mar | 1st Floor Center | #2 1st Center) 4" | 2003 | ||
| 206 | 1554 | FS1554-3 | Wet | Annual/ Mar | 1st Floor North | #3 1st N.) 2.5" | 2003 | ||
| 207 | 1554 | FS1554-4 | Wet | Annual/ Mar | 1st Floor South | #4 1st S.) 2.5" | 2003 | ||
| 208 | 1554 | FS1554-5 | Wet | Annual/ Mar | 2nd Floor | #5 2nd Floor Main) 4" | 2003 | ||
| 209 | 1554 | FS1554-6 | Wet | Annual/ Mar | 2nd Floor North | #6 2nd N.) 3" | 2003 | ||
| 210 | 1554 | FS1554-7 | Wet | Annual/ Mar | 2nd Floor South | #7 2nd S) 3" | 2003 | ||
| 211 | 1554 | FS1554-8 | Wet | Annual/ Mar | 2nd Floor Center | #8 2nd Center) 4" | 2003 | ||
| 212 | 1554 | FS1554-9 | Wet | Annual/ Mar | 3rd Floor | #9 3rd Floor Main) 4" | 2003 | ||
| 213 | 1650 | FS1650-1 | Wet | Annual/ Apr | Fire Riser Rm. | Has Backflow | 4" 5 Zones | 2010 | |
| 214 | 1659 | FS1659-1 | Wet | Annual/ Apr | Mech. Rm. | Has Backflow | 4" | ||
| 215 | 1663 | FS1663-1 | Glycol | Annual/ Apr | Basement Riser Rm. | One Backflow Protects all Systems | #1 Basement Glycol) 2.5" | 2005 | |
| 216 | 1663 | FS1663-2 | Wet | Annual/ Apr | 1st Floor | #2 1st floor) 2" | 2005 | ||
| 217 | 1663 | FS1663-3 | Wet | Annual/ Apr | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 218 | 1663 | FS1663-4 | Wet | Annual/ Apr | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 219 | 1664 | FS1664-1 | Glycol | Annual/ Apr | Basement Riser Rm. | One Backflow Protects all Systems | #1 Basement Glycol) 2.5" | 2005 | |
| 220 | 1664 | FS1664-2 | Wet | Annual/ Apr | 1st Floor | #2 1st floor) 2" | 2005 | ||
| 221 | 1664 | FS1664-3 | Wet | Annual/ Apr | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 222 | 1664 | FS1664-4 | Wet | Annual/ Apr | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 223 | 1665 | FS1665-1 | Glycol | Annual/ Apr | Basement Riser Rm. | One Backflow Protects all Systems | #1 Basement Glycol) 2.5" | 2005 | |
| 224 | 1665 | FS1665-2 | Wet | Annual/ Apr | 1st Floor | #2 1st floor) 2" | 2005 | ||
| 225 | 1665 | FS1665-3 | Wet | Annual/ Apr | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 226 | 1665 | FS1665-4 | Wet | Annual/ Apr | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 227 | 1666 | FS1666-1 | Glycol | Annual/ Apr | Basement Riser Rm. | One Backflow Protects all Systems | #1 Basement Glycol) 2.5" | 2005 | |
| 228 | 1666 | FS1666-2 | Wet | Annual/ Apr | 1st Floor | #2 1st floor) 2" | 2005 | ||
| 229 | 1666 | FS1666-3 | Wet | Annual/ Apr | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 230 | 1666 | FS1666-4 | Wet | Annual/ Apr | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 231 | 1667 | FS1667-1 | Glycol | Annual/ Apr | Basement Riser Rm. | Has Backflow | #1 Basement Glycol) 2.5" | 2005 | |
| 232 | 1667 | FS1667-2 | Wet | Annual/ Apr | 1st Floor | One Backflow Protects all Systems | #2 1st floor) 2" | 2005 | |
| 233 | 1667 | FS1667-3 | Wet | Annual/ Apr | 2nd Floor | #3 2nd floor) 1.5" | 2005 | ||
| 234 | 1667 | FS1667-4 | Wet | Annual/ Apr | 3rd Floor | #4 3rd floor) 1.5" | 2005 | ||
| 235 | 1682 | FS1682-1 | Wet | Annual/ Jul | North Mech. Rm. | No Backflow | 4" | 2001 | |
| 236 | 1682 | FS1682-2 | Dry | Annual/ Jul | South Mech. Rm. | Has Backflow | 6" | 1964 | |
| 237 | 1692 | FS1692-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 1964 | |
| 238 | 1805 | FS1805-1 | Dry | Annual/ Sep | Mech. Rm. | One Backflow Protects all Systems | #1 Dry) 6" | 2005 | |
| 239 | 1805 | FS1805-2 | Wet | Annual/ Sep | Mech. Rm. | #2 Wet) 4" | 2005 | ||
| 240 | 1816 | FS1816-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 4" | 1985 | |
| 241 | 1829 | FS1829-1 | Dry | Annual/ Jun | Mech. Rm. | Has Backflow | 6" | 2000 | |
| 242 | 1840 | FS1840-1 | Wet | Annual/ Sep | Mech. Rm. | Has Backflow | 6" | 2011 | |
| 243 | 1843 | FS1843-1 | Wet | Annual/ Oct | Fire Riser Rm. | Has Backflow | 4" | 1996 | |
| 244 | 1882 | FS1882-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 4" | 1981 | |
| 245 | 1925 | FS1925-1 | Wet | Annual/ Sep | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | 2011 | |
| 246 | 1925 | FS1925-2 | Wet | Annual/ Sep | 2nd Floor & Elevator | #2 2nd floor) 4" & Elevator Shaft | 2011 | ||
| Offline | 1950 | FS1950-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 9 Zones | ||
| Offline | 1950 | FS1950-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | |||
| Online | 1951 | FS1951-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| Online | 1951 | FS1951-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | |||
| Offline | 1952 | FS1952-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| Offline | 1952 | FS1952-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | |||
| 247 | 1953 | FS1953-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 248 | 1953 | FS1953-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | 1999 | ||
| Offline | 1954 | FS1954-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| Offline | 1954 | FS1954-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | |||
| 249 | 1957 | FS1957-1 | Wet | Annual/ Sep | Fire Riser Rm. | Has Backflow | 4" | 2010 | |
| 250 | 1958 | FS1958-1 | Wet | Annual/ Sep | Riser Rm. In Supply Cage | Has Backflow | 4" | 2009 | |
| 251 | 1959 | FS1959-1 | Wet | Annual/ Dec | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 3" & Elevator Mech. | 2012 | |
