This document provides specifications for metal roof panel systems for a construction project at the 142nd Fighter Wing facility in Oregon. Key requirements include steel roof panels that meet standards for material composition and performance. Panels must resist hydrostatic head per ASTM E2140 and wind uplift loads per ASTM E1592 and UL 580. Accessories and fasteners must be compatible with the panels. The project is solicited under Solicitation Number W50S8Y24B0001 for the 142nd Fighter Wing B235 Additional/Alteration construction by the Department of the Army Oregon Army National Guard. Responses are due by the date specified in the solicitation.
View the file
Other files for this federal contract opportunity
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T Y P E B - 3 F I N A L
Add/Alter B235 Corrosion Control Project Number TQKD209002
Specifications (Divisions 07-22)
Prepared for
142nd Civil Engineering Squadron
Oregon Air National Guard
Portland ANG Base
February 2023
CH2M HILL – HDR JV
1100 NE Circle Blvd., Suite 300
Corvallis OR, 97330
Add/Alter B235 OR Air National Guard Portland Air National Guard Base, OR Project No. TQKD209002
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 31 50 REQUEST FOR INFORMATION
01 32 01.00 10 PROJECT SCHEDULE
01 32 16.00 20 CONSTRUCTION PROGRESS DOCUMENTATION
01 33 00 SUBMITTAL PROCEDURES
01 33 29 SUSTAINABILITY REPORTING
01 35 13 SPECIAL PROJECT PROCEDURES
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 35 40.00 20 ENVIRONMENTAL MANAGEMENT
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND
CONTROLS
01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS
01 57 20.00 10 ENVIRONMENTAL PROTECTION
01 57 23 TEMPORARY STORM WATER POLLUTION CONTROL
01 58 00 PROJECT IDENTIFICATION
01 74 19 CONSTRUCTION AND DEMOLITION WASTE
MANAGEMENT
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.15 TOTAL BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION AND DECONSTRUCTION
02 81 00 TRANSPORTATION AND DISPOSAL OF
HAZARDOUS MATERIALS
02 83 00 LEAD REMEDIATION
02 84 16 HANDLING OF LIGHTING BALLASTS AND
LAMPS CONTAINING PCBs AND MERCURY
02 84 33 REMOVAL AND DISPOSAL OF
POLYCHLORINATED BIPHENYLS (PCBs)
02 85 00 MOLD REMEDIATION
DIVISION 03 - CONCRETE
03 01 00 REHABILITATION OF CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
05 05 20.00 27 POST-INSTALLED CONCRETE AND MASONRY
ANCHORS
05 05 23.13 10 ULTRASONIC INSPECTION OF WELDMENTS
05 05 23.16 STRUCTURAL WELDING
05 12 00 STRUCTURAL STEEL
PROJECT TABLE OF CONTENTS Page 1 SECTION PROJECT Page 1
VOLUME 01 (DIVISIONS 01-06)
05 30 00 STEEL DECKS
05 51 33 METAL LADDERS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL
CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 19 00 WATER REPELLENTS
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 41 13 METAL ROOF PANELS
07 42 13 METAL WALL PANELS
07 54 19 POLYVINYL-CHLORIDE ROOFING
07 60 00 FLASHING AND SHEET METAL
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS AND FRAMES
08 31 00 ACCESS DOORS AND PANELS
08 33 23 OVERHEAD COILING DOORS
08 51 13 ALUMINUM WINDOWS
08 60 45 TRANSLUCENT PANELS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 22 36 LATH
09 24 23 CEMENT STUCCO
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 65 00 RESILIENT FLOORING
09 67 23.15 FUEL RESISTIVE RESINOUS FLOORING,
3-COAT SYSTEM
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
10 51 13 METAL LOCKERS
DIVISION 12 - FURNISHINGS
PROJECT TABLE OF CONTENTS Page 2 SECTION PROJECT Page 2
VOLUME 02 (DIVISIONS 07-22)
12 24 13 ROLLER WINDOW SHADES
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
DIVISION 13 - SPECIAL CONSTRUCTION
13 48 73 SEISMIC CONTROL FOR MISCELLANEOUS
EQUIPMENT
DIVISION 21 - FIRE SUPPRESSION
21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE
PROTECTION
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 48.19 SEISMIC BRACING FOR HVAC
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR
HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL
SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES
FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC
AND OTHER BUILDING CONTROL SYSTEMS
23 09 93 SEQUENCES OF OPERATION FOR HVAC CONTROL
23 11 20 FACILITY GAS PIPING
23 23 00 REFRIGERANT PIPING
23 30 00 HVAC AIR DISTRIBUTION
23 52 00 HEATING BOILERS
23 80 20.00 10 GAS-FIRED HEATING EQUIPMENT
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11 CYBERSECURITY FOR LOW IMPACT
FACILITY-RELATED CONTROL SYSTEMS
25 08 10 UTILITY MONITORING AND CONTROL SYSTEM
TESTING
DIVISION 26 - ELECTRICAL
26 05 48.00 10 SEISMIC PROTECTION FOR ELECTRICAL
EQUIPMENT
26 08 00 APPARATUS INSPECTION AND TESTING
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 13 SWITCHBOARDS
26 29 23 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS UNDER 600 VOLTS
26 41 00 26 51 00 26 56 00
LIGHTNING PROTECTION SYSTEM
INTERIOR LIGHTING
EXTERIOR LIGHTING
PROJECT TABLE OF CONTENTS Page 3 SECTION PROJECT Page 3
25 10 10 UTILITY MONITORING AND CONTROL STYSTEM
(UMCS) FRONT AND INTEGRATION
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
VOLUME 3 (DIVISIONS 23-33)
DIVISION 27 - COMMUNICATIONS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING
SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 31 76 INTERIOR FIRE ALARM AND MASS
NOTIFICATION SYSTEM, ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 11 00 CLEARING AND GRUBBING
31 63 29 DRILLED CONCRETE PIERS AND SHAFTS
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 23 AGGREGATE BASE COURSES
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 31 13 CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
DIVISION 33 - UTILITIES
33 11 00 WATER UTILITY DISTRIBUTION PIPING
33 11 23 NATURAL GAS AND LIQUID PETROLEUM PIPING
33 30 00 SANITARY SEWERAGE
33 40 00 STORM DRAINAGE UTILITIES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4 SECTION PROJECT Page 4
VOLUME 04
APPENDICES GEOTECHNICAL REPORT
HAZMAT REPORT
CODES AND STANDARDS REFERENCED HEREIN
THIS PROJECT IS DESIGNED IN ACCORDANCE WITH THE 2018 INTERNATIONAL BUILDING
CODE (IBC) AND THE 2018 INTERNATIONAL EXISTING BUILDING CODE (IEBC) AS
MODIFIED BY UFC 1-200-01, 01 OCTOBER 2020.
