05h Paine-Field-Analysis-asbestos_Jun2021.pdf
PDF 606 KB Posted
- Solicitation number
- W50S9E24QA003
- Issued by
-
Department of the Army National Guard
About this file
This document is an analytical report from Eurofins FGS, Seattle regarding asbestos and lead testing performed at Building 531 located at Paine Field in Everett, Washington for the Washington Air National Guard.
The key details are:
- Asbestos testing was performed on various materials including ceiling tiles, floor tiles, mastic, and pipe insulation. Chrysotile asbestos was detected in some floor tiles and mastic at levels up to 8%.
- Lead testing was performed on several solid samples. Lead levels ranged from 160 mg/kg to 1,900 mg/kg.
- The sample collection date was April 22, 2021 and the samples were received by the lab on June 3, 2021.
- The analytical work was subcontracted to EM Lab Seattle.
The related federal contract opportunity is for the demolition of Building 531 located at Paine Field in Everett, Washington. The solicitation number is W50S9E24QA003. Key details include:
- The contractor shall provide all materials, labor, equipment, and incidentals to perform the demolition work per the Statement of Work.
- A site visit is scheduled for April 17, 2024 and all questions must be submitted as RFIs by April 24, 2024.
- Quotes must include the contractor name, UEID/CAGE code, and be valid through September 30, 2024.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ANALYTICAL REPORT
Eurofins FGS, Seattle 5755 8th Street East Tacoma, WA 98424 Tel: (253)922-2310
Laboratory Job ID: 580-103522-1 Laboratory Sample Delivery Group: Paine Field Everett Client Project/Site: Building 531 Asbestos/Lead testing
For:
Washington Air National Guard
254 RHS/CEV
104 Air Defense Lane Camp Murray, Washington 98430-5022
Attn: Cheryl Settle
Authorized for release by:
6/15/2021 4:40:42 PM
Sheri Cruz, Project Manager I (253)922-2310 Sheri.Cruz@Eurofinset.com
This report has been electronically signed and authorized by the signatory. Electronic signature is intended to be the legally binding equivalent of a traditionally handwritten signature.
Results relate only to the items tested and the sample(s) as received by the laboratory.
https://secure.testamericainc.com/TotalAccess/login.aspx http://www.testamericainc.com/services-we-offer/ask-the-expert http://www.eurofinsus.com/Env mailto:Sheri.Cruz@Eurofinset.com
Table of Contents
Client: Washington Air National Guard Project/Site: Building 531 Asbestos/Lead testing
Laboratory Job ID: 580-103522-1 SDG: Paine Field Everett
Eurofins FGS, Seattle
6/15/2021
Cover Page
Table of Contents
Case Narrative
Definitions
Client Sample Results
QC Sample Results
Chronicle
Certification Summary
Sample Summary
Subcontract Data
Chain of Custody
Receipt Checklists
Case Narrative Client: Washington Air National Guard Job ID: 580-103522-1 Project/Site: Building 531 Asbestos/Lead testing SDG: Paine Field Everett
Job ID: 580-103522-1
Laboratory: Eurofins FGS, Seattle
Narrative
Job Narrative 580-103522-1
Comments
6/10/21 client confirmed sample 580-102522-11 (21-029 Paine Lead) should be total lead and not TCLP Cr per the COC.
Receipt
The samples were received on 6/3/2021 9:30 AM. Unless otherwise noted below, the samples arrived in good condition. The temperature of the cooler at receipt was 23.4º C.
GC/MS VOA
No analytical or quality issues were noted, other than those described in the Definitions/Glossary page.
Metals No analytical or quality issues were noted, other than those described above or in the Definitions/Glossary page.
General Chemistry Method 1311: EPA Method 1311 requires the room temperature to be maintained at 23 +/- 2 degrees Celsius for the duration of the leaching process. For batch 580-358698, the temperature was outside of this range by 0.5 C on the upper end. As a result, the test was not fully compliant with the requirements of 40 CFR Part 261.
Method 1311: Insufficient sample was provided to perform the leaching procedure with the required 100g for the following sample: 21-032 Parts (580-103522-14). The volume of leaching fluid was adjusted proportionally to maintain a 20:1 ratio of leaching fluid to weight of sample. Reporting limits (RLs) are not affected.
Method 1311: Insufficient sample was provided to perform the leaching procedure with the required 100g for the following sample:
21-030-VM WeldingRod (580-103522-12). The volume of leaching fluid was adjusted proportionally to maintain a 20:1 ratio of leaching fluid to weight of sample. Reporting limits (RLs) are not affected.
Method 1311: Insufficient sample was provided to perform the leaching procedure with the required 100g for the following sample: 21-035 VM-Paintbooth (580-103522-17). The volume of leaching fluid was adjusted proportionally to maintain a 20:1 ratio of leaching fluid to weight of sample. Reporting limits (RLs) are not affected.
No additional analytical or quality issues were noted, other than those described above or in the Definitions/Glossary page.
VOA Prep
No analytical or quality issues were noted, other than those described in the Definitions/Glossary page.