| 252 | 1959 | FS1959-2 | Wet | Annual/ Dec | 2nd Floor & Elevator | #2 2nd floor) 3" | 2012 | ||
| 253 | 1982 | FS1982-1 | Wet | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 1982 | |
| 254 | 2010 | FS2010-1 | Wet | Annual/ Dec | East Warehouse | One Backflow Protects all Systems | #1 East Warehouse) 8" | 2011 | |
| 255 | 2010 | FS2010-2 | Wet | Annual/ Dec | West Warehouse | #2 West Warehouse) 8" | 2011 | ||
| 256 | 2010 | FS2010-3 | Wet | Annual/ Dec | Admin Area | #3 Admin) 6" | 2011 | ||
| 257 | 2029 | FS2029-1 | Wet | Annual/ Dec | SE Corner of Bldg. | Has Backflow | 6" | 2003 | |
| 258 | 2039 | FS2039-1 | Wet/Fire Pump | Annual/ Nov | Fire Riser Rm. | Has Backflow x 2 | #1 4" Wet | 2014 | |
| 259 | 2039 | FS2039-2 | Wet | Annual/ Nov | Fire Riser Rm. | #2 4" Wet | 2014 | ||
| 260 | 2039 | FS2039-3 | Pre-Action | Annual/ Nov | Fire Riser Rm. | #3 4" Pre-Action | 2014 | ||
| 261 | 2050 | FS2050-1 | Wet | Annual/ Jan | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1998 | |
| 262 | 2050 | FS2050-2 | Glycol | Annual/ Jan | Fire Riser Rm. | #2 Glycol) 2" | 1998 | ||
| 263 | 2051 | FS2051-1 | Wet | Annual/ Jan | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 264 | 2051 | FS2051-2 | Glycol | Annual/ Jan | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 265 | 2052 | FS2052-1 | Wet | Annual/ Jan | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 266 | 2052 | FS2052-2 | Glycol | Annual/ Jan | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 267 | 2053 | FS2053-1 | Wet | Annual/ Jan | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 9 Zones | 1999 | |
| 268 | 2053 | FS2053-2 | Glycol | Annual/ Jan | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 269 | 2054 | FS2054-1 | Wet | Annual/ Jan | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 270 | 2054 | FS2054-2 | Glycol | Annual/ Jan | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 271 | 2057 | FS2057-1 | Wet | Annual/ Dec | Riser Rm. In Supply Cage | Has Backflow | 4" 5 Zones | 2009 | |
| 272 | 2058 | FS2058-1 | Wet | Annual/ Dec | Riser Rm. In Supply Cage | Has Backflow | 4" 5 Zones | 2009 | |
| 273 | 2070 | FS2070-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 9 Zones | ||
| 274 | 2070 | FS2070-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | |||
| 275 | 2071 | FS2071-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| 276 | 2071 | FS2071-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | |||
| 277 | 2072 | FS2072-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 2000 | |
| 278 | 2072 | FS2072-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | 2000 | ||
| 279 | 2073 | FS2073-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 2001 | |
| 280 | 2073 | FS2073-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | 2001 | ||
| 281 | 2074 | FS2074-1 | Wet | Annual/ Jan | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| 282 | 2074 | FS2074-2 | Glycol | Annual/ Jan | Dorm Room | #2 Glycol) 2" | |||
| 283 | 2077 | FS2077-1 | Wet | Annual/ Sep | Riser Rm. In Supply Cage | Has Backflow | 6" | 2009 | |
| 284 | 2078 | FS2078-1 | Wet | Annual/ Sep | Riser Rm. In Supply Cage | Has Backflow | 6" | 2009 | |
| 285 | 2082 | FS2082-1 | Wet | Annual/ Feb | Mech. Rm. | Has Backflow | 6" | 1979 | |
| 286 | 2131 | FS2131-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 4" | 2009 | |
| 287 | 2132 | FS2132-1 | Wet | Annual/ Nov | Bldg. A 3rd Floor | One Backflow Protects all Systems | #1 Bldg A) 4" | 2008 | |
| 288 | 2132 | FS2132-2 | Wet | Annual/ Nov | Bldg. B & C 1st Floor | #2 Bldg B) 4" | 2008 | ||
| 289 | 2132 | FS2132-3 | Wet | Annual/ Nov | Bldg. 2 2nd Floor | #3 Bldg C) 4" | 2008 | ||
| 290 | 2132 | FS2132-4 | Wet | Annual/ Nov | 1st Floor | #4 1st) 4" & Elevator Mech. | 2008 | ||
| 291 | 2132 | FS2132-5 | Wet | Annual/ Nov | 2nd Floor | #5 2nd) 4" | 2008 | ||
| 292 | 2132 | FS2132-6 | Wet | Annual/ Nov | 3rd Floor | #6 3rd) 4" & Elevator Shaft | 2008 | ||
| 293 | 2135 | FS2135-1 | Pre-Action | Annual/ Jun | High Bays | One Backflow Protects all Systems | #1) 6" | 1998 | |
| 294 | 2135 | FS2135-2 | Pre-Action | Annual/ Jun | Under Mezz. System | #2) 6" | 1998 | ||
| 295 | 2135 | FS2135-3 | Wet | Annual/ Jun | Admin Area | #3) 6" | 1998 | ||
| 296 | 2144 | FS2144-1 | Wet | Annual/ Sep | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 4" and Elevator Mech. | 2009 | |
| 297 | 2144 | FS2144-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 4" | 2009 | ||
| 298 | 2144 | FS2144-3 | Wet | Annual/ Sep | 3rd Floor | #3 3rd floor) 4" | 2009 | ||
| 299 | 2144 | FS2144-4 | Wet | Annual/ Sep | 4th Floor | #4 4th floor) 4" | 2009 | ||
| 300 | 2146 | FS2146-1 | Wet | Annual/ Sep | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 4" and Elevator Mech. | 2009 | |
| 301 | 2146 | FS2146-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 4" | 2009 | ||
| 302 | 2146 | FS2146-3 | Wet | Annual/ Sep | 3rd Floor | #3 3rd floor) 4" | 2009 | ||
| 303 | 2146 | FS2146-4 | Wet | Annual/ Sep | 4th Floor | #4 4th floor) 4" | 2009 | ||
| 304 | 2150 | FS2150-1 | Wet | Annual/ Feb | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 305 | 2150 | FS2150-2 | Glycol | Annual/ Feb | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 306 | 2151 | FS2151-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1998 | |