THE UNITED FACILITIES GUIDE SPECIFICATIONS (UFGS) ARE UPDATED REGULARLY.
THE VERSION OR EDITION OF CODES AND STANDARDS REFERENCED HEREIN MAY
DIFFER FROM THOSE SPECIFIED IN CHAPTER 35 OF THE 2018 IBC AND CHAPTER 16 OF
THE 2018 IEBC. IN THE EVENT OF DISCREPENCIES REGARDING VERSION OR EDITION OF
CODES AND STANDARDS, THE 2018 IBC AND 2018 IEBC WILL TAKE PRECEDENCE.
Section 07 19 00 Page 1
SECTION 07 19 00
WATER REPELLENTS
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA)
AAMA 501.1 (2017) Standard Test Method for Water
Penetration of Windows, Curtain Walls and
Doors Using Dynamic Pressure
ASTM INTERNATIONAL (ASTM)
ASTM C140/C140M (2022a) Standard Test Methods for Sampling and Testing Concrete Masonry Units and
Related Units
ASTM D2369 (2010; R 2015; E 2015) Volatile Content of
Coatings
ASTM E96/E96M (2022) Standard Test Methods for Gravimetric
Determination ofWater Vapor Transmission Rate of Materials
ASTM E514/E514M (2020) Standard Test Method for Water
Penetration and Leakage Through Masonry
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1000 Air Contaminants
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-03 Product Data
Water Repellents
SD-06 Test Reports
Water Absorption
Section 07 19 00 Page 2
Moisture Vapor Transmission
Water Penetration and Leakage
SD-07 Certificates
Manufacturer's Qualifications
Applicator's Qualifications
Evidence of Acceptable Variation
Warranty
SD-08 Manufacturer's Instructions
Application Instructions
Provide manufacturer's instructions including preparation, application, recommended equipment to be used, safety measures, and protection of completed application.
Manufacturer's Safety Data Sheets
1.3 QUALITY ASSURANCE
1.3.1 Qualifications
a. Manufacturer's qualifications: Minimum five years record of successful in-service experience of water repellent treatments manufactured for concrete masonry, application.
b. Applicator's qualifications: Minimum five years successful experience in projects of similar scope using specified or similar treatment materials and manufacturer's approval for application.
1.3.2 Performance Requirements
a. Water absorption: ASTM C140/C140M. Comparison of treated and untreated specimens.
b. Moisture vapor transmission: ASTM E96/E96M. Comparison of treated and untreated specimens.
c. Water penetration and leakage through masonry: ASTM E514/E514M.
1.3.3 Evidence of Acceptable Variation
If a product proposed for use does not conform to requirements of the referenced specification, submit for approval to the Contracting Officer, evidence that the proposed product is either equal to or better than the product specified. Include the following:
a. Identification of the proposed substitution;
b. Reason why the substitution is necessary;
Section 07 19 00 Page 3
c. A comparative analysis of the specified product and the proposed substitution, including tabulations of the composition of pigment and vehicle;
d. The difference between the specified product and the proposed substitution; and
e. Other information necessary for an accurate comparison of the proposed substitution and the specified product.
1.4 SAMPLE TEST PANEL
1.4.1 Pre-Installation Meeting
a. Attend pre-installation meeting required prior to commencement of concrete masonry, installation.
b. Review procedures and coordination required between water repellent treatment work and work of other trades which could affect work to be performed under this section of the work.
c. Convene additional pre-installation meeting prior to water repellent treatment application for coordination with work not previously coordinated including joint sealants.
1.5 REGULATORY REQUIREMENTS
1.5.1 Environmental Protection
In addition to requirements specified in Section 01 57 19 TEMPORARY
ENVIRONMENTAL CONTROLS for environmental protection, provide coating materials that conform to the restrictions of the Local Air Pollution
Control jurisdiction . Notify the Contracting Officer of any water repellent coating specified herein which fails to conform to the local Air
Quality Management District Rules at the location of the Project. In localities where the specified coating is prohibited, the Contracting
Officer may direct the substitution of an acceptable coating.
1.6 DELIVERY, STORAGE, AND HANDLING
Deliver materials in original sealed containers, clearly marked with the manufacturer's name, brand name, type of material, batch number, percent solids by weight and volume, and date of manufacturer. Store materials off the ground, in a dry area where the temperature will be not less 50 degrees
F nor more than 85 degrees F.
