B632_Addendum_1_Drawings_20260811.pdf

PDF 2 MB Posted

Attached to
Repair B632, Fire Suppression and Hangar Door
Solicitation number
W50S7T26BA004
Issued by

About this file

This is a Type B3 100% Final Submittal design document for the 182nd Airlift Wing, Peoria Air National Guard, Building 632 Repair of Fire Suppression and Hangar Doors, dated March 27, 2026, Project Number JLQN202002.

The project encompasses comprehensive repairs and installations for Building 632 at the Peoria Air National Guard facility. The scope includes: (1) fire alarm system design with addressable initiating devices and notification appliances throughout the building, utilizing existing Mass Notification System speakers for voice evacuation; (2) fire suppression system installation in the hangar with AFFF (Aqueous Film-Forming Foam) capability, hydraulically calculated to deliver 0.20 GPM/sq.ft. over 5,000 sq.ft., connected to existing 8" underground pipe, including an 8" vertical sprinkler zone control assembly with supervisory switches and check valves; (3) electrical work including removal of existing hangar door equipment, provision of safety disconnects, power supply to new equipment, task lighting on catwalk, emergency generator installation, automatic transfer switch, generator grounding, and service conductors; and (4) hangar door replacement with associated control systems. The submittal includes detailed floor plans, fire alarm riser diagrams, sprinkler system layout, electrical power and grounding plans, single-line diagrams, duct bank schedules, generator specifications (750kW/900kVA standby rated at 277/480V), and equipment schedules. The design documents reference compliance with UFC 4-211-01, NFPA standards, and current NEC provisions. All drawings are prepared by GFD and GFT and include comprehensive keynotes, general notes, and abbreviation/symbol legends for construction administration.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

SHEET LIST

AREA MAP LOCATION MAP

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/7/2026 10:59:02 AM C:\Users\YTAN6\Documents\Revit 2024 Local Files\12607256-GHD-632-IMP-MDL-FA-R24_YinZhet.Tan_GVUXBKFGRZCS.rvt

G-001

BLDG 632 - COVER SHEET

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

182ND AIRLIFT WING, PEORIA AIR NATIONAL GUARD

BUILDING 632 REPAIR OF FIRE SUPPRESSION AND HANGAR DOORS

TYPE B3 - 100% FINAL SUBMITTAL

MARCH 27, 2026

PROJECT NUMBER: JLQN202002

JLQN202002 MARCH 27, 2026

IS

TG

ACJ

ACJ

YZT

YZT

TYPE B3 - 100% FINAL SUBMITTAL

DRAWING INDEX - 632

PROJECT No. DRAWING TITLE

DRG NO.

SHEET

JLQN202002 A-001 ARCHITECTURAL ABBREVIATIONS & SYMBOLS

JLQN202002 A-002 GENERAL NOTES

JLQN202002 A-100 BLDG 632 DEMOLITION PLAN

JLQN202002 A-101 BLDG 632 FLOOR PLAN

JLQN202002 A-102 BLDG 632 CATWALK PLANS

JLQN202002 A-201 BLDG 632 ELEVATIONS

JLQN202002 A-301 BLDG 632 BUILDING SECTIONS

JLQN202002 A-401 BLDG 632 CATWALK SECTIONS

JLQN202002 A-501 BLDG 632 ARCHITECTURAL DETAILS

JLQN202002 S-001 BLDG 632 GENERAL STRUCTURAL NOTES

JLQN202002 S-002 BLDG 632 GENERAL STRUCTURAL NOTES

JLQN202002 S-003 SPECIAL INSPECTIONS TABLE

JLQN202002 S-010 TYPICAL STEEL DETAILS

JLQN202002 S-101 BLDG 632 FOUNDATION PLAN

JLQN202002 S-102 BLDG 632 CATWALK FRAMING REFERENCE PLAN

JLQN202002 S-103 BLDG 632 ROOF FRAMING PLAN

JLQN202002 S-201 BLDG 632 ELEVATION

JLQN202002 S-401 BLDG 632 CATWALK FRAMING PLANS AND SECTIONS

JLQN202002 S-501 BLDG 632 STRUCTURAL DETAILS

JLQN202002 S-502 BLDG 632 STRUCTURAL DETAILS

JLQN202002 S-503 BLDG 632 STRUCTURAL DETAILS

JLQN202002 S-701 BLDG 632 LOAD DIAGRAMS

JLQN202002 FA-001 BLDG 632 FIRE ALARM SYMBOLS, LEGEND, ABBREVIATIONS AND

NOTES

JLQN202002 FA-101 BLDG 632 DEMOLITION PLAN

JLQN202002 FA-111 BLDG 632 FLOOR PLAN

JLQN202002 FA-112 BLDG 632 CATWALK PLANS

JLQN202002 FA-401 BLDG 632 ENLARGED PLANS & SECTIONS

JLQN202002 FA-501 BLDG 632 FIRE ALARM DETAILS

JLQN202002 FA-601 BLDG 632 FIRE ALARM MATRIX & RISER DIAGRAM

JLQN202002 FX-001 BLDG 632 FIRE SUPPRESSION SYMBOLS, LEGEND, ABBREVIATIONS

AND NOTES

JLQN202002 FX-101 BLDG 632 DEMOLITION PLAN

JLQN202002 FX-111 BLDG 632 FLOOR PLAN

DRAWING INDEX - 632

PROJECT No. DRAWING TITLE

DRG NO.

SHEET

JLQN202002 FX-401 BLDG 632 ENLARGED PLANS & SECTIONS

JLQN202002 FX-501 BLDG 632 FIRE SUPPRESSION DETAILS

JLQN202002 E-001 REFERENCE SHEET - ELECTRICAL

JLQN202002 E-101 BLDG 632 DEMOLITION PLAN

JLQN202002 E-111 BLDG 632 POWER PLAN

JLQN202002 E-112 BLDG 632 LIGHTING PLAN

JLQN202002 E-113 BLDG 632 PARTIAL SITE PLAN

JLQN202002 E-201 BLDG 632 CATWALK SECTION VIEW

JLQN202002 E-501 BLDG 632 PARTIAL SINGLE-LINE DIAGRAMS

JLQN202002 E-502 BLDG 632 HANGAR NEW DOOR INTERCONNECTION DIAGRAM

JLQN202002 E-503 BLDG 632 LIGHTING AND PANEL SCHEDULES

JLQN202002 E-601 BLDG 632 ELECTRICAL DETAILS

PROJECT SITE

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

5 TYPE B3 (100%)SUBMITTAL IS 03-27-2026

1 PRE-BID INQUIRIES 08-07-2026

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/7/2026 10:57:32 AM C:\Users\YTAN6\Documents\Revit 2024 Local Files\12607256-GHD-632-IMP-MDL-FA-R24_YinZhet.Tan_GVUXBKFGRZCS.rvt

FA-001

BLDG 632 FIRE ALARM SYMBOLS,

LEGEND, ABBREVIATIONS AND

NOTES

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ACJ

ACJ

NIS

NIS

TYPE B3 - 100% FINAL SUBMITTAL

GENERAL NOTES

1.

A.

B.

C.

D.

E.

2.

3.

4.

A.

B.

C.

D.

5.

6.

7.

8.

9.

10.

11.

12.

A.

B.

C.

D.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

THE SCOPE OF THIS PROJECT INCLUDES DESIGNING AND PROVIDING A SIMPLEX FIRE ALARM SYSTEM AS DESCRIBED HEREIN FOR HANGAR B632 LOCATED AT PEORIA AIR

NATIONAL GUARD, ILLINOIS. THIS INCLUDES THE FOLLOWING:

REMOVE THE EXISTING AFFF RELEASING SYSTEM CONTROL PANEL AND APPLIANCES LOCATED THROUGHOUT THE BUILDING.

REMOVE FIRE ALARM DEVICES AND APPLIANCES LOCATED THROUGHOUT THE BUILDING INCLUDING HEAT DETECTORS, MANUAL PULL STATIONS, SMOKE DETECTORS, AFFF MANUAL RELEASE STATIONS, ASSOCIATED CONDUIT/CIRCUITS AND FIRE ALARM SIGNAGE.

PROVIDE FIRE ALARM SYSTEM AND APPLIANCES THAT ARE COMPATIBLE WITH EXISTING MASS NOTIFICATION SYSTEM.

PROVIDE TAMPER SWITCH AND WATERFLOW SWITCH TO SERVE THE OVERHEAD SPRINKLER SYSTEM IN THE HANGAR.

FIRE ALARM SYSTEM SHALL BE NETWORKED TO FIRE ALARM REPORTING SYSTEM VIA FIBER LOCATED IN BUILDINGS 541 (FIRE DEPARTMENT) AND 636 (SECURITY

BDOC).

THE SYSTEM MUST INCLUDE WIRING, RACEWAYS, PULL BOXES, TERMINAL CABINETS, OUTLET AND MOUNTING BOXES, CONTROL EQUIPMENT, INITIATING DEVICES, INTERFACE EQUIPMENT, AND OTHER ACCESSORIES AND MISCELLANEOUS ITEMS INCLUDING SOFTWARE, SYSTEM PROGRAMMING, TESTING AND CONSTRUCTION PERMITS REQUIRED FOR A COMPLETE OPERATING SYSTEM EVEN THOUGH EACH ITEM IS NOT SPECIFICALLY MENTIONED OR DESCRIBED. PROVIDE SYSTEM COMPLETE AND READY FOR OPERATION.