| 307 | 2151 | FS2151-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 1998 | ||
| 308 | 2152 | FS2152-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1998 | |
| 309 | 2152 | FS2152-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 1998 | ||
| 310 | 2153 | FS2153-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 311 | 2153 | FS2153-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 1999 | ||
| 312 | 2154 | FS2154-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 2000 | |
| 313 | 2154 | FS2154-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 2000 | ||
| 314 | 2157 | FS2157-1 | Wet | Annual/ Sep | Riser Rm. In Supply Cage | Has Backflow | 4" | 2009 | |
| 315 | 2158 | FS2158-1 | Wet | Annual/ Sep | Riser Rm. In Supply Cage | Has Backflow | 6" | 2009 | |
| 316 | 2160 | FS2160-1 | Pre-Action | Annual/ Jun | Basement Riser Cage | Has Backflow | 6" | 1995 | |
| 317 | 2250 | FS2250-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 2000 | |
| 318 | 2250 | FS2250-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 2000 | ||
| 319 | 2251 | FS2251-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1998 | |
| 320 | 2251 | FS2251-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 1998 | ||
| 321 | 2252 | FS2252-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1998 | |
| 322 | 2252 | FS2252-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 1998 | ||
| 323 | 2253 | FS2253-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 2000 | |
| 324 | 2253 | FS2253-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 2000 | ||
| 325 | 2254 | FS2254-1 | Wet | Annual/ Feb | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 2000 | |
| 326 | 2254 | FS2254-2 | Glycol | Annual/ Feb | Dorm Room | #2 Glycol) 2" | 2000 | ||
| 327 | 2257 | FS2257-1 | Wet | Annual/ Mar | Riser Rm. In Supply Cage | Has Backflow | 6" 5 Zones | 2009 | |
| 328 | 2258 | FS2258-1 | Wet | Annual/ Mar | Riser Rm. In Supply Cage | Has Backflow | 6" 5 Zones | 2009 | |
| 329 | 2259 | FS2259-1 | Wet | Annual/ Apr | Mech. Rm. | Has Backflow | 4" | 1981 | |
| 330 | 2260 | FS2260-1 | Wet | Annual/ Nov | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 6" | 2012 | |
| 331 | 2260 | FS2260-2 | Wet | Annual/ Nov | 2nd Floor & Elevator | #2 2nd floor) 6" | 2012 | ||
| 332 | 2330 | FS2330-1 | Wet/Fire Pump | Annual/ Sep | Mech. Rm. | Has Backflow | 4" | 2009 | |
| 333 | 2340 | FS2340-1 | Wet | Annual/ Sep | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 4" and Elevator Mech. | 2009 | |
| 334 | 2340 | FS2340-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 4" | 2009 | ||
| 335 | 2340 | FS2340-3 | Wet | Annual/ Sep | 3rd Floor | #3 3rd floor) 4" | 2009 | ||
| 336 | 2340 | FS2340-4 | Wet | Annual/ Sep | 4th Floor | #4 4th floor) 4" | 2009 | ||
| 337 | 2344 | FS2344-1 | Wet | Annual/ Sep | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 4" and Elevator Mech. | 2009 | |
| 338 | 2344 | FS2344-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 4" | 2009 | ||
| 339 | 2344 | FS2344-3 | Wet | Annual/ Sep | 3rd Floor | #3 3rd floor) 4" | 2009 | ||
| 340 | 2344 | FS2344-4 | Wet | Annual/ Sep | 4th Floor | #4 4th floor) 4" | 2009 | ||
| 341 | 2346 | FS2346-1 | Wet | Annual/ Sep | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 4" and Elevator Mech. | 2009 | |
| 342 | 2346 | FS2346-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 4" | 2009 | ||
| 343 | 2346 | FS2346-3 | Wet | Annual/ Sep | 3rd Floor | #3 3rd floor) 4" | 2009 | ||
| 344 | 2346 | FS2346-4 | Wet | Annual/ Sep | 4th Floor | #4 4th floor) 4" | 2009 | ||
| 345 | 2358 | FS2358-1 | Pre-Action | Annual/ May | Comm. Bldg. | No Backflow | 2" | 1995 | |
| 346 | 2392 | FS2392-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 1965 | |
| 347 | 2420 | FS2420-1 | Dry | Annual/ Dec | Mech. Rm. | Has Backflow | 4" | 1997 | |
| 348 | 2426 | FS2426-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 2.5" | 2007 | |
| 349 | 2427 | FS2427-1 | Wet | Annual/ Dec | Behind Paint Booth | Has Backflow | 6" | 1985 | |
| 350 | 2428 | FS2428-1 | Wet | Annual/ Dec | Garage | One Backflow Protects all Systems | 2.5" this building fed from 2429 | 1994 | |
| 351 | 2429 | FS2429-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 4" | 1993 | |
| 352 | 2435 | ICAS2435-1 | Clean Agent HFC-125 | Annual/ Apr | Center | Annual Inspection ONLY | |||
| 353 | 2450 | FS2450-1 | Wet | Annual/ Feb | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 354 | 2450 | FS2450-2 | Glycol | Annual/ Feb | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 355 | 2451 | FS2451-1 | Wet | Annual/ Feb | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 356 | 2451 | FS2451-2 | Glycol | Annual/ Feb | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 357 | 2452 | FS2452-1 | Wet | Annual/ Feb | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1999 | |
| 358 | 2452 | FS2452-2 | Glycol | Annual/ Feb | Fire Riser Rm. | #2 Glycol) 2" | 1999 | ||
| 359 | 2453 | FS2453-1 | Wet | Annual/ Feb | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1998 | |
| 360 | 2453 | FS2453-2 | Glycol | Annual/ Feb | Fire Riser Rm. | #2 Glycol) 2" | 1998 | ||
| 361 | 2454 | FS2454-1 | Wet | Annual/ Feb | Fire Riser Rm. | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | 1998 | |
