VGLZ162323 B154 Addendum 01.pdf

PDF 4 MB Posted

Attached to
VGLZ 162323: ADAL Fuel Cell & Corrosion Control, Bldg. 154
Solicitation number
W50S8523B0004
Issued by

About this file

This solicitation provides the project details for VGLZ 162323: ADAL Fuel Cell & Corrosion Control, Bldg. 154. The project includes renovating and adding onto an existing 17,650 square foot facility to enhance support areas and offices, replace finishes and fixtures, upgrade utilities, and renovate two hangar bays in phases. Proposed site improvements involve parking lot and utility modifications. The solicitation is for a firm fixed-price construction contract to be awarded by the Department of the Army Michigan Army National Guard. The work includes renovating and reconfiguring the administration and support areas of the existing building, replacing doors, windows and finishes, upgrading electrical and mechanical systems, and renovating the hangar bays in phases to allow continued operations. The exterior work involves demolishing existing structures and pavements and improving utilities, including a new water storage tank, pumping station and distribution mains to supply fire suppression to multiple buildings.

View the file

Other files

File Type Posted
W50S8523B0004 OF_1419 page 1.pdf PDF
OF_1419A page 2 of 2 W50S8524B0004.pdf PDF
Bid Opening sign in sheet W50S8523B0004.pdf PDF
VGLZ162323 B154 Addendum 02.pdf PDF
Amendment 5 W50S8523B0004.pdf PDF
W50S8523B0004 Request for Information Log pre bid as of 16 June 23.pdf PDF
RFI 45 answer 17 of 33 A7 Wall Section Details.pdf PDF
W50S8523B0004 Request for Information Log pre bid as of 14 June 23.pdf PDF
RFI LOG pre bid W50S8523B0004 ADAL Bldg 154.pdf PDF
Amendment 3 W50S8523B004.pdf PDF
Amendment 2 W50S8523B0004.pdf PDF
Bldg 154 Pre-Bid Conference_Site Visit.pdf PDF
4 May Pre bid Conference Sign in Sheet.pdf PDF
W50S8523B0004 Amendment 1.pdf PDF
VGLZ 162323- Brand Name Justification - Automated Logic (under SAT).pdf PDF
221216_Vol 1 of 4 Specifications_Selfridge ADAL B154_B3 Final HEF Mod.pdf PDF
VGLZ162323 - SOW - ADAL Fuel Cell and Corrosion Control.pdf PDF
127 SFS Vetted Form 2021.xlsx XLSX spreadsheet
VGLZ 162323- Brand Name Justification - Marshall_LOCKS.pdf PDF
VGLZ 162323- Brand Name Justification - Advantor (under SAT).pdf PDF
COMPLETE SET DRAWAINGS Project VGLZ162323 ADAL Fuel Cell and Corrosion.pdf PDF
221216_Vol 2 of 4 Specifications_Selfridge ADAL B154_B3 Final HEF Mod.pdf PDF
W50S8523B0004.pdf PDF
Source ID Docs SANGB MI.pdf PDF
221216_Vol 3 of 4 Specifications_Selfridge ADAL B154_B3 Final HEF Mod.pdf PDF
VGLZ162323 - Brand Name Justification - Simplex (Control No. 2023-01).pdf PDF
221216_Vol 4 of 4 Specifications_Selfridge ADAL B154_B3 Final HEF Mod.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VGLZ162323 B154 Addendum 01 Page 1 of 2

Project name:

ADAL Fuel Cell/Corrosion Control

Hangar, Building 154 Client: Selfridge ANGB

Project location: Harrison Township, MI Client representative: Derek Probstfeld

Project number: VGLZ162323 Date: June 2, 2023

TO ALL BIDDERS: You are requested to make all changes and/or additions contained in this Addendum to the Bidding Documents. Failure to acknowledge this Addendum in Proposal shall result in rejection of bid.

I. DRAWINGS

A. Drawing -A-101:

1. Updated Keyed Note 4.122 to read “RELOCATED EXTERNAL JET FUEL TANK…”

B. Drawing A-102:

1. Updated Keyed Note 4.705 to read “ALL INTERIOR WALLS AND EXPOSED STRUCTURE

TO RECEIVE PAINT FINISH (PT-1), FLOOR TO BE SEALED CONCRETE (SC-1), SEE A-

601 FOR ARCHITECRUAL FINISHES SCHEDULE.”

C. Drawing A-121:

1. Add in Keyed Note “4.181 FALL PROTECITON EQUIPMENT, REFERENCE STRUCTURAL

DRAWINGS”

D. Drawing A-401:

1. Updated Toilet Accessory Key to indicate items not used. Clarified LSD on plans/details 3, 4, 5, 8, 17, 18, 20, 23, and 24.

E. Drawing A-602:

1. Updated Door and Hardware Schedule General Notes to identify which were not used.

F. Drawing F-001:

1. Removed TEXT SIGN from FIRE ALARM/MNS SYMBOLS.

G. Drawing F-102:

1. Added General Note I regarding foam removal and disposal.

H. Drawing F-103:

1. Removed Text Sign symbol from 6 locations.

I. Drawing F-602:

1. Remove column for Initiate Text Signs.

Addendum No. 1

VGLZ162323 B154 Addendum 01 Page 2 of 2

J. Drawing F-603:

1. Remove Text Signs (6 total) from Fire Alarm/MNS Riser Diagram.

2. Modified notification appliance circuits in Fire Alarm System Riser Diagram.

K. Drawing F-605:

1. Modified circuits in from Fire Alarm Riser Diagram.

II. SPECIFICATIONS

A. Table of Contents

a. Add Section 33 52 43.13 to the TOC.

B. Section 01 33 00

a. Replace existing Submittal Register with updated Submittal Register attached. Added submittal requirements for Section 33 52 43.13 to the list.

C. Section 22 00 00

a. Section 3.12 TABLES: Table II: Add “SERVICE E” column to table.

D. Section 28 31 76

a. In 1.1 References: Add in ASTM F402, UFC 3-600-01, UFC 4-211-01, ANGETL 15-01-03, UL 497A, UL 2024, and UL 2075 and their titles in the correct alphanumeric locations.

b. Delete “textual visual, “ from paragraph 1.4.3, third line.

c. Delete “Textual Display Signs; G” from SD-03 Product Data in paragraph 1.5

SUBMITTALS.

d. Delete “textual display sign “ from paragraph 1.6 SYSTEM OPERATION, first line.

e. Replace Class “A” with Class “B” in paragraph 1.6.1.a and 1.6.1.b.

f. Delete subparagraph “g. One textual visual notification appliance.” from paragraph 1.11.1.

g. Section 2.3.c: replace “Provide adequate discrete outputs to temporarily deactivate fire alarm audible notification, initiate/synchronize strobes and initiate textual visual notification appliances.” with “Provide adequate discrete outputs to temporarily deactivate fire alarm audible notification and initiate/synchronize strobes.”

h. Delete “ or LED text displays.” from end of third to last sentence of paragraph 2.3.4.a.

i. Delete “ or LED text displays.” from last sentence of paragraph 2.4.1.

j. Replace Class “A” with Class “B” in paragraph 2.9 and 2.10.

k. Delete last sentence of paragraph 2.12.2.1.d.

l. Delete last sentence of paragraph 2.14.1.1.

E. Section 33 52 43.13

a. Add attached new section to the specifications.

F. Section 33 56 10

a. Replace existing section 33 56 10 with updated version attached.

END OF ADDENDUM

F.E.F.E.

F .E

. F .E

F .E

F.E.

F .E

F.E.

FLOOR PLAN GENERAL NOTES:

1. SITE DATUM OF FINISHED FIRST FLOOR INDICATED ON SITE PLAN = 100'-0" ON

ARCHITECTURAL DRAWINGS.

2. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THE

ATTENTION OF THE CONTRACTING OFFICER FOR FINAL DECISION.

3. ALL INTERIOR DIMENSIONS ARE FROM FINISH FACE OF WALLS (I.E. GYPSUM

WALLBOARD OR CMU), UNLESS NOTED OTHERWISE.

4. FINISH FLOOR ELEVATIONS ARE TO THE TOP OF CONCRETE, UNLESS NOTED

OTHERWISE.

5. REFERENCE SHEET G-011 AND G-021 FOR ALL CODE, FIRE RATING, AND

SEPARATION REQUIREMENTS.

6. GENERAL CONTRACTOR SHALL PATCH AND REPAIR EXISTING CONSTRUCTION

(WALLS, DOORS, CEILINGS, FLOORS, ETC.) AS REQUIRED FROM DEMOLITION

OR CONSTRUCTION TO ALLOW FOR THE PREP WORK AND NEW OR

COMPLETION OF EXISTING FINISHES. PROVIDE CONCRETE/PLASTER PARGE AT

ALL CMU JAMBS AND PERPENDICULAR WALL REMOVAL. REPAIRS OR

REPLACEMENTS MUST BE DURABLE, SEAMLESS, AND MATCH THE EXISTING

MATERIAL.

7. GENERAL CONTRACTOR SHALL PATCH ALL FLOOR AND WALL PENETRATIONS

CAUSED BY DEMOLITION OF MECHANICAL, ELECTRICAL, TECHNOLOGY, AND

PLUMBING, INCLUDING BUT NOT LIMITED TO PIPING AND CONDUIT RUNS, IN A

MANNER THAT IS CONSISTENT WITH THE EXISTING FLOOR AND WALL

CONSTRUCTION AND FINISH. ALL PENETRATIONS SHALL MEET REQUIRED FIRE

RATINGS.

8. COORDINATE THE INSTALLATION OF ALL OWNER-SUPPLIED EQUIPMENT.

REFERENCE PLANS, SPECS, AND INTERIOR ELEVATIONS FOR SPECIFIC

EQUIPMENT AND ITS INSTALLATION REQUIREMENTS.

9. GENERAL CONTRACTOR SHALL PROVIDE BLOCKING, STIFFENERS, BRACINGS,

BACKING PLATES, SUPPORTING BRACKETS, AND NECESSARY SELECTIVE

DEMOLITION REQUIRED FOR THE PROPER INSTALLATION OF ALL CASEWORK,

TOILET ROOM ACCESSORIES, TOILET PARTITIONS AND MISCELLANEOUS

EQUIPMENT.

10. EXISTING AND INFILL CONCRETE SUB-FLOOR SHALL BE MADE LEVEL, PLUMB

AND IN SOUND CONDITION AS REQUIRED FOR THE INSTALLATION OF FINAL

FLOOR FINISHES, TYPICAL. PROVIDE ARDEX OR EQUAL LEVELING CONCRETE

TO PROVIDE A SMOOTH WALKABLE AREA.

11. ALL RECESSED CABINETS, PANELS, BOXES, ETC. LOCATED IN FIRE-RATED

PARTITIONS SHALL BE INSTALLED IN A MANNER WHICH MAINTAINS THE FIRE

RATED CONSTRUCTION.

12. SEE ENLARGED PLANS FOR NOTES, DIMENSIONS, AND WALL TYPES WITHIN

THE DETAIL CALLOUT BOUNDARIES.

13. REFERENCE SHEET A-002 FOR INTERIOR PARTITION TYPES. INTERIOR

PARTITION TAGS NOTED ENCOMPASS THE ENTIRE LENGTH OF WALL SHOWN

TO CORNERS OF ROOM, OVER AND AROUND DOORWAYS SHOWN.