EXCEPT WHERE OTHERWISE NOTED ON THE CONTRACT DOCUMENTS. THE SYSTEM MUST COMPLY WITH UFC 3-600-01 WITH CHANGE 6, 05-09-2021, UFC 4-211-01 WITH CHANGE 3, 04-20-2021, NFPA STANDARDS 70 (2023), 72 (2025) AND 409 (2022). IN ADDITION, PROVIDE THE EQUIPMENT FROM A SINGLE MANUFACTURER AND LISTED FOR THE INTENDED PURPOSE BY A NATIONAL RECOGNIZED TESTING LABORATORY. CONTRACTOR IS RESPONSIBLE FOR THE SOFTWARE, SYSTEM PROGRAMMING, TESTING AND CONSTRUCTION PERMITS REQUIRED FOR A COMPLETE OPERATING SYSTEM AND SHALL SECURE ALL NECESSARY CONSTRUCTION PERMITS, INSPECTIONS AND FINAL SYSTEM ACCEPTANCE

FROM BUILDING OFFICIALS (AHJ).

PROVIDE WIRING FROM APPLIANCE TERMINAL TO APPLIANCE TERMINAL. PROVIDE CONDUCTORS THAT ARE TERMINATED, SPLICED, OR OTHERWISE INTERRUPTED IN ENCLOSURE, CABINET, MOUNTING, OR JUNCTION BOX CONNECTED TO SCREW-TYPE TERMINAL BLOCKS. WIRE NUTS AND SIMILAR DEVICES ARE PROHIBITED.

PROVIDE FIRE ALARM CIRCUITS SUPERVISED AS FOLLOWS IN ACCORDANCE WITH NFPA 72:

INITIATING DEVICE CIRCUITS (IDC) - CLASS B

SIGNALING LINE CIRCUITS (SLC) - CLASS B

NOTIFICATION APPLIANCE CIRCUITS (NAC) - CLASS B

PATHWAY SURVIVABILITY - LEVEL 1

LABEL ADDRESSABLE INPUT/OUTPUT FIRE ALARM COVER PLATES AND APPLIANCES (INCLUDING ADDRESSABLE MODULES) WITH THEIR ADDRESS UTILIZING A LABELING MACHINE. HAND WRITTEN LABELS MUST NOT BE USED. ADDRESS MUST INCLUDE SLC NUMBER FOLLOWED BY APPLIANCE NUMBER. EACH SLC FIELD APPLIANCE ADDRESS

MUST MATCH THE FIRE ALARM DISPLAY ADDRESS.

LABEL CONDUCTORS INDIVIDUALLY WITH PERMANENT MARKINGS. LABEL MUST BE PRINTED AND PERMANENTLY AFFIXED TO CONDUCTOR WITH SHRINK WRAP.

UNLESS NOTED OTHERWISE THE PROJECT ELECTRICAL CONDUIT STANDARD IS RIGID METALLIC CONDUIT (RMC) WITH THREADED FITTINGS AND PROVIDE THROUGHOUT THE PROJECT. REFERENCE TO CONDUIT IS EQUIVALENT TO STATING RMC. PROVIDE ALL WIRING IN CONDUIT. FLEXIBLE METAL CONDUIT IS LIMITED TO 6 FEET AND SECURED PER

THE NATIONAL ELECTRIC CODE.

PROVIDE CONDUIT AS UNOBTRUSIVELY AS POSSIBLE, AS CLOSE AS POSSIBLE TO FLOOR/ CEILING SLAB AND PARALLEL AND AT RIGHT ANGLES TO STRUCTURAL STEEL OR

CONCRETE ELEMENTS. THESE DRAWINGS ARE DIAGRAMMATIC TO SHOW DESIGN INTENT ONLY.

PROVIDE ELECTRICAL BOXES AS FOLLOWS: UNLESS NOTED OTHERWISE PROVIDE CAST METAL BELL TYPE BOXES WITH THREADED HUBS ON EXPOSED WORK, EXCEPT WHERE FACTORY BOXES ARE PROVIDED. CONCEALED BOXES MAY BE STAMPED STEEL BOXES. PROVIDE TERMINAL CABINETS OF SOLID WALL CONSTRUCTION WITH NO FACTORY

CONDUIT KNOCK OUTS.

CORE DRILL PENETRATIONS IN MASONRY WALLS AND FLOOR/CEILING SLABS.

AFTER CONDUIT INSTALLATION, ALL PENETRATIONS IN FIRE AND SMOKE RATED WALLS, CEILINGS AND FLOORS SHALL BE PROTECTED WITH UL LISTED THROUGH- PENETRATION FIRE-STOP SYSTEMS OF EQUAL OR GREATER FIRE RESISTANCERATING TO THE PENETRATING MEMBER. REFER TO ARCHITECTURAL AND/OR LIFE SAFETY DRAWINGS FOR FIRE (AND/OR SMOKE) RESISTIVE ASSEMBLY LOCATIONS AND RATINGS. PENETRATIONS INTO NON-FIRE-RESISTANCE RATED ASSEMBLIES SHALL BE SEALED TO

BE SMOKE-TIGHT AT A MINIMUM.

BOTH EXPOSED AND CONCEALED CONDUIT MUST UTILIZE COMPRESSION TYPE STEEL FITTINGS AND CONNECTORS. UNLESS NOTED OTHERWISE, PROVIDE CONDUIT 3/4 INCH MINIMUM TRADE SIZE. PROVIDE PLENUM RATED WIRING CONDUCTORS (TYPE FPLP) WHEN FLEX CONDUIT IS UTILIZED. PROVIDE WIRING UL LISTED FOR ITS INTENDED USE.

PROVIDE SOLID COPPER WIRING CONDUCTORS IN CONDUIT FOR THE FOLLOWING CIRCUITS (AT MINIMUM):

NOTIFICATION APPLILANCE CIRCUIT: 14 AWG, TYPE FPLR/FPLP, SOLID COPPER, TWISTED PAIR

INITIATION - 14/2 AWG

SIGNALING LINE CIRCUIT - 16/2 AWG TWISTED SHIELDED PAIR

120 VAC - PRIMARY POWER - NO. 12 AWG, THHN/THWN 600VAC INSULATED

SECURE NECESSARY CONSTRUCTION PERMITS, INSPECTIONS AND FINAL SYSTEM ACCEPTANCE.

ALL CONTRACT DRAWINGS (INCLUDING ALL DISCIPLINES) AND ALL CONTRACT SPECIFICATIONS MUST BE USED IN CONJUNCTION TO OBTAIN COMPLETE CONSTRUCTION INFORMATION. REPORT ANY INFORMATION CONFLICTS BETWEEN THE SPECIFICATIONS AND DRAWINGS TO THE CONTRACTING OFFICER'S ATTENTION. THE CONTRACTOR MUST NOT PROCEED WITH ANY WORK, EXCEPT AT THEIR OWN RISK UNTIL CLARIFICATIONS OF THE CONFLICTS ARE ISSUED TO THE CONTRACTOR BY THE CONTRACTING OFFICER.

INFORMATION CONTAINED IN THESE DRAWINGS IS BASED ON EXISTING DOCUMENTS, LIMITED FIELD SURVEYS, ARCHITECTURAL AND STRUCTURAL INFORMATION. THE INFORMATION CONTAINED HEREIN MAY REQUIRE ADJUSTMENTS AND/OR MODIFICATIONS TO CONFORM TO EXISTING BUILDING CONDITIONS. VERIFY DIMENSIONS AND CONDITIONS AT JOB SITE CONCERNING THE WORK BEFORE PROCEEDING WITH EITHER FABRICATION OR INSTALLATION OF WORK. LOCATION OF EQUIPMENT IS APPROXIMATE.

VERIFY THE LOCATION OF SYSTEM COMPONENTS. REPORT ANY DISCREPANCIES WITH THESE DRAWINGS TO THE CONTRACTING OFFICER IMMEDIATELY.

AVOID CONFLICTS WITH LIGHT FIXTURES, HVAC DIFFUSERS, GRILLS, DUCTS, CONDUIT AND OTHER PIPING OR OTHER OBSTRUCTIONS ENCOUNTERED. COORDINATE WORK WITH FIELD CONDITIONS. PROMPTLY NOTIFY CONTRACTING OFFICER PRIOR TO INITIATING WORK IF ANY MOUNTING LOCATIONS ARE OBSTRUCTED AND/OR IF ANY MOUNTING

CONFLICTS OR PROBLEMS ARE DISCOVERED.

DO NOT CUT, DRILL OR BURN ANY STRUCTURAL MEMBERS UNLESS PREVIOUSLY APPROVED BY THE CONTRACTING OFFICER. DO NOT CUT OR PATCH STRUCTURAL WORK IN A MANNER THAT WOULD RESULT IN A REDUCTION OF LOAD-CARRYING OR LOAD-DEFLECTION RATIO.

COORDINATE WORK WITH THE CONTRACTING OFFICER, INCLUDING ACCESS TO THE BUILDING. SCHEDULE WORK TO MINIMIZE DISRUPTION TO OCCUPANTS OF THE BUILDING.

BEFORE THE EXISTING FIRE ALARM AND RELEASING SYSTEM IS SHUTDOWN, NOTIFY THE CONTRACTING OFFICER 14 DAYS IN ADVANCE.

MAINTAIN CLEAR EGRESS PATHS IN BUILDING DURING CONSTRUCTION IF AREA IS TO REMAIN OCCUPIED. ROPE OFF OCCUPIED WORK AREAS. CONSTRUCTION WORK WHICH BLOCKS OR OTHERWISE IMPEDES AN EGRESS PATH MUST ONLY BE PERFORMED DURING HOURS WHEN THE BUILDING IS UNOCCUPIED.

