B632_Addendum_1_Narrative_20260811.pdf

PDF 109 KB Posted

Attached to
Repair B632, Fire Suppression and Hangar Door
Solicitation number
W50S7T26BA004
Issued by

About this file

This is an addendum to specifications and drawings for the 182nd Airlift Wing, Peoria Air National Guard Building 632 Repair of Fire Suppression and Hangar Doors contract, issued August 7, 2026.

The addendum makes multiple specification revisions across several sections. In Section 05 12 00, two ASTM references (F1136/F1136M and F2833) are deleted. Section 05 50 13 undergoes substantial revisions, including deletion of seven welding and aluminum-related standards (AA DAF45, AWS D1.2/D1.2M, ASTM B26/B26M, B108/B108M, B209/B209M, B221, B221M), complete removal of welder qualification requirements, deletion of aluminum alloy product specifications, removal of aluminum surface treatment paragraphs, and deletion of the second sentence in the Dissimilar Metals section. Similar aluminum and welding-related deletions apply to Section 05 50 33. Section 08 34 16.20 removes requirements for belt/wire rope system specifications and backup door operation procedures. Section 26 32 15 changes the engine-generator frequency parameter from 50 Hz to 60 Hz. New requirements are added to Section 26 36 23 for a camlock docking station assembly supporting full-capacity portable load bank testing at 1200A, 480V, 3-phase, with NEMA 4X stainless steel pad-mounted enclosure, shunt trip circuit breaker, female camlock configuration, and specified outlet configurations. Section 28 31 70 removes audible notification appliance and horn requirements while revising visual notification appliances to reference "Fire" instead of "Alert." Revised drawings effective August 8, 2026 accompany this addendum covering fire alarm, electrical, and related building systems.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

The Power of Commitment

12607256 | B632 Addendum 1 Narrative 1

182ND AIRLIFT WING, PEORIA AIR NATIONAL GUARD

BUILDING 632 REPAIR OF FIRE SUPPRESSION AND HANGAR DOORS

Addendum 1

August 7, 2026

Change Change Format

Specifications

Revise Paragraph Section 05 12 00

1.1 References

Delete “ASTM F1136/F1136M”

Delete “ASTM F2833”

Revise Paragraph Section 05 50 13

1.1 References

Delete “AA DAF45”

Delete “AWS D1.2/D1.2M”

Delete “ASTM B26/B26M”

Delete “ASTM B108/B108M”

Delete “ASTM B209/B209M”

Delete “ASTM B221”

Delete “ASTM B221M”

Revise Paragraph Section 05 50 13

1.3.b Qualification of Welders

Delete paragraph in its entirety.

Revise Paragraph Section 05 50 13

2.1.9 Aluminum Alloy Products

Delete paragraph in its entirety.

Revise Paragraph Section 05 50 13

2.2.6 Aluminum Surfaces

Delete paragraph in its entirety including subparagraphs 2.2.6.1 and

2.2.6.2

Revise Paragraph Section 05 50 13

3.6 Dissimilar Metals

12607256 | B632 Addendum 1 Narrative 2

Delete second sentence in its entirety.

Revise Paragraph Section 05 50 33

1.1 References

Delete “AA DAF45”

Delete “ASTM B26/B26M”

Delete “ASTM B108/B108M”

Delete “ASTM B209/B209M”

Delete “ASTM B221”

Revise Paragraph Section 05 50 33

2.2.5 Aluminum Alloy Products

Delete paragraph in its entirety.

Revise Paragraph Section 05 50 33

2.3.6 Aluminum Surfaces

Delete paragraph in its entirety including subparagraphs 2.3.6.1 and

2.3.6.2

Revise Paragraph Section 05 50 33

3.5.1 Dissimilar Metals

Delete second sentence in its entirety.

Revise Paragraph Section 08 34 16.20

2.3.2 Belt/Wire Rope System

Delete second paragraph in its entirety.

Revise Paragraph Section 08 34 16.20

2.9.3 Backup Door Operation

Delete paragraph in its entirety.

Revise Paragraph Section 26 32 15

2.1.1 Engine-Generator Parameter Schedule

Under Frequency, replace “50 Hz” with “60 Hz”

New Paragraph Section 26 36 23

1.2 Submittals

Insert “Camlock Docking Station Drawings; G” under SD-02 Shop

Drawings

New Paragraph Section 26 36 23

Insert

12607256 | B632 Addendum 1 Narrative 3

“2.6 Camlock Docking Station for Portable Load Bank Test

2.6.1 Provide camlock docking station assembly to allow for full capacity portable load bank generator test under all operating conditions and connection for temporary source.

2.6.2 The docking station connection point shall be mechanically interlocked or otherwise designed to prevent inadvertent energization during load bank connection, and shall comply with NFPA 70, NFPA 70E, and UFC 3-540-01 requirements for safe temporary equipment connection and maintenance access.

2.6.3 Provide docking station assembly rated for the full generator output capacity with following parameters:

a. 1200A at 480 V, 3 phase 4 wires.

b. Enclosure – Pad mounted, NEMA 4X Stainless Steel.

c. Shunt trip circuit breaker on load bank connection with LSIA and ERMS.

d. Camlock configuration – Female type. Verify with final user prior to placing the order

e. Two-wire auto start.

f. Battery charger outlet, 120V, 20A, GFI protected.

g. Convenience outlet, 120V, 20A, GFI protected.

h. Block heater outlet, 120V, 30A L5-30.

i. Strip heater and thermostat.”

New Paragraph Section 26 36 23

Insert

“3.5 3.5 CAMLOCK DOCKING STATION

Install camlock docking station on the concrete pad.

a. Demonstrate functionality of the manual transfer switch and circuit breaker while load bank is connected to the camlocks.

b. Test strip heater and convenience outlet while the generator is running.”

Delete Paragraph Section 28 31 70

2.10.1 Audible Notification Appliances

Delete this paragraph in its entirety.

Delete Paragraph Section 28 31 70

2.10.1.1 Horns

Delete this paragraph in its entirety.

Revise Paragraph Section 28 31 70

2.10.2 Visual Notification Appliances

In the second sentence replace “Alert” with “Fire”.

12607256 | B632 Addendum 1 Narrative 4

Change Change Format

Drawings

Revise Drawing The following drawings are revised as of August 8, 2026:

Sheet No:

G-001 Cover Sheet

FA-001 Fire Alarm Symbols, Legend, Abbreviations and Notes

FA-111 Floor Plan

FA-401 Enlarged Plans & Sections

FA-601 Fire Alarm Matrix & Riser Diagram

FX-111 Floor Plan

E-001 Reference Sheet – Electrical

E-111 Power Plan

E-113 Partial Site Plan

E-501 Partial Single Line Diagram

These revised drawings accompany this Addendum