14. REFERENCE SHEET A-800'S FOR SIGNAGE LAYOUTS AND COORDINATION

REQUIREMENTS.

15. REFERENCE SHEET A-900'S FOR FURNITURE AND EQUIPMENT LAYOUTS AND

COORDINATION REQUIREMENTS.

16. REFERENCE V-001 FOR ALL CONSTRUCTION HAUL ROUTE AND STAGING

REQUIREMENTS.

L K J H G F E D.3 D C B A

1.3

7.3

A-301

A-301

7.5

CLASSROOM/

BREAK

OFFICE

OFFICE

OPEN OFFICE

EXTERNAL

FUEL TANK

OFFICE/ TOOL

STORAGE

EXTERNAL

FUEL TANK

UTILITY

FIRE

PROTECTION

ROOM

ELECTRICAL

MAINTENANCE/

CORROSION

DOCK

MAINTENANCE/

CORROSION

DOCK

WASH ROOM

SHOWER

GEAR

LOCKER/

LAUNDRY

CORRIDOR

CORRIDOR

VESTIBULE

WOMEN'S

MEN'S

JANITOR

CORRIDOR

STORAGE

STORAGE

89'-8"

A-2014

A-201

A-201

A-201 2

A-301

A-501

SIM.

A-501

SIM.

A-301

A-401

A-401

7'-8" 3'-4" 6'-8" 14'-8" 13'-5"

A-301

W1

A

B

B

119B

119A

129A 129B

130B 130A

E104B

E104C

E104AE103A

E103C

E103B

C

VEST

SHOWER

VEST

E104DE103D

MA8

MA8

MA8

MA8

MA8

MA8

MA8

MA8

MA8

MA8

MA8

1H

MA8

1H

W2W1

W2

A-4213

/4

/2

10'-9 1/2"

17'-10 1/2"

A-501

SIM.

4.108 4.108

4.110 4.110

4.1054.105 4.105

4.105

4.104

4.122

4.133 4.133

4.134

4.134

4.136

105A

F

IE

L D

V E

R

IF

Y

24'-6" 18'-3" 7'-3" 7'-8" 33'-6" 18'-6" 18'-6" 10'-6" 1'-0" 18'-8" 18'-3" 18'-3" 24'-6"

A-301

4.1384.138

4.151

4.153

4.1544.154 4.154

4.154

MA6

2'-0" 5

+/- 14' - 4"

4.106 4.106

G F E

A-301

A-301

A-301

/8

2'-0 3/8"

4.152

4.152

4.151

4.151

MA2

2H

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

/1

/2

:2

:1

A

M C

R e v it L o c a l\

-1

.0

-A

-C e n tr a l-

P a t.

C a s e y

L L

F U

.r v t

M

IC

H

IG

A N

A

IR

N A

T

IO

N A

L G

U A

R D

W

IL

B

U R

W R

IG

H

T B

L V

D

H A

R R

IS

O

N T

W P

M

IC

H

IG

A

N

A D

A L F

U E

L C

E L L

C O

R R

O S

IO

N

C O

N T

R O

L

B L D

G

A-101

FIRST FLOOR PLAN

VGLZ162323ANG NO.:

3141700-181848.01

PJC

REK, KM

December 16, 2022

PJC

KEYED NOTES

4.104 PROVIDE OVERHEAD SECTIONAL DOOR AND FRAME - SEE SCHEDULE.

PATCH, REPAIR AND INFILL ADJACENT OPENINGS WITH MASONRY AND

EXTERIOR METAL PANEL CLADDING TO MATCH EXISTING WALL FINISH.

PROVIDE PROPER METAL PANEL J-CHANNEL OR SHEET METAL FLASHING

CLOSURE ELEMENT AT CUT LOCATIONS.

4.105 PROVIDE ALUMINUM FRAME INSULATED GLAZED WINDOWS. REFERENCE

WINDOW TYPES.

4.106 PROVIDE NEW SEALANT ALL AROUND PERIMETER, PAINT DOOR AND

FRAME.

4.108 INFILL OPENING WITH CMU WALL TO MATCH EXISTING THICKNESS AND

FINISH

4.110 HANGAR DOOR, UPGRADE ELECTRICAL TO PROVIDE EMERGENCY POWER

AND OPERATION BY THE FIRE DEPARTMENT, SEE ELECTRICAL DRAWINGS

FOR ADDITIONAL REQUIREMENTS.

4.122 RELOCATED EXTERNAL JET FUEL TANK, SEE CIVIL AND PLUMBING PLANS

FOR ADDITIONAL REQUIREMENTS.

4.133 RESURFACE FLOOR, GRIND EXISTING FLOOR, PROVIDE ESD-1

(ELECTROSTATIC DISSIPATIVE) RESINOUS EPOXY FLOOR WITH

POLYURETHANE TOP COAT.

4.134 INSTALL BOLLARDS, REFERENCE STRUCTURAL FOR DETAILS

4.135 METAL TRANSITION STRIP

4.136 INSTALL MASONRY WALL CLEAR OF EXISTING BRIDGE CRANE RAILS

4.138 (ABI #1) REPLACE FABRIC ON HANGAR DOORS - BOTH SIDES.

4.151 ROOF ACCESS LADDER

4.152 GUARD RAIL, EXTEND TO NEAREST WALL OR 6 FEET MINIMUM FROM

SURFACE EDGE

4.153 GENERATOR ACCESS PLATFORM, REFERENCE STRUCTURAL AND

ELECTRICAL DRAWINGS.

4.154 PROVIDE WINDOW BLINDS,

1/8" = 1'-0"1

FIRST FLOOR PLAN 12/16/22 TYPE B3 FINAL

HEF MOD

A 06/02/23 ADDENDUM #1

1/8" = 1'-0"2

MEZZANINE PLAN

A

FLOOR PLAN GENERAL NOTES:

1. SITE DATUM OF FINISHED FIRST FLOOR INDICATED ON SITE PLAN = 100'-0" ON

ARCHITECTURAL DRAWINGS.

2. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THE

ATTENTION OF THE CONTRACTING OFFICER FOR FINAL DECISION.

3. ALL INTERIOR DIMENSIONS ARE FROM FINISH FACE OF WALLS (I.E. GYPSUM

WALLBOARD OR CMU), UNLESS NOTED OTHERWISE.

4. FINISH FLOOR ELEVATIONS ARE TO THE TOP OF CONCRETE, UNLESS NOTED

OTHERWISE.

5. REFERENCE SHEET G-011 AND G-021 FOR ALL CODE, FIRE RATING, AND

SEPARATION REQUIREMENTS.

6. GENERAL CONTRACTOR SHALL PATCH AND REPAIR EXISTING CONSTRUCTION

(WALLS, DOORS, CEILINGS, FLOORS, ETC.) AS REQUIRED FROM DEMOLITION

OR CONSTRUCTION TO ALLOW FOR THE PREP WORK AND NEW OR

COMPLETION OF EXISTING FINISHES. REPAIRS OR REPLACEMENTS MUST BE

DURABLE, SEAMLESS, AND MATCH THE EXISTING MATERIAL.

7. GENERAL CONTRACTOR SHALL PATCH ALL FLOOR AND WALL PENETRATIONS

CAUSED BY DEMOLITION OF MECHANICAL, ELECTRICAL, TECHNOLOGY, AND

PLUMBING, INCLUDING BUT NOT LIMITED TO PIPING AND CONDUIT RUNS, IN A

MANNER THAT IS CONSISTENT WITH THE EXISTING FLOOR AND WALL

CONSTRUCTION AND FINISH. ALL PENETRATIONS SHALL MEET REQUIRED FIRE

RATINGS.

8. COORDINATE THE INSTALLATION OF ALL OWNER-SUPPLIED EQUIPMENT.

REFERENCE PLANS, SPECS, AND INTERIOR ELEVATIONS FOR SPECIFIC

EQUIPMENT AND ITS INSTALLATION REQUIREMENTS.

9. GENERAL CONTRACTOR SHALL PROVIDE BLOCKING, STIFFENERS, BRACINGS,

BACKING PLATES, SUPPORTING BRACKETS, AND NECESSARY SELECTIVE

DEMOLITION REQUIRED FOR THE PROPER INSTALLATION OF ALL CASEWORK,

TOILET ROOM ACCESSORIES, TOILET PARTITIONS AND MISCELLANEOUS

EQUIPMENT.

10. EXISTING AND INFILL CONCRETE SUB-FLOOR SHALL BE MADE LEVEL, PLUMB

AND IN SOUND CONDITION AS REQUIRED FOR THE INSTALLATION OF FINAL

FLOOR FINISHES, TYPICAL. PROVIDE ARDEX OR EQUAL LEVELING CONCRETE

TO PROVIDE A SMOOTH WALKABLE AREA.

11. ALL RECESSED CABINETS, PANELS, BOXES, ETC. LOCATED IN FIRE-RATED

PARTITIONS SHALL BE INSTALLED IN A MANNER WHICH MAINTAINS THE FIRE

RATED CONSTRUCTION.

12. SEE ENLARGED PLANS FOR NOTES, DIMENSIONS, AND WALL TYPES WITHIN

THE DETAIL CALLOUT BOUNDARIES.

13. REFERENCE SHEET A-002 FOR INTERIOR PARTITION TYPES. INTERIOR

PARTITION TAGS NOTED ENCOMPASS THE ENTIRE LENGTH OF WALL SHOWN

TO CORNERS OF ROOM, OVER AND AROUND DOORWAYS SHOWN.

4.004

4.004

4.004

4.004

4.004

4.004

4.001

4.001

4.001

4.005

A-2021 A-202 4

A-202

A-202

1'-2 1/2" 24'-11"

1'-2 1/2"

11'-4"

A-302

A-302

4.102

4.108

4.108

4.108

FIRE PUMP

ROOM

E10

TRANSFORMER SEE ELECTRICAL GENERATOR SEE ELECTRICAL

EQUIPMENT PAD

SEE STRUCTURAL

4.705

4.705

/4

13'-9"

/4

A-202 4

A-202

A-302

A-302

4.170

4.169

4.170

4.171

4.203

2'-4"

2'-4"

Roof Zone 2

ASCE-7

Roof Zone 3

ASCE-7

DEMOLITION PLAN GENERAL NOTES:

1. THE GENERAL CONTRACTOR SHALL VERIFY ALL BUILDING AND SITE

CONDITIONS AND REPORT ANY DISCREPANCIES TO THE CONTRACTING

OFFICER BEFORE PROCEEDING WITH ANY SCHEDULED DEMOLITION WORK.

2. THE GENERAL CONTRACTOR SHALL COORDINATE ARCHITECTURAL,

STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL, TECHNOLOGY, AND

PLUMBING WORK AND ALL SUBCONTRACTORS FOR DEMOLITION AND REPAIR

WORK.

3. IT IS THE INTENT OF THESE DRAWINGS TO INDICATE THE REMOVAL OF ALL

ITEMS WHICH INTERFERE WITH THE FINAL CONSTRUCTION AS SHOWN ON

THE FLOOR PLANS, ELEVATIONS, DETAILS, AND SCHEDULES. ALL FLOOR

FINISHES, BASE, CEILINGS, ABANDONED FURNITURE, WINDOW TREATMENTS,

SHELVING, SIGNAGE, AND ROOFING MATERIALS SHALL BE DEMOLISHED IN

THEIR ENTIRETY.