1.7 SAFETY METHODS
Apply coating materials using safety methods and equipment in accordance with Section 01 57 19 TEMPORARY ENVIRONMENTAL CONTROLS, and the following:
1.7.1 Toxic Materials
To protect personnel from overexposure to toxic materials, conform to the most stringent guidance of:
Section 07 19 00 Page 4
a. The coating manufacturer when using solvents or other chemicals. Use impermeable gloves, chemical goggles or face shield, and other recommended protective clothing and equipment to avoid exposure of skin, eyes, and respiratory system. Conduct work in a manner to minimize exposure of building occupants and the general public.
b. 29 CFR 1910.1000.
c. Threshold Limit Values (R) of the American Conference of Governmental
Industrial Hygienists.
d. Manufacturer's Safety Data Sheets.
1.8 ENVIRONMENTAL CONDITIONS
1.8.1 Weather and Substrate Conditions
Do not proceed with application of water repellents under any of the following conditions, except with written recommendations of manufacturer.
a. Ambient temperature is less than 40 degrees F.
b. Substrate faces have cured less than one month.
c. Rain or temperature below 40 degrees F are predicted for a period of 24 hours before or after treatment.
d. Earlier than three days after surfaces are wet.
e. Substrate is frozen or surface temperature is less than 40 degrees F and falling.
1.8.2 Moisture Condition
Determine moisture content of substrate meets manufacturer's requirements prior to application of water repellent material.
1.9 SEQUENCING AND SCHEDULING
1.9.1 Masonry Surfaces
Do not start water repellent coating until all joint tooling, pointing and masonry cleaning operations have been completed. Allow masonry to cure for at least 60 days under normal weather conditions before applying water repellent.
1.9.2 Sealants
Do not apply water repellents until the sealants for joints adjacent to surfaces receiving water repellent treatment have been installed and cured.
a. Water repellent work may precede sealant application only if sealant adhesion and compatibility have been tested and verified using substrate, water repellent, and sealant materials identical to those used in the work.
b. Provide manufacturers' test results of compatibility.
Section 07 19 00 Page 5
1.10 INSPECTIONS
Notify the manufacturer's representative a minimum of 72 hours prior to scheduled application of water repellents for field inspection. Inspect surfaces and obtain approval in writing from the manufacturer's representative prior to any application of any water repellent coating.
1.11 SURFACES TO BE COATED
Coat all exterior masonry, surfaces. This includes back faces of parapets, top of walls, edges and returns adjacent to windows and door frames and free standing walls.
1.12 WARRANTY
Provide a warranty, issued jointly by the manufacturer and the applicator of the water repellent treatment against moisture penetration through the treated structurally sound surface for a period of five years. Warranty to provide the material, labor, and equipment necessary to remedy the problem.
At the satisfactory completion of the work, complete the warranty sign, notarize, and submit to the Contracting Officer.
PART 2 PRODUCTS
2.1 MATERIALS
Water repellent solution shall be a clear, non-yellowing, deep-penetrating, VOC compliant solution. Material shall not stain or discolor and shall produce a mechanical and chemical interlocking bond with the substrate to the depth of the penetration.
2.2 WATER REPELLENTS
2.2.1 VOC-Complying Water Repellents
Two-component, water activated, cold-applied, solvent-free, non-shrink, liquid waterproofing membrane.
a. Solids by weight: ASTM D2369, 96 percent.
b. Volatile Organic Content (VOC) after blending: Less than 47 grams per liter.
c. Water Vapor Transmission: ASTM E96, 0.1 perm in.
d. Tensile Strength: ASTM D412, 350 psi.
Products certified by the manufacturer that they comply with local regulations controlling use of volatile organic compounds (VOC's).
PART 3 EXECUTION
3.1 EXAMINATION
Examine masonry surfaces to be treated to ensure that:
Section 07 19 00 Page 6
a. All visible cracks, voids or holes have been repaired.
b. All mortar joints in masonry are tight and sound, have not been re-set or misaligned and show no cracks or spalling.
c. Moisture contents of walls does not exceed 15 percent when measured on an electronic moisture register, calibrated for the appropriate substrate.
d. Concrete surfaces are free of form release agents, curing compounds and other compounds that would prevent full penetration of the water repellent material.
Do not start water repellent treatment work until all deficiencies have been corrected, examined and found acceptable to the Contracting Officer and the water repellent treatment manufacturer. Do not apply treatment to damp, dirty, dusty or otherwise unsuitable surfaces. Comply with the manufacturer's recommendations for suitability of surface.
3.2 PREPARATION
3.2.1 Surface Preparation
Prepare substrates in accordance with water repellent treatment manufacturer's recommendation. Clean surfaces of dust, dirt, efflorescence, alkaline, and foreign matter detrimental to proper application of water repellent treatment.
3.2.2 Protection
Provide masking or protective covering for materials which could be damaged by water repellent treatment.
a. Protect glass, glazed products, and prefinished products from contact with water repellent treatment.
b. Protect landscape materials with breathing type drop cloths: plastic covers are not acceptable.
3.2.3 Compatibility
a. Confirm treatment compatibility with each type of joint sealer within or adjacent to surfaces receiving water repellent treatment in accordance with manufacturer's recommendations.
b. When recommended by joint sealer manufacturer, apply treatment after application and cure of joint sealers. Coordinate treatment with joint sealers.
c. Mask surfaces indicated to receive joint sealers which would be adversely affected by water repellent treatment where treatment must be applied prior to application of joint sealers.
3.3 MIXING
Mix water repellent material thoroughly in accordance with the manufacturer's recommendations. Mix, in quantities required for that days
Section 07 19 00 Page 7 work, all containers prior to application. Mix each container the same length of time.
3.4 APPLICATION
In strict accordance with the manufacturers written requirements. Do not start application without the manufacturer's representative being present or his written acceptance of the surface to be treated.
