This is a maintenance issues inventory spreadsheet documenting alarm system failures and problems across multiple buildings at Otis Air National Guard Base. The spreadsheet lists specific security and alarm devices by building location (Buildings 100, 101, 104, 155, 162, 168, 165, 330), including alarm identification numbers, device types and manufacturers (Honeywell, Bosch, BMS Sentrol), and associated maintenance issues. Critical problems documented include full communication failures in Vindicator systems at Buildings 100 and 101 that persist despite multiple technician visits and resets, discontinued product models (Honeywell Tuxedo Keypad, Honeywell IS-280 Motion Sensor, BMS Sentrol 2707A-L) creating long-term serviceability concerns, intermittent communication failures affecting building security posture, and various sensor failures including motion detectors, duress pins, and keypads. The spreadsheet identifies primary and alternate Site Security Officers (SSOs) for each location and documents troubleshooting steps attempted, such as hard resets, system timing adjustments, and power cycling. Notable constraints include a command decision to defer $20K Vindicator maintenance vendor visit pending execution of a formal maintenance contract, and licensing restrictions preventing unauthorized technicians from servicing Vindicator equipment. This inventory directly supports the federal maintenance contract opportunity (W50S80-26-Q-0023) for Vindicator maintenance services at Otis Air National Guard Base with an anticipated performance period starting September 1, 2026.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Bldg 100 + 101

Device TypeMake/ModelALARM ID #Location DescriptorBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot StepsComments
SEC/ACC KeypadHoneywell Tuxedo Keypad301B-100 Munitions Inside Bunker100102nd LRSMr. Steven MirandaTSGT DEWITTFULL COMM FAIL; WILL NOT RESTORE; POWER DISTRO BOX NOT LIGHTINGPOWER ON/OFF BREAKER AND PANEEL. NO CHANGE. HAD SECURITY 101 OUT HERE TWICE, STILL IN FAILURE.Keypad is non operational. **THIS PRODUCT IS DISCONTINUED**
BMSSentrol 2707A-L302B-100 Munitions Inside Bunker100102nd LRSMr. Steven MirandaTSGT DEWITT****Both 100/101 have consitantly been in and out of full communication failure. I have been able to restore 100/101 only twice, and they go back into communication failure within 24 hrs of reset. I have had a technichian out here two separate times, each not being able to restore comms or not allowed to touch Vindicator Equipment due to licencing requirements. Still reaching out to other companies for troubleshooting / awaiting Maint. Contract. CC does not want to spend 20K for Vin to come out, wants to wait for Maint. Contract
PIRHoneywell IS-280 Ceiling Mount Motion Sensor303B-100 Munitions Inside Bunker100102nd LRSMr. Steven MirandaTSGT DEWITT******PRODUCT DISCONTINUED FOR PRODUCTION**
Duressunknown304B-100 Munitions Inside Bunker100102nd LRSMr. Steven MirandaTSGT DEWITT****unknown model
Low BatteryStandard308B-100 Munitions Inside Bunker100102nd LRSMr. Steven MirandaTSGT DEWITT****
AC FailStandard309B-100 Munitions Inside Bunker100102nd LRSMr. Steven MirandaTSGT DEWITT****
TamperStandard310B-100 Munitions Inside Bunker100102nd LRSMr. Steven MirandaTSGT DEWITT****
SEC/ACC KeypadHoneywell Tuxedo Keypad311B-101 Munitions Inside Bunker101102nd LRSMr. Steven MirandaTSGT DEWITT****Keypad is non operational. **THIS PRODUCT IS DISCONTINUED**
BMSSentrol 2707A-L312B-101 Munitions Inside Bunker101102nd LRSMr. Steven MirandaTSGT DEWITT****
PIRHoneywell IS-280 Ceiling Mount Motion Sensor313B-101 Munitions Inside Bunker101102nd LRSMr. Steven MirandaTSGT DEWITT******PRODUCT DISCONTINUED FOR PRODUCTION**
Duressunknown314B-101 Munitions Inside Bunker101102nd LRSMr. Steven MirandaTSGT DEWITT****unknown model
Low BatteryStandard318B-101 Munitions Inside Bunker101102nd LRSMr. Steven MirandaTSGT DEWITT****
AC FailStandard319B-101 Munitions Inside Bunker101102nd LRSMr. Steven MirandaTSGT DEWITT****
TamperStandard320B-101 Munitions Inside Bunker101102nd LRSMr. Steven MirandaTSGT DEWITT****