4. REMOVE ALL ITEMS OF DEMOLITION WORK FROM THE PROJECT DAILY AND

DISPOSE OF PROPERLY.

5. EXISTING CONCRETE AND STEEL STRUCTURE TO REMAIN, TYP. PROTECT

COLUMNS, PILASTERS, BEAMS, AND SLABS.

6. THE EXISTING MECHANICAL, ELECTRICAL,TECHNOLOGY, AND PLUMBING

ITEMS AND/OR SYSTEMS, AND GAS, WATER AND ELECTRICAL METERS ARE

GENERALLY INTENDED TO REMAIN. WHERE WORK CONFLICTS WITH NEW

WORK, DEMOLITION OR REROUTING OF EXISTING INFRASTRUCTURE SHALL

BE REQUIRED. REF: MEP FOR ALL ITEMS TO BE REUSED TYP. ALL ITEMS TO BE

DEMOLISHED SHALL BE REMOVED IN THEIR ENTIRETY, BACK TO THE ORIGINAL

SOURCE. SURROUNDING MATERIALS WHICH ARE DISTURBED OR

DEMOLISHED THAT ARE SCHEDULED TO REMAIN SHALL BE PATCHED WITH

LIKE SURROUNDING MATERIALS, TYPICAL.

7. DEMOLISH CONCRETE FLOOR SLABS AS REQUIRED TO INSTALL NEW

EQUIPMENT, UNDERGROUND CONDUIT, PLUMBING SYSTEMS, AND FLOOR

DRAINS, REF: STRUCTURAL, EQUIPMENT, ELECTRICAL, PLUMBING

DEMOLITION, AND PLUMBING DRAWINGS.

8. PROTECT EXISTING SURFACES TO REMAIN DURING DEMOLITION AND

CONSTRUCTION.

9. REPAIR OR REPLACE ANY EXISTING CONSTRUCTION (WINDOWS, WALLS,

DOORS, CEILINGS, FLOORS, ETC.) TO REMAIN WHICH ARE DAMAGED DURING

CONSTRUCTION. REPLACEMENT MATERIAL SHALL MATCH IN KIND.

10. REFERENCE SHEET G-101 PHASING PLAN FOR CONSTRUCTION PHASING /

SEQUENCING AND SITE ACCESS.

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

/1

/2

:3

:2

A

M C

R e v it L o c a l\

-1

.0

-A

-F P

-C e n tr a l-

P a t.

C a s e y

L L

F U

.r v t

M

IC

H

IG

A N

A

IR

N A

T

IO

N A

L G

U A

R D

W

IL

B

U R

W R

IG

H

T B

L V

D

H A

R R

IS

O

N T

W P

M

IC

H

IG

A

N

A D

A L F

U E

L C

E L L

C O

R R

O S

IO

N

C O

N T

R O

L

B L D

G

A-102

B158 FIRE PUMP

BUILDINGS PLANS

VGLZ162323ANG NO.:

3141700-181848.01

PJC

REK

December 16, 2022

PJC

KEYED NOTES

4.001 REMOVE WALL IN ITS ENTIRETY. PATCH, REPAIR AND PREP ADJACENT

SURFACES TO ACCEPT NEW CONSTRUCTION

4.004 REMOVE EXISTING DOOR, FRAME AND ASSOCIATED HARDWARE. PATCH

REPAIR AND PREP FOR NEW CONSTRUCTION

4.005 REMOVE EXISTING ALUMINUM WINDOW, FRAME AND ASSOCIATED

HARDWARE, PATCH, REPAIR AND PREP FOR NEW CONSTRUCTION

4.102 PROVIDE HM DOORS WITH HM FRAMES, AND HARDWARE - REFERENCE

SCHEDULE.

4.108 INFILL OPENING WITH CMU WALL TO MATCH EXISTING THICKNESS AND

FINISH

4.169 PATCH AND REPAIR ROOF WHERE MECHANICAL EQUIPMENT WAS

REMOVED, SEE MECHANICAL PLANS, SPLICE NEW MEMBRANE TO EXISTING

WITH MANUFACTURER'S RECOMMENDED CONNECTIONS TO MAINTAIN

ROOF WARRANTY. MATCH SLOPE WITH ADJACENT ROOF SURFACES.

4.170 PROVIDE SINGLE PLY ROOF.

4.171 PROVIDE SCUPPER BOX AND DOWNSPOUT

4.203 PREFINISHED METAL COPING TO MATCH EXISTING PROFILE

4.705 ALL INTERIOR WALLS AND EXPOSED STRUCTURE TO RECEIVE PAINT FINISH

(PT-1), FLOOR TO BE SEALED CONCRETE (SC-1), SEE A-601 FOR

ARCHITECTURAL FINISHES SCHEDULE

1/4" = 1'-0"1

DEMOLITION PLAN

1/4" = 1'-0"2

FIRST FLOOR PLAN

1/4" = 1'-0"3

ROOF PLAN

12/16/22 TYPE B3 FINAL

HEF MOD

A 06/02/23 ADDENDUM #1

L K J H G F E D.3 D C B A

1.3

7.3

A-301

A-301

7.5

A-301

A-301

ACP-1

9'-0"

ACP-1

9'-0"

ACP-1

9'-0"

ACP-1

9'-0"

ACP-2

9'-0"

ACP-2

9'-0"

ACP-1

9'-0"

ACP-1

9'-0"

ACP-1

9'-0"

GYP-1

9'-0"

GYP-1

9'-0"

ACP-2

9'-0"

ACP-1

9'-0"

ACP-1

9'-0"

ACP-1

9'-0"

ACP-2

9'-0"

EXP EXP

EXP

EXP

EXP

EXP

EXP

EXP EXP

GYP-1

9'-0"

GYP-1

9'-0"

A-301

A-501

A-501

TYP.

A-501

A-501

A-501

4.1814.181 4.1814.181

AA

4.1814.181

A A

4.1814.181

CEILING PLAN GENERAL NOTES:

1. SEE ROOM FINISH SCHEDULE FOR FLOOR, WALL AND CEILING FINISHES AND

ROOM HEIGHTS.

2. FIELD VERIFY ALL DIMENSIONS, BRING ANY DISCREPANCIES TO THE

ATTENTION OF THE CONTRACTING OFFICER FOR FINAL DECISION.

3. ALL RECESSED LIGHTS, SPRINKLERS, FIRE DETECTION EQUIPMENT,

OCCUPANCY SENSORS, ETC. SHALL BE CENTERED IN THE TILES UNLESS

NOTED OTHERWISE.

4. CENTER ALL CEILING GRIDS IN SPACE UNLESS NOTED OTHERWISE.

5. ALL METAL LINEAR DIFFUSERS SHALL BE PAINTED TO MATCH SURROUNDING

WALL OR CEILING SURFACE.

2' x 2' SUSPENDED CEILING GRID

LIGHT FIXTURE (RECESSED MOUNTED)

GYPSUM BOARD CEILING/

PORTLAND CEMENT PLASTER (PAINTED)

LIGHT FIXTURE (SURFACE MOUNTED)

SUPPLY AIR DIFFUSER

RETURN AIR DIFFUSER / EXHAUST GRILL

LIGHT FIXTURE (RECESSED CAN)

LIGHT FIXTURE (SURFACE MOUNTED)

EXHAUST FAN

LIGHT FIXTURE (SUSPENDED)

LIGHT FIXTURE (SUSPENDED)OR

CEILING PLAN LEGEND: SEE ELECTRICAL FOR

EXACT FIXTURE MODEL

LIGHT FIXTURE (RECESSED MOUNTED 4" WIDE OR LESS)

8"6"

CEILING RECEPTACLES

CEILING OCCUPANCY SENSOR

CEILING FIRE ALARM DEVICES

CEILING MASS NOTIFICATION DEVICE

CEILING SPEAKER

SPRINKLER HEADS

CEILING SECURITY STRODE

CEILING CAMERA

LIGHT FIXTURE (RECESSED MOUNTED)OR

XX-X

X'-X" ELEVATION ABOVE FINISHED FLOOR

CEILING TYPE

CEILING TYPE TAG

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

/3

/2

:0

:2

A

M C

R e v it L o c a l\

-1

.0

-A -C e n tr a l-

N a te

D e

M a s te r.

rv t

M

IC

H

IG

A N

A

IR

N A

T

IO

N A

L G

U A

R D

W

IL

B

U R

W R

IG

H

T B

L V

D

H A

R R

IS

O

N T

W P

M

IC

H

IG

A

N

A D

A L F

U E

L C

E L L

C O

R R

O S

IO

N

C O

N T R

O L

B L D

G

A-121

FIRST FLOOR

CEILING PLAN

VGLZ162323ANG NO.:

3141700-181848.01

PJC

REK.KM

December 16, 2022

PJC

1/8" = 1'-0"1

REFELECTED CEILING PLAN

KEYED NOTES

4.181 FALL PROTECTION EQUIPMENT, REFERENCE STRUCTURAL DRAWINGS

12/16/22 TYPE B3 FINAL

HEF MOD

ID-03

ID-01

ID

-0

E D.3

1.3

A-301

A-301

MA6

MA8

MA8

MA8

MA8

MA8

MA8

MA8

MA6

MA6MA6

MA6

4.126

4.1264.1264.126

4.126

WOMEN'S

MEN'S

JANITOR

CORRIDOR

A-501

SIM.

A-501

SIM.

A-501

SIM.

OPP.

A-401

A-401 11

A-40113 12

TPD

GB-1

GB-3

GB-2

CR/VSC

CR/VSC

CR/VSC

MIR

LSD

LSD

PTD

EWC

URSURS

GB-1

GB-3

GB2

SND TPD

6'-8" 1'-0" 11'-3 3/8"

A-401

A-401 910

1'-9 5/8" 11'-8 1/2" 7'-1 3/4" 5'-5 3/4"

/8

/2

/2

3'-0"

A-401

MIR

PTD

LSD

GB-1

GB-4

GB-1

GB-4

HSD

HSD

CR/VSC

CR/VSC

4.125

4.125

4.1214.121

MA6

/8

MA6

1'-0"

1'-0"

3'-4"

4.157

4.157

4.157

5'-0"

/4

G F E

A-301

A-301

MA8

1H, 194"

MA8

1H, 194"

MA8

1H, 194"

MA8

1H, 194"

MA8

194"

MA8

MA8

194"

MA8

194"

4.139

4.1264.126

4.126

4.131

4.131

129A 129B 130B 130A

VEST

SHOWER

SHOWER

WASH ROOM

GEAR

LOCKER/

LAUNDRY

CORRIDOR129

VEST

MAINTENANCE/

CORROSION

DOCK

MAINTENANCE/

CORROSION

DOCK

8 3/16"

19'-4" 19'-4"

+/- 9'-6" 10'-1 7/8" 11'-4"

2'-2 3/8"

5'-2"

/8

+/-7'-11" 23'-8" 8'-0"

A-401

20 19

A-40121 15 MIR

MIR

LSD

LSD

PTD

MA8

194"

A-301

GB-4

GB-1

CR/VSC

GB-4

GB-1

CR/VSC

RH

RH

4.125

4.1414.141

4.142

4.142

TYP

1'-6"

T Y

P

4.1574.157

CONTINUOUS WOOD

BENCH WITH 1/2"

RADIUS EDGES. SEE

PLAN FOR LENGTH

STEEL BENCH

SUPPORT SEE PLAN

FOR LOCATIONS1

1'-8"

SEE STRUCTURAL FOR

SUPPORT TYPE AND

ANCHORAGE TO FLOOR

AND BENCH

FD = FLOOR DRAIN (PITCH FLOOR TO DRAIN)

CR = CURTAIN ROD (36" OPENING)

DCS = DIAPER CHANGING STATION (NOT USED)

EWC = ELECTRIC WATER COOLER

FSS = FOLDING SHOWER SEAT

GB1 = GRAB BAR (36"w. x 54"d. x 33 A.F.F.)