3.4.1 Water Repellent Treatment
3.4.1.1 Spray Application
Spray apply water repellent material to exterior masonry surfaces using low-pressure airless spray equipment in strict accordance with manufacturer's printed application, instructions, and precautions. Maintain copies at the job site. Apply flood coat in an overlapping pattern allowing approximately
8 to 10 inch rundown on the vertical surface. Maintain a wet edge at all overlaps, both vertical and horizontal. Hold gun maximum 18 inches from wall.
3.4.1.2 Brush or Roller Application
Brush or roller apply water repellent material only at locations where overspray would affect adjacent materials and where not practical for spray applications.
3.4.1.3 Covered Surfaces
Coat all exterior masonry surfaces including back faces of parapets, tops of walls, edges and returns adjacent to window and door frames, window sills, and free-standing walls.
3.4.1.4 Rate of Application
Apply materials to exterior surfaces at the coverages recommended by the manufacturer and as determined from sample panel test. Increase or decrease application rates depending upon the surface texture and porosity of the substrate so as to achieve even appearance and total water repellency.
3.4.1.5 Number of Coats
The sample panel test shall determine the number of coats required to achieve full coverage and protection.
3.4.1.6 Appearance
If unevenness in appearance, lines of work termination or scaffold lines exist, or detectable changes from the approved sample panel occur, the
Contracting Officer may require additional treatment at no additional cost to the Government. Apply any required additional treatment to a natural break off point.
3.5 CLEANING
Section 07 19 00 Page 8
Clean all runs, drips, and overspray from adjacent surfaces while the water repellent treatment is still wet in a manner recommended by the manufacturer.
3.6 FIELD QUALITY CONTROL
Do not remove drums containing water repellent material from the job site until completion of all water repellent treatment and until so authorized by the Contracting Officer.
3.6.1 Field Testing
AAMA 501.1. At a time not less than twenty days after completion of the water repellent coating application, subject a representative wall area of the building to the Navy Hose Stream Field Test similar to AAMA 501.1 hose test to simulated rainfall for a period of three hours. Use a minimum 5/8 inch diameter hose and a fixed lawn sprinkler spray head which will direct a full flow of water against the wall. Place the sprinkler head so that the water will strike the wall downward at a 45 degree angle to the wall. If the inside of the wall shows any trace of moisture during or following the test, apply another coat of water repellent, at the manufacturer's recommended coverage rate to the entire building. Repeat testing and re-coating process until no moisture shows on the inside wall face. Accomplish any required work retesting and re-coating at no additional cost to the Government.
3.6.2 Site Inspection
Inspect treatment in progress by manufacturer's representative to verify compliance with manufacturer instructions and recommendations.
-- End of Section --
Section 07 21 13 Page 1
SECTION 07 21 13
BOARD AND BLOCK INSULATION
ASTM C612 (2014; R 2019) Standard Specification for
Mineral Fiber Block and Board Thermal
Insulation
ASTM C930 (2019) Standard Classification of Potential
Health and Safety Concerns Associated with
Thermal Insulation Materials and Accessories
ASTM C1338 (2014) Standard Test Method for Determining
Fungi Resistance of Insulation Materials and
Facings
ASTM D224 Standard Specification for Smooth-Surfaced
Asphalt Roll Roofing (Organic Felt)
ASTM E84 (2020) Standard Test Method for Surface
Burning Characteristics of Building Materials
ASTM E96/E96M (2016) Standard Test Methods for Water Vapor
Transmission of Materials
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2021) International Building Code
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 31 (2020) Standard for the Installation of Oil-
Burning Equipment
NFPA 54 (2021) National Fuel Gas Code
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4) National
Electrical Code
NFPA 211 (2019) Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances
Section 07 21 13 Page 2
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Manufacturer's Standard Details; G
Block or Board Insulation; G
Accessories including sealants; G
Block or Board Insulation; G
Draft Special Warranties; G
Final Special Warranties; G
Indoor Air Quality For Block Or Board Insulation; S
Block or Board Insulation
Adhesive
1.3 MANUFACTURER'S DETAILS
Submit manufacturer's standard details indicating methods of attachment and spacing, transition and termination details, and installation details.
Include verification of existing conditions.
1.4 PRODUCT DATA
Include data for material descriptions, recommendations for product shelf life, requirements for protection board or coatings, and precautions for flammability and toxicity. Include data to verify compatibility of sealants with insulation.
1.5 DELIVERY, STORAGE, AND HANDLING
1.5.1 Delivery
Deliver materials to the site in original sealed wrapping bearing manufacturer's name and brand designation, specification number, type, grade, R-value, and class. Store and handle to protect from damage. Do not allow insulation materials to become wet, soiled, crushed, or covered with ice or snow. Comply with manufacturer's recommendations for handling, storing, and protecting of materials before and during installation.
1.5.2 Storage
Section 07 21 13 Page 3
Inspect materials delivered to the site for damage and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling. Keep materials wrapped and separated from off-gassing materials
(such as drying paints and adhesives). Do not use materials that have visible moisture or biological growth. Comply with manufacturer's recommendations for handling, storage, and protection of materials before and during installation.
1.6 SAFETY PRECAUTIONS
1.6.1 Other Safety Considerations
Comply with the safety requirements of ASTM C930.
1.7 SPECIAL WARRANTIES
1.7.1 Guarantee
Guarantee insulation installation against failure due to ultraviolet light exposure for a period of three years from the date of Beneficial Occupancy or Substantial Completion. Submit draft and final guarantees in accordance with Sections 01 78 00 CLOSEOUT SUBMITTALS and 01 78 23 OPERATION AND
MAINTENANCE DATA.