Bldg 104 rm 8

Device TypeMake/ModelALARM ID #Location DescriptorBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot StepsComments
Sec/ACCHoneywell Tuxedo Keypad421B-104 Rm 8104 RM 8102d Comm SqMSGT PELLETIERSSGT UHOMOIBHIDELAY ON INTRUSION ALARMS, OVER 40 SEC BEFORE IT ACTIVATESCHANGED FROM DELAYED TO STANDARD IN DRAKE IDS SYS; STILL NOT ACTIVATING ASAPDelay issues will auto resolve and then re occur randomly. Reset and power cycled each time as well as system timing changes in SmartPak. Keypad is operational but product is discontinued
BMSSentrol 2707A-L422B-104 Rm 8 Main Dr Left104 RM 8102d Comm SqMSGT PELLETIERSSGT UHOMOIBHIDELAY ON INTRUSION ALARMS, OVER 40 SEC BEFORE IT ACTIVATESCHANGED FROM DELAYED TO STANDARD IN DRAKE IDS SYS; STILL NOT ACTIVATING ASAPDelay issues will auto resolve and then re occur randomly. Reset and power cycled each time as well as system timing changes in SmartPak.
BMSSentrol 2707A-L423B-104 Rm 8 Main Dr Right104 RM 8102d Comm SqMSGT PELLETIERSSGT UHOMOIBHIDELAY ON INTRUSION ALARMS, OVER 40 SEC BEFORE IT ACTIVATESCHANGED FROM DELAYED TO STANDARD IN DRAKE IDS SYS; STILL NOT ACTIVATING ASAPDelay issues will auto resolve and then re occur randomly. Reset and power cycled each time as well as system timing changes in SmartPak.

Bldg 155 WPNS VAULT

Device TypeMake/ModelALARM ID #Location DescriptorBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot StepsComments
PIRBosch DS9370 Series panoramic TriTech Detector1572155 ARMAG PIR155102D LRSTSGT KINGMSGT BORGESIntermittent Comm fails, Will usually self resolve. VCC at BDOC will also report COMM FAIL but Keypad at 155 Armag Panel is showing Green and Secure. PIR # 1572 is delayed on activation occasionally, it is random (rear PIR)Hard panel reset. Alarms will reset and continue normal ops. Randomly will experience issues.Site commander is no longer in production.
DURESS PINStandard1585155 ARMAG DURESS PIN155102D LRSTSGT KINGMSGT BORGESDuress Pin will sometimes not clear on BDOC end or Site Commander. (fixed)Hard panel reset. Alarms will reset and continue normal ops. Randomly will experience issues

Bldg 155 SIPR

Device TypeMake/ModelALARM ID #Location DescriptorBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot StepsComments
DURESS PINStandard1565Rm 124 DURESS PIN155102ND LRSSMSGT JACOBSCAPT MONTGOMERYDURESS ALARM WILL NOT RESETINPUTTING IN CODE AGAIN WITH # MULTIPLE RETRYS. HARD RESET OF PANEL MUTLIPLE TIMES, WILL NOT CLEAR.Keypad Duress. Keypad is no longer in production.

Bldg 162

ALARM ID #Location DescriptorAlarm Point on DeviceBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot StepsComments
162102ND CSMSGT KRUGERMR ALLENNo reported Issues to ESS

Bldg 168

Device TypeMake/ModelALARM ID #Location DescriptorBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot StepsComments
SEC/ACC KeypadHoneywell AFL08A501DGS SEC/ACC168102D ISRGANDREA MEDEIROSMSGT REESERFULL COMM FAILKEYPAD IS GOING TO BE REPLACED; NOT SURE IF IT WILL RESET THE OTHER COMMS ASSOCIATED WITH ITIntermittent Comm fails, Will usually self resolve. VCC at BDOC will also report COMM FAIL but VCC at 168 Panel is showing Green and Secure
PIRBosch DS9370 Series panoramic TriTech Detector538Rm 127 PIR168102D ISRGANDREA MEDEIROSMSGT REESERFULL COMM FAILPIR alarm point will not clear. MSgt Reeser has done hard reset on associated panel. Still troubleshooting on his endIntermittent Comm fails, Will usually self resolve. VCC at BDOC will also report COMM FAIL but VCC at 168 Panel is showing Green and Secure

Bldg 165 OPS FLOOR

Device TypeMake/ModelALARM ID #Location DescriptorBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot Steps
PIRHoneywell 316-30812-001819SCIF Rm 141 PIR165202 ISRGTSGT SPONSLERIssue with PIR, changed settings moved printer, still false alarms occasionally. Command is aware and assumes risk on that point only until Maint. Team can assessSSO has done internal troubleshooting and environmental changes to assist in PIR activation; still will randomly activate

Bldg 330 CRYPTO VAULT

Device TypeMake/ModelALARM ID #Location DescriptorBldg #SquadronPrimary SSOAlternate SSOMaint IssueTroubleshoot StepsComments
SEC/ACC KeypadHoneywell Tuxedo Keypad951B-330 Open Storage Area330253 CEIGMSGT WHITEMSGT NADEUMESSAGE DISPLAY BOX WILL NOT CLOSE; COVERING PANEL KEYSPOWER ON/OFF- STILL APPEARS AFTER REBOOTKeypad is partially operational, error message "cannot connect to panel" obstructs number pad, users are still able to push numbers beneath it. Attempted multiple resets, still ongoing issue, access to facility remains uninterrupted. **THIS PRODUCT HAS BEEN DISCONTUNED**