PREPARE A DETAILED WRITTEN PHASING PLAN AND SUBMIT FOR APPROVAL TO THE CONTRACTING OFFICER. WORK MUST NOT START UNTIL THIS PLAN IS APPROVED. REPORT

CHANGES TO THE CONTRACTING OFFICER ON A WEEKLY BASIS.

"PROVIDE" MEANS CONTRACTOR MUST FURNISH NEW AND INSTALL COMPLETE AND READY FOR INTENDED USE.

"REMOVE" MEANS CONTRACTOR MUST DISCONNECT, REMOVE FROM SITE (ONLY IF APPROVED BY CONTRACTING OFFICER) AND LEGALLY DISPOSE.

STROBE NOTIFICATION APPLIANCE CIRCUIT POWER REQUIREMENTS AND CONDUCTOR SIZES SHALL NOT EXCEED A 10% VOLTAGE DROP. EACH VISUAL NOTIFICATION

APPLIANCE CIRCUIT SHALL NOT EXCEED 80% OF ITS RATED OUTPUT.

ALL INSTALLED SIGNALING LINE CIRCUITS AND NOTIFICATION APPLIANCE CIRCUITS SHALL HAVE 20 PERCENT SPARE CAPACITY. ALL AMPLIFIERS SHALL HAVE 20 PERCENT SPARE CAPACITY. BATTERY SIZE SHALL BE A MINIMUM OF 125% OF THE CALCULATED REQUIREMENT.

CONTRACTOR SHALL COORDINATE LOCATION OF AUTOMATIC SPRINKLER FLOW SWITCHES AND TAMPER SWITCHES WITH FIRE PROTECTION DRAWINGS.

ABBREVIATIONS

EXISTING TO REMAIN LINE TYPE

EXISTING TO BE REMOVED LINE TYPE

NEW WORK LINE TYPE

FIRE ALARM STROBE SIGNALING DEVICE,

CEILING MOUNTED, XX=CANDELA RATING

FIRE ALARM STROBE SIGNALING DEVICE,

WALL MOUNTED, XX=CANDELA RATING

ADDRESSABLE MANUAL PULL STATION

AFFF SYSTEM ABORT SWITCH

AFFF SYSTEM MANUAL RELEASE STATION

ULTRAVIOLET/INFARED FLAME DETECTOR (UV/IR)

ADDRESSABLE HEAT DETECTOR

X=MOUNT; W=WALL, C=CEILING

ADDRESSABLE SMOKE DETECTOR

X=MOUNT; W=WALL, C=CEILING

ADDRESSABLE DUCT SMOKE DETECTOR

REMOTE TEST STATION

MULTI-VOLTAGE RELAY

ADDRESSABLE INPUT MODULE

ADDRESSABLE OUTPUT MODULE

VALVE SUPERVISORY SWITCH, CONNECTION ONLY

WATERFLOW SWITCH, CONNECTION ONLY

LOW TEMPERATURE SENSOR

FIRE ALARM CONTROL UNIT

MASS NOTIFICATION SYSTEM CONTROL UNIT

BATTERY CABINET

RELEASING FIRE ALARM CONTROL UNIT

NOTIFICATION APPLIANCE PANEL

SURGE PROTECTION DEVICE

FIRE ALARM ANNUNCIATOR

LOCAL OPERATING CONSOLE

AMPLIFIER CABINET

FIRE ALARM DOCUMENTATION CABINET

DET-TRONICS PANEL

POWER SUPPLY PANEL

FIBER OPTIC NETWORK CONNECTION

120 VAC, 20 AMP FIRE ALARM POWER SUPPLY

KEYNOTE INDICATOR

DETAIL NUMBER

DETAIL IDENTIFICATION BUBBLE

SHEET DETAIL IS SHOWN ON

SECTION NUMBER

SECTION IDENTIFICATION BUBBLE

SHEET SECTION IS SHOWN ON

SYMBOL LIST

AIM

AOM

VS

WF

BATT

NAP

SPD

FAA

LOC

SYMBOL DESCRIPTION ABBREVIATION DESCRIPTION

AFFF

AMP

AWG

BLDG

EMT

FACU

HVAC

IDC

MNSCU

NAC

NAP

NFPA

RFACU

SLC

TYP

UFC

VAC

W

XP

AQUEOUS FILM-FORMING FOAM

AMPERE

AMERICAN WIRE GAUGE

BUILDING

ELECTRICAL METALLIC TUBING

FIRE ALARM CONTROL UNIT

HEATING, VENTILATION, AND AIR CONDITIONING

INITIATING DEVICE CIRCUIT

MASS NOTIFICATION SYSTEM CONTROL UNIT

NOTIFICATION APPLIANCE CIRCUIT

NOTIFICATION APPLIANCE PANEL

NATIONAL FIRE PROTECTION ASSOCIATION

RELEASING FIRE ALARM CONTROL UNIT

SIGNALING LINE CIRCUIT

TYPICAL

UNIFIED FACILITIES CRITERIA

VOLTS ALTERNATING CURRENT

WATT

EXPLOSION PROOF

AMP

F

UV/IR

X

X

RTS

R

XX

XX

A

R

RFCU

MNSCU

FACU

LT

FADC

DET

PSP

FONC

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

5 TYPE B3 (100%)SUBMITTAL IS 03-27-2026

F F F

F

R

TS

R

TS

RTS

R

TS

R

TS

F

FA

A

F

R

TS

R

TS

F

F F

R

TS

F

LT LT

LT LT

LT

F

W F

AI

M

WF

AIM

W F

AI

M

W F

AI

M

R

TS

11075

15 15

W P

W P

AOM

AOM

AOM

AOM

AOM

AOM

AOM

AOM

AOM

1 2 3 4 5 6 8 9 10 11 12

A

B

C

D

E F

G

FUEL CELL/CORR.

CONTROL BAY

BEAD BLAST RM

PAINT PREP. RM

STORAGE

PAINT STORAGE

PAINT ROOM

NOSE ROOM

FOAM STORAGE

VEST

MENS SHOWER

MEN TOILET

WOMENS SHOWER

WOMENS TOILET

CORRIDOR

JAN.

CORR. OFFICE

FAB. OFFICE

VEST.

FUEL OFFICE

TRAINING/BREAK

ROOM

GENERAL EQUIPMENT

AFFF RM

ELECTRICAL RM

MECHANICAL RM

FA-401

MAU-3

MAU-7

MAU-5

MAU-1

MAU-6

MAU-2

MAU-4

MAU-8

MAU-9

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/7/2026 10:57:35 AM C:\Users\YTAN6\Documents\Revit 2024 Local Files\12607256-GHD-632-IMP-MDL-FA-R24_YinZhet.Tan_GVUXBKFGRZCS.rvt

1/8" = 1'-0" FA-111

BLDG 632 FLOOR PLAN

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ACJ

ACJ

NIS

NIS

TYPE B3 - 100% FINAL SUBMITTAL 1/8" = 1'-0"1 BLDG 632 FLOOR PLAN - FIRE ALARM

KEYNOTES #

1.

2.

PROVIDE LOW TEMPERATURE SENSOR AT CEILING LEVEL (SAME LEVEL AS

SPRINKLER BRANCHLINES). SET TEMPERATURE SENSOR TO 32°F.

ADDRESSABLE INPUT MODULES ARE LOCATED WITHIN AFFF ROOM 122.

PROVIDE DUCT SMOKE DETECTOR DOWNSTREAM OF THE AIR FILTERS AND

AHEAD OF ANY BRANCH CONNECTIONS IN THE AIR SUPPLY SYSTEM. PROVIDE

ADDRESSABLE OUTPUT MODULE WITHIN 3-FEET OF MAU DISCONNECT TO

SHUT DOWN THE UNIT UPON SMOKE DETECTION. PROVIDE REMOTE TEST

STATION FOR THE DUCT SMOKE DETECTOR ON THE WALL ADJACENT TO THE

DUCT SMOKE DETECTOR. LABEL DUCT SMOKE DETECTOR HOUSING, OUTPUT

MODULE, AND TEST STATION WITH MAU DESIGNATION.

1. PROVIDE AN ADDRESSABLE FIRE ALARM SYSTEM FOR B632. PROVIDE

INITIATING DEVICES AND NOTIFICATION APPLIANCES THROUGHOUT THE

BUILDINGS AS INDICATED ON THE DRAWINGS. MASS NOTIFICATION SYSTEM IS

EXISTING TO REMAIN. FIRE ALARM SYSTEM TO UTILIZE EXISTING MNS

SPEAKERS FOR VOICE EVACUATION.

SHEET NOTES

N

SCALE: 1/8" = 1'-0"

016' 8' 4'

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

AIM AIM

WF VS

C

BATT

SPD

AIM AIM

WF VS

AIM

VS

M N

SC

U

B

AM

P

SP

D

AOM

AIM AIM

AIM AIM

AIM

SPD

W P

W W

C

SP

D

NAP

SPD

FACU

FONC

AOM AOM AIM AIM AIM

UV

/IR

UV/IR

UV

/IR

FACU

DET

W

VSWF

AIMAIM

F W

F

CC

W

C

C

W

C

W

M N

SC

U

AM

P

SP

D

W

RFCU

SP

D

NAP

NAP

PSP

VS

AIM

VSWF

AIMAIM

VS

AIM

10 11 12

E

F

6 6 7

FA-401

FADC

12 13 14 1

10 11 12

E

F 1

F.F.