1.7.2 Warranty
Provide manufacturer's material warranty for all system components for a period of three years from the date of Beneficial Occupancy or Substantial
Completion. Submit draft and final warranties in accordance with Sections
01 78 00 CLOSEOUT SUBMITTALS and 01 78 23 OPERATION AND MAINTENANCE DATA.
2.1 BLOCK OR BOARD INSULATION
Provide thermal insulating materials as recommended by manufacturer for each type of application indicated. Provide insulation with the following physical properties and in accordance with the following standards:
a. Mineral Fiber Bock and Board Thermal Insulation: ASTM C612. Provide non-combustible, non-deteriorating, inorganic, UV-resistant black facing behind façade system. Insulation must repel and drain water.
2.1.1 Thermal Resistance
Unless otherwise indicated, provide thickness as indicated on the drawings.
2.1.2 Fire Protection Requirements
a. Flame spread index of 75 or less when tested in accordance with ASTM
E84.
b. Smoke developed index of 15 or less when tested in accordance with ASTM
E84.
Section 07 21 13 Page 4
c. Provide insulated assemblies in accordance ICC IBC Chapter Fire and
Smoke Protection Features.
d. Non-combustible.
2.1.3 Other Material Properties
Provide thermal insulating materials with the following properties:
a. Water Vapor Permeance: Not more than 47 Perms or less when measured according to ASTM E96/E96M, desiccant method, in the thickness required to provide the specified thermal resistance, including facings, if any.
b. Fungi Resistance per ASTM C1338.
c. UV Testing per ICC-ES AC38 Section 4.1.2 UV Exposure with ASTM D224
Color Evalution.
2.1.4 Recycled Materials
Provide thermal insulation containing recycled materials to the extent practicable, provided that the material meets all other requirements of this section. The minimum required recycled material contents (by weight, not volume) are:
USACE / NAVFAC / AFCEC / NASA UFGS-07 21 13 (February 2016)
Change 2 - 08/20
Preparing Activity: NAVFAC SupersedingUFGS-07 21 13 (May 2011)
Provide data identifying percentage of recycled content for block or board insulation.
2.1.5 Indoor Air Quality
Provide certification of indoor air quality for block or board insulation.
2.1.6 Prohibited Materials
Do not provide materials containing asbestos.
2.2 ACCESSORIES
2.2.1 Adhesive
As recommended by insulation manufacturer.
2.2.2 Mechanical Fasteners
Corrosion resistant fasteners as recommended by the insulation manufacturer.
Section 07 21 13 Page 5
3.1 EXISTING CONDITIONS
Prior to installation, ensure all areas that are in contact with the insulation are dry and free of projections that could cause voids, compressed insulation, or punctured vapor retarders. For foundation perimeter or under slab applications, check that subsurface fill is flat, smooth, dry, and well tamped. Do not proceed with installation if moisture or other conditions are present, and notify the Contracting Officer of such conditions. Do not proceed with the work until conditions have been corrected and verified to be dry.
3.2.1 Blocking Around Heat Producing Devices
Provide noncombustible blocking at all spaces between heat producing devices and the floors, ceilings and roofs through which they pass. Provide in accordance with ICC IBC Section 2111.12 Fireplace Blocking and with the following clearances:
a. Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing devices, unless certified for installation surrounded by insulation: 3 inches from outside face of fixtures and devices or as required by NFPA 70 and, if insulation is placed above fixture or device, 24 inches above fixture.
b. Masonry chimneys or masonry enclosing a flue: 2 inches from outside face of masonry. Masonry chimneys for medium and high heat operating appliances: Minimum clearances required by NFPA 211.
c. Vents and vent connectors used for venting products of combustion, flues, and chimneys other than masonry chimneys: Minimum clearances as required by NFPA 211.
d. Gas Fired Appliances: Clearances as required in NFPA 54.
e. Oil Fired Appliances: Clearances as required in NFPA 31.
Blocking is not required if chimneys or flues are certified in writing by the chimney or flue manufacturer for use in contact with specific insulating materials.
3.3 INSTALLATION
3.3.1 Installation and Handling
Provide insulation in accordance with the manufacturer's printed installation instructions. Keep material dry and free of extraneous materials.
3.3.2 Electrical Wiring
Do not install insulation in a manner that would enclose electrical wiring between two layers of insulation.
3.3.3 Cold Climate Requirement
Section 07 21 13 Page 6
Place insulation on the outside of pipes.
3.3.4 Continuity of Insulation
Butt tightly against adjoining boards, studs, rafters, joists, sill plates, headers and obstructions. Provide continuity and integrity of insulation at corners, wall to ceiling joint, roof, and floor. Avoid creating thermal bridges and voids. Provide and verify continuity of insulative barrier throughout the building enclosure.
3.3.5 Coordination
Verify final installed insulation thicknesses comply with thicknesses indicated, R-values specified herein, and with the approved insulation submittal(s).
3.4 INSTALLATION ON WALLS
3.4.1 Installation using Furring Strips
Install insulation between members as recommended by insulation manufacturer and as indicated on drawings.
3.4.2 Installation on Masonry Walls
Apply board directly to masonry with adhesive or fasteners as recommended by the insulation manufacturer. Fit between obstructions without impaling board on ties or anchors. Apply in parallel courses with joints breaking midway over course below. Place boards in moderate contact with adjoining insulation without forcing and without gaps. Cut and shape as required to fit around wall penetrations, projections or openings to accommodate conduit or other utilities. Seal around cutouts with sealant.
3.4.3 Mechanical Attachment on Concrete and Masonry Walls
Cut insulation to cover walls. Apply adhesive to wall and set clip or other mechanical fastener in adhesive as recommended by manufacturer. After curing of adhesive, install insulation over fasteners and bend split prongs to provide a flush condition with the insulation. Butt all edges of insulation and seal with tape.