| 362 | 2454 | FS2454-2 | Glycol | Annual/ Feb | Fire Riser Rm. | #2 Glycol) 2" | 1998 | ||
| 363 | 2457 | FS2457-1 | Wet | Annual/ Mar | Riser Rm. In Supply Cage | Has Backflow | 6" 6 Zones | 2009 | |
| 364 | 2458 | FS2458-1 | Wet | Annual/ Mar | Riser Rm. In Supply Cage | Has Backflow | 6" 6 Zones | 2009 | |
| 365 | 2492 | FS2492-1 | Dry Nitrogen | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 1965 | |
| 366 | 2550 | FS2550-1 | Wet | Annual/ Aug | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 19 Zones | 2000 | |
| 367 | 2550 | FS2550-2 | Glycol | Annual/ Aug | Dorm Room | #2 Glycol) 2" | 2000 | ||
| Offline | 2551 | FS2551-1 | Wet | Annual/ Aug | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| Offline | 2551 | FS2551-2 | Glycol | Annual/ Aug | Dorm Room | #2 Glycol) 2" | |||
| Offline | 2552 | FS2552-1 | Wet | Annual/ Aug | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| Offline | 2552 | FS2552-2 | Glycol | Annual/ Aug | Dorm Room | #2 Glycol) 2" | |||
| Offline | 2554 | FS2554-1 | Wet | Annual/ Aug | Dorm Room | One Backflow Protects all Systems | #1 Wet) 2.5" with 18 Zones | ||
| Offline | 2554 | FS2554-2 | Glycol | Annual/ Aug | Dorm Room | #2 Glycol) 2" | |||
| 367 | 2557 | FS2557-1 | Wet | Annual/ Apr | Riser Rm. In Supply Cage | Has Backflow | 4" 6 Zones | 2009 | |
| 368 | 2558 | FS2558-1 | Wet | Annual/ Apr | Riser Rm. In Supply Cage | Has Backflow | 4" 6 Zones | 2009 | |
| 369 | 2600 | FS2600-1 | Wet | Annual/ Jun | Admin Area | One Backflow Protects all Systems | #1) 4" | ||
| 370 | 2600 | FS2600-2 | Wet | Annual/ Jun | Readiness Area | #2) 4" | |||
| 371 | 2600 | FS2600-3 | Dry | Annual/ Jun | Hard Stand | #3) 6" | |||
| 372 | 2604 | FS2604-1 | Wet | Annual/ Oct | SE Corner of Bldg. | Has Backflow | 4" | ||
| 373 | 2605 | FS2605-1 | Wet | Annual/ Oct | Fire Riser Rm. | Has Backflow | 6" | ||
| 374 | 2607 | FS2607-1 | Wet | Annual/ Oct | Fire Riser Rm. | Has Backflow | 4" | ||
| 375 | 2610 | FS2610-1 | Dry | Annual/ Jul | Hard Stand | One Backflow Protects all Systems | #1) 4" | ||
| 376 | 2610 | FS2610-2 | Wet | Annual/ Jul | Readiness Area | #2) 4" | |||
| 377 | 2610 | FS2610-3 | Wet | Annual/ Jul | Admin Area | #3) 4" | |||
| 378 | 2614 | FS2614-1 | Wet | Annual/ Nov | SW Corner of Bldg. | Has Backflow | 4" | ||
| 379 | 2615 | FS2615-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 6" | ||
| 380 | 2617 | FS2617-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 4" | ||
| 381 | 2620 | FS2620-1 | Wet | Annual/ Jul | Readiness Area | One Backflow Protects all Systems | #2) 4" | ||
| 382 | 2620 | FS2620-2 | Wet | Annual/ Jul | Admin Area | #3) 4" | |||
| 383 | 2620 | FS2620-3 | Dry | Annual/ Jul | Hard Stand | #1) 4" | |||
| 384 | 2624 | FS2624-1 | Wet | Annual/ Nov | SW Corner of Bldg. | Has Backflow | 4" | 2009 | |
| 385 | 2625 | FS2625-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 6" | ||
| 386 | 2627 | FS2627-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 4" | ||
| 387 | 2630 | FS2630-1 | Wet | Annual/ Jul | Readiness Area | One Backflow Protects all Systems | #1) 4" | ||
| 388 | 2630 | FS2630-2 | Wet | Annual/ Jul | Admin Area | #2) 4" | |||
| 389 | 2630 | FS2630-3 | Dry | Annual/ Jul | Mod 3 Hard Stand | #3) 6" | |||
| 390 | 2630 | FS2630-4 | Dry | Annual/ Jul | Mod 6 Hard Stand | #4) 6" | |||
| 391 | 2634 | FS2634-1 | Wet | Annual/ Nov | SE Corner of Bldg. | Has Backflow | 4" | ||
| 392 | 2635 | FS2635-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 6" | ||
| 393 | 2637 | FS2637-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 4" | 2011 | |
| 394 | 2640 | FS2640-1 | Dry | Annual/ Jul | Hard Stand | One Backflow Protects all Systems | #1) 6" | ||
| 395 | 2640 | FS2640-2 | Wet | Annual/ Jul | Admin Area | #2) 6" | |||
| 396 | 2640 | FS2640-3 | Wet | Annual/ Jul | Readiness Area | #3) 4" | |||
| 397 | 2644 | FS2644-1 | Wet | Annual/ Nov | SE Corner of Bldg. | Has Backflow | 4" | ||
| 398 | 2645 | FS2645-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 6" | ||
| 399 | 2647 | FS2647-1 | Wet | Annual/ Nov | Fire Riser Rm. | Has Backflow | 4" | 2008 | |
| 400 | 2650 | FS2650-1 | Wet | Annual/ Jun | Admin Area | One Backflow Protects all Systems | #2) 4" | 2008 | |
| 401 | 2650 | FS2650-2 | Wet | Annual/ Jun | Readiness Area | #3) 4" | |||
| 402 | 2650 | FS2650-3 | Dry | Annual/ Jun | Hard Stand | #1) 6" | |||
| 403 | 2651 | FS2651-1 | Wet | Annual/ Jun | SE Corner of Bldg. | Has Backflow | 4" | ||
| 404 | 2655 | FS2655-1 | Wet | Annual/ Jun | Fire Riser Rm. | Has Backflow | 6" | ||
| 405 | 2657 | FS2657-1 | Wet | Annual/ Jun | Fire Riser Rm. | Has Backflow | 4" | ||
| 406 | 2692 | FS2692-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | ||
| 407 | 2758 | FS2758-1 | Wet | Annual/ Mar | Mod 4 | Has Backflow | 4" 6 Zones | ||
| 408 | 2764 | FS2764-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | 4" | ||
| 409 | 2792 | FS2792-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 2013 | |
| 410 | 2992 | FS2992-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 2013 | |
| 411 | 3092 | FS3092-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 2011 | |
| 412 | 3192 | FS3192-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 2012 | |