GB2 = GRAB BAR (36" L. x 33" A.F.F.)

GB3 = GRAB BAR (42" L. x 33" A.F.F.)

GB4 = GRAB BAR (28" L. x 33" A.F.F.)

HSD = HAND SANITIZER DISPENSER

LSD = LIQUID SOAP DISPENSER

(OWNER FURNISHED, CONTRACTOR INSTALLED)

MS = MOP STRIP

MIR = MIRROR - FRAMELESS

PTD = PAPER TOWEL DISPENSER/DISPOSAL

RH = ROBE HOOK

SCD = SEAT COVER DISPENSER (RECESSED)(NOT USED)

SD = SOAP DISH (NOT USED)

SND = SANITARY NAPKIN DISPOSAL

TPD = (2) TOILET PAPER DISPENSERS - (2 ROLL)

WR = WASTE RECEPTACLE

VSC = VINYL SHOWER CURTAIN

TOILET ROOM

ACCESSORY GENERAL NOTES:

1. LAVATORIES IN TOILET ROOM ARE SOLID SURFACE COUNTERTOPS WITH

UNDERCOUNTER MOUNTED BOWLS, BACKSPLASH SHALL BE INTEGRAL WITH

COUNTERTOP.

2. PROVIDE BLOCKING IN WALLS FOR ALL WALL MOUNTED ACCESSORIES.

3. ALL EXPOSED SURFACES OF MILLWORK TO BE P. LAMINATE ON 3/4" PART.

BD., TYPICAL, UNLESS NOTED OTHERWISE.

4. PROVIDE WATER RESISTANT GYPSUM WALLBOARD AT ALL WET AREAS

AND/OR AREAS TO RECEIVE WALL TILE.

5. SEE "ARCHITECTURAL FINISH SCHEDULE" FOR MATERIAL INFORMATION.

6. SEE SHEET A-121 FOR "CEILING FINISH" ABBREVIATIONS.

7. SEE DETAIL 7/ A-411 FOR ALL TOILET ACCESSORY MOUNTING HEIGHTS.

TOILET ACCESSORY KEY

A

A

M A

X

"M A

X

MIN

1'-3"

(URS)

URINAL

URINAL

@ NON-ADA

ACCESSIBLE

@ ADA

ACCESSIBLE

'-1

URINAL

SCREEN

(URS)

TOILET

PARTITION

(PART)

FLOOR LINE

M A

X

LIQUID SOAP

DISPENSER

(LSD)

(GFCI)

LAVATORY

MIRROR

(MIR)

C L R

M A

X

M A

X

ELECTRIC

WATER

COOLER

HI-LO

(EWC)

M

IN

SHOWER

CURTAIN

ROD

(SCR)

ROBE

HOOK

(RH)

PAPER

TOWEL

DISP.

(PTD)

(GFCI)

SANITARY

NAPKIN

DISPOSAL

(SND)

FAUCET ON

OPPOSITE WALL

FROM MOP

STRIP

(IF APPLICABLE)

SHELF W/

MOP STRIP

(MS)

MOP BASIN

FIRE

EXTINGUISHER

CABINET

(FEC)

M

A X

FOLDING

SHOWER

SEAT

(FSS)

MAX

2'-3"

1'-4" SHOWER HEIGHT

ACCESSORIES

" 2

M A

X

T.O. HOSE MOUNTING

BRACKET

DESIGN OPTION,

STD HEAD

FLEXIBLE SHOWER

SPRAY HOSE - 60" L

SINGLE LEVEL MIXING

VALVE CONTROL

GRAB BAR (GB4)

FLOOR LINE

MAX

6"

MAX

1'-0"

T

O

GRAB BAR,

REQD (GB3)

GRAB BAR,

REQD (GB1)

GRAB

BAR,

REQD

(GB2)

(2) TOILET PAPER

HOLDER DBL

ROLL (TPH)

SANITARY NAPKIN

DISPOSAL (SND)

WALL

MOUNT

TOILET

41"

39" TO

MIN

3'-6"

1'-6" 7" 8"

MIN

3'-0"

A D

A R

E Q

M A

X

HAND

SANITIZER

DISPENSER

(HSD)

PART

MIR

LSD

CR

3'-0"

1'-0"

A-421

A-401

4.158

MIR

LSD PTD

4.158

GB2

SND

TPD GB1

GB34.158

1'-0"

4.126

4.158

RH

4.158

CR/VSC

4.158

C T

B -1

C T

-2

C T

-3

C

T -2

URS

PART

CR

4.158

CR/VSC

MIR

LSD LSD

1'-0"

5'-10"

" 4

1'-0"1'-0"

A-421

4.1264.126

1'-8" 2'-8" 1'-8"

4.158

PARTPART

1'-0" 1'-0"

4.126

4.158

URS URS

T Y

P

2'-8" 2'-7" 1'-5"

2'-7" 2'-7" 2'-8 3/4"

4.126

TYP

1'-0"

4.158

PART PART

CR/VSC

CR/VSC

RH

RH

4.207

4.158

CR/VSC CR/VSC

4.158

LSD

MIR

FIRE ALARM CONTROL PANEL

4.158

CR/VSC

LSD

MIR

PTD

4.158

4.158

MIR

LSD LSD

CR/VSC

5'-10"

A-421

EQ 3'-0" EQ

4.1584.158

GFGI WASHERGFGI DRYER

1'-6"

A-401

1'-6"

FIRE ALARM CONTROL PANEL

1'-6"

4.126

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

/1

/2

:2

:2

A

M C

R e v it L o c a l\

-1

.0

-A

-C e n tr a l-

P a t.

C a s e y

L L

F U

.r v t

M

IC

H

IG

A N

A

IR

N A

T

IO

N A

L G

U A

R D

W

IL

B

U R

W R

IG

H

T B

L V

D

H A

R R

IS

O

N T

W P

M

IC

H

IG

A

N

A D

A L F

U E

L C

E L L

C O

R R

O S

IO

N

C O

N T

R O

L

B L D

G

A-401

ENLARGED PLANS,

ELEVATIONS AND

DETAILS

VGLZ162323ANG NO.:

3141700-181848.01

PJC

REK.KM

December 16, 2022

PJC

1/4" = 1'-0"4

RESTROOMS

1/4" = 1'-0"18

CONTAMINATION CONTROL AREA

KEYED NOTES

4.121 ALIGN WALL WITH EXISTING WALL

4.125 ADA BENCH, REFERENCE SPECIFICATIONS

4.126 PROVIDE HDPE LOCKERS WITH SLOPE TOP, ON 4" BASE BY MFR.

4.131 PROVIDE EMERGENCY EYE WASH AND SHOWER, COORDINATE WITH

PLUMBING.

4.139 ROOF ACCESS LADDER

4.141 FRONT LOAD DRYERS, GOVERNMENT FURNISHED, GENERAL CONTRACTOR

TO INSTALL. (GFCI)

4.142 FRONT LOAD WASHERS, GOVERNMENT FURNISHED, GENERAL

CONTRACTOR TO INSTALL. (GFCI)

4.157 SHOWER INSERT, REFERENCE PLUMBING DRAWINGS

4.158 SEE DETAIL 22/ A-401 FOR TYP. CT PATTERNING

4.207 MECHANICAL EQUIPMENT, REFERENCE MECHANICAL DRAWINGS

1 1/2" = 1'-0"1

ADA LOCKER ROOM BENCH

1/4" = 1'-0"17

ACCESSORY MOUNTING HEIGHTS

1/4" = 1'-0"8

WOMENS NORTH

12/16/22 TYPE B3 FINAL

HEF MOD

A 06/02/23 ADDENDUM #1

1/4" = 1'-0"5

WOMENS EAST

1/4" = 1'-0"14

WOMENS WEST

1/4" = 1'-0"11

WOMENS LOCKER EAST

1/4" = 1'-0"12

WOMENS SHOWER EAST

1/4" = 1'-0"13

WOMENS SHOWER WEST

1/4" = 1'-0"22

TYPICAL TILE WALL ELEVATION

1/4" = 1'-0"2

MENS NORTH

1/4" = 1'-0"3

MENS SOUTH

1/4" = 1'-0"6

MENS EAST

1/4" = 1'-0"7

MENS WEST

1/4" = 1'-0"9

MENS SHOWER EAST

1/4" = 1'-0"10

MENS SHOWER WEST

1/4" = 1'-0"23

WASHROOM NORTH

1/4" = 1'-0"24

WASHROOM SOUTH

1/4" = 1'-0"19

WASHROOM EAST

1/4" = 1'-0"20

WASHROOM WEST

1/4" = 1'-0"15

GEAR LOCKER/ LAUNDRY EAST

1/4" = 1'-0"21

GEAR LOCKER/ LAUNDRY WEST

1/4" = 1'-0"16

GEAR LOCKER/ LAUNDRY NORTH

1/4" = 1'-0"25

GEAR LOCKER/ LAUNDRY SOUTH

A

AA

A A A

A

A

A

A

F

FLUSH DOOR

SCHED.

SEE

S E

E S

C H

E D

F2

S E

E S

C H

E D

2"

SCHED.

SEE 2"

SEALANT AND BACKER

ROD, TYP. BOTH SIDES

PRE-FINISHED METAL HEAD

FLASHING WITH HEMMED

EDGE SET IN SEALANT

2" RIGID INSULATION

AIR/MOISTURE/VAPOR BARRIER

(SHOWN DASHED) ON 12" CMU

BACKUP (8" CMU BACKUP AT

SIMILAR LOCATIONS)

WEEP VENTS AT 16" O.C., TYP.

BRICK SOLDIER COURSE TO

MATCH EXISTING

MEMBRANE FLASHING

WITH TERMINATION BAR

PAINT EXPOSED STEEL

DOOR, SEE SCHEDULE

1'-1 1/4"

7 5/8" 2" 3 5/8"

5 1/4"

SEALANT AND BACKER

ROD, TYP. BOTH SIDES

2" RIGID INSULATION

AIR/MOISTURE/VAPOR BARRIER

(SHOWN DASHED) ON 12" CMU

BACKUP (8" CMU BACKUP AT

SIMILAR LOCATIONS)

BRICK

DOOR, SEE SCHEDULE

5 1/4"

DOOR

(SEE SCHEDULE)

EXTERIOR FACE OF

WALL BEYOND

THRESHOLD SET IN

SEALANT

1/2" RIGID INSULATION

BETWEEN CONCRETE

STOOP AND

CONCRETE SLAB

2" RIGID INSULATION

WALL BEYOND

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

/1

/2

:3

:2

A

M C

R e v it L o c a l\

-1

.0

-A

-F P

-C e n tr a l-

P a t.