Section 07 21 16 Page 1
SECTION 07 21 16
MINERAL FIBER BLANKET INSULATION
ASTM C665 (2017) Standard Specification for Mineral-
Fiber Blanket Thermal Insulation for Light
Frame Construction and Manufactured Housing
ASTM C930 (2019) Standard Classification of Potential
Health and Safety Concerns Associated with
Thermal Insulation Materials and Accessories
ASTM D3575 (2020) Flexible Cellular Materials Made From
Olefin Polymers
ASTM D3833/D3833M (1996; R 2011) Water Vapor Transmission of
Pressure-Sensitive Tapes
ASTM D5359 (2015) Standard Specification for Glass
Cullet Recovered from Waste for Use in
Manufacture of Glass Fiber
ASTM E136 (2019a) Standard Test Method for Assessing
Combustibility of Materials Using a Vertical
Tube Furnace at 750 Degrees C
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2010; Version 1.1) Standard Method for the
Testing and Evaluation of Volatile Organic
Chemical Emissions from Indoor Sources using
Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
NFPA 31 (2020) Standard for the Installation of Oil-
Burning Equipment
Section 07 21 16 Page 2
NFPA 54 (2021) National Fuel Gas Code
NFPA 70 (2020; ERTA 20-1 2020; ERTA 20-2 2020; TIA
20-1; TIA 20-2; TIA 20-3; TIA 20-4) National
Electrical Code
NFPA 211 (2019) Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2017) Adhesive and Sealant Applications
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.134 Respiratory Protection
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For
Chemical Emissions For Building Materials, Finishes And Furnishings submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Blanket Insulation
Sill Sealer Insulation
Pressure Sensitive Tape
Accessories
Insulation
1.3 CERTIFICATIONS
Submit required indoor air quality certifications and validations in one submittal package.
1.3.1 Insulation Products
Section 07 21 16 Page 3
Provide product certified to meet indoor air quality requirements by UL 2818
(Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification by other third-party programs. Provide current product certification from certification body.
1.3.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL
2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver materials to site in original sealed wrapping bearing manufacturer's name and brand designation, specification number, type, grade, R-value, and class. Store and handle to protect from damage. Do not allow insulation materials to become wet, soiled, crushed, or covered with ice or snow.
Comply with manufacturer's recommendations for handling, storing, and protecting of materials before and during installation.
1.4.2 Storage
Inspect materials delivered to the site for damage; unload and store out of weather in manufacturer's original packaging. Store only in dry locations, not subject to open flames or sparks, and easily accessible for inspection and handling.
1.5 SAFETY PRECAUTIONS
1.5.1 Respirators
Provide installers with dust/mist respirators, training in their use, and protective clothing, all approved by National Institute for Occupational
Safety and Health (NIOSH)/Mine Safety and Health Administration (MSHA) in accordance with 29 CFR 1910.134.
1.5.2 Other Safety Concerns
Consider other safety concerns and measures as outlined in ASTM C930.
2.1 BLANKET INSULATION
ASTM C665, Type I, blankets without membrane coverings and II, blankets with non-reflecting coverings; Class A, membrane-faced surface with a flame spread of 25 or less, except a flame spread rating of 75 or less and a smoke developed rating of 150 or less when tested in accordance with ASTM E84.
2.1.1 Thermal Resistance Value (R-VALUE)
Section 07 21 16 Page 4
The R-Value must be as indicated on drawings.
2.1.2 Recycled Materials
Provide insulation materials containing the following minimum percentage of recycled material content by weight:
Fiberglass: 20 percent glass cullet complying with ASTM D5359
2.1.3 Prohibited Materials
Do not provide asbestos-containing materials.
2.2 SILL SEALER INSULATION
Provide polyethylene foam sill sealer 3.5 and 5.5 inches in width with the following characteristics:.
USACE / NAVFAC / AFCEC / NASA UFGS-07 21 16 (November 2011)
Change 4 - 08/18
Preparing Activity: NAVFAC SupersedingUFGS-07 21 16 (May 2011)
2.3 BLOCKING
Wood, metal, unfaced mineral fiber blankets in accordance with ASTM C665, Type I, or other approved materials. Use only non-combustible materials meeting the requirements of ASTM E136 for blocking around chimneys and heat producing devices.
2.4 PRESSURE SENSITIVE TAPE
As recommended by the vapor retarder manufacturer and having a water vapor permeance rating of one perm or less when tested in accordance with ASTM
D3833/D3833M.
2.5 ACCESSORIES
2.5.1 Adhesive
As recommended by the insulation manufacturer. Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) that meet either emissions requirements of CDPH
SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168.
Provide aerosol adhesives used on the interior of the building that meet either emissions requirements of CDPH SECTION 01350 (use the office or classroom requirements, regardless of space type) or VOC content requirements of GS-36.
2.5.2 Mechanical Fasteners
Corrosion resistant fasteners as recommended by the insulation manufacturer.
Section 07 21 16 Page 5
3.1 EXISTING CONDITIONS
Before installing insulation, ensure that areas that will be in contact with the insulation are dry and free of projections which could cause voids, compressed insulation, or punctured vapor retarders. If moisture or other conditions are found that do not allow the workmanlike installation of the insulation, do not proceed but notify Contracting Officer of such conditions.
3.2.1 Blocking at Attic Vents and Access Doors
Prior to installation of insulation, install permanent blocking to prevent insulation from slipping over, clogging, or restricting air flow through soffit vents at eaves. Install permanent blocking to maintain accessibility to equipment or controls that require maintenance or adjustment.
