10 14 00.20 Interior Signage.pdf

PDF 22 KB Posted

Attached to
Renovate Comm (Bldg. 27) & Security Forces (Bldg. 26) Federal contract opportunity
Solicitation number
W50S8J-20-R-0002
Issued by
Department of the Army New York Army National Guard

About this file

This solicitation package includes specifications for interior signage and details regarding the renovation of Building 27 and Security Forces Building 26 at an Army National Guard base in New York. Required signage products include standard room signs, changeable message strip signs, tactile letters and Braille, and graphics adhering to accessibility guidelines. Signage must be fabricated from durable acrylic or vinyl materials and installed at standard heights and locations. Interested parties should attend the mandatory pre-proposal site visit and conference on April 10, 2020 to inspect the project sites and facilities. Attendance is limited to two representatives per company and all attendees must wear masks and not have been exposed to COVID-19. Proposals are due by the date specified in the solicitation document.

View the file

Other files for this federal contract opportunity

Other files attached to Renovate Comm (Bldg. 27) & Security Forces (Bldg. 26), newest first.
File Type Posted
08 33 23 Overhead Coiling Doors.pdf PDF
08 41 13 Aluminum-Framed Entrances and Storefronts.pdf PDF
B26 Existing Roof As Built.pdf PDF
Amendnment 02.pdf PDF
14 21 16 Wheel Chair Lift.pdf PDF
Amendment Report 001.docx DOCX document
1160647 NYANG Stratton-Repair CF-SF B26-27_SIGNAGE.pdf PDF
20-R-0002-0001.pdf PDF
Site Visit Sign In Sheet.pdf PDF
Site Visit Fact Sheet.pdf PDF
B26_27 Pre-proposal Conference Slides.pdf PDF
B26 and 27 - Complete Specs.pdf PDF
B26 and 27 - Drawings.pdf PDF
Exhibit A- Technical Evaluation - Subfactor 1 Worksheet (Word Copy).docx DOCX document
W50S8J-20-R-0002.pdf PDF
Exhibits B and C - Past Peformance Reference Questionnaire (Word Copy).docx DOCX document
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VBDZ162001 Repair Comm. & SFS, Bldg 26/27 Revised 6 May 2020

SECTION 10 14 00.20

INTERIOR SIGNAGE

08/17

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.

AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)

ANSI Z97.1 (2015) Safety Glazing Materials Used in Buildings - Safety Performance Specifications and Methods of Test

U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)

36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines

1.2 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability eNotebook. Submit the following in accordance with Section

01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Detail Drawings ; G

SD-03 Product Data

Installation ; G

Warranty ; G

SD-04 Samples

Interior Signage ; G

SD-10 Operation and Maintenance Data

Approved Manufacturer's Instructions ; G

Protection and Cleaning ; G

SECTION 10 14 00.20 Page 1

1.3 EXTRA MATERIALS

Provide 5 extra frames and extra stock of the following: 5 blank plates of each color and size for sign types. Provide 10 paper inserts for user produced signs and inserts after project completion and equipment necessary for removal of signage parts and pieces.

1.4 QUALITY ASSURANCE

1.4.1 Samples

Submit interior signage samples of each of the following sign types showing typical quality, workmanship and color: Standard Room sign, Changeable message strip sign. The samples may be installed in the work, provided each sample is identified and location recorded.

1.4.2 Detail Drawings

Submit detail drawings showing elevations of each type of sign, dimensions, details and methods of mounting or anchoring, mounting height, shape and thickness of materials, and details of construction. Include a schedule showing the location, each sign type, and message.

1.5 DELIVERY, STORAGE, AND HANDLING

Materials must be packaged to prevent damage and deterioration during shipment, handling, storage and installation. Product must be delivered to the jobsite in manufacturer's original packaging and stored in a clean, dry area in accordance with manufacturer's instructions.

1.6 WARRANTY

Warrant the interior signage for a period of 2 years against defective workmanship and material. Warranties must be signed by the authorized representative of the manufacturer. Submit warranty accompanied by the document authenticating the signer as an authorized representative of the guarantor. Guarantee that the signage products and the installation are free from any defects in material and workmanship from the date of delivery.

PART 2 PRODUCTS

2.1 STANDARD PRODUCTS

Signs, plaques, directories, and dimensional letters must be the standard product of a manufacturer regularly engaged in the manufacture of such products that essentially duplicate signs that have been in satisfactory use at least 2 years prior to bid opening. Obtain signage from a single manufacturer with edges and corners of finished letterforms and graphics true and clean.

2.2 ROOM IDENTIFICATION

2.2.1 Standard Room Signs

Signs must consist of acrylic plastic 0.080 inch thickness minimum conforming to ANSI Z97.1 and must conform to the following:

a. Units must be frameless. Corners of signs must be squared.

SECTION 10 14 00.20 Page 2

2.2.2 Changeable Message Strip Signs

Changeable message strip signs must be of same construction as standard room signs to include a clear sleeve that will accept a paper or plastic insert identifying changeable text. The insert must be prepared typeset message mounted on paper card stock . Provide paper by owner for Owner production of paper inserts after project completion. Furnish one suction device to assist in removing face sheet.