0' - 0"

AFFF RM.

FINISHED FLOOR

0' - 0"

FIRE

ALARM

CONTROL

UNIT

BATT

FADC

NAP

FONC

6'

0"

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/7/2026 10:57:36 AM C:\Users\YTAN6\Documents\Revit 2024 Local Files\12607256-GHD-632-IMP-MDL-FA-R24_YinZhet.Tan_GVUXBKFGRZCS.rvt

As indicated FA-401

BLDG 632 ENLARGED PLANS &

SECTIONS

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ACJ

ACJ

NIS

NIS

TYPE B3 - 100% FINAL SUBMITTAL

1/4" = 1'-0"2 ENLARGED PLAN - AFFF AND ELECTRICAL ROOM - NEW WORK

1/4" = 1'-0"1 ENLARGED PLAN - AFFF AND ELECTRICAL ROOM - DEMOLITION

SHEET NOTES

KEYNOTES

1.

2.

DEVICE LAYOUT HAS BEEN TRANSCRIBED FROM EXISTING AS-

BUILT DRAWINGS AND FIELD VERIFICATION. VERIFY

DIMENSIONS, EXISTING CONDITIONS, AND ASSOCIATED

EQUIPMENT PRIOR TO COMMENCING WORK.

MASS NOTIFICATION SYSTEM IS EXISTING TO REMAIN. FIRE

ALARM SYSTEM TO UTILIZE EXISTING MNS SPEAKERS FOR

VOICE EVACUATION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

REMOVE AFFF CONTROL PANEL. SALVAGE THE PANEL

INCLUDING ALL INTERNAL COMPONENTS. DELIVER EQUIPMENT

TO CE IN BUILDING 528.

REMOVE EXISTING FIRE ALARM CONTROL UNIT. SALVAGE THE

PANEL INCLUDING ALL INTERNAL COMPONENTS. DELIVER

EQUIPMENT TO CE IN BUILDING 528.

PROVIDE SIMPLEX FIRE ALARM CONTROL UNIT THAT IS

COMPATIBLE WITH THE EXISTING SAFEPATH SP40S MASS

NOTIFICATION PANEL. SURGE PROTECTIVE DEVICE SHALL BE

UL1283 AND UL1449 RATED. PANEL TO INCLUDE BATTERY

BACKUP AND BE SIZED TO ACCOMMODATE ALL SLC AND NAC

CIRCUITS PLUS 20 PERCENT SPACE CAPACITY. PROVIDE

120VAC FIRE ALARM SYSTEM DEDICATED EMERGENCY

BACKED PRIMARY POWER CIRCUIT FOR THE FIRE ALARM

EQUIPMENT FROM PANEL LI BREAKER 36. FIRE ALARM

CONTROL UNIT SHALL BE CONNECTED TO EXISTING MASS

NOTIFICATION PANEL, REFER TO DETAIL 3 ON SHEET FA-501.

PROVIDE ADDRESSABLE INPUT MODULES FOR SUPERVISION

OF LOW TEMPERATURE IN HANGAR BAY.

NOT USED.

PROVIDE ADDRESSABLE INPUT MODULE FOR FIRE ALARM

MONITORING OF SPRINKLER SYSTEM WATERFLOW AND

TAMPER SWITCHES.

PROVIDE ADDRESSABLE INPUT MODULE FOR FIRE ALARM

MONITORING OF MAIN SHUTOFF VALVE TAMPER SWITCH.

PROVIDE WEATHERPROOF EXTERIOR ELECTRIC FIRE ALARM

BELL ABOVE FIRE DEPARTMENT CONNECTION. PROVIDE

ADDRESABLE OUTPUT MODULE FOR ACTIVATION OF ELECTRIC

BELL UPON WATERFLOW DETECTION IN THE SPRINKLER

SYSTEM. PROVIDE ADDRESSABLE OUTPUT MODULE WITH

NEMA 4 ENCLOSURE.

REMOVE DET-TRONICS PANEL AND ASSOCIATED RELAYS,

WIRE AND CONDUIT.

MASS NOTIFICATION CONTROL UNIT, AMP AND POWER

SUPPLIES TO REMAIN.

SURGE PROTECTIVE DEVICE (SPD) FOR ALARM BELL. SPD

SHALL BE UL1283 AND UL1449 RATED.

PROVIDE ADDRESSABLE OUTPUT MODULE TO DEACTIVATE

FIRE ALARM STROBES UPON MASS NOTIFICATION SYSTEM

ACTIVATION.

PROVIDE ADDRESSABLE OUTPUT MODULE TO ACTIVATE "FIRE

ALARM" MESSAGE ON EXISTING WHEELOCK SAFEPATH SP40S

ACU.

PROVIDE ADDRESSABLE INPUT MODULE TO MONITOR ALARM,

TROUBLE AND SUPERVISORY SIGNALS ON ON EXISTING

WHEELOCK SAFEPATH SP40S ACU.

SCALE: 1/4" = 1'-0"

08' 4' 2'

1/2" = 1'-0"3 SECTION - FIRE ALARM CONTROL UNIT - AFFF RM. 122 - FIRE ALARM

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

FACU

AFFF ROOM 122

BATT

SPD

AIM

AIM

B

FF

AOM

AIM

WF VS

AIMAIM

VSWF

AIMAIM

VS

AIM

AIM

ELECTRICAL ROOM 123

FFFF

VESTIBULE 118

FAA

FF

SPD

FF

OFFICE AREAHANGAR BAY

FF FF

LT

FAIM

WF

F

LTLT

AIM

WF

FAIM

WF

LT

FAIM

WF

OFFICE AREA

A B

B

B

A

A

B B B

BBB B

A

MNSCU AMP

SPD

FADC

LT

AIM

B

NAP

SPD

C

FONC

C

TO CATWALK

NOTIFICATION APPLIANCES

C

LOW CATWALKLOW CATWALK

HIGH CATWALK

BLDG 541 (FIRE DEPARTMENT) &

BLDG 636 (SECURITY BDOC)

RECEIVE SIGNALS

AOM AOM AIM AIM AIM

RTS

AOM

RTS

AOM

RTS

AOM

RTS

AOM

RTS

AOM

RTS

AOM

RTS

AOM

MAU-1 MAU-5 MAU-7 MAU-3 MAU-4 MAU-6 MAU-2

RTS

AOM

RTS

AOM

MAU-8 MAU-9

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/7/2026 10:57:37 AM C:\Users\YTAN6\Documents\Revit 2024 Local Files\12607256-GHD-632-IMP-MDL-FA-R24_YinZhet.Tan_GVUXBKFGRZCS.rvt

12" = 1'-0" FA-601

BLDG 632 FIRE ALARM MATRIX &

RISER DIAGRAM

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

IYS

ACJ

ACJ

NIS

NIS

TYPE B3 - 100% FINAL SUBMITTAL

N.T.S.1 FIRE ALARM RISER DIAGRAM

C NOTIFICATION CIRCUIT B LEVEL 1

B INITIATING DEVICE CIRCUIT B LEVEL 1

A SIGNALING LINE CIRCUIT B LEVEL 1

LABEL TYPE CLASS SURVIVABILITY

FIRE ALARM CIRCUIT LEGEND

HVAC Bypass X X X X Audible & Visual Bypass X X X X Acknowledge X Alarm Silence X X System Reset X X

SYSTEM FUNCTIONS

Activation of Mass Notification System Trouble Signal X X X Activation of Mass Notification System Supervisory Signal X X X Activation of Mass Notification System Alarm Signal X X X X X X

Battery Supervision Fault (low voltage, open circuit, battery charge failure, etc.) X X X

Low Battery X X X Primary Power Failure X X X Ground Circuit, Open Circuit, Missing Device, Device Fault X X X

SYSTEM FAULTS

Low Temperature Sensor X X X Sprinkler System Control Valve Tamper Switch X X X Sprinkler System Water Flow Switch X X X X X X Eyewash Station Waterflow X X X Manual Pull Station X X X X X Area Smoke Detector X X X X X Duct Smoke Detector (AHU) X X X X

INITITATING DEVICES

AL

AR

M S

IG

N

AL

A

T

FA

C U

, R

FA

C U s

FA

As

SU

PE

R

VI

SO

R

Y

SI

G N

AL

A

T

FA

C U

, R

FA

C U s

FA

As

TR

O

U

BL

E

SI

G N

AL

A

T

FA

C U

, R

FA

C U s

FA

As

SE

N

D A

LA

R

M S

IG

N

AL

T

O B

AS

E

FI

R

E D

EP

AR

TM

EN

T D

IS

PA

TC

H

SE

N

D S

U

PE

R

VI

SO

R

Y

SI

G N

AL

T

O B

AS

E

FI

R

E D

EP

AR

TM

EN

T D

IS

PA

TC

H

SE

N

D T

R O

U

BL

E

SI

G N

AL

T

O B

AS

E

FI

R

E D

EP

AR

TM

EN

T D

IS

PA

TC

H

AC

TI

VA

TE

C

LE

AR

S

TR

O

BE

S

TH

R

O U

G H

O U

T

BU

IL

D

IN

G

AC

TI

VA

TE

M

AS

S N

O

TI

FI

C

AT

IO

N S

PE

AK

ER

S

AC

TI

VA

TE

M N

S "F

IR

E

AL

AR

M " M

ES

SA

G E

AC

TI

VA

TE

E

XT

ER

IO

R E

LE

C

TR

IC

B

EL

L

D

IS

AB

LE

A U

D

IO

/V

IS

U

AL

C

IR

C U

IT

S

D

IS

AB

LE

A

IR

H

AN

D

LI

N G

U N

IT

S

H U

TD

O

W N

SH

U

T D

O W

N R

ES

PE

C

TI

VE

A

H U

R

EC

O R

D C

H

AN

G E

O F

ST

AT

U S

D E-

AC

TI

VA

TE

C

LE

AR

S

TR

O

BE

S

R

ES

TO

R

E

SY

ST

EM

T O

N O

R M

AL

, I

F N

O A

LA

R

M

SU

PE

R

VI

SO

R

Y, O

R T

R O

U

BL

E

SI

G N

AL

S

AR

E

AC

TI

VE

O

N T

H E

SY

ST

EM

INPUT DEVICE OUTPUT

ANNUNCIATION REPORTING NOTIFICATION CONTROLS

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

1 2 3 4 5 6 8 9 10 11 12

A

B

C

D

E

F

G

FUEL CELL/CORR.