3.2.2 Blocking Around Heat Producing Devices
Install non-combustible blocking around heat producing devices to provide the following clearances:
a. Recessed lighting fixtures, including wiring compartments, ballasts, and other heat producing devices, unless these are certified by the manufacturer for installation surrounded by insulation: 3 inches from outside face of fixtures and devices or as required by NFPA 70 and, if insulation is to be placed above fixture or device, 24 inches above fixture.
b. Masonry chimneys or masonry enclosing a flue: 2 inches from outside face of masonry. Masonry chimneys for medium and high heat operating appliances: Minimum clearances required by NFPA 211.
c. Vents and vent connectors used for venting the products of combustion, flues, and chimneys other than masonry chimneys: Minimum clearances as required by NFPA 211.
d. Gas Fired Appliances: Clearances as required in NFPA 54.
e. Oil Fired Appliances: Clearances as required in NFPA 31.
3.3 INSTALLATION
3.3.1 Insulation
Install and handle insulation in accordance with manufacturer's instructions. Keep material dry and free of extraneous materials. Any materials that show visual evidence of biological growth due to presence of moisture must not be installed on the building project. Ensure personal protective clothing and respiratory equipment is used as required. Observe safe work practices.
3.3.1.1 Electrical wiring
Section 07 21 16 Page 6
Do not install insulation in a manner that would sandwich electrical wiring between two layers of insulation.
3.3.1.2 Continuity of Insulation
Install blanket insulation to butt tightly against adjoining blankets and to studs, rafters, joists, sill plates, headers and any obstructions. Where insulation required is thicker than depth of joist, provide full width blankets to cover across top of joists. Provide continuity and integrity of insulation at corners, wall to ceiling joints, roof, and floor. Avoid creating thermal bridges.
3.3.1.3 Installation at Bridging and Cross Bracing
Insulate at bridging and cross bracing by splitting blanket vertically at center and packing one half into each opening. Butt insulation at bridging and cross bracing; fill in bridged area with loose or scrap insulation.
3.3.1.4 Cold Climate Requirement
Place insulation to the outside of pipes.
3.3.1.5 Insulation without Affixed Vapor Retarder
Provide snug friction fit to hold insulation in place. Stuff pieces of insulation into cracks between trusses, joists, studs and other framing, such as at attic access doors, door and window heads, jambs, and sills, band joists, and headers.
3.3.1.6 Sizing of Blankets
Provide only full width blankets when insulating between trusses, joists, or studs. Size width of blankets for a snug fit where trusses, joists or studs are irregularly spaced.
3.3.1.7 Installation of Sill Sealer
Size sill sealer insulation and place insulation over top of masonry or concrete perimeter walls or concrete perimeter floor slab on grade. Fasten sill plate over insulation.
3.3.1.8 Access Panels and Doors
Affix blanket insulation to access panels greater than one square foot and access doors in insulated floors and ceilings. Use insulation with same R-
Value as that for floor or ceiling.
Section 07 22 00 Page 1
SECTION 07 22 00
ROOF AND DECK INSULATION
ASTM C726 (2017) Standard Specification for Mineral
Wool Roof Insulation Board
ASTM C1177/C1177M (2017) Standard Specification for Glass Mat
Gypsum Substrate for Use as Sheathing
ASTM C1289 (2020) Standard Specification for Faced Rigid
Cellular Polyisocyanurate Thermal Insulation
Board
ASTM D226/D226M (2017) Standard Specification for Asphalt-
Saturated Organic Felt Used in Roofing and
Waterproofing
ASTM D2178/D2178M (2015a) Asphalt Glass Felt Used in Roofing and Waterproofing
ASTM D4601/D4601M (2004; R 2020) Standard Specification for
Asphalt-Coated Glass Fiber Base Sheet Used in
Roofing
FM GLOBAL (FM)
FM 4450 (1989) Approval Standard for Class 1
Insulated Steel Deck Roofs
FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/
INTERNATIONAL CODE COUNCIL (ICC)
ICC IBC (2021) International Building Code
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
Section 07 22 00 Page 2
UL 1256 (2002; Reprint Jul 2013) Fire Test of Roof
Deck Constructions
UL 2818 (2013) GREENGUARD Certification Program For
Chemical Emissions For Building Materials, Finishes And Furnishings approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
SD-02 Shop Drawings
Insulation Board Layout and Attachment; G
Verification of Existing Conditions; G
Insulation; G
Cover Board; G
Fasteners; G
Flame Spread Rating; G
Installer Qualifications; G
Nails and Fasteners; G
Roof Insulation; G
1.3 SHOP DRAWINGS
Submit insulation board layout and attachment indicating methods of attachment and spacing, transitions, tapered components, thicknesses of materials, and closure and termination conditions. Show locations of ridges, valleys, crickets, interface with, and slope to, roof drains. Base shop drawings on verified field measurements and include verification of existing conditions. Show location and spacing of wood nailers required for securing of insulation.
1.4 PRODUCT DATA
Section 07 22 00 Page 3
Include data for material descriptions, recommendations for product shelf life, requirements for cover board or coatings, and precautions for flammability and toxicity. Include data to verify compatibility of sealants with insulation.
1.5 MANUFACTURER'S INSTRUCTIONS
Include field of roof and perimeter attachment requirements.
Provide a complete description of installation sequencing for each phase of the roofing system. Include weatherproofing procedures.
1.6 QUALITY CONTROL
Provide certification of installer qualifications from the insulation manufacturer confirming the specific installer has the required qualifications for installing the specific roof insulation system(s) indicated.
1.7 FM APPROVAL REQUIREMENTS
Provide fastening patterns in accordance with FM 1-90 for insulation on steel decks.