| 413 | 3292 | FS3292-1 | Dry | Annual/ Jul | Mech. Rm. | Has Backflow | 6" | 2012 | |
| 414 | 3450 | FS3450-1 | Wet | Annual/ Nov | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 6" | 1994 | |
| 415 | 3450 | FS3450-2 | Wet | Annual/ Nov | 2nd Floor | #2 2nd floor) 4" | |||
| 416 | 3490 | FS3490-1 | Wet/Fire Pump | Annual/ May | Mech. Rm. | One Backflow Protects all Systems | #1) 6" | 2016 | |
| 417 | 3490 | FS3490-2 | Wet | Annual/ May | 2nd Floor | #2) 6" | 1998 | ||
| 418 | 3490 | FS3490-3 | Dry | Annual/ May | North Storage | #3) 4" | 1995 | ||
| 419 | 3490 | FS3490-4 | Dry | Annual/ May | Center Storage | #4) 4" | 1995 | ||
| 420 | 3490 | FS3490-5 | Dry | Annual/ May | South Storage | #5) 4" | 1995 | ||
| 421 | 3492 | FS3492-1 | Wet | Annual/ May | 1st Floor & Elevator | One Backflow Protects all Systems | #1) 6", #2) 6" | 2011 | |
| 422 | 3492 | FS3492-2 | Wet | Annual/ May | 2nd Floor | 2011 | |||
| 423 | 3496 | FS3496-1 | Wet | Annual/ May | NW Corner Warehouse | Has Backflow | 6" | 2011 | |
| 424 | 3605 | FS3605-1 | Wet | Annual/ May | 1st Floor & Elevator | One Backflow Protects all Systems | #1) 3" | ||
| 425 | 3605 | FS3605-2 | Wet | Annual/ May | 2nd Floor | #2) 3" | 2010 | ||
| 426 | 4356 | FS4356-1 | Wet | Annual/ Jul | Mech. Rm. | Has Backflow | 4" | ||
| 427 | 4790 | FS4790-1 | Wet | Annual/ Jun | Mech. Rm. | Has Backflow | 6" | ||
| 428 | 5939 | FS5939-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | 4" | ||
| 429 | 5950 | FS5950-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | 4" | ||
| 430 | 6013 | FS6013-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 2.5" | ||
| 431 | 6058 | FS6058-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | 6" | ||
| 432 | 6060 | FS6060-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | 4" | ||
| 433 | 6110 | FS6110-1 | Wet | Annual/ Apr | Food Court | One Backflow Protects all Systems | #1 Food Court) 6" | ||
| 434 | 6110 | FS6110-2 | Wet | Annual/ Apr | Main Retail | #2 Main Retail) 6" | |||
| 435 | 6110 | FS6110-3 | Wet | Annual/ Apr | Main Retail | #3 Stock Rm/Retail) 6" | |||
| 436 | 6110 | FS6110-4 | Wet | Annual/ Apr | Warehouse | One Backflow Protects all Systems | #4 Warehouse) 6 | ||
| 437 | 6110 | FS6110-5 | Wet | Annual/ Apr | Main Retail | #5 SW Retail) 6" | |||
| 438 | 6110 | FS6110-6 | Glycol | Annual/ Apr | Garden Center | #6 Garden Center) 3" | |||
| 439 | 6203 | FS6203-1 | Wet | Annual/ Aug | Mech. Rm. | Has Backflow | 4" | ||
| 440 | 6204 | FS6204-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 441 | 6236 | FS6236-1 | Wet | Annual/ Aug | 1st Floor Center Office | No Backflow | 3" | ||
| 442 | 6236 | FS6236-2 | Dry | Annual/ Aug | Attic System | No Backflow | 3" | ||
| 443 | 6237 | FS6237-1 | Wet | Annual/ Aug | 1st Floor Center Office | One Backflow Protects all Systems | 3" | ||
| 444 | 6237 | FS6237-2 | Dry | Annual/ Aug | Attic System | 3" | |||
| 445 | 6256 | FS6256-1 | Pre-Action | Annual/ Jan | Comm. Bldg. | No Backflow | 2" | ||
| 446 | 7300 | FS7300-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 6" | ||
| 447 | 7314 | FS7314-1 | Wet | Annual/ May | Mech. Rm. | Has Backflow | #1) 3" | ||
| 448 | 7314 | FS7314-2 | Dry | Annual/ May | Mech. Rm. | #2) 6" | |||
| 449 | 7330 | FS7330-1 | Wet | Annual/ May | 1st Floor & Elevator | One Backflow Protects all Systems | #1) 6" | ||
| 450 | 7330 | FS7330-2 | Wet | Annual/ May | 2nd Floor | #2) 6" | |||
| 451 | 7330 | FS7330-3 | Dry | Annual/ May | Hard Stand | #3) 6" | |||
| 452 | 7400 | FS7400-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 453 | 7402 | FS7402-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 454 | 7403 | FS7403-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 3" | ||
| 455 | 7404 | FS7404-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 456 | 7410 | FS7410-1 | Wet | Annual/Mar | Mech. Rm. | Has Backflow | 4" | 2018 | |
| 457 | 7412 | FS7412-1 | Wet | Annual/ Mar | 1st Floor East | One Backflow Protects all Systems | #1) 6" Wet | ||
| 458 | 7412 | FS7412-2 | Wet | Annual/ Mar | 1st Floor West | #2) 4" Wet | |||
| 459 | 7412 | FS7412-3 | Wet | Annual/ Mar | 2nd Floor | #3) 6" Wet | |||
| 460 | 7412 | FS7412-4 | Dry | Annual/ Mar | Hard Stand | #4) 2.5" Dry | |||
| 461 | 7416 | FS7416-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 462 | 7417 | FS7417-1 | Wet | Annual/ Mar | Center Warehouse | Has Backflow | 4" | ||
| 463 | 7418 | FS7418-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 464 | 7419 | FS7419-1 | Wet | Annual/ Mar | Center Warehouse | Has Backflow | 2.5" | ||
| 465 | 7420 | FS7420-1 | Wet | Annual/ Mar | Center Warehouse | Has Backflow | 2.5" | ||
| 466 | 7421 | FS7421-1 | Wet | Annual/ Mar | Center Warehouse | Has Backflow | 2.5" | 2015 | |
| 467 | 7423 | FS7423-1 | Wet | Annual/ Mar | Center Warehouse | Has Backflow | 2.5" | ||
| 468 | 7426 | FS7426-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 6" | ||
| 469 | 7429 | FS7429-1 | Wet | Annual/ Jan | Mech. Rm. | Has Backflow | |||
| 470 | 7431 | FS7431-1 | Wet | Annual/ May | Mech. Rm. 109 | Has Backflow | 4" | ||
| 471 | 7436 | FS7436-1 | Wet | Annual/ Feb | Mech. Rm. | Has Backflow | 8" | ||
| 472 | 7437 | FS7437-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 2.5" | ||
| 473 | 7438 | FS7438-1 | Wet | Annual/ Mar | Mech. Rm. | One Backflow Protects all Systems | #1) 4" | ||