CONTROL BAY

BEAD BLAST RM

PAINT PREP. RM

STORAGE

PAINT STORAGE

PAINT ROOM

NOSE ROOM

FOAM STORAGE

VEST

MENS SHOWER

MEN TOILET

WOMENS SHOWER

WOMENS TOILET

CORRIDOR

JAN.

CORR. OFFICE

FAB. OFFICE

VEST.

118 FUEL OFFICE

TRAINING/BREAK

ROOM

GENERAL EQUIPMENT

AFFF RM

ELECTRICAL RM

MECHANICAL RM

FX-401

3 3

FX-501

6" 6"

6" 6"

6" 6"

6" 6"

6" 6"

2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2" 2 1/2"

6"6"

4" 4"

6" 6"

6" 6"

6" 6"

6" 6"

6" 6"

8"

8"

19 20

FX-401

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/7/2026 11:02:54 AM C:\Users\YTAN6\Documents\Revit 2024 Local Files\12607256-GHD-632-IMP-MDL-FA-R24_YinZhet.Tan_GVUXBKFGRZCS.rvt

1/8" = 1'-0" FX-111

BLDG 632 FLOOR PLAN

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ACJ

ACJ

YZT

YZT

TYPE B3 - 100% FINAL SUBMITTAL 1/8" = 1'-0"1 BLDG 632 FLOOR PLAN - SPRINKLER

SHEET NOTES

KEYNOTES #

1. PROVIDE SPRINKLER PROTECTION UNDERNEATH

MECHANICAL EQUIPMENT AND OBSTRUCTIONS

EXCEEDING 48" IN WIDTH.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

PROVIDE SPRINKLER SYSTEM IN HANGAR IN

ACCORDANCE WITH SUNDOWN POLICY FOR FOAM

FIRE SUPPRESSION SYSTEMS CHANGE 2, 29

DECEMBER 2022 AND UFC 4-211-01. SYSTEM MUST

BE HYDRAULICALLY CALCULATED TO DELIVER 0.20

GPM/SQ.FT. OVER 5,000 SQ.FT.

TO EXISTING 8" UNDERGROUND PIPE.

PROVIDE DRAFT CURTAIN. REFER TO STRUCTURAL

DRAWINGS FOR DETAIL.

PROVIDE AUTOMATIC AIR VENT AT THE HIGHEST

ACCESSIBLE POINT OF THE SPRINKLER SYSTEM.

PROVIDE SIDEWALL SPRINKLER UNDER ROLLUP

DOOR.

TO EXISTING SPRINKLER SYSTEM SERVING THE

ADMINISTRATIVE SPACE.

PROVIDE 8" VERTICAL SPRINKLER ZONE CONTROL

ASSEMBLY FOR SPRINKLERS IN HANGAR B632.

CONTROL ASSEMBLY MUST INCLUDE INDICATING

TYPE CONTROL VALVE WITH SYPERVISORY

SWITCH (SUPERVISED OPEN), CHECK VALVE,

WATERFLOW SWITCH, PRESSURE GAUGE AND

TEST-DRAIN VALVE WITH PRESSURE RELIEF

VALVE.

SHADED AREA NOT IN CONTRACT.

PROVIDE 8" PIPE AND CONNECT TO EXISTING

OS&Y VALVE.

PROVIDE 8" PIPE AND TEE WITH CLEANOUT IN

AFFF VALVE PIT.

N

SCALE: 1/8" = 1'-0"

016' 8' 4'

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

FACU

+48"

400/3

OR

DENOTES HEIGHT IN INCHES

AFF (INTERIOR) AFG

(EXTERIOR)

L1-4

INDICATES

BRANCH

PANEL

INDICATES CIRCUIT NUMBER

COMMA INDICATES

MULTI-POLE CIRCUIT

L1-6,8

OR

60/3/50/4X

SCOPE OF WORK

WIRING AND CONDUIT

208Y/120V PANEL

FIRE ALARM CONTROL UNIT

EQUIPMENT

GENERAL NOTESELECTRICAL SYMBOLS AND ABBREVIATIONS.

DUPLEX RECEPTACLE, 20A 125V 2P 3W,

GROUNDING TYPE, MOUNTING HEIGHT: +18" AFF UNO

SINGLE RECEPTACLE, 20A 125V 2P 3W, GROUNDING

TYPE,MOUNTING HEIGHT: +18" AFF UNO

QUAD RECEPTACLE, 20A 125V 2P 3W, GROUNDING TYPE

PULL BOX OR JUNCTION BOX, CODE SIZED, UNO

DISCONNECT SWITCH. SIZE/POLE/FUSE SIZE/NEMA

TYPE ENCLOSURE. NF - NON-FUSED.

GROUND ROD, GROUNDING RECEPTACLE

POWER

#8

CONDUIT HOME RUN TO DESIGNATED

PANEL,

EXAMPLES:

THE TIC MARKS INDICATE THE QUANTITY OF #12 AWG

WIRES OR, IF INDICATED, QUANTITY OF OTHER SIZE

WIRE OR CABLES. LONG MARK INDICATES NEUTRAL.

EXAMPLES:

OBJECT LINES

NEW OBJECTS (HEAVY CONTINUOUS LINES,

UNDERGROUND CONDUIT HEAVY DASHED LINES)

EXISTING OBJECTS TO REMAIN. MAY INCLUDE

NEW CIRCUITING ETC. (FINE CONTINUOUS LINES,

UNDERGROUND CONDUIT FINE DASHED LINES)

EXISTING OBJECTS TO BE REMOVED

(EXTRA FINE DASHED LINES, SCREENED)

ABBREVIATIONS

ALARM, INDICATING LIGHT, SIGNAL

LIGHT OR STROBE

CIRCUIT BREAKER - SIZE AND TYPE AS

INDICATED

DISCONNECT SWITCH WITH FUSE

FUSE - SIZE AS INDICATED

UTILITY TRANSFORMER, POLE

MOUNTED

GROUNDING ELECTRODE OR

CONNECTION

ONE-LINE DIAGRAM

EXISTING OBJECTS TO BE DEMOLISHED

THE SCOPE FOR THE ELECTRICAL PART OF THIS PROJECT

IS AS FOLLOWS:

1.

2.

3.

4.

5.

6.

7.

8.

REMOVE ALL ELECTRICAL EQUIPMENT AND

WIRING ASSOCIATED WITH HANGAR DOOR

SCHEDULED FOR REPLACEMENT.

PROVIDE SAFETY DISCONNECTS FOR

EQUIPMENT ASSOCIATED WITH NEW HANGAR

DOOR.

PROVIDE POWER TO NEW EQUIPMENT TO

MAKE HANGAR DOOR OPERATIONAL AND

FUNCTIONAL.

PROVIDE TASK LIGHTING ON THE CATWALK.

PROVIDE EMERGENCY GENERATOR.

PROVIDE AUTOMATIC TRANSFER SWITCH

(ATS).

PROVIDE GENERATOR GROUNDING.

PROVIDE SERVICE CONDUCTORS TO ATS.

EQUIPMENT GROUNDING CONDUCTOR IS NOT

SHOWN BUT MUST BE IN EVERY CONDUIT.

3#12,1#12G, 3/4"C.

6#8,1#10G,1 1/4"C.

JB

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

"PROVIDE" MEANS CONTRACTOR MUST FURNISH NEW INSTALL COMPLETE TESTED AND

READY FOR INTENDED USE.

"REMOVE" MEANS CONTRACTOR MUST DISCONNECT, REMOVE FROM SITE AND LEGALLY

DISPOSE OF.

"WIRING" MEANS WIRES AND RACEWAYS.

DRAWINGS INDICATE THE REQUIRED EQUIPMENT, DEVICES, FIXTURES, ETC.

AND THEIR RELATED CIRCUITING REQUIREMENTS. COORDINATE DEVICE LOCATIONS

WITH ALL DISCIPLINES.

REFER TO SPECIFICATION FOR ALLOWABLE WIRING METHODS AND MATERIALS. TYPE.

NM, NMC, AND NMS CABLES MUST NOT BE USED FOR THIS PROJECT.

VERIFY FIELD CONDITIONS AND DIMENSIONS BEFORE CONSTRUCTION BEGINS. NOTIFY

THE CONTRACTING OFFICER SHOULD DISCREPANCIES OCCUR.

PROTECT EXISTING EQUIPMENT, CONDUIT AND WIRE THAT IS EXISTING TO REMAIN.