Subcontract Work Method Asbestos PLM. EPA600/R-93-1.: This method was subcontracted to EM Lab Seattle WA. The subcontract laboratory certification is different from that of the facility issuing the final report.
Eurofins FGS, Seattle Page 3 of 28 6/15/2021
Definitions/Glossary Job ID: 580-103522-1Client: Washington Air National Guard
SDG: Paine Field EverettProject/Site: Building 531 Asbestos/Lead testing
Qualifiers
GC/MS VOA
Qualifier Description
D The reported value is from a dilution.
Qualifier
U Undetected at the Limit of Detection.
Metals Qualifier Description
J Estimated: The analyte was positively identified; the quantitation is an estimation
Qualifier
U Undetected at the Limit of Detection.
Glossary
These commonly used abbreviations may or may not be present in this report.
¤ Listed under the "D" column to designate that the result is reported on a dry weight basis
Abbreviation
%R Percent Recovery
CFL Contains Free Liquid
CFU Colony Forming Unit
CNF Contains No Free Liquid
DER Duplicate Error Ratio (normalized absolute difference)
Dil Fac Dilution Factor
DL Detection Limit (DoD/DOE)
DL, RA, RE, IN Indicates a Dilution, Re-analysis, Re-extraction, or additional Initial metals/anion analysis of the sample
DLC Decision Level Concentration (Radiochemistry)
EDL Estimated Detection Limit (Dioxin)
LOD Limit of Detection (DoD/DOE)
LOQ Limit of Quantitation (DoD/DOE)
MCL EPA recommended "Maximum Contaminant Level"
MDA Minimum Detectable Activity (Radiochemistry)
MDC Minimum Detectable Concentration (Radiochemistry)
MDL Method Detection Limit
ML Minimum Level (Dioxin)
MPN Most Probable Number
MQL Method Quantitation Limit
NC Not Calculated
ND Not Detected at the reporting limit (or MDL or EDL if shown)
NEG Negative / Absent
POS Positive / Present
PQL Practical Quantitation Limit
PRES Presumptive
QC Quality Control
RER Relative Error Ratio (Radiochemistry)
RL Reporting Limit or Requested Limit (Radiochemistry)
RPD Relative Percent Difference, a measure of the relative difference between two points
TEF Toxicity Equivalent Factor (Dioxin)
TEQ Toxicity Equivalent Quotient (Dioxin)
TNTC Too Numerous To Count
Eurofins FGS, Seattle
Page 4 of 28 6/15/2021
Client Sample Results
SDG: Paine Field EverettProject/Site: Building 531 Asbestos/Lead testing
Lab Sample ID: 580-103522-9Client Sample ID: 21-027-Paine Asbestos Matrix: SolidDate Collected: 04/22/21 11:30
Date Received: 06/03/21 09:30
Method: 6010D - Metals (ICP)
LOQ DL
Lead 1900 1.5 0.22 mg/Kg 06/12/21 09:53 06/14/21 19:28 1
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins FGS, Seattle
Page 5 of 28 6/15/2021
1296447923C Text Box Accidently marked the CoC for lead not asbestos - this is a dud sample
SDG: Paine Field EverettProject/Site: Building 531 Asbestos/Lead testing
Lab Sample ID: 580-103522-10Client Sample ID: 21-028-Paine Lead Matrix: SolidDate Collected: 04/22/21 12:00
Date Received: 06/03/21 09:30
Method: 6010D - Metals (ICP)
LOQ DL
Lead 450 1.3 0.20 mg/Kg 06/12/21 09:53 06/14/21 19:46 1
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins FGS, Seattle
Page 6 of 28 6/15/2021
1296447923C
This sample was pure paint chips to see if the paint had lead in it. It does not represent the entire article. Another sample was taken later that included a full cross section of the article.
SDG: Paine Field EverettProject/Site: Building 531 Asbestos/Lead testing
Lab Sample ID: 580-103522-11Client Sample ID: 21-029-Paine Lead Matrix: SolidDate Collected: 04/22/21 12:00
Date Received: 06/03/21 09:30
Method: 6010D - Metals (ICP)
LOQ DL
Lead 160 1.5 0.22 mg/Kg 06/12/21 09:53 06/14/21 19:53 1
Analyte Dil FacAnalyzedPreparedUnit DResult Qualifier
Eurofins FGS, Seattle
Page 7 of 28 6/15/2021
1296447923C
This sample was pure paint chips to see if the paint had lead in it. It does not represent the entire article. Another sample was taken later that included a full cross section of the article.
