TE 2.4 Fire Detection Protection Spreadsheet_Rev1.xlsx

XLSX spreadsheet 84 KB Posted

Attached to
Picatinny Arsenal Base Operations (BASOPS) Federal contract opportunity
Solicitation number
W15QKN-21-R-5005
Issued by
Department of the Army Materiel Command Contracting Command Picatinny Arsenal

About this file

This document contains a federal contract opportunity notification for solicitation number W15QKN-21-R-5005 for base operations services at Picatinny Arsenal. The solicitation seeks to provide base operations services and will close for proposals on February 2, 2021 at 2:00 PM EST. The solicitation is issued by the Department of the Army Materiel Command Contracting Command Picatinny Arsenal for base operations requirements at Picatinny Arsenal. Interested offerors are notified of the opportunity to submit proposals for these services prior to the closing date.

View the file

Other files for this federal contract opportunity

Other files attached to Picatinny Arsenal Base Operations (BASOPS), newest first.
File Type Posted
Recommended Sol Closing Instruction_PicaBASOPS_20210507.doc DOC document
W15QKN21R5005_Amendment 0006.docx DOCX document
DD Form 1423-1-A018 (Tree Srvc-Maint PMP)-REVISED.pdf PDF
Consolidated List of Questions (for publication) AMD 0006.xlsx XLSX spreadsheet
W15QKN21R5005_Amendment 0005.docx DOCX document
011.1-USAG Picatinny VGSA-DD 254 Continuation Sheet.docx DOCX document
08.1-Davis Bacon Wage Determination-Building-REVISION 01 (NJ20210038-1 Jan 21).pdf PDF
7.6-LRC Picatinny Maintenance SOP 2020-NEW.pdf PDF
DD Form 1423-1-A041 (Scheduled Pest Inspections-Work)-NEW.pdf PDF
DD Form 1423-1-A039 (HVAC Emergency Personnel Roster)-NEW.pdf PDF
DD Form 1423-1-A036 (Quarterly Visual Insp Report)-NEW.pdf PDF
DD Form 1423-1-A026 (Quality Control Report)-NEW.pdf PDF
DD Form 1423-1-A013 (Damage Report)-REVISION 01.pdf PDF
DD Form 1423-1-A007 (Key Control)-REVISION 01.pdf PDF
DD Form 1423-1-A004 (Accident Reporting)-REVISION 01.pdf PDF
TE 2.5 IDS Zones by Bldg_Rev1.docx DOCX document
TE 2.2 Attachment A Equipment List_2020_Rev1.pdf PDF
07.1-Preaward_Survey_of_Prospective_Contractor_Accounting_System_Checklist-NEW.pdf PDF
08.2-Davis Bacon Wage Determination-Highways-NEW (NJ20210002-1 Jan 21).pdf PDF
DD Form 1423-1-A043 (Schedule of High Pressure Boiler Inspections)-NEW.PDF PDF
DD Form 1423-1-A040 (Indoor Pest Control Management Program (IPCMP))-NEW.pdf PDF
DD Form 1423-1-A034 (Integrated Cont Plan (ICP) for Spill Control and Resp)-NEW.pdf PDF
DD Form 1423-1-A030 (Elevator Maint Schedule)-NEW.pdf PDF
DD Form 1423-1-A029 (Snow and Ice Removal Plan)-NEW.pdf PDF
DD Form 1423-1-A025 (Warranty Program Plan)-NEW.pdf PDF
DD Form 1423-1-A016 (Contractor Vehicles Registration)-REVISION 01.pdf PDF
DD Form 1423-1-A015 (Transition Plans)-REVISION 01.pdf PDF
DD Form 1423-1-A008 (Training Certificates)-REVISION 01.pdf PDF
DD Form 1423-1-A002 (PW Metrics)-REVISION 01.pdf PDF
DD Form 1423-1-A001 (Contractor Roster)-REVISION 01.pdf PDF
TE 3.13 Wash Rack Preventative Maintenance Checklist_Rev1.docx DOCX document
Consolidated List of Questions (for publication) post 20210303 thru 20210319.xlsx XLSX spreadsheet
TE 3.5 Picatinny Owned Lights on Base as July 22nd_Rev1.xlsx XLSX spreadsheet
21R5005 BASOPS Consolidated QAs-20210315 (pricing) published.xls XLS spreadsheet
W15QKN-21-R-5005 BASOPS Consolidated QAs-20200303 (published).xlsx XLSX spreadsheet
USAG Picatinny COVID-19 Questionnaire.docx DOCX document
0002 - Technical Exhibits 2.1-2.9 (9 each) - GFP-GFE-GFM.zip ZIP file
0003.1 - Technical Exhibits 3.1-3.15 (15 each) - FMI w-Facilities & Structures.zip ZIP file
0004 - Technical Exhibit - List of Picatinny Historic Buildings-Use and Distribution.pdf PDF
0006.1 - Technical Exhibits 6.1-6.4 (3 each) - Facilities Management & Real Property Pubs.zip ZIP file
0006.2 - Technical Exhibits 6.5-6.11 (7 each) - Environmental #1.zip ZIP file
0006.3 - Technical Exhibits 6.12-6.15 (4 each) - HAZMAT & Solid Waste.zip ZIP file
0003.3 - Technical Exhibits 3.20-3.29 (10 each) - Best Management Practices (BMP).zip ZIP file
0005 - Technical Exhibit - Support for Annual Events.docx DOCX document
0006.4 - Technical Exhibits - 6.16 - Picatinny Spill Response and Contingency Plan.pdf PDF
0011 - Technical Exhibits - 11.1-11.2 (2 each) - Affirmative Procurement.zip ZIP file
0014 - Technical Exhibits 14.1-14.10 (10 each) - Stormwater Mngmt Requirements.zip ZIP file
0000 - General SOLICITATION Exhibits (10 each).zip ZIP file
0001.1 - CLS-408-Pavement Clearance.docx DOCX document
0003.2 - Technical Exhibits 3.16-3.19; 6.2 (5 each) - Storm Prep and Snow Removal.zip ZIP file
Show all 50

Picatinny Arsenal Base Operations (BASOPS) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire Detection & Protection Sys

Building numberSub BldgSecLocationStatusSystem typeFire Panel ModelDialer ModelYear InstalledPass / FailLast AnnualRepairs Required
526PavOnCO2Kidde Aegis2015F5/14/20Need to fix nitrogen lines to dampers, (4) and refill nitrogen cylinder. Dampers stuck closed right now. Lockout valve needs to be adjusted. Oderizer needs to be checked for proper position. Batteries need to be replaced.
1MainFront ClosetOnDryVictaulic 768N2019P3/30/20
1NorthMech RoomOnDryVictaulic 768N2019P3/30/20
1SouthClosetOnDryVictaulic 768N2019P3/30/20
9Mech RoomOnDryVikingIP Dialer2012P12/8/20
10Mech ClosetOnDryVikingIP Dialer2012P1/22/20
18CMech RoomOnDryReliable - Model DP10/30/20
34HR OfficeOnDryTYCO DVP-1P5/22/20
45OnDryP5/20/20
61AMech RoomOnDry4" TycoP10/8/20
62AMech RoomOnDryTycoP2/