USEB132001_Mustang_Building Fire Suppression List.pdf

PDF 147 KB Posted

Attached to
Repair Water Mains and Roads
Solicitation number
W50S9A-20-B-0001
Issued by

About this file

This federal contract opportunity solicitation seeks bids for a construction project to repair water mains and roads at the 151st Air Refueling Wing, Roland R. Wright ANG Base in Salt Lake City, Utah. The project includes construction of roads, curb gutters, sidewalks, replacement of water service mains and laterals, fire hydrants, storm drain catch basins, and installation of new water meters and detector check valves. The base bid is for work on Mustang Lane and North Loop, with optional additional work on Patriot Way and Sabre Street. Interested parties must be registered in SAM and the projected value is between $5-10 million. The pre-bid conference is August 11 and bids are due August 31, with the contract period being 365 days after notice to proceed. This acquisition is set aside for small businesses in NAICS code 237110 for water and sewer line construction with a size standard of $39.5 million.

View the file

Other files

File Type Posted
Repair Water Mains and Roads_Questions_Answers_28 Aug 2020.pdf PDF
USEB132009_Sabre Street_Revised Drawing C-02_28 Aug 2020.pdf PDF
Solicitation Amendment_W50S9A-20-B-0001-0003 Repair Water Mains and Roads.pdf PDF
USEB132019_Patriot Way_Revised Drawing GC-03_27 Aug 2020.pdf PDF
Repair Water Mains and Roads_Questions_Answers_27 Aug 2020.pdf PDF
USEB132009_Sabre Street_Revised Drawing GC-03_27 Aug 2020.pdf PDF
USEB132001_Mustang Lane_Revised Drawing GC-03_27 Aug 2020.pdf PDF
W50S9A-20-B-0001-0002_Repair Water Mains and Roads.pdf PDF
USEB132001_Mustang_IRP Summary and Locations Rev2_27 Aug 2020.pdf PDF
Solicitation Amendment_W50S9A-20-B-0001-0001_Repair Water Mains and Roads.pdf PDF
Mustang RFI 01_Marked Drawing.pdf PDF
Repair Water Mains and Roads_Questions_Answers_24 Aug 2020.pdf PDF
USEB132009_Sabre Street_Geotech Report.pdf PDF
USEB132001_Mustang_Geotechnical Report.pdf PDF
USEB132001_Mustang Lane_BN Justification_KO Signed_Redacted.pdf PDF
USEB132001_Mustang Lane_Specifications_23Jul20.pdf PDF
USEB132019_Patriot Way_Design Narrative.pdf PDF
USEB132019_Patriot Way_Specifications_23Jul20.pdf PDF
W50S9A-20-B-0001 Repair Water Mains and Roads.pdf PDF
USEB132009_Sabre Street_Specifications_23Jul20.pdf PDF
USEB132019_Patriot Way_Geotechnical Report.pdf PDF
USEB132001_Mustang_Design Narrative.pdf PDF
USEB132001_Mustang_Env Summary.pdf PDF
USEB132009_Sabre Street_Design Narrative.pdf PDF
Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

WATER MODEL ANALYSIS

BOWEN COLLINS & ASSOCIATES

UTAH AIR NATIONAL GUARD 10

Table A4 Building Fire Flow Demands

Fire Suppression Facility Square Ft

Fire Flow Demand

(gpm)

Sprinkler Demand

(gpm)

Hydrant Demand

(gpm)

Yes 3 31,557 2,880 - 880 Yes 7 15,807 1,750 875 - Yes 10 12,912 1,500 1,500 Yes 19 30,039 2,880 - 880 Yes 23 18,635 2,000 1,000 - Yes 25 17,000 1,750 875 - No 37 12,338 1,500 - 1,500 No 40 27,049 2,500 - 2,500 Yes 45 16,236 1,750 875 - No 50 21,931 2,250 - 2,250 No 104 647 1,500 - 1,500 Yes 112 15,074 1,750 875 - Yes 122 42,694 3,000 1,500 - No 150 900 1,500 - 1,500 No 200 400 1,500 - 1,500 Yes 205 1,680 1,500 750 - Yes 208 25,619 2,500 1,250 - Yes 210 46,170 3,000 1,500 - Yes 212 400 2,000 750 - Yes 215 5,000 1,500 750 - No 218 4,000 1,500 - 1,500 Yes 220 38,493 2,750 1,375 - No 301 22,082 2,250 - 2,250 Yes 302 14,318 1,750 875 - No 303 24,560 2,500 - 2,500 No 304 3,872 1,500 - 1,500 No 400 2,635 1,500 - 1,500 Yes 403 2,400 1,500 750 - Yes 404 4,000 1,500 750 - Yes 407 4,000 1,500 750 - Yes 408 800 1,500 750 - No 1522 4,800 1,500 - 1,500 No 1604 1,750 1,500 - 1,500

No Future Hangar NA 2,500 - 2,500

File details come from the government source that posted it. Updated .