C a s e y

L L

F U

.r v t

M

IC

H

IG

A N

A

IR

N A

T

IO

N A

L G

U A

R D

W

IL

B

U R

W R

IG

H

T B

L V

D

H A

R R

IS

O

N T

W P

M

IC

H

IG

A

N

A D

A L F

U E

L C

E L L

C O

R R

O S

IO

N

C O

N T

R O

L

B L D

G

A-602

B158 SCHEDULES

VGLZ162323ANG NO.:

3141700-181848.01

PJC

REK

December 16, 2022

PJC

2021DOOR AND HARDWARE SCHEDULE

DOOR

NUMBER

DOOR FRAME MISCELLANEOUS

REMARKS

LEAF SIZE

TYPE MAT'L

GLAZING

TYPE FINISH TYPE MAT'L

DETAILS

FINISH LABEL

HDWR

SET LINTELQTY. WIDTH HEIGHT HEAD JAMB OTHER

102 (1) 3'-0" 7'-0" F HM - PT F HM 3/A-602 2/A-602 PT -

E101 (2) 3'-0" 8'-4" N EX - PT EX EX - - - PT -

DOOR AND HARDWARE SCHEDULE ABBREVIATIONS

EX = EXISTING

FG = FIRE GLASS

IN = INSULATED

L = LEXAN MARGARD

P = 1/4" PLATE

S = SAFETY

T = TEMPERED

DOOR AND HARDWARE SCHEDULE ABBREVIATIONS

DOOR/FRAME MATERIALS

AL = ALUMINUM

EX = EXISTING

FR = FABRIC ROLL-UP

FRP = FIBERGLASS REINFORCED PLASTIC

G = GALVANIZED

HM = HOLLOW METAL

PL = PLASTIC ROLL-UP

R = RUBBER ROLL-UP

SS = STAINLESS STEEL

ST = STEEL

WD = WOOD

GLAZING TYPES

DOOR AND HARDWARE SCHEDULE GENERAL NOTES

1. PROVIDE STAINLESS STEEL GUARD CHAIN WITH CAUTION SIGN ACROSS INTERIOR SIDE OF DOOR. (NOT USED)

2. LINTEL L1 SHALL BE (2) #5 BARS, 1 COURSE HIGH.(NOT USED - SEE STRUCUTRAL FOR LINTEL SCHEDULE)

3. OPERABLE LEAF SHALL BE DOOR TYPE B AND FIXED LEAF SHAL BE DOOR TYPE A.(NOT USED)

1/4" = 1'-0"

DOOR TYPES

1/4" = 1'-0"

FRAME TYPES

1 1/2" = 1'-0"3

EXTERIOR DOOR HEAD AT BRICK

1 1/2" = 1'-0"2

EXTERIOR DOOR JAMB AT BRICK

1 1/2" = 1'-0"1

EXTERIOR DOOR SILL

12/16/22 TYPE B3 FINAL

HEF MOD

HYDRAULIC REFERENCE NODE

OS&Y VALVE WITH TAMPER

SWITCH

ISOLATION VALVE

CHECK VALVE

WATERFLOW SWITCH

PRESSURE REDUCING VALVE

POST INDICATOR VALVE

WET PIPE SYSTEM

PIPE ELEVATION AFF

FIRE DEPARTMENT

CONNECTION

PIPE CONTINUATION

DIRECTION OF FLOW

SP

[ X'-X"]

FIRE PROTECTION SYMBOLS FIRE ALARM/ MNS SYMBOLS FIRE PROTECTION GENERAL NOTES FIRE ALARM/MNS GENERAL NOTES FIRE PROTECTION ABBREVIATIONS

RSFACU

s

F

C

M

RA

FIRE ALARM/ MASS NOTIFICATION CONTROL

PANEL

REMOTE ANNUNCIATOR PANEL

FIRE ALARM/ MNS STROBE - WALL MOUNT

-XX DENOTES CANDELA RATING

FIRE ALARM/ MNS STROBE - CEILING MOUNT

-XX DENOTES CANDELA RATING

-WP DENOTES WEATHERPROOF

SPEAKER - WALL MOUNT

-WP DENOTES WEATHERPROOF

HORN - WALL MOUNT

FIRE ALARM/COMBINATION SPEAKER

/STROBE - CEILING MOUNT

-XX DENOTES CANDELA RATING

FIRE ALARM/ MNS SPEAKER - CEILING MOUNT

-WP DENOTES WEATHERPROOF

SMOKE DETECTOR - PHOTOELECTRIC

CARBON MONOXIDE DETECTOR

DUCT SMOKE DETECTOR

FIRE ALARM MANUAL PULL STATION

ADDRESSABLE INITIATING DEVICE MODULE

ADDRESSABLE CONTROL (RELAY) MODULE

PRESSURE SWITCH

WATERFLOW SWITCH

TAMPER SWITCH

EXTERIOR FIRE ALARM BELL

TRANSIENT VOLTAGE SURGE SUPPRESSOR

REMOTE TEST STATION

LOCAL OPERATING CONSOLE

RADIO TRANSMITTER

ANTENNA

REMOTE POWER SUPPLY

TEMPERATURE SENSOR

KNOX BOX

DET-TRONICS X3301 MULTISPECTRUM IR

OPTICAL FLAME DETECTOR

RELEASING SERVICE FIRE ALARM CONTROL

UNIT

TVSS

RTS

FMCP

D

LOC

XX

C

C

RT

RPS

T

K

CO

1. FIRE PROTECTION SYSTEMS SHALL COMPLY WITH PROJECT

SPECIFICATIONS, UFC 3-600-01, UFC 4-211-01, ETL 15-01-03, NFPA 13,

NFPA 20, NFPA 24, AND ALL APPLICABLE CODES AND STANDARDS.

2. THESE DRAWINGS ARE DIAGRAMMATIC AND INDICATE A GENERAL

ARRANGEMENT OF WORK. GENERAL DESIGN CONCEPTS INDICATED

MUST BE FOLLOWED OR BETTERED. THE BID SHALL INCLUDE

OFFSETS, ADDITIONAL PIPING, VALVES, AND FIRE PROTECTION

EQUIPMENT AS REQUIRED TO MEET CONSTRUCTION CONDITIONS

FOR PROPER OPERATION. DEVELOP AND SUBMIT COORDINATION

DRAWINGS.

3. PIPING WILL NOT BE SHOWN FOR THE SPRINKLER SYSTEM. THE

CONTRACTOR SHALL PROVIDE FINAL ROUTING FOR ALL PIPING AND

SHALL PROVIDE SHOP DRAWINGS THAT INCLUDE: EXACT

DIMENSIONED ROUTING OF ALL PIPE, PIPE SIZES, DIMENSIONED TIE-

IN LOCATIONS AT EXISTING PIPING, AND FIRE RATED

CONSTRUCTION PENETRATIONS DETAILS. THE CONTRACTOR SHALL

AVOID INTERFERENCES WITH OTHER PIPING, EQUIPMENT, CODE

REQUIRED CLEARANCES, AND THE WORK OF OTHER DISCIPLINES.

FIELD ROUTED LIQUID-FILLED PIPING SHALL NOT BE ROUTED ABOVE

ELECTRICAL OR ELECTRONIC EQUIPMENT.

4. INSTALLING CONTRACTOR SHALL OBTAIN ALL REQUIRED PERMITS

AND LICENSES.

5. DESIGN AND INSTALLATION SUBJECT TO FINAL INSPECTION AND

APPROVAL BY CONTRACTING OFFICER.

6. CUTTING OF STRUCTURAL AND/OR ARCHITECTURAL MEMBERS

SHALL BE DONE ONLY WITH THE WRITTEN APPROVAL OF THE

CONTRACTING OFFICER.

7. FIRE STOP ALL PENETRATIONS OF SMOKE/FIRE WALLS, RATED

WALLS, CEILINGS, FLOOR, ROOFS, ETC. FLASH AND COUNTERFLASH

ANY ROOF PENETRATIONS.

8. METHOD OF HANGING PIPES, HEADERS, AND BRANCHLINES SHALL

BE IN ACCORDANCE WITH NFPA 13.

9. ALL VALVES FOR FIRE SERVICE SHALL BE LISTED BY THE

UNDERWRITER'S LABORATORIES, INC. AND/OR THE FACTORY

MUTUAL LABORATORIES. VALVES SHALL BE FACTORY MARKED "UL"

AND/OR "FM" OR EQUIVALENT.

10. ALL NORMALLY OPEN VALVES ON THE FIRE PROTECTION SYSTEM

SHALL BE ELECTRICALLY SUPERVISED AND SHALL BE THE

RESPONSIBILITY OF THE FIRE SPRINKLER CONTRACTOR.

11. PROVIDE A PERMANENTLY ATTACHED HYDRAULIC NAME PLATE

STATING THE REQUIRED DESIGN CRITERIA FOR EACH

HYDRAULICALLY DESIGNED SYSTEM IN ACCORDANCE WITH NFPA 13.

12. ONLY NEW MATERIALS SHALL BE USED IN THE INSTALLATION OF

THESE SYSTEMS.

13. ALL SUPPORTS SHALL BE ATTACHED TO THE BUILDING'S

STRUCTURAL FRAME IN ACCORDANCE WITH NFPA 13.

14. INSTALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S

INSTRUCTIONS.

15. ROD STIFFERNER REQUIRED FOR ALL-THREAD ROD HANGERS OVER

6' IN LENGTH.

16. INSTALL UNIONS IN PIPES 2" AND SMALLER, ADJACENT TO EACH

VALVE. UNIONS ARE NOT REQUIRED ON FLANGED DEVICES OR IN

PIPING INSTALLATIONS USING GROOVED MECHANICAL COUPLINGS.

17. SAFEGUARDING DURING CONSTRUCTION SHALL BE IN ACCORDANCE

WITH ARMY CORPS OF ENGINEERING MANUAL (EM), EM-385-1-1,

SAFETY AND HEALTH REQUIREMENTS MANUAL AND NFPA 241.

CONTRACTOR SHALL COORDINATE SPECIFIC PLAN FOR FIRE

PROTECTION DURING CONSTRUCTION WITH THE CONTRACTING

OFFICER.

18. SPRINKLERS INSTALLED IN HIGH HEAT AREAS, INCLUDING BUT NOT

LIMITED TO, ATTIC SPACES, OR IN CLOSE PROXIMITY TO UNIT

HEATERS, SHALL HAVE A TEMPERATURE CLASSIFICATION IN

ACCORDANCE WITH NFPA 13.

19. EQUIPMENT SHALL BE INSTALLED WITH A MINIMUM CLEARANCE OF

36" ACCESS TO AND IN FRONT OF ALL EQUIPMENT AND 6" BEHIND

THE EQUIPMENT.

20. PROVIDE SPRINKLER PROTECTION IN COMBUSTIBLE CONCEALED

LOCATIONS IN ACCORDANCE WITH NFPA 13.

21. ALL SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK STEEL.

22. SEE SHEAR WALLS PLANS IN STRUCTURAL DRAWINGS FOR SHEAR

WALL LOCATIONS AND RESTRICTIONS ON PENETRATIONS.

1. FIRE ALARM/MASS NOTIFICATION SYSTEMS SHALL COMPLY

WITH UFC 3-600-01, UFC 4-021-01, UFC 4-211-01, ETL 15-01-03,

NFPA 70, NFPA 72, AND PROJECT SPECIFICATIONS. NOTE THAT

THE FIRE PUMP HOUSE WILL NOT BE PROVIDED WITH MASS

NOTIFICATION.