Approved by:
Approved Signatory David Andrews
Report for:
Sheri Cruz TestAmerica-Seattle 5755 8th Street East Tacoma, WA 98424
Regarding: Project: 580-103522-1; Building 531 Asbestos/Lead Testing
EML ID: 2656326
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 06-04-2021 and 06-09-2021
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267) NVLAP Lab Code 600266-0
EMLab ID: 2656326, Page 1 of 3Eurofins EPK Built Environment Testing, LLC
Page 21 of 28 6/15/2021
Eurofins EMLab P&K 19515 North Creek Pkwy N, #100, Bothell, WA 98011
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: TestAmerica-Seattle
C/O: Sheri Cruz Re: 580-103522-1; Building 531 Asbestos/Lead Testing
Date of Sampling: 05-22-2021 Date of Receipt: 06-04-2021 Date of Report: 06-09-2021
ASBESTOS PLM REPORT
Total Samples Submitted: 8 Total Samples Analyzed: 8
Total Samples with Layer Asbestos Content > 1%: 4
Location: 21-022-CM-Tile Lab ID-Version‡: 12694073-1
Sample Layers Asbestos Content Tan Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 55% Cellulose 40% Glass Fibers
Sample Composite Homogeneity: Good
Location: 21-023A-Asbestos-Mastic Lab ID-Version‡: 12694074-1
Sample Layers Asbestos Content Black Mastic 4% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 21-023B-Asbestos-Tile Lab ID-Version‡: 12694075-1
Sample Layers Asbestos Content Gray Floor Tile 8% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 21-024A-Asbestos-Mastic Lab ID-Version‡: 12694076-1
Sample Layers Asbestos Content Black Mastic 4% Chrysotile
Yellow Mastic ND Sample Composite Homogeneity: Moderate
EMLab ID: 2656326, Page 2 of 3Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Page 22 of 28 6/15/2021
Eurofins EMLab P&K 19515 North Creek Pkwy N, #100, Bothell, WA 98011
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: TestAmerica-Seattle
C/O: Sheri Cruz Re: 580-103522-1; Building 531 Asbestos/Lead Testing
Date of Sampling: 05-22-2021 Date of Receipt: 06-04-2021 Date of Report: 06-09-2021
ASBESTOS PLM REPORT
Location: 21-024B-Asbestos-Tile Lab ID-Version‡: 12694077-1
Sample Layers Asbestos Content Gray Floor Tile 8% Chrysotile White Floor Tile ND
Sample Composite Homogeneity: Moderate
Location: 21-025-Paine Asbestos Lab ID-Version‡: 12694078-1
Sample Layers Asbestos Content Brown Ceiling Tile ND
Composite Non-Asbestos Content: 90% Cellulose Sample Composite Homogeneity: Moderate
Location: 21-025A-Paine Asbestos Lab ID-Version‡: 12694079-1
Sample Layers Asbestos Content Brown Mastic ND
Sample Composite Homogeneity: Moderate
Location: 21-026-Paine Asbestos Lab ID-Version‡: 12694080-1
Sample Layers Asbestos Content Gray Pipe Insulation ND
Composite Non-Asbestos Content: 95% Cellulose Sample Composite Homogeneity: Good
EMLab ID: 2656326, Page 3 of 3Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. Eurofins EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Page 23 of 28 6/15/2021
Page 24 of 28 6/15/2021
Page 25 of 28 6/15/2021
Page 26 of 28 6/15/2021
Page 27 of 28 6/15/2021
Login Sample Receipt Checklist
Client: Washington Air National Guard Job Number: 580-103522-1
SDG Number: Paine Field Everett
Login Number: 103522
Question Answer Comment
Creator: Blankinship, Tom X
List Source: Eurofins FGS, Seattle
List Number: 1
TrueRadioactivity wasn't checked or is </= background as measured by a survey meter.
TrueThe cooler's custody seal, if present, is intact.
TrueSample custody seals, if present, are intact.
TrueThe cooler or samples do not appear to have been compromised or tampered with.
FalseSamples were received on ice. Thermal preservation not required.
TrueCooler Temperature is acceptable.
TrueCooler Temperature is recorded.
TrueCOC is present.
TrueCOC is filled out in ink and legible.
TrueCOC is filled out with all pertinent information.
TrueIs the Field Sampler's name present on COC?
TrueThere are no discrepancies between the containers received and the COC.
TrueSamples are received within Holding Time (excluding tests with immediate HTs)
TrueSample containers have legible labels.
TrueContainers are not broken or leaking.
TrueSample collection date/times are provided.
TrueAppropriate sample containers are used.
TrueSample bottles are completely filled.
N/ASample Preservation Verified.
TrueThere is sufficient vol. for all requested analyses, incl. any requested MS/MSDs
N/AContainers requiring zero headspace have no headspace or bubble is <6mm (1/4").
TrueMultiphasic samples are not present.
TrueSamples do not require splitting or compositing.
N/AResidual Chlorine Checked.
Eurofins FGS, Seattle Page 28 of 28 6/15/2021
| 1. Cover Page |
| 2. Table of Contents |
| 3. Case Narrative |
| 4. Definitions |
| 5. Client Sample Results |
| 6. QC Sample Results |
| 7. Chronicle |
| 8. Certification Summary |
| 9. Sample Summary |
| 10. Subcontract Data |
| 11. Chain of Custody |
| 12. Receipt Checklists |
File details come from the government source that posted it. Updated .