| 474 | 7438 | FS7438-2 | Dry | Annual/ Mar | Parachute Tower | #2) 2.5" | |||
| 475 | 7438 | FS7438-3 | Wet | Annual/ Mar | South Warehouse | Has Backflow | #3) 6" | ||
| 476 | 7440 | FS7440-1 | Wet | Annual/ Mar | Warehouse | Has Backflow | 4" | ||
| 477 | 7440 | FS7440-2 | Wet | Annual/ Mar | SE Mech. Rm. | Has Backflow | 2.5" | ||
| 478 | 7450 | FS7450-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 479 | 7462 | FS7462-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 480 | 7464 | FS7464-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 4" | ||
| 481 | 7465 | FS7465-1 | Dry | Annual/ Mar | Mech. Rm. | Has Backflow | 6" | 2016 | |
| 482 | 7467 | FS7467-1 | Dry | Annual/ Mar | North End | One Backflow Protects all Systems | #1 N. Warehouse) 6" | 2016 | |
| 483 | 7467 | FS7467-2 | Dry | Annual/ Mar | Admin Area | #2 Commons) 4" | 2016 | ||
| 484 | 7467 | FS7467-3 | Dry | Annual/ Mar | South Warehouse | #3 S. Warehouse) 6" | |||
| 485 | 7472 | FS7472-1 | Wet | Annual/ Jan | Mech. Rm. | Has Backflow | |||
| 486 | 7473 | FS7473-1 | Wet | Annual/ Apr | Mech. Rm. | One Backflow Protects all Systems | #1) 4" | ||
| 487 | 7473 | FS7473-2 | Wet | Annual/ Apr | Mech. Rm. | #2) 4" | |||
| 488 | 7473 | FS7473-3 | Dry | Annual/ Apr | Readiness Area | #3) 3" Rm. 120 Readiness Area | |||
| 489 | 7475 | IACS7475-1 | Clean Agent HFC-125 | Annual/ Apr | Center | Annual Inspection ONLY | |||
| 490 | 7480 | FS7480-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 6" 4 Zones | ||
| 491 | 7481 | FS7481-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 6" | ||
| 492 | 7482 | FS7482-1 | Wet | Annual/ Mar | Mech. Rm. | Has Backflow | 6" 4 Zones | ||
| 493 | 7492 | FS7492-1 | Wet | Annual/ May | Mech. Rm. | Has Backflow | 6" | ||
| 494 | 7493 | FS7493-1 | Wet | Annual/ Nov | Mech. Rm. | One Backflow Protects all Systems | |||
| 495 | 7493 | FS7493-2 | Dry | Annual/ Nov | East Attic | ||||
| 496 | 7493 | FS7493-3 | Dry | Annual/ Nov | West Attic | ||||
| 497 | 7493 | FS7493-4 | Wet | Annual/ Nov | Mech. Rm. | No Backflow | |||
| 498 | 7494 | FS7494-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | |||
| 499 | 7495 | FS7495-1 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | |||
| 500 | 7506 | FS7506-1 | Wet | Annual/ Sep | 1st & 2nd Center | One Backflow Protects all Systems | #1 Center) 2.5" | ||
| 501 | 7506 | FS7506-2 | Wet | Annual/ Sep | 1st West | #2 1st West) 2.5" | |||
| 502 | 7506 | FS7506-3 | Wet | Annual/ Sep | 1st East | #3 1st East) 2.5" | |||
| 503 | 7506 | FS7506-4 | Wet | Annual/ Sep | 2nd West | #4 2nd West) 2.5" | |||
| 504 | 7506 | FS7506-5 | Wet | Annual/ Sep | 2nd East | #5 2nd East) 2.5" | |||
| 505 | 7508 | FS7508-1 | Wet | Annual/ Sep | Mech. Rm. | Has Backflow | 4" | ||
| 506 | 7800 | FS7800-1 | Wet | Annual/ Aug | Mech. Rm. | One Backflow Protects all Systems | #1) 4" Wet | ||
| 507 | 7800 | FS7800-2 | Dry | Annual/ Aug | Mech. Rm. | #2) 3" Dry | |||
| 508 | 7803 | FS7803-1 | Dry | Annual/ Aug | SE Corner of Bldg. | Has Backflow | 4" | ||
| 509 | 8000 | FS8000-1 | Wet | Annual/ Aug | Weld Shop | One Backflow Protects all Systems | #1) 6" | ||
| 510 | 8000 | FS8000-2 | Wet | Annual/ Aug | Weld Shop | #2) 8" | 2001 | ||
| 511 | 8000 | FS8000-3 | Wet | Annual/ Aug | Weld Shop | #3) 6" | |||
| 512 | 8000 | FS8000-4 | Wet | Annual/ Aug | Metal Shop | #4) 6" | 1981 | ||
| 513 | 8000 | FS8000-5 | Wet | Annual/ Aug | Machine Shop | #5) 6" | 1986 | ||
| 514 | 8000 | FS8000-6 | Wet | Annual/ Aug | Canvas Shop | #6) 8" | 1986 | ||
| 515 | 8000 | FS8000-7 | Wet | Annual/ Aug | Canvas Shop | #7) 6" | 1986 | ||
| 516 | 8004 | FS8004-1 | Wet | Annual/ Aug | Spray Booth | One Backflow Protects all Systems | #1 Booth) 2.5" | 1986 | |
| 517 | 8004 | FS8004-2 | Wet | Annual/ Aug | Overhead | #2 Overhead) 4" | 1993 | ||
| 518 | 8008 | FS8008-1 | Pre-Action | Annual/ Jan | Comm. Bldg. | Has Backflow | 2" | 1993 | |
| 519 | 8009 | FS8009-1 | Dry/Fire Pump | Annual/ Aug | Fire Riser Rm. | Has Backflow | 6" | 2013 | |
| 520 | 8010 | FS8010-1 | Wet/Fire Pump | Annual/ Aug | Mech. Rm. | Has Backflow | #1) 4" Wet | 2013 | |
| 521 | 8021 | FS8021-1 | Wet | Annual/ Aug | Mech. Rm. | Has Backflow | 2.5" | 2011 | |
| 522 | 8030 | FS8030-10 | Wet | Annual/ Aug | North Side Hallway | #10) 4" | 2009 | ||
| 523 | 8030 | FS8030-8 | Wet | Annual/ Aug | North Side Hallway | One Backflow Protects all Systems | #8) 4" | 2011 | |
| 524 | 8030 | FS8030-9 | Wet | Annual/ Aug | North Side Hallway | #9) 4" | 2009 | ||
| 525 | 8100 | FS8100-1 | Wet | Annual/ Aug | Mech. Rm. | Has Backflow | 6" | ||
| 526 | 8110 | FS8110 | Wet/ Fire Pump | Annual/ Dec | Fire Riser Rm. | Has Backflow | 6" Wet | 2011 | |
| 527 | 8142 | FS8142-1 | Wet | Annual/ Aug | Mech. Rm. | Has Backflow | 6" | 2011 | |
| 528 | 8152 | FS8152-1 | Wet | Annual/ Aug | Mech. Rm. | Has Backflow | 4" | 1981 | |
| 529 | 8200 | FS8200-1 | Wet | Annual/ Aug | Mech. Rm. | One Backflow Protects all Systems | #1) 3" Wet | 2013 | |
| 530 | 8200 | FS8200-2 | Dry | Annual/ Aug | Mech. Rm. | #2) 3" Dry | 2013 | ||
| 531 | 8300 | FS8300-1 | Wet | Annual/ Aug | Mech. Rm. | One Backflow Protects all Systems | #1) 4" Wet | ||
| 532 | 8300 | FS8300-2 | Dry | Annual/ Aug | Mech. Rm. | #2) 6" Dry | |||
