RFIs and Responses_14 May 2024.pdf

PDF 128 KB Posted

Attached to
B420 HVAC Repairs Federal contract opportunity
Solicitation number
W50S8R-24-B-0002
Issued by
Department of the Army Ohio Army National Guard

About this file

This document contains Requests for Information (RFIs) and responses related to Solicitation W50S8R-24-B-0002 for the B420 HVAC Repairs project. The solicitation is set aside for small businesses and includes the replacement of a 12,000 CFM air handling unit and a 90-ton packaged chiller. Key details include:

The RFIs cover clarification on the existing HVAC equipment and drawings, ductwork capacity, ceiling type, roof condition, testing and balancing requirements, and crane staging. The responses provide additional details, including that the ductwork layout is shown in the drawings previously posted to SAM.gov, the ceiling is lay-in tiles, the roof is Duro-last and not under warranty, and the entire system must be tested and balanced. The project scope also requires reinstalling all connections made to the existing equipment. The solicitation is currently scheduled for bid opening on May 16, 2024, and interested bidders must be registered in SAM.gov.

View the file

Other files for this federal contract opportunity

Other files attached to B420 HVAC Repairs, newest first.
File Type Posted
Abstract_B420 HVAC REPAIRS.pdf PDF
sign in sheet_bid opening.pdf PDF
W50S8R-24-B-0002 02.pdf PDF
RFI 02_attachment_SOW Rev 01.pdf PDF
W50S8R-24-B-0002 01.pdf PDF
Attachment 03_Drawings.pdf PDF
Pre-Bid Conference minutes_B420 HVAC.pdf PDF
Pre-Bid Conference-slides.pptx PPTX presentation
Pre-Bid sign in sheet.pdf PDF
W50S8R-24-B-0002.pdf PDF
Attachment 02_Specifications.pdf PDF
Exhibit A_Sealed Bid Checklist_Reminders.pdf PDF
Attachment 01_SOW_B420 HVAC.pdf PDF
Exhibit B_Checklist for Bid Bonds.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Requests for Information (RFI’s) and Responses - W50S8R-24-B-0002 – B420 HVAC Repairs

(as of 14 May 2024)

RFI 01

Is there a print of existing HVAC and chiller units for this project? Including ductwork beneath and electrical?

RESPONSE: See drawings previously posted in SAM.gov for this solicitation

RFI 02

- The scope of work indicates that there is an existing 12,000 cfm air handling unit and 90 Ton packaged chiller that needs replaced, but doesn’t include identifiers/plan callouts. Please confirm this project includes the replacement of AHU-2, Dining Hall Roof and Air Cooled Chiller #1 on

H2.1?

RESPONSE: Correct. AHU-2 and Chiller #1.

- The scope of work (2.1.B) indicates to install new like-in-kind AHU, 13,000 cfm to replace an existing 12,000 cfm air handling unit. Can the ductwork handle the increased cfm?

RESPONSE: This is a typo in the SOW. Refer to 1.1A. (Revised SOW attached, correcting typo).

- What is the ceiling below the AHU ductwork drops, drywall, lay-in, spline or another kind?

RESPONSE: Lay-in ceiling tile.

- What kind of roof does the air handling unit sit on and is it still under warranty?

RESPONSE: Duro-last type roof, not under warranty.

- Scope of work (2.1.G) states to test and balance the new system. What are the requirements for the TAB – does each diffuser downstream of the unit need balanced or just an overall balance of the new unit? If so, please provide the ductwork layout downstream of unit.

RESPONSE: Existing ductwork layout shown in drawings.

- The project scope of work does not mention disconnecting or reconnecting controls or smoke detectors. Is that included in the scope of work?

RESPONSE: All connections made to the existing equipment must be reinstalled.

- Please provide markup plan where the Crane can be located.

RESPONSE: See drawings site utility plan (previously posted to SAM.gov for this solicitation).

Drive on south side of building will be used for crane staging.

(END OF RFI’S AND RESPONSES)