2. PENETRATIONS IN FIRE RATED ASSEMBLIES SHALL BE FIRE-

STOPPED WITH LISTED MATERIALS/ ASSEMBLIES IN

ACCORDANCE WITH THE PROJECT SPECIFICATIONS.

3. FIRE SUPPRESSION SYSTEM WATERFLOW AND CONTROL VALVE

SUPERVISORY SWITCHES SHALL BE MONITORED BY THE

BUILDING FIRE ALARM/ MASS NOTIFICATION SYSTEM.

4. THE FIRE ALARM CONTRACTOR IS RESPONSIBLE FOR

COORDINATION OF SYSTEM REQUIREMENTS WITH ALL

CONDITIONS OF THE BUILDING AND SITE INCLUDING, BUT NOT

LIMITED TO, BLIND SPACES, SHELVING, LIGHTS, HVAC GRILLES

AND DIFFUSERS, PIPING, DUCT WORK, DOORS, WINDOWS,

EQUIPMENT PLATFORMS, WALLS (FIRE RATED AND NON FIRE

RATED), BEAMS, JOISTS, COLUMNS, HVAC EQUIPMENT,

ELECTRICAL PANELS AND EQUIPMENT, CEILINGS, AREAS

WITHOUT CEILINGS, WALL CONSTRUCTION, FLOORS AND ALL

CONSTRUCTION, EQUIPMENT AND BUILDING APPURTENANCES.

5. THE FIRE ALARM CONTRACTOR SHALL BE RESPONSIBLE FOR

PERFORMING, DOCUMENTING, AND CERTIFYING REQUISITE

INSPECTION AND TESTS IN ACCORDANCE WITH APPLICABLE

CODES AND STANDARDS FOR ALL FIRE ALARM EQUIPMENT

FURNISHED UNDER THIS PROJECT. AFTER COMPLETING THE

TESTING, THE CONTRACTOR SHALL DEMONSTRATE FULL

OPERATIONAL CAPABILITY OF THE FIRE ALARM/ MASS

NOTIFICATION SYSTEM, AS WELL AS FULL COMPLIANCE WITH

ALL DESIGN DOCUMENTS, CODES AND STANDARDS.

6. CONTRACTOR SHALL PROVIDE ALL MISCELLANEOUS MATERIAL

FOR A COMPLETE INSTALLATION.

7. EACH CONVENTIONAL FIRE ALARM DEVICE MUST HAVE ITS OWN

MONITOR MODULE.

8. ALL CONDUCTORS SHALL BE INSTALLED IN METALLIC

CONDUITS.

9. ALL FIRE ALARM MODULES LOCATED WITHIN 15' OF A

SPRINKLER/STANDPIPE SYSTEM RISER SHALL BE

WEATHERPROOF WITH LIQUID TIGHT CONDUIT.

10. ALL CONDUIT FROM ANY FIRE ALARM DEVICE CONNECTED TO A

DEVICE THAT MAY BE IN CONTACT WITH WATER SHALL BE

LIQUID TIGHT. THIS INCLUDES, BUT IS NOT LIMITED TO,

WATERFLOW SWITCHES, PRESSURE SWITCHES & TAMPER

SWITCHES.

11. TELECOMMUNICATIONS CONDUIT SHALL BE INSTALLED IN

ACCORDANCE WITH DIVISION 27 OF THE PROJECT

SPECIFICATIONS.

12. PROVIDE A LABEL ON THE EXTERIOR OF EACH FIRE ALARM

DEVICE THAT MATCHES THE DEVICE NUMBER (ADDRESS) AT

THE FMCP. DEVICE ID NUMBERS SHALL BE VISIBLE FROM THE

FLOOR TO THE MAXIMUM EXTENT PRACTICAL. MONITOR

MODULES & CONTROL/RELAY MODULES SHALL ALSO BE

LABELED AS TO WHAT THEY CONTROL.

13. ALL WIRING, CONDUIT, AND DEVICES LOCATED IN HAZARDOUS

ATMOSPHERES, AS DEFINED BY NFPA 70, SHALL BE EXPLOSION

PROOF. REFER TO THE ELECTRICAL PLANS FOR LOCATIONS.

ABOVE FINISHED FLOOR

AUTOMATIC TRANSFER SWITCH

CANDELA

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CHECK VALVE

CHEMICAL

CEMENT LINED DUCTILE IRON PIPE

CONTROL PANEL

DECIBEL

FIRE ALARM

FIRE ALARM BELL

FIRE ALARM CONTROL PANEL

FIRE DEPARTMENT CONNECTION

FIRE EXTINGUISHER

FIRE EXTINGUISHER CABINET

FACTORY MUTUAL

FIBER OPTIC

FIBER OPTIC TRANSCEIVER MODULE

FIRE PUMP CONTROLLER

FLOW SWITCH

FIRE SEPARATION DISTANCE

GOVERNMENT FURNISHED GOVERNMENT INSTALLED

IN ACCORDANCE WITH

INTERNATIONAL BUILDING CODE

MANUFACTURER

MASS NOTIFICATION SYSTEM

NOTIFICATION APPLIANCE CIRCUIT

NORMALLY CLOSED

NATIONAL FIRE PROTECTION ASSOCIATION

OUTSIDE STEM AND YOKE

PUMP

POST INDICATOR VALVE

PRESSURE REDUCING VALVE

RISER CHECK VALVE

RELEASING SERVICE FIRE ALARM CONTROL UNIT

SOUNDER BASE

SCHEDULE

PHOTOELECTRIC SMOKE DETECTOR

SIGNALING LINE CIRCUIT

TANK

TO BE DETERMINED

TAMPER SWITCH

TRANSIENT VOLTAGE SURGE SUPPRESSOR

UNIFIED FACILITIES CRITERIA

UNDERWRITER'S LABORATORIES

UNLESS OTHERWISE NOTED

UNITED STATES AIR FORCE

VALVE

VARIABLE FREQUENCY DRIVE

WEATHERPROOF

ZONE CONTROL ASSEMBLY

AFF

ATS

CD

CFCI

CHKV

CHEM

CLDIP

CP

DB

FA

FAB

FACP

FDC

FE

FEC

FM

FO

FOTM

FPC

FS

FSD

GFGI

IAW

IBC

MFG

MNS

NAC

NC

NFPA

OS&Y

P

PIV

PRV

RCV

RSFAC

SB

SCH

SD

SLC

T

TBD

TS

TVSS

UFC

UL

UON

USAF

V

VFD

WP

ZCA

H

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

6/ 2/

:1

5:

P M

C :\U se rs

\B

EN

.S H

AF

FE

R \D oc um en ts

\3

-1

8.

-F

-C en tra l-2

0_

BE

N

.S H

AF

FE

R .rv t

M

IC

H

IG

AN

A

IR

N

AT

IO

N

AL

G U

AR

D

W

IL

BU

R W

R

IG

H T

BL

VD

H

AR

R

IS

O

N T

W P, M

IC

H

IG

AN

AD

AL

F U

EL

C

EL

L

C

O R

R O

SI

O

N C

O N

TR

O

L -B

LD

G

F-001

FIRE PROTECTION

LEGEND AND

SYMBOLS

VGLZ162323ANG NO.:

3141700-184848.01

RAB

RDV

December 16, 2022

RAB

12/16/22 TYPE B3 FINAL

HEF MOD

MAINTENANCE/

CORROSION

DOCK

MAINTENANCE/

CORROSION

DOCK

CLASSROOM/

BREAK

OPEN OFFICE

OFFICE

CORRIDOR

CORRIDOR

JANITOR

MEN'S

WOMEN'S

OFFICE

CORRIDOR

EXTERNAL FUEL

TANK OFFICE/

TOOL STORAGE

ELECTRICAL

FIRE

PROTECTION

ROOM

UTILITY

EXTERNAL FUEL

TANK

VESTIBULE

STORAGE

STORAGE

F-301

F-301

L K J H G F E D.3

D C B

A

1.3

7.3

7.5

F-401

WASH ROOM

123 SHOWER

GEAR LOCKER/

LAUNDRY

SHOWER

VEST

129 VEST

4" ø

(S P-

3)

4"ø (SP-3)

4"ø (FDC)

4" ø

(S P-

3)

4" ø

(S P-

2)

4"ø (SP-1)

4"ø (SP-2)

4"ø (SP-1)

4" ø

(S P-

3) 4" ø (S

P- 3)

4" ø

(S P-

1)

4" ø

(S P-

1)

4" ø

(S P-

2)

4" ø

(S P-

2)

142136

134128

79 80

69 70

45 4644

4"ø (SP-2)

2"ø (SP-2)

2"ø (SP-2)

2"ø (SP-2)

2"ø (SP-2)

2"ø (SP-2)

5.103

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

6/ 2/

:1

6:

P M

C :\U se rs

\B

EN

.S H

AF

FE

R \D oc um en ts

\3

-1

8.

-F

-C en tra l-2

0_

BE

N

.S H

AF

FE

R .rv t

M

IC

H

IG

AN

A

IR

N

AT

IO

N

AL

G U

AR

D

W

IL

BU

R W

R

IG

H T

BL

VD

H

AR

R

IS

O

N T

W P, M

IC

H

IG

AN

AD

AL

F U

EL

C

EL

L

C

O R

R O

SI

O

N C

O N

TR

O

L -B

LD

G

F-102

FIRE PROTECTION

PLAN

VGLZ162323ANG NO.:

3141700-184848.01

RAB

RDV

December 16, 2022

RAB

A. FOR FIRE PROTECTION GENERAL NOTES, LEGEND, &

ABBREVIATIONS, SEE SHEET F-001.

B. THE BUILDING SHALL BE PROVIDED WITH AN

AUTOMATIC SPRINKLER SYSTEM THROUGHOUT IN

ACCORDANCE WITH NFPA 13, UFC 3-600-01, & UFC

4-211-01.

C. DESIGN THE SPRINKLER PIPING SUCH THAT THE

MAJORITY OR ALL OF THE SYSTEM DRAINS BACK TO

THE RISER. MINIMIZE OR ELIMINATE THE

REQUIREMENT FOR REMOTE DRAINAGE

CONNECTIONS IN THE HANGAR BAY.

D. EQUIPMENT IN THE HANGAR BAY AND ROOMS WITH

DOORS TO THE HANGAR BAY SHALL BE RATED FOR

CLASS I DIV II OR LOCATED 18" ABOVE FINISHED

FLOOR.

E. DEMOLISH ALL EXISTING FIRE PROTECTION

EQUIPMENT.

F. PROVIDE SPRINLKER PROTECTION BENEATH

OBSTRUCTIONS GREATER THAN 4FT INCLUDING

DUCTWORK AND PIPING GROUPINGS.

G. INSTALL AUTOMATIC AIR VENT(S) AT AN ACCESSIBLE

HIGH POINT OF EACH SPRINKLER SYSTEM IN A LEVEL

POSITION WHERE PRESSURE GAUGE CAN BE VIEWED

FROM BELOW.

H. PARTIAL SPRINKLER SYSTEM LAYOUT IS PROVIDED

ONLY TO VERIFY HYDRAULIC DEMAND. CONTRACTOR

IS RESPONSIBLE FOR COMPLETE SYSTEM DESIGN

THROUGHOUT BUILDING.