COORDINATE SHUTDOWN OF EXISTING BUILDING SYSTEMS TO MINIMIZE OUTAGE TIME.

PROVIDE SUPPORTS FOR CONDUIT AND ELECTRICAL EQUIPMENT THAT IS SHOWN ON

THE DRAWINGS. PROVIDE SUPPLEMENTAL ATTACHMENT AND ANCHORAGE AS NEEDED.

PROVIDE ANCHOR BOLTS OF THE SIZE, TYPE, AND LENGTH REQUIRED TO SATISFY THE

NEC CURRENT EDITION AND THE EQUIPMENT MANUFACTURER'S RECOMMENDATIONS.

PROVIDE MINIMUM BRANCH CIRCUIT WIRING 2#12 AWG,1#12 GR, IN 3/4"C., UNLESS

NOTED OTHERWISE.

ELECTRICAL EQUIPMENT INSTALLED IN THIS PACKAGE WITHIN ROOMS 101 & 107 FOR

BUILDING 632, MUST BE MOUNTED AT OR ABOVE 18" FROM THE FLOOR TO AVOID

HAZARDOUS AREA ENVELOPE.

NO METAL CLAD TYPE CABLE ALLOWED FOR THIS PROJECT.

INDICATING LIGHT/ SIGNAL LIGHT AND

HORN

AMPERES

ALTERNATING CURRENT

AMPERES FRAME SIZE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

APPROXIMATELY

AMPERE TRIP RATING

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

CONDUIT

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

CONCRETE EQUIPMENT PAD

CIRCUITS

COLOR RENDERING INDEX

COPPER

DUCT BANK

DESIGN LIGHTS CONSORTIUM

DOOR MANUFACTURER

DISCONNECT SWITCH

ELECTRICAL CONTRACTOR

EMERGENCY GENERATOR

FIRE ALARM

FIRE ALARM CONTROL UNIT

GROUND

GENERAL ELECTRIC

GROUNDING ELECTRODE CONDUCTOR

GROUND FAULT CIRCUIT INTERRUPTER

GROUND FAULT PROTECTION

ILLUMINATING ENGINEERING SOCIETY

INPUT/OUTPUT

JUNCTION BOX

KELVIN

KILO-AMPS INTERRUPTING CAPACITY

KILOVOLT

KILOVOLT-AMPERE

KILOWATT

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN CONTROL PANEL

MAIN LUGS ONLY

MANUAL TRANSFER SWITCH

NATIONAL ELECTRICAL CODE

NOT IN CONTRACT

NOT TO SCALE

ON CENTER

OVERHEAD

PHASE

POWER FACTOR

PANEL

POLYVINYL CHLORIDE

REMOTE CONTROL PANEL

RECEPTACLE, OUTLET

ROOM

RESTRICTION OF HAZARDOUS

SUBSTANCES

SQUARE D

TOTAL HARMONIC DISTORTION

TYPICAL

THERMOSTAT

UNDERGROUND

UNIT HEATER

UNDERWRITERS LABORATORY

UNLESS NOTED OTHERWISE

UNLESS OTHERWISE NOTED

VOLT, VOLTAGE

VOLT-AMPERE

WIRE

WITH

WEATHERPROOF

TRANSFORMER

A

AC

AF

AFF

AFG

APPROX

AT

ATS

AWG

C

CB

CCT

CEP

CKTS

CRI

CU

DB

DLC

DM

DSC SW

EC

EG

FA

FACU

G, GR

GE

GEC

GFI

GFP

IES

I/O

JB

K kAIC kV kVA kW

MCB

MCC

MCP

MLO

MTS

NEC

NIC

NTS

OC

OH

Ø OR ɸ

PF

PNL

PVC

RCP

REC

RM

ROHS

SqD

THD

TYP

TSTAT

OR T

UG

UH

UL

UNO

UON

V

VA

W W/

WP

XFMR

PB

LIST OF DRAWINGS

M ELECTRICAL MOTOR LOAD

DS OR

LIGHTING

LIGHT SWITCH NOTATION

3 = THREE WAY SWITCH

X = SWITCHING CIRCUIT ID

$x

LIGHT FIXTURE NOTATION

X = SWITCHING CIRCUIT ID

Y = FIXTURE TYPExY

NEW/EXISTING TEXT IDENTIFIER:

EXISTING EQUIPMENT, CONDITIONS, AND STRUCTURES

ARE SHOWN IN THIS TEXT FORMAT

NEW WORK, EQUIPMENT, AND STRUCTURES ARE SHOWN

IN THIS TEXT FORMAT.

(E) - EXISTING ITEM TO REMAIN

GROUNDING NOTES

1.

2.

3.

4.

5.

6.

GROUNDING: ELECTRICAL SYSTEMS SHALL BE GROUNDED AS SPECIFIED AND SHOWN ON

THE CONTRACT DRAWINGS. WORK SHALL ALSO BE PERFORMED IN ACCORDANCE WITH

ARTICLE 250 OF THE MOST RECENT REVISION OF THE NATIONAL ELECTRIC CODE. REFER

TO DETAILS FOR GROUNDING SCHEMATICS AND FOR GENERAL GROUNDING

REQUIREMENTS OF ELECTRICAL EQUIPMENT. GROUND GRID CONNECTIONS SHOWN ON

THE INDIVIDUAL PLANS ARE MINIMUM REQUIREMENTS. ALL REQUIRED CONNECTIONS ARE

NOT SHOWN ON PLANS FOR BREVITY. CONTRACTOR SHALL COORDINATE NEW

CONNECTIONS TO THE EXISTING GROUND GRIDS AS NECESSARY. REFER TO GROUNDING

NOTES BELOW AND ELECTRICAL DETAILS FOR ADDITIONAL INFORMATION.

THE GROUNDING SYSTEM IS SHOWN DIAGRAMMATICALLY. EXACT LOCATION OF CABLE,

GROUND RODS AND CONNECTIONS SHALL BE DETERMINED IN THE FIELD.

ALL BURIED GROUNDING CABLES SHALL BE TINNED COATED AND ALL CONNECTIONS

SHALL BE CADWELD OR THERMOWELD. THE WELDED CONNECTIONS SHALL BE LEFT

EXPOSED FOR INSPECTION BY ENGINEER PRIOR TO BACKFILLING.

WHERE EXPOSED TO MECHANICAL INJURY, THE GROUNDING CONDUCTOR SHALL BE

SUITABLY PROTECTED BY PIPE OR OTHER MECHANICAL PROTECTION. EACH END OF

PROTECTING CONDUIT (IF METALLIC) SHALL BE GROUNDED TO THE BARE CABLE.

ALL EXPOSED CABLE LUGS AND CONNECTORS SHALL BE OF THE COMPRESSION TYPE,

UNLESS OTHERWISE NOTED.

STEEL MUST BE CLEANED THOROUGHLY AND CABLE MUST BE COMPLETELY DRY BEFORE

MAKING WELD CONNECTIONS.

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/6/2026 3:29:25 PM \\ghdnet\ghd\US\Baltimore\Projects\565\12607256\Digital_Design\Revit 2024\12607256-GHD-632-IMP-MDL-EL-R24.rvt

As indicated E-001

REFERENCE SHEET - ELECTRICAL

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ZM

ST

DR

ZM

TYPE B3 - 100% DESIGN SUBMITTAL

SHEET

NUMBER SHEET NAME

E-001 REFERENCE SHEET - ELECTRICAL

E-101 BLDG 632 DEMOLITION PLAN

E-111 BLDG 632 POWER PLAN

E-112 BLDG 632 LIGHTING PLAN

E-113 BLDG 632 PARTIAL SITE PLAN

E-201 BLDG 632 CATWALK SECTION VIEW

E-501 BLDG 632 PARTIAL SINGLE-LINE DIAGRAMS

E-502 BLDG 632 HANGAR NEW DOOR INTERCONNECTION

DIAGRAM

E-503 BLDG 632 LIGHTING AND PANEL SCHEDULES

E-601 BLDG 632 ELECTRICAL DETAILS

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

5 TYPE B3 (100%) SUBMITTAL IS 03-27-2026

M M M M MM M

1 4 5 6 7 8 9 11 12

A

B

C

D

E F

G

2 10

A

B

C

D

E F

G

E-201

FOAM STOR.

108 MENS

WOMENS

JAN

GEN. EQUIP.

AFFF RM.

ELEC RM.

MECH RM.

124TRAINING/BREAK

FUEL OFF.

VEST

118FAB. OFF.

COOR. OFF.

COORIDOR

114VEST

PAINT ROOM

PAINT STORAGE

STOR

PAINT PREP RM

BEAD BLAST RM

REMOTE

CONTROL

PANEL FOR

HANGAR DOOR

DS

MAIN CONTROL

PANEL FOR

HANGAR DOOR

MCC (E)

DSDSDSDS DS

DS

1 1 1 1

I/O BOXI/O BOX I/O BOX

DISCONNECT

SWITCH

FOR MCP.

100/3/100/3R

NOSE ROOM

FUEL CELL/CORR.

CONTROL BAY

LIGHT/HORN

FACU

DS

L1 - 19 L1 - 21

EXISTING GROUNDING

WELL (TYP) 6 7

555 5 5

CATWALK

LIGHT/HORN

LIGHT/HORN

E1 (E)

TO GENSET,

REFER TO E-113

TO SERVICE

TRANSFORMER,

REFER TO E-113

ATS, TOP

CONDUIT ENTRY.