1.8 FIRE PERFORMANCE REQUIREMENTS
1.8.1 Insulation in Roof Systems
Comply with the requirements of ICC IBC or UL 1256 or FM 4450. Roof insulation to have a flame spread rating of 75 or less when tested in accordance with ASTM E84. Additional documentation of compliance with flame spread rating is not required when insulation of the type used for this project as part of the specific roof assembly is listed and labeled as FM
Class 1 approved. Only roof assemblies that pass FM 4450 may be used.
1.8.2 Fire Resistance Ratings for Roofs
Provide in accordance with ICC IBC Chapter 7 and Table 721.1(3) Min Fire and
Smoke Protection For Floor and Roof Systems.
1.9 CERTIFICATIONS
Provide products certified to meet indoor air quality requirements by UL
2818(Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification by other third-party programs. Provide current product certification documentation from certification body.
1.10 DELIVERY, STORAGE, AND HANDLING
1.10.1 Delivery
Deliver materials to the project site in manufacturer's unopened and undamaged standard commercial containers bearing the following legible information:
a. Name of manufacturer
Section 07 22 00 Page 4
b. Brand designation
c. Specification number, type, and class, as applicable, where materials are covered by a referenced specification
Deliver materials in sufficient quantity to allow continuity of the work.
1.10.2 Storage and Handling
Store and handle materials in accordance with manufacturer's printed instructions. Protect from damage, exposure to open flame or other ignition sources, wetting, condensation, and moisture absorption. Keep materials wrapped and separated from off-gassing materials (such as drying paints and adhesives). Do not use materials that have visible moisture or biological growth. Store in an enclosed building or trailer that provides a dry, adequately ventilated environment. Replace damaged material with new material.
1.11 ENVIRONMENTAL CONDITIONS
Do not install roof insulation during inclement weather or when air temperature is below 40 degrees F and interior humidity is 45 percent or greater, or when there is visible ice, frost, or moisture on the roof deck.
1.12 PROTECTION
1.12.1 Completed Work
Cover completed work with cover board for the duration of construction.
Avoid traffic on completed work particularly when ambient temperature is above 80 degrees F. Replace crushed or damaged insulation prior to roof surface installation.
2.1 INSULATION
2.1.1 Insulation Types
Provide the following roof insulation materials. Provide roof insulation that is compatible with attachment methods for the specified insulation and roof membrane.
a. Polyisocyanurate Board: Provide in accordance with ASTM C1289 REV A
Type II, fibrous felt or glass mat membrane both sides, except minimum compressive strength of 20 pounds per square inch (psi).
2.1.2 Mineral Fiber Insulation Board
Provide in accordance with ASTM C726.
2.1.3 Recycled Materials
Provide thermal insulation materials containing recycled content. Unless specified otherwise, the minimum required recycled content for listed materials are:
Section 07 22 00 Page 5
USACE / NAVFAC / AFCEC / NASA UFGS-07 22 00 (February 2016)
Change 3 - 11/18
Preparing Activity: NAVFAC SupersedingUFGS-07 22 00 (August 2011)
2.1.4 Indoor Air Quality
Provide certification of indoor air quality for insulation.
2.1.5 Insulation Thickness
As necessary to provide the thermal resistance (R-value) indicated for average thickness of tapered system. Base calculation on the R-value for aged insulation. For insulation over steel decks, satisfy both specified R-value and minimum thickness for width of rib opening recommended in insulation manufacturer's published literature.
2.1.6 Tapered Roof Insulation
One layer of the tapered roof insulation assembly must be factory tapered to a slope of not less than one in 24 or 1/2 inch per foot. Factory fabricate mitered joints from two diagonally cut boards or one board shaped to provide required slopes.
2.1.7 Cants and Tapered Edge Strips
Provide preformed cants and tapered edge strips of the same material as the roof insulation. When unavailable, provide pressure-preservative treated wood, wood fiberboard, or rigid perlite board cants and edge strips as recommended by the roofing manufacturer for the specific application, unless otherwise indicated. Face of cant strips to incline at 45 degrees with a minimum vertical height of 4 inches. Taper edge strips at a rate of one to
1 1/2 inch per foot down to approximately 1/8 inch thick.
2.2 COVER BOARD
For use as a thermal barrier (underlayment), fire barrier (overlayment), or cover board for hot-mopped, torched-down, or adhesive-applied roofing membrane over roof insulation.
2.2.1 Glass Mat Gypsum Roof Board
ASTM C1177/C1177M, 0 Flame Spread and 0 Smoke Developed when tested in accordance with ASTM E84, 500 psi, Class A, non-combustible, 1/2 inch thick,4 by 8 feet board size.
2.3 MOISTURE CONTROL
2.3.1 Vapor Retarder
2.3.1.1 Asphalt Saturated Felt Base Sheet for Single Layer Application
Provide in accordance with ASTM D4601/D4601M, weighing not less than 35 pounds per 100 square feet.
Section 07 22 00 Page 6
2.3.1.2 Asphalt-Coated Glass Felt
Provide in accordance with ASTM D2178/D2178M, Type IV.
2.3.2 Organic Roofing
Provide in accordance with ASTM D226/D226M, Type I.
2.4 FASTENERS
Provide flush-driven fasteners through flat round or hexagonal steel or plastic plates. Provide zinc-coated steel plates, flat round not less than
1 3/8 inch diameter, hexagonal not less than 28 gage. Provide high-density plastic plates, molded thermoplastic with smooth top surface, reinforcing ribs and not less than 3 inches in diameter. Fully recess fastener head into plastic plate after it is driven. Form plates to prevent dishing. Do not use bell or cup shaped plates. Provide fasteners in accordance with insulation manufacturer's recommendations for holding power when driven, in steel deck. Provide fasteners for steel or concrete decks in accordance with FM APP GUIDE (http://www.approvalguide.com/) for Class I roof deck construction, and spaced to withstand uplift pressure of 90 pounds per square foot.
2.4.1…