I. DEMOLISH ALL EXISTING FOAM EQUIPMENT. PERFORM

LABORATORY ANALYTICAL TESTING OF FOAM

CONCENTRATE TO DETERMINE POTENTIAL PFOS/PFOA

CONSTITUENTS PRESENT FOR PROPER DISPOSAL

REQUIREMENTS, AS NEEDED, IAW WITH DOD

GUIDELINES. RINSE SYSTEM PIPING AND EQUIPMENT

TO REMOVE ANY FOAM CONCENTRATE (IF POTENTIAL

PFOS/PFOA CONSTITUENTS PRESENT) PRIOR TO

SYSTEM DISPOSAL. UTILIZE A CREDITED COMPANY

FOR TRANSPORT AND DISPOSAL OF THE FOAM.

GENERAL NOTES

KEYED NOTES

1/8" = 1'-0"1 FIRE PROTECTION PLAN

5.103 PROVIDE BRANCHLINE AT ROOF PEAK TO CONNECT

BRANCHES TO REDUCE THE NUMBER OF AIR VENTS

REQUIRED IN THE SYSTEM (TYPICAL FOR BOTH

HANGAR BAYS).

12/16/22 TYPE B3 FINAL

HEF MOD

F

FF

F

F

FF

F

F

F

15 15

CO

D

D D

D

D

D

MAINTENANCE/

CORROSION

DOCK

MAINTENANCE/

CORROSION

DOCK

CLASSROOM/

BREAK

OPEN OFFICE

OFFICE

CORRIDOR

JANITOR

MEN'S

OFFICE

CORRIDOR

EXTERNAL FUEL

TANK OFFICE/

TOOL STORAGE

ELECTRICAL

FIRE

PROTECTION

ROOM

UTILITY

EXTERNAL FUEL

TANK

VESTIBULE

STORAGE

STORAGE

WP

WP WP

WP

WP

WP

WP

WP

WP

WP

WP

WP

177177177

F-301

F-301

L K J H G F E D.3

D C B

A

1.3

7.3

7.5

177 177

FM

C

P

M

K

R

PS

R T

M

RA

WASH ROOM

GEAR LOCKER/

LAUNDRY

VEST

VEST

SHOWER

124SHOWER

WP

C C

M M

WOMEN'S

C RTS

CR

TS

R

TS

C

LCOATE DUCT SMOKE DETECTOR

ON THE SUPPLY SIDE OF MAU-1

LCOATE DUCT SMOKE DETECTOR

ON THE SUPPLY SIDE OF RTU-1

CO RTS

R

TS

R

TS

CO

CO

15 WP

WP15

W

P

5.117

5.119

5.120

5.125

5.126

5.127

5.130 5.109

5.110

5.1175.1175.117

5.119

M MM M

T

5.114

M M M M

RSFACU RPS

T

T

5.160

5.159

5.161

5.161

A

AA

A

A A

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

6/ 2/

:1

6:

P M

C :\U se rs

\B

EN

.S H

AF

FE

R \D oc um en ts

\3

-1

8.

-F

-C en tra l-2

0_

BE

N

.S H

AF

FE

R .rv t

M

IC

H

IG

AN

A

IR

N

AT

IO

N

AL

G U

AR

D

W

IL

BU

R W

R

IG

H T

BL

VD

H

AR

R

IS

O

N T

W P, M

IC

H

IG

AN

AD

AL

F U

EL

C

EL

L

C

O R

R O

SI

O

N C

O N

TR

O

L -B

LD

G

F-103

FIRE ALARM/ MNS

PLAN

VGLZ162323ANG NO.:

3141700-184848.01

RAB

RDV

December 16, 2022

RAB

1/8" = 1'-0"1 FIRE ALARM/ MNS PLAN

A. FOR FIRE PROTECTION GENERAL NOTES, LEGEND, &

ABBREVIATIONS, SEE SHEET F-001.

B. DEMOLISH ALL EXISTING FIRE ALARM EQUIPMENT, WIRING,

PATHWAYS, AND ASSOCIATED EQUIPMENT.

C. MAINTAIN EXISTING FIRE ALARM EQUIPMENT FULLY

OPERATIONAL UNTIL THE NEW EQUIPMENT HAS BEEN

TESTED AND ACCEPTED BY THE CONTRACTING OFFICER.

D. LOCATE CONTROL MODULES WITHIN 36" OF CONTROL

EQUIPMENT IN ACCORDANCE WITH NFPA 72.

E. DO NOT LOCATE MONITOR AND CONTROL MODULES IN

HANGAR BAY.

F. REFER TO MECHANICAL PLANS FOR EXACT LOCATION OF

DUCT SMOKE DETECTORS AND HVAC RETURN AIR UNITS

OVER 2000 CFM.

G. EQUIPMENT INCLUDING FIRE ALARM DEVICES IN THE

HANGAR BAY AND ROOMS WITH DOORS TO THE HANGAR

BAY SHALL BE RATED FOR CLASS I DIV II UNLESS LOCATED

MORE THAN 18" ABOVE FINISHED FLOOR.

H. THE HANGAR BAY SHALL BE EQUIPPED WITH NEMA 250

TYPE 4 WALL-MOUNTED DEVICES. CONDUIT AND

JUNCTION BOXES SHALL BE WATERTIGHT.

I. PROVIDE FIRE ALARM MASS NOTIFICATION CONTROL

PANEL COMPATIBLE WITH BASE WIDE SIMPLEX SYSTEM.

J. CONTRACTOR IS RESPONSIBLE FOR OBTAINING FINAL

FLAME DETECTOR LAYOUT FROM DET-TRONICS.

GENERAL NOTES KEYED NOTES

5.109 INSTALL FIRE ALARM BELL ABOVE FDC.

5.110 WET-PIPE RISER TAMPER AND FLOW SWITCH.

5.114 SPRINKLER RISER ROOM TEMPERATURE

MONITORING.

5.117 DIRECTIONAL LOUDSPEAKERS WITH A MINIMUM

SOUNDPOWER OF 90 dBA DIRECTED TOWARDS

HANGAR BAY DOOR ONLY.

5.119 PROVIDE DISABLE SWITCH FOR FIRE ALARM

NOTIFICATION APPLIANCE TO PREVENT MICROPHONE

FEEDBACK DURING TESTING.

5.120 MAIN SYSTEM OS&Y ISOLATION VALVE.

5.125 PROVIDE KNOX BOX WITH TAMPER SWITCH

CONNECTED TO THE FIRE ALARM SYSTEM.

5.126 SHUT DOWN HVLS FANS UPON BUILDING ALARM.

5.127 AUTOMATIC GAS SHUT OFF.

5.130 RATE ALL FIRE ALARM DEVICES AND CONDUIT

LOCATED IN EXTERNAL FUEL TANK 119 AND

EXTERNAL FUEL TANK OFFICE/ TOOL STORAGE 115

FOR CLASS I DIV II IN ACCORDANCE WITH NFPA 70.

5.159 RELEASING SERVICE FIRE ALARM CONTROL UNIT.

5.160 RSFACU MONITORING MODULES.

5.161 HANGAR BAY TEMPERATURE MONITORING.

12/16/22 TYPE B3 FINAL

HEF MOD

ALARM SIGNALS

MANUAL FIRE ALARM PULL STATION

SMOKE DETECTOR

WATERFLOW SWITCH

RSFACU ALARM SIGNAL

SUPERVISORY SIGNALS

AU

D

IO

-V

IS

U

AL

F

IR

E

AL

AR

M

IN

D

IC

AT

IO

N

AU

D

IO

-V

IS

U

AL

C

O M

M O

N S

U

PE

R

VI

SO

R

Y

IN

D

IC

AT

AU

IO

-V

IS

U

AL

C

O M

M O

N T

R O

U

BL

E

IN

D

IC

AT

IO

N

FI

R

E

AL

AR

M

S

IG

N

AL

B Y

D

EV

IC

E

TY

PE

C O

M M

O N

F

IR

E

AL

AR

M

S U

PE

R

VI

SO

R Y

SI

G

N

AL

C O

M M

O N

F

IR

E

AL

AR

M

T R

O U

BL

E

SI

G

N

AL

COMMON SUPERVISORY SIGNAL BY DEVICE

DUCT SMOKE/CARBON MONOXIDE

DETECTOR

RSFACU COMMON SUPERVISORY SIGNAL

ANNUNCIATION AT FMCP TRANSMIT SIGNALS TO

RECEIVING STATION

SH

U

T D

O W

N A

SS

O

C

IA

TE

D

F

AN

(S

AUXILIARY FUNCTIONS NOTIFICATION/

EVACUATION SIGNALS

AC

TI

VA

TE

E

XT

ER

IO

R W

AT

ER

FL

O

W

AL

AR

M B

EL

L

IN

IT

IA

TE

G

EN

ER

AL

F

IR

E

AL

AR

M

/M N

S

AU

D

IB

LE

/V

IS

IB

LE

N

O

TI

FI

C

AT

IO

N A

PP

LI

AN

C

ES

OPTICAL FLAME DETECTION INHIBITED

SUPERVISORY FROM RSFACU

SH

U

T D

O W

N H

VL

S

FA

N

S

IN

H

AN

G

AR

B

AY

KNOX BOX

AU

D

IO

-V

IS

U

AL

S

U

PE

R

VI

SO

R

Y

IN

D

IC

AT

FO

R

F A

O

VE

R R

ID

E

BY

M

N S

SU

PE

R

VI

SO

R

Y

SI

G N

AL

F

O R

F A

O

VE

R R

ID

E

BY

M

N S

SH

U

T O

FF

G

AS

IN

H

AN

G

AR

TE

M

PO

R

AR

IL

Y O

VE

R

R

ID

E

TH

E

FI

R E

AL

AR

M A

U D

IB

LE

M

ES

SA

G

E

C

AR

BO

N

M O

N O

XI

D

E D

ET

EC

ET

AC

TI

VA

TI

O N

CARBON MONOXIDE DETECTOR

C

AR

BO

N

M O

N O

XI

D

E

AL

AR

M

S

IG

N

AL

IN

IT

IA

TE

F

IR

E C

AR

BO

N M

O N

O

XI

D E

PR

E-

R

EC

O R

D

ED

M

ES

SA

G

E

AN

D S

TR

O

BE

S

IN

IT

IA

TE

F

IR

E

AL

AR

M

S

PE

AK

ER

S O

N

LY

C

LO

SE

A

SS

O

C

IA

TE

D

F

IR

E/

SM

KE

AM

PE

R

TR

AN

SM

IT

A

LA

R M

S

IG

N

AL

T O

B M

S

AC

TI

VA

TE

H

AN

G

AR

B

AY

F

IR

E

AL

AR

M

M

ES

SA

G E

AC

TI

VA

TE

A C

TI

VE

S H

O O

TE

R

M

ES

SA

G

E

TEMPERATURE MONITOR

FUEL CONTAINMENT TANK 5% OF

VOLUME EXCEEDED

A

TROUBLE SIGNALS

SIGNALING LINE CIRCUIT OPEN

SIGNALING LINE CIRCUIT SHORT

SIGNALING LINE CIRCUIT GROUND

FACP CIRCUIT FAULT

FACP SUPERVISED COMPONENT FAILURE

FACP AC POWER FAILURE

FACP LOW BATTERY VOLTAGE

NOTIFICATION APPLIANCE CIRCUIT SHORT

MNS MESSAGE VIA TELEPHONE

MNS PRE-RECORDED MESSAGE

CONCURRENT FA AND MNS ALARM

GENERAL PAGING

ACTIVE SHOOTER BUTTON ON FMCP OR LOC

MASS NOTIFICATION SYSTEM (MNS) SIGNALS

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

6/ 2/

:1

6:

P M

C :\U se rs

\B

EN

.S H

AF

FE

R \D oc um en ts

\3

-1

8.