CIRCUIT

BREAKER

ENCLOSURE

GENERATOR

REMOTE

CONTROL PANEL1

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/6/2026 3:29:26 PM \\ghdnet\ghd\US\Baltimore\Projects\565\12607256\Digital_Design\Revit 2024\12607256-GHD-632-IMP-MDL-EL-R24.rvt

3/32" = 1'-0" E-111

BLDG 632 POWER PLAN

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ZM

ST

DR

ZM

TYPE B3 - 100% DESIGN SUBMITTAL

KEYNOTES #

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

PROVIDE DISCONNECT SWITCH AND ASSOCIATED

WIRES AND CONDUITS BACK TO HANGAR DOOR

CONTROL PANEL.

3 - 4"C RUN EXPOSED, PROVIDE REQUIRED

SUPPORT FROM CEILING UNDERSLAB.

PROVIDE CONTROL WIRES AS INDICATED ON

E-502.

PROVIDE POWER TO FACU FROM PANEL E1 IN

ROOM 123. CONNECT TO SPARE 20A/1P CIRCUIT

BREAKER. PROVIDE LABEL AND UPDATE PANEL

SCHEDULE.

PROVIDE GFI DUPLEX RECEPTACLE AND

ASSOCIATED WIRES AND CONDUITS BACK TO

PANELBOARD. PROVIDE WP COVER. INSTALL

RECEPTACLE APPROX. 48" ABOVE CATWALK

FLOOR.

PROVIDE CONNECTION TO NEAREST GROUND

BUS. USE #2 GROUND WIRE. TYPICAL FOR THE

ENTIRE PROJECT.

PROVIDE GROUND JUMPERS BETWEEN PARTS OF

CATWALK.

PROVIDE 4" CONCRETE PAD.

REFER TO INSTALLATION SEQUENCE.

WATERPROOF SEAL WALL PENETRATIONS.

RESTORE ALL DISTURBED SURFACES.

24"X16"X12" PULL BOX ON THE WALL. MOUNT MIN.

8' AFG.

EXISTING 3-4"C. UNDERGROUND DUCT BANK WITH

NEW SERVICE CONDUCTORS.

3-4"C. WITH NEW SERVICE CONDUCTORS RUN

EXPOSED. PROVIDE REQUIRED SUPPORT FROM

CEILING UNDERSLAB

3-4"C. UNDERGROUND DUCT BANK WITH

GENERATOR SERVICE CONDUCTORS, CONCRETE

ENCASED UNDER ROAD CROSSING.

PROVIDE PULL BOX ON THE TOP OF THE MCC,

APPROXIMATE DIMENSIONS 20"X20", HEIGHT AS

REQUIRED FOR CABLE PULLING.

2"C. FOR COMMUNICATION WIRING.

GENERAL NOTES

1.

2.

3.

SEE E-501 AND E-502 FOR SINGLE-LINE DIAGRAMS,

WIRE AND CONDUIT SIZES AND MOTOR NAME

TAGS.

ELECTRICAL PANELS L1, L2, & H2 ARE IN THE MCC

IN ELEC. ROOM 123.

ALL METAL RACEWAYS, METAL-JACKETED CABLES,

ENTIRE CATWALK STRUCTURE AND ALL NON-

CURRENT CARRYING METAL PARTS OF FIXED OR

PORTABLE ELECTRICAL EQUIPMENT, REGARDLESS

OF VOLTAGE & FREQUENCY, SHALL BE GROUNDED

AS PROVIDED IN ARTICLE 250 OF NEC, LATEST

EDITION. GROUNDING IN CLASSIFIED HAZARDOUS

LOCATIONS SHALL COMPLY WITH SECTION 501-16

OF NEC, LATEST EDITION.

N

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

5 TYPE B3 (100%) SUBMITTAL IS 03-27-2026

1 PRE-BID INQUIRIES 08-07-2026

1.

2.

3.

4.

5.

DISCONNECT EXISTING SERVICE

CONDUCTORS FROM SERVICE

TRANSFORMER SECONDARY

COMPARTMENT AND MCC MAIN CIRCUIT

BREAKER.

REMOVE SERVICE CONDUCTORS.

INTERCEPT EXISTING DUCT BANK AS

CLOSE TO THE BUILDING BY INSTALLING

EXPOSED IMC CONDUITS ALONG THE WALL

TO THE PULL BOX.

RUN CONDUITS FROM THE PULL BOX TO

THE ATS.

PULL NEW SERVICE CONDUCTORS AND

MAKE FINAL CONNECTIONS.

INSTALLATION SEQUENCE:

SCALE: 3/32" = 1'-0"1 BLDG 632 ELECTRICAL FLOOR PLAN - NEW WORK

FHYD 7-5

SNMH12/4

E

E

E

E

E

ST

18"

18"

STMH32/1

STCB32/3

STCB32/2 STCB32/1

STMH32/10

S A N

SN

SAN

SA

N

SAN

OW

6"

6"

6"

6"OW

6"

8"

8"

CO

M

C O M

C O M

C O M

DW

DW

DW DW DW

D W

DW

DW

DWV 7

DB-EG

CEP

GENERATOR

ENCLOSURECP

CB

BOLLARD

(TYP.)

DB

-S

T

(E) SERVICE

TRANSFORMER

BLDG 632

MAIN CIRCUIT

BREAKER

GENERATOR

CONTROL PANEL

E-601

E-601

BOLLARD (TYP.)

BOLLARD (TYP.)

PULLBOX

PULLBOX

4' - 0"

E

E

E

E

E

E

E

SAN

SA

N

SA

N

SA

N

SA

N

SA

N

SA

N

S A N

S A N

S A N

S A N

S A N

S A N

S A N

S A N

D W

D W

CO

M

CO

M

CO

M

CO

M

CO

M

CO

M

CO

M

CO

M

CO

M

CO

M

CO

M

CO

M

E

E

3'

- 0

CAMLOCK

DOCKING STATION

ENCLOSURE

A 4" 4" 2"

4" 4" 2" 1"B

1 2 3 4

DB-EG

A1 - 4"C - GEN. POWER FEEDER

A2 - 4"C - SPARE

A3 - 2"C - W/ 3CKTS FOR BATTERY

CHARGER, BATTERY HEATER, & OIL

HEATER

B1 - 4"C - GEN. POWER FEEDER

B2 - 4"C - GEN. POWER FEEDER

B3 - 2"C W/ CONTROL WIRES

B4 - 1"C W/ CKT FOR GEN. SPACE HEATER

A 4" 4"

4" 4"B

1 2

DB-ST

A1 - EXISTING 4"C. W/ NEW CONDUCTORS

A2 - EXISTING SPARE

B1 - EXISTING 4"C. W/ NEW CONDUCTORS

B2 - EXISTING 4"C. W/ NEW CONDUCTORS

CEP

#4/0 AWG GROUND GRID

CONDUCTOR (TYP)

GROUND CONNECTION:

BOND TO GENERATOR

ENCLOSURE

GROUND CONNECTION:

BOND TO STRUCTURAL

REBAR (TYP)

GROUND CONNECTION:

BOND TO GENERATOR

GROUNDING

DRAWING KEY NOTES:

CB

CP

DUCT BANK MARKER

DUCT BANK (REFER

TO SITE PLAN FOR

CONTINUATION)

GROUND CONNECTION:

BOND TO DUCT BANK REBAR

1.

2.

3.

4.

5.

INSTALL DUCT BANK PER SITE PLAN DRAWINGS.

GROUND CONNECTION: BOND TO GENERATOR NEUTRAL

DUCT BANK STUB-UPS: COORDINATE WITH GENERATOR

INSTALLATION. PROVIDE WORKING SPACE REQUIREMENTS FOR

EQUIPMENT AS REQUIRED PER NEC.

COORDINATE FINAL EQUIPMENT PAD DIMENSIONS AND

MOUNTING BOLT LOCATIONS WITH THE GENERATOR

MANUFACTURER AFTER SUBMITTAL APPROVAL.

REFER TO GENERATOR CONCRETE PAD DETAIL.

GROUND ROD w/

TEST WELL (TYP)

2 3

4 5

6"

(TYPICAL ALL AROUND: UNLESS

NOTED OTHERWISE ON

DRAWINGS)

3"

COVER 1 TO 2

12"

FR

OS

T

DE

PT

H

TURNED-DOWN SLAB EDGE

ALL AROUND PERIMETER

COMPACTED FILL (TYP)

6"

#5@12" EACH WAY, CENTERED

IN SLAB

8"

EQUIPMENT:

SEE ELECTRICAL DRAWINGS

MINIMUM 6" LAYER COMPACTED

FILL OR #57 STONE

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/6/2026 3:29:27 PM \\ghdnet\ghd\US\Baltimore\Projects\565\12607256\Digital_Design\Revit 2024\12607256-GHD-632-IMP-MDL-EL-R24.rvt

As indicated E-113

BLDG 632 PARTIAL SITE PLAN

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ZM

ST

DR

ZM

TYPE B3 - 100% DESIGN SUBMITTAL

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

5 TYPE B3 (100%) SUBMITTAL IS 03-27-2026

1 PRE-BID INQUIRIES 08-07-2026

SCALE: 3/32" = 1'-0"1 PARTIAL SITE PLAN

NOT TO SCALE2 DUCT BANK SCHEDULE - DB-EG

NOT TO SCALE3 DUCT BANK SCHEDULE - DB-ST

GENERAL NOTES

1.

2.

SEE E-501 AND E-502 FOR SINGLE-LINE DIAGRAMS,

WIRE AND CONDUIT SIZES AND MOTOR NAME

TAGS.