| 533 | 8930 | FS8930-1 | Wet/Fire Pump | Annual/ Aug | Overhead | One Backflow Protects all Systems | #1 Racks) 4" | ||
| 534 | 8930 | FS8930-2 | Wet | Annual/ Aug | Rack Storage | #2 Overhead) 4" | |||
| 535 | 8932 | FS8932-1 | Wet | Annual/ Jan | Fire Riser Rm. | One Backflow Protects all Systems | #1) 4" | ||
| 536 | 8932 | FS8932-2 | Wet | Annual/ Jan | Fire Riser Rm. | #2) 4" | 2011 | ||
| 537 | 9060 | FS9060-1 | Wet | Annual/ Jan | Mech. Rm. | Has Backflow | 6" | 2011 | |
| 538 | 9061 | FS9061-1 | Wet | Annual/ Jan | Mech. Rm. | Has Backflow | 6" | 2011 | |
| 539 | 9062 | FS9062-1 | Wet | Annual/ May | 1st Floor & Elevator | One Backflow Protects all Systems | #1 1st floor) 6" | 2015 | |
| 540 | 9062 | FS9062-2 | Wet | Annual/ May | 2nd Floor | #2 2nd floor) 6" | 2009 | ||
| 541 | 9067 | FS9067-1 | Wet/Fire Pump | Annual/ Oct | Mech. Rm. | One Backflow Protects all Systems | #1) 3" Wet | ||
| 542 | 9067 | FS9067-2 | Wet | Annual/ Oct | Mech. Rm. | #2) 6" Wet | |||
| 543 | 9067 | FS9067-3 | Dry | Annual/ Oct | Mech. Rm. | #3) 4" Dry | |||
| 544 | 9072 | FS9072-1 | Wet | Annual/ Jul | Mech. Rm. | Has Backflow | 4" | ||
| 545 | 9079 | FS9079-1 | Wet/Fire Pump | Annual/ Jul | Mech. Rm. | One Backflow Protects all Systems | #1) 4' Wet | ||
| 546 | 9079 | FS9079-2 | Dry | Annual/ Jul | Hard Stand | #2) 4" Dry | |||
| 547 | 9090 | FS9090-1 | Wet | Annual/ Oct | South Mech. Rm. | Has Backflow | #1) 6" Wet | ||
| 548 | 9090 | FS9090-2 | Dry | Annual/ Oct | North Storage | #2) 3" Dry | 2011 | ||
| 549 | 9091 | FS9091-1 | Wet | Annual/ Oct | West Mech. Rm. | One Backflow Protects all Systems | #1) 3" Wet | 2015 | |
| 550 | 9091 | FS9091-2 | Dry | Annual/ Oct | West Mech. Rm. | #2) 3" Dry | 2015 | ||
| 551 | 9092 | FS9092-1 | Wet | Annual/ Oct | 1st Floor | One Backflow Protects all Systems | #1) 4" | ||
| 552 | 9092 | FS9092-2 | Wet | Annual/ Oct | 2nd Floor | #2) 4" | |||
| 553 | 9093 | FS9093-1 | Wet | Annual/ Oct | East Mech. Rm. | Has Backflow | 6" | ||
| 554 | 9097 | FS9097 | Wet | Annual/ Jan | East Mech. Rm. | Has Backflow | 4" | Mar-20 | |
| 555 | 9097 | FS9097A | Dry Nitrogen | Annual/ Jun | East Mech. Rm. | Has Backflow | 6" | Jun-20 | |
| 556 | 9244 | FS9244-1 | Wet | Annual/ Feb | SE Corner of Bldg. | Has Backflow | 4" | ||
| 557 | 9248 | FS9248-1 | Wet | Annual/ Feb | Corner of Bldg. | Has Backflow | 8" with 2 Zones | ||
| 558 | 9280 | FS9280-1 | Wet | Annual/ Mar | Fire Riser Rm. | Has Backflow | 4" | ||
| 559 | 9368 | FS9368 | Wet | Annual/ Nov | Mech. Rm. | Has Backflow | 6" | 7/30/20 | |
| 560 | 9374 | FS9374-1 | Wet | Annual/ Nov | Mech. Rm. | One Backflow Protects all Systems | #1) 3" | 7/30/20 | |
| 561 | 9374 | FS9374-2 | Dry | Annual/ Nov | Mech. Rm. | #2) 6" | 7/30/20 | ||
| 562 | 9374 | FS9374-3 | Dry | Annual/ Nov | Mech. Rm. | #3) 6" | 7/30/20 | ||
| 563 | 9420 | FS9420-1 | Wet | Annual/ Oct | Fire Riser Rm. | One Backflow Protects all Systems | #1) 4" | ||
| 564 | 9420 | FS9420-2 | Wet | Annual/ Oct | 1st Floor & Elevator | #2) 4" | |||
| 565 | 9420 | FS9420-3 | Wet | Annual/ Oct | 2nd Floor | #3) 4" | 2011 | ||
| 566 | 9420 | FS9420-4 | Wet | Annual/ Oct | 3rd Floor | #4) 4" | |||
| 567 | 9420 | FS9420-5 | Wet | Annual/ Oct | Penthouse | #5) 1.5" | |||
| 568 | 9424 | FS9424-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | ||
| 569 | 9425 | FS9425-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | ||
| 570 | 9426 | FS9426-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2014 | |
| 571 | 9432 | FS9432-1 | Wet | Annual/ Jun | Mech. Rm. | Has Backflow | 6" | ||
| 572 | 9433 | FS9433-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | ||
| 573 | 9436 | FS9436-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | ||
| 574 | 9437 | FS9437-1 | Wet | Annual/ Jul | Mech. Rm. | One Backflow Protects all Systems | #1) 6" Wet | ||
| 575 | 9437 | FS9437-2 | Dry | Annual/ Jul | Mod 2 Hard Stand | #2) 4" Dry | 2014 | ||
| 576 | 9439 | FS9439-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 4" | 2011 | |
| 577 | 9441 | FS9441-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2011 | |
| 578 | 9442 | FS9442-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2015 | |
| 579 | 9446 | FS9446-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | ||
| 580 | 9447 | FS9447-1 | Wet | Annual/ Jul | Readiness Area | One Backflow Protects all Systems | #1) 6" Wet | ||
| 581 | 9447 | FS9447-2 | Wet | Annual/ Jul | Admin Area | #2) 4" Wet | |||
| 582 | 9447 | FS9447-3 | Dry | Annual/ Jul | Mech. Rm. | #3) 6" Dry | 2014 | ||
| 583 | 9449 | FS9449-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 6" 13 Zones | 2004 | |
| 584 | 9452 | FS9452-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2004 | |
| 585 | 9453 | FS9453-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 2015 | ||
| 586 | 9456 | FS9456-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2004 | |
| 587 | 9457 | FS9457-1 | Wet | Annual/ Jul | Readiness Area | One Backflow Protects all Systems | #1) 6" Wet | 2004 | |
| 588 | 9457 | FS9457-2 | Wet | Annual/ Jul | Admin Area | #2) 4" Wet | 2004 | ||
| 589 | 9457 | FS9457-3 | Dry | Annual/ Jul | Mech. Rm. | #3) 4" Dry | 2004 | ||
| 590 | 9459 | FS9459-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 6" 13 Zones | 2004 | |