-F

-C en tra l-2

0_

BE

N

.S H

AF

FE

R .rv t

M

IC

H

IG

AN

A

IR

N

AT

IO

N

AL

G U

AR

D

W

IL

BU

R W

R

IG

H T

BL

VD

H

AR

R

IS

O

N T

W P, M

IC

H

IG

AN

AD

AL

F U

EL

C

EL

L

C

O R

R O

SI

O

N C

O N

TR

O

L -B

LD

G

F-602

FIRE ALARM

FUNCTIONAL MATRIX

VGLZ162323ANG NO.:

3141700-184848.01

RAB

RDV

December 16, 2022

RAB

NTS1 FIRE ALARM FUNCTIONAL MATRIX

FIRE ALARM/MNS GENERAL NOTES

A. FOR FIRE PROTECTION GENERAL NOTES, LEGEND, &

ABBREVIATIONS, SEE SHEET F-001.

12/16/22 TYPE B3 FINAL

FIRE ALARM / MASS

NOTIFICATION SYSTEM

CONTROL PANEL (FMCP)

BATTERIES

G

EN

EE

R L

AL

AR

M S

IG

N

AL

M M M

RSFACU

M

SIGNALING

LINE CIRCUIT

DEDICATED

120V CIRCUIT TVSS

M M

TELEPHONE

CONNECTION

EXTERIOR FIRE ALARM

BELL CIRCUIT

C O

M M

O N

S U

PE

R

VI

SO

R Y

SI

G

N

AL

C O

M M

O N

T R

O U

BL

E

SI

G

N

AL

M

NOTIFICATION

APPLIANCE CIRCUIT

x1 x17 x14 x6

O

PT

IC

AL

F

LA

M E

D

ET

EC

TO

IN

H

IB

IT

ED

S

U

PE

R

VI

SO

R

Y

REMOTE POWER SUPPLY

DEDICATED

120V CIRCUIT TVSS

x10 F x2

NOTIFICATION APPLIANCE

CIRCUIT

x9

WP

REMOTE

ANNUNCIATOR

RADIO

TRANSMITTER

DEDICATED

120V CIRCUIT TVSS

C

H

VL

S

FA

N S

H U

T D

O W

N

M

FU

EL

C O

N

TA

IN

M

EN

T

TA

N

K

LE

VE

L

M

TE

M

PE

R

AT

U

R E

M O

N

IT

O R

IN

G

S

EN

SO

R

RTS

D x3 C

H

VA

C U

N

IT

S H

U

TD

O W

N x3x2

NOTIFICATION APPLIANCE

CIRCUIT

x9

TO BUILDING MANAGEMENT

SYSTEM (BMS/EMSC). REFER

TO MECH. PLANS FOR

LOCATION

NOTIFICATION APPLIANCE

CIRCUIT

x4

DIRECTIONAL LOUD SPEAKERS

CO

x3

RTS

FMCP RADIO TRANSMITTER SCHEDULE

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

ALARM - MANUAL FIRE ALARM STATION

ALARM - WATERFLOW

ALARM - RSFACU ALARM SIGNAL

ALARM - SMOKE DETECTOR

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

ALARM - CARBON MONOXIDE

SUPERVISORY - COMMON SUPERVISORY

TROUBLE - COMMON TROUBLE

TROUBLE - MNS OVERRIDE OF FA SYSTEM

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SUPERVISORY - OPTICAL FLAME DETECTION INHIBITED

SPARE

TO FIRE

STATION 859

x1

D

CO

x3

WP

x2 x3

WP

x1

WP

SPARE

SPARE

SPARE

x3

SPARE

EOL

EOL

EOL

EOL

EOL

A

A

A

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

6/ 2/

:1

6:

P M

C :\U se rs

\B

EN

.S H

AF

FE

R \D oc um en ts

\3

-1

8.

-F

-C en tra l-2

0_

BE

N

.S H

AF

FE

R .rv t

M

IC

H

IG

AN

A

IR

N

AT

IO

N

AL

G U

AR

D

W

IL

BU

R W

R

IG

H T

BL

VD

H

AR

R

IS

O

N T

W P, M

IC

H

IG

AN

AD

AL

F U

EL

C

EL

L

C

O R

R O

SI

O

N C

O N

TR

O

L -B

LD

G

F-603

FIRE ALARM SYSTEM

RISER DIAGRAM

VGLZ162323ANG NO.:

3141700-184848.01

RAB

RDV

December 16, 2022

RAB

NTS1 FIRE ALARM/ MNS RISER DIAGRAM

GENERAL NOTES

A. FOR FIRE PROTECTION GENERAL NOTES, LEGEND, &

ABBREVIATIONS, SEE SHEET F-001.

B. THE CONTRACTOR SHALL PROVIDE DETAILED POINT TO

POINT WIRING DIAGRAMS WITH UNIQUE DEVICE NAMES

FOR EACH FIRE ALARM DEVICE.

C. EACH NOTIFICATION APPLIANCE CIRCUIT SHALL INCLUDE

A MINIMUM 25% SPARE CAPACITY.

D. ALL TVSS SHALL BE UL 1449 AND UL 1263 LISTED.

12/16/22 TYPE B3 FINAL

FIRE ALARM CONTROL

PANEL (FACP)

BATTERIES

SIGNALING

LINE CIRCUIT

DEDICATED

120V CIRCUIT TVSS

M M

EXTERIOR FIRE ALARM

BELL CIRCUIT

M x1 x14x2 F

RADIO

TRANSMITTER

DEDICATED

120V CIRCUIT TVSS

NOTIFICATION APPLIANCE

CIRCUIT

x2

M

K

TO FIRE

STATION 859

SIGNALING

LINE CIRCUITM

x3

TVSSTVSS

TANK MONITOR

MODULES

CO

x2

M x3

HEAT TRACE MONITOR

MODULES

H

M M M M M

FI

R

E

PU

M P

R U

N N

IN

G

LO

SS

O F

PH

AS

E

PH

AS

E R

EV

ER

SA

L

C O

N

TR

O

LL

ER

C

O N

N

EC

TE

D

T O

A

LT

ER

N

AT

E

SO

U

R C

E

AL

TE

R N

AT

E

SO

U

R C

E C

IR

C

U

IT

B R

EA

KE

R O

PE

N

C O

M M

O N

T R

O U

BL

E

FIRE PUMP

CONTROLLER

M M M M M M

FI

R

E

PU

M P

R U

N N

IN

G

LO

SS

O F

PH

AS

E

PH

AS

E R

EV

ER

SA

L

C O

N

TR

O

LL

ER

C

O N

N

EC

TE

D

T O

A

LT

ER

N

AT

E

SO

U

R C

E

AL

TE

R N

AT

E

SO

U

R C

E C

IR

C

U

IT

B R

EA

KE

R O

PE

N

C O

M M

O N

T R

O U

BL

E

FIRE PUMP

CONTROLLER

A

EOL

EOL

A

A

A

SHEET NO.:

SHEET CONTENTS

DO NOT SCALE DRAWINGS

M&H NO.:

DATE:

DESIGNED BY:

DRAWN BY:

CHECKED BY:

ISSUED

© Copyright This document, or any portion thereof, shall not be duplicated, disclosed, or used on any other project or extension of this project except by written agreement with Mead & Hunt, Inc. Mead & Hunt shall not be responsible for any unauthorized use of, or alteration to these documents.

710 Avis Drive, Suite 100, Ann Arbor, MI 48108 phone: 810-956-9300

6/ 2/

:1

8:

P M

C :\U se rs

\B

EN

.S H

AF

FE

R \D oc um en ts

\3

-1

8.

-F

-F P-

C en tra l-2

0_

BE

N

.S H

AF

FE

R .rv t

M

IC

H

IG

AN

A

IR

N

AT

IO

N

AL

G U

AR

D

W

IL

BU

R W

R

IG

H T

BL

VD

H

AR

R

IS

O

N T

W P, M

IC

H

IG

AN

AD

AL

F U

EL

C

EL

L

C

O R

R O

SI

O

N C

O N

TR

O

L -B

LD

G

F-605

B158 FIRE ALARM

SYSTEM RISER

DIAGRAM

VGLZ162323ANG NO.:

3141700-181848.01

RAB

RDV

December 16, 2022

RAB

NTS1 FIRE ALARM RISER DIAGRAM

A. FOR FIRE PROTECTION GENERAL NOTES, LEGEND, &

ABBREVIATIONS, SEE SHEET F-001.

B. ACTUAL NUMBER OF DEVICES PER NOTIFICATION

APPLIANCE CIRCUT SHALL BE DETERMINED BY THE

FIRE ALARM CONTRACTOR'S DETAILED VOLTAGE AND

BATTERY DROP CALCULATIONS.

C. THE CONTRACTOR SHALL PROVIDE DETAILED POINT

TO POINT WIRING DIAGRAMS WITH UNIQUE DEVICE

NAMES FOR EACH FIRE ALARM DEVICE.

D. EACH NOTIFICATION APPLIANCE CIRCUIT SHALL

INCLUDE A MINIMUM 25% SPARE CAPACITY.

E. ALL TVSS SHALL BE UL 1449 AND UL 1263 LISTED.

F. PROVIDE FIRE ALARM CONTROL PANEL COMPATIBLE

WITH BASE WIDE SIMPLEX SYSTEM.

GENERAL NOTES

12/16/22 TYPE B3 FINAL

ADAL Fuel Cell & Corrosion Control, Bldg. 154

VGLZ162323

ADDENDUM 01

02 JUN 2023

PROJECT TABLE OF CONTENTS Page 1

PROJECT TABLE OF CONTENTS

VOLUME 1

DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS

00 31 32 GEOTECHNICAL DATA

00 31 32A GEOTECHNICAL REPORT

00 31 33 LAND USE AND SOIL CONTROL DOCUMENTATION

00 31 33A SOIL RELOCATION GUIDANCE FOR SELFRIDGE ANGB

00 31 33B CROCK WELLS AND GROUNDWATER WELLS GUIDANCE FOR

SELFRIDGE ANGB

00 31 33C FINAL DD – SITE 7

00 31 33D 2003JUNE20 – IRP SITES 3, 6, 7, 9, 12, 13, 15, 19,

31, AND 36

DIVISION 01 - GENERAL REQUIREMENTS

01 00 00 GENERAL REQUIREMENTS

SUPPLEMENT 1 – VETTING FORM

SUPPLEMENT 2 – SUBMITTAL REGISTER

SUPPLEMENT 3 – AF FORM 3000 – MATERIAL APPROVAL SUBMITTAL

SUPPLEMENT 4 – REQUEST FOR INFORMATION

SUPPLEMENT 5 – AF FORM 3064 – CONTRACT PROGRESS SCHEDULE