BOLLARDS PROTECTING THE GENERATOR SHALL

BE 4' APART OC. AND APPROX. 12" CLEARANCE

FROM GENERATOR PAD. REFER TO BOLLARD

DETAIL ON E-601.

N

NOT TO SCALE5 GENERATOR GROUNDING PLAN

NOT TO SCALE4 GENERATOR CONCRETE PAD DETAIL

N

L

E

FROM UTILITY

MANHOLE

50A

13.2KV

750 KVA

277/480V

1200:5

277V 120V

60A

1000AT

1200AF

(E) SOLID STATE WITH

GR. FAULT PROTECTION

4#6 XHHW 1#8GR 480V 4 POLE & GR.

60A GENERATOR

RECEPTACLE

MAIN CONTROL

PANEL FOR

HANGAR DOOR

4#6 XHHW 1#8GR

(E) PAD MOUNTED

OIL-FILLED

TRANSFORMER

(E) IN 1 1/2''C.

60A MTS

AT NE

CORNER

OF 101

4#6 XHHW 1#8GR

(E) 3#2 1#2GR 15kV CABLE

IN EXISTING DUCT

(E) 3 SET OF 4-400kcmil

XHHW

1 #3/0 GR IN 4''C. &

1-4''. SPARE

CONCRETE ENCASED

BUILDING LOADS

(E) MCC IN

ELECTRICAL ROOM

POWER AND

CONTROL WIRES

IN MULTIPLE C.

(E) IN 1 1/2''C.

(E) IN 1 1/2''C.

60A/3P

DISCONNECT

SWITCH

REMOTE CONTROL

PANEL FOR

HANGAR DOOR

(E) IN 1 1/2''C.

4#6 XHHW 1#8GR

FROM UTILITY

MANHOLE

50A

13.2KV

750 KVA

277/480V

1200:5

277V 120V

80AT/150AF

1000AT

1200AF

(E) SOLID STATE WITH

GR. FAULT PROTECTION

PERMANENT

GENERATOR

(E) PAD MOUNTED

OIL-FILLED

TRANSFORMER

(E) IN 1 1/2''C.

4#4, 1#8GR

(E) 3#2 1#2GR 15kV CABLE

IN EXISTING DUCT

3 SET OF 4-400kcmil XHHW

1 #3/0 GR IN EXISTING 4''C. & 1-4''C. SPARE

CONCRETE ENCASED (UNDERGROUND)

BUILDING LOADS

(E) MCC IN

ELECTRICAL ROOM 123

POWER AND

CONTROL WIRES

IN 1 1/2''C.

100/3/100/3R

DISCONNECT

SWITCH

4#4, 1#8GR

(REFER TO E-502)

REMOTE CONTROL

PANEL FOR

HANGAR DOOR

MAIN CONTROL

PANEL FOR

HANGAR DOOR

N

L

E

AFFF ROOM 122

INTERCEPT EXISTING CONDUIT

NEAR DISCONNECT SWITCH,

PROVIDE NEW CONDUIT TO SWITCH

1200AT

1200AF

#3/0 IN 1 1/2" C. GEC

6 7

1200AT

1200AF

5 4

PULLBOX PULLBOX

1200AT

1200AF

SYSTEM VOLTAGE 480V, 3PH, 4W

PROPOSED

LOADS

MOTOR

SIZE, kW

NOMINAL

CURRENT, AMPS

DOOR 1 9.2

DOOR 2 4.6

DOOR 3 9.2

MULLION 1 2.8

MULLION 2 2.8

TOTAL 28.6

DEMAND FACTOR

DEMAND LOAD, AMP

PROVIDE 4#4, 1#8GR, 1 1/2"C. FEEDER

PROVIDE 80AT/150AF/3P

CIRCUIT BREAKER IN MCC.

CALCULATED V- DROP

16.6 8.3 16.6 5.7 5.7 52.9

1.25

66.13

2%

AB

N

C

A

A

B

BC

C

N

NG

G

GENSET

GFP

CIRCUIT

BREAKER

BYPASS

ISOLATION

4-POLE ATS

BOND TO

HOUSING

FR

OM

U

TI

LIT

Y

TR

AN

SF

OR

ME

R

1#3/0 GR 1#3/0 GR

3 SETS OF 4-400KCMIL, 1#3/0 GR.

SERVICE CONDUCTORS IN 4"C,

1-4" SPARE

3 SETS OF 4-400KCMIL, 1#3/0 GR.

SERVICE CONDUCTORS IN 4"C,

1-4" SPARE TO EXISTING MCC

GFP

CIRCUIT

BREAKER

Arch D SizeTitle

Sheet

Status Code of

Plot Date: Path and File Name:

Client

Conditions of Use This document and the ideas and designs incorporated herein, as an instrument of professional service, is the property of GHD. This document may only be used by GHD ’s client (and any other person who GHD has agreed can use this document) for the purpose for which it was prepared and must not be used by any other person or for any other purpose.

GHD Inc.

www.ghd.com No. Issue Checked Approved

Project Manager

Project Director

Drafting Check

Design Check

Author

Designer

Sheet No.

Project

Project No. Date Scale

Date

1"

Bar is One inch on original size sheet

14501 George Carter Way, Suite 102 Chantilly VA 20151 USA T 1 571 325 5000 W www.ghd.com

8/6/2026 3:29:27 PM \\ghdnet\ghd\US\Baltimore\Projects\565\12607256\Digital_Design\Revit 2024\12607256-GHD-632-IMP-MDL-EL-R24.rvt

As indicated E-501

BLDG 632 PARTIAL SINGLE-LINE

DIAGRAMS

Final 100%

182ND AIRLIFT WING, PEORIA AIR

NATIONAL GUARD

BLDG 734 & BLDG 632 REPAIR OF FIRE

SUPPRESSION AND HANGAR DOORS

JLQN202002 MARCH 27, 2026

IS

TG

ZM

ST

DR

ZM

TYPE B3 - 100% DESIGN SUBMITTAL

NOT TO SCALE1 BLDG 632 - PARTIAL ELECTRICAL SINGLE-LINE DIAGRAM - DEMOLITION

NOT TO SCALE2 BLDG 632 - PARTIAL ELECTRICAL SINGLE-LINE DIAGRAM - NEW WORK

KEYNOTES #

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

DEMOLISH EXISTING WIRING AND CONDUIT

ASSOCIATED WITH DOOR MOTORS.

GENERATOR REMOTE CONTROL PANEL.

PROVIDE 24 CONTROL WIRES IN 2"C.

BYPASS ISOLATION ATS, WITH TRANSFER TIME

DELAY, RATED 1000A, 480V 4-POLE, 4-WIRES,

65kAIC, NEMA 3R ENCLOSURE.

SOLID STATE ENCLOSED CIRCUIT BREAKER, WITH

GROUND FAULT PROTECTION , WALL MOUNTED IN

NEMA 3R ENCLOSURE, GROUND FAULT MAX

SETTING 240A.

EMERGENCY GENERATOR CONTROL TYPE -

UTILITY - GENERATOR WITH PREFERRED UTILITY

SOURCE.

EMERGENCY GENERATOR, 750kW / 900kVA, STANDBY RATED, 277/40V, 4-POLE, WITH INTEGRAL

FUEL TANK AND MAIN CIRCUIT BREAKER, PAD

MOUNTED. SEE PARTIAL SITE PLAN.

PROVIDE CAMLOCK MANUAL TRANSFER STATION

IN NEMA 4X STAINLESS STEEL PAD MOUNTED

ENCLOSURE. PROVIDE CAMLOCK ASSEMBLY

SUITABLE TO ACCEPT PORTABLE LOAD BANK

WIRING. COORDINATE WITH FINAL USER.

PORTABLE LOAD BANK AND CONNECTING WIRING

IS NOT PART OF THE PROJECT.

TEMPORARY/ALTERNATE SOURCE CONNECTING

POINT, NOT PART OF THIS PROJECT.

1 35% SUBMITTAL SJ 11-07-2024

2 REVISED 35% SUBMITTAL IS 09-22-2025

3 TYPE B1 (65%) SUBMITTAL IS 01-05-2026

4 TYPE B2 PRE-FINAL SUBMITTAL IS 03-02-2026

5 TYPE B3 (100%) SUBMITTAL IS 03-27-2026

1 PRE-BID INQUIRIES 08-07-2026

NOT TO SCALE3 4-POLE ATS CONFIGURATION DETAIL

B632 CoverSheet Addendum_1 2026-08-07
G-001 - BLDG 632 - COVER SHEET
B632 Fire Alarm Addendum_1 2026-08-07
FA-001 - BLDG 632 FIRE ALARM SYMBOLS, LEGEND, ABBREVIATIONS AND NOTES
FA-111 - BLDG 632 FLOOR PLAN
FA-401 - BLDG 632 ENLARGED PLANS & SECTIONS
FA-601 - BLDG 632 FIRE ALARM MATRIX & RISER DIAGRAM
B632 Fire Sprinkler Addendum_1 2026-08-07
FX-111 - BLDG 632 FLOOR PLAN
B632 Electrical Addendum_1 2026-08-06
E-001 - REFERENCE SHEET - ELECTRICAL
E-111 - BLDG 632 POWER PLAN
E-113 - BLDG 632 PARTIAL SITE PLAN
E-501 - BLDG 632 PARTIAL SINGLE-LINE DIAGRAMS

File details come from the government source that posted it. Updated .