| 591 | 9462 | FS9462-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | ||
| 592 | 9463 | FS9463-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2015 | |
| 593 | 9466 | FS9466-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 2011 | |
| 594 | 9467 | FS9467-1 | Wet | Annual/ Jul | Readiness Area | One Backflow Protects all Systems | #1) 6" Wet | 2010 | |
| 595 | 9467 | FS9467-2 | Wet | Annual/ Jul | Admin Area | #2) 4" Wet | |||
| 596 | 9467 | FS9467-3 | Dry | Annual/ Jul | Mech. Rm. | #3) 6" Dry | |||
| 597 | 9469 | FS9469-1 | Wet | Annual/ Dec | Mech. Rm. | Has Backflow | 6" 13 Zones | ||
| 598 | 9471 | FS9471-1 | Wet | Annual/ Sep | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | ||
| 599 | 9471 | FS9471-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 3" | |||
| 600 | 9472 | FS9427-1 | Wet | Annual/ Jul | Mech. Rm. | One Backflow Protects all Systems | #1) 6" Wet | ||
| 601 | 9472 | FS9427-2 | Dry | Annual/ Jul | Mod 2 Hard Stand | #2) 4" Dry | |||
| 602 | 9472 | FS9472-1 | Wet | Annual/ Sep | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | 1964 | |
| 603 | 9472 | FS9472-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 3" | 1964 | ||
| 604 | 9473 | FS9473-1 | Wet | Annual/ Sep | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | 1964 | |
| 605 | 9473 | FS9473-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 3" | 1964 | ||
| 606 | 9474 | FS9474-1 | Wet | Annual/ Sep | 1st Floor | One Backflow Protects all Systems | #1 1st floor) 4" | 1964 | |
| 607 | 9474 | FS9474-2 | Wet | Annual/ Sep | 2nd Floor | #2 2nd floor) 3" | 1964 | ||
| 608 | 9476 | FS9476-1 | Wet | Annual/ Jan | One Backflow Protects all Systems | #1) 6" | 11/16/21 | ||
| 609 | 9476 | FS9467-2 | Wet | Annual/ Jan | #2) 6" | 11/16/21 | |||
| 610 | 9476 | FS9476C-1 | Wet | Annual/ Jan | Fire Riser Rm. | Has Backflow | #1) 8" | 11/16/21 | |
| 611 | 9476 | FS9476C-2 | Wet | Annual/ Jan | Fire Riser Rm. | Has Backflow | #1) 8" | 11/16/21 | |
| 612 | 9476 | FS9476C-3 | Wet | Annual/ Jan | Fire Riser Rm. | Has Backflow | #1) 8" | 11/16/21 | |
| 613 | 9476 | FS9476E | Dry Nitrogen | Annual/ May | Fire Riser Rm. | Has Backflow | 6" | 11/16/21 | |
| 614 | 9478 | FS9478-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 1962 | ||
| 615 | 9484 | FS9484-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 1962 | |
| 616 | 9485 | FS9485-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 1963 | |
| 617 | 9486 | FS9486-1 | Wet | Annual/ Oct | Mech. Rm. | Has Backflow | 6" | 1965 | |
| 618 | 9487 | FS9487-1 | Wet | Annual/ Jun | Readiness Area | One Backflow Protects all Systems | #1) 6" Wet | 1965 | |
| 619 | 9487 | FS9487-2 | Wet | Annual/ Jun | Admin Area | #2) 4" Wet | 1965 | ||
| 620 | 9487 | FS9487-3 | Dry | Annual/ Jun | Hard Stand | #3) 6" Dry | 1974 | ||
| 621 | 9496 | FS9496-1 | Wet | Annual/ Jan | One Backflow Protects all Systems | #1) 6" | 11/16/21 | ||
| 622 | 9496 | FS9496-2 | Wet | Annual/ Jan | #2) 6" | 11/16/21 | |||
| 623 | 9496 | FS9496A | Wet | Annual/ Jan | Main Entry | Has Backflow | 8" | 11/16/21 | |
| 624 | 9496 | FS9496B | Dry Nitrogen | Annual/ May | Fire Riser Rm. | Has Backflow | 6" | 11/16/21 | |
| 625 | 9496 | FS9496C | Dry Nitrogen | Annual/ May | Fire Riser Rm. | Has Backflow | 6" | 11/16/21 | |
| 626 | 9535 | IACS9535-1 | Clean Agent HFC-125 | Annual/ Apr | Center | Annual Inspection ONLY | |||
| 627 | 9543 | FS9543-1 | Wet | Annual/ | 1st Floor | One Backflow Protects all Systems | 6" Wet | 2020 | |
| 628 | 9543 | FS9543-2 | wet | Annual/ | 2nd Floor | 4" Wet | 2020 | ||
| 629 | 9545 | IACS9545-1 | Clean Agent HFC-125 | Annual/ Apr | Center | Annual Inspection ONLY | |||
| 630 | 9550 | FS9550-1 | Wet | Annual/ Sep | Mech. Rm. | Has Backflow | 6" | 1972 | |
| 631 | 9612 | FS9612-1 | Wet | Annual/ Sep | Clipper Rm. | Has Backflow | 4" | 2014 | |
| 632 | 9619 | FS9619-1 | Dry | Annual/ Apr | SE Corner of Bldg. | Has Backflow | 1) 6" | 2014 | |
| 633 | 9620 | FS9620-1 | Wet | Annual/ Sep | Front Entrance Cage | No Backflow | #1 Admin) 6" | 2014 | |
| 634 | 9620 | FS9620-2 | Deluge | Annual/ Sep | South End | Open Head System | #2 S. Hanger) 6" | 2014 | |
| 635 | 9620 | FS9620-3 | Deluge | Annual/ Sep | Center | Open Head System | #3 Center Hanger) 6" | 2014 | |
| 636 | 9620 | FS9620-4 | Deluge | Annual/ Sep | North End | Open Head System | #4 N. Hanger) 6" | 2014 | |
| 637 | 9620 | FS9620-5 | Wet | Annual/ Sep | North End | Has Backflow | #5 N. addition 6" | 2017 | |
| 638 | 9624 | FS9624-1 | Wet | Annual/ Feb | NW Corner Warehouse | Has Backflow | 6" | 2014 | |
| 639 | 9628 | FS9628-1 | Dry | Annual/ Sep | Mech. Rm. | Has Backflow | 6" | 2014 | |
| 640 | 9630 | FS9630-1 | Wet | Annual/ Jun | A-C Hanger Bays | No Backflow Needed | (2)6", (1) 8" & (1) 3" Dry Rm. 142 | 2014 | |
| 641 | 9630 | FS9630-10 | HE Foam | Annual/ Jun | C/D Rm. 164 | No Backflow Needed | (2) 4" & (1) 6" Rm. 164 | ||
| 642 | 9630 | FS9630-2 | Wet | Annual/ Jun | D-E Hanger Bays | No Backflow Needed | 6" | 2014 | |
| 643 | 9630 | FS9630-3 | Wet | Annual/ Jun | Admin Area | No Backflow Needed | 6" | 2014 | |
| 644 | 9630 | FS9630-4 | Dry | Annual/ Jun | Main Entry | No Backflow Needed | 3" Dry Rm. 142 | 2014 | |
| 645 | 9630 | FS9630-5 | Dry | Annual/ Jun | Outside Storage | No Backflow Needed | 6" Dry Rm 111 | 2014 |