2.2.3 Type of Mounting For Signs

Surface mounted signs must be mounted with 1/16 inch thick closed cell vinyl foam with adhesive backing. Adhesive must be transparent, long aging, high tech formulation on two sides of the vinyl foam. fabricated from materials that are not corrosive to sign material and mounting surface.

2.2.4 Graphics

Signage graphics for modular signs must conform to the following:

2.2.4.1 Subsurface Copy

Copy is transferred to the back face of clear acrylic sheeting forming the panel face to produce precisely formed opaque image. This method bonds all sign elements (color, graphics, lettering, Braille and substrate) into a single unit.

2.2.5 Character Proportions and Heights

Letters and numbers on signs conform to 36 CFR 1191 .

2.2.6 Tactile Letters, Symbols and Braille

Raised letters and numbers on signs must conform to 36 CFR 1191 .

2.3 FABRICATION AND MANUFACTURE

2.3.1 Factory Workmanship

Holes for bolts and screws must be drilled or punched. Drilling and punching must produce clean, true lines and surfaces. Exposed surfaces of work must have a smooth finish and exposed riveting must be flush.

Fastenings must be concealed where practicable.

2.3.2 Dissimilar Materials

Where dissimilar metals are in contact, the surfaces will be protected to prevent galvanic or corrosive action.

2.4 COLOR, FINISH, AND CONTRAST

Color must be per base standard . Finish of all signs must be eggshell, matte, or other non-glare finish as required in handicapped-accessible buildings.

SECTION 10 14 00.20 Page 3

2.5 TYPEFACE

ADA-ABA compliant font for Room Signs.

PART 3 EXECUTION

3.1 INSTALLATION

Signs must be installed plumb and true and in accordance with approved manufacturer's instructions at locations shown on the detail drawings.

Submit six copies of operating instructions outlining the step-by-step procedures required for system operation. The instructions must include simplified diagrams for the system as installed, the manufacturer's name, model number, service manual, parts list, and brief description of all equipment and their basic operating features. Each set must be permanently bound and must have a hard cover. The following identification must be inscribed on the covers: the words "OPERATING AND MAINTENANCE INSTRUCTIONS", name and location of the facility, name of the Contractor, and contract number. Mounting height and mounting location must conform to 36 CFR 1191 . Required blocking must be installed. Signs on doors or other surfaces must not be installed until finishes on such surfaces have been installed. Signs installed on glass surfaces must be installed with matching blank back-up plates in accordance with manufacturer's instructions.

Do not install items that show visual evidence of biological growth.

3.1.1 Anchorage

Anchorage must be in accordance with approved manufacturer's instructions. In high humidity interior spaces (for example, bathrooms, locker rooms, pools, trainers) and unconditioned spaces, use corrosion-resistant anchors/fasteners or with approval by the manufacturer, waterproof silicone adhesive. Anchorage not otherwise specified or shown must include slotted inserts, expansion shields, and powder-driven fasteners when approved for concrete; toggle bolts and through bolts for masonry; machine carriage bolts for steel; lag bolts and screws for wood. Exposed anchor and fastener materials must be compatible with metal to which applied and must have matching color and finish. At interior applications in heavy traffic areas, firmly attach signage to structure walls with tamper-proof fasteners.

a. Signs mounted to painted gypsum board surfaces must be removable for painting maintenance.

b. Mount signs mounted to lay-in ceiling grids with clip connections to ceiling tees.

c. Install signs mounted on metal surfaces with magnetic tape.

d. Install signs mounted on fabric surfaces with hook and loop tape or pin mount.

3.1.2 Protection and Cleaning

Protect the work against damage during construction. Hardware and electrical equipment must be adjusted for proper operation. Glass, frames, and other sign surfaces must be cleaned at completion of sign installation in accordance with the manufacturer's approved instructions

SECTION 10 14 00.20 Page 4 and the requirements of Section 01 78 23 OPERATION AND MAINTENANCE DATA, Package 1. Submit six copies of maintenance instructions listing routine procedures, repairs, and guides.

-- End of Section --

SECTION 10 14 00.20 Page 5

DIVISION 10 - SPECIALTIES
10 14 00.20 - INTERIOR SIGNAGE
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 EXTRA MATERIALS
1.4 QUALITY ASSURANCE
1.4.1 Samples
1.4.2 Detail Drawings
1.5 DELIVERY, STORAGE, AND HANDLING
1.6 WARRANTY
PART 2 PRODUCTS
2.1 STANDARD PRODUCTS
2.2 ROOM IDENTIFICATION
2.2.1 Standard Room Signs
2.2.2 Changeable Message Strip Signs
2.2.3 Type of Mounting For Signs
2.2.4 Graphics
2.2.4.1 Subsurface Copy
2.2.5 Character Proportions and Heights
2.2.6 Tactile Letters, Symbols and Braille
2.3 FABRICATION AND MANUFACTURE
2.3.1 Factory Workmanship
2.3.2 Dissimilar Materials
2.4 COLOR, FINISH, AND CONTRAST
2.5 TYPEFACE
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Anchorage
3.1.2 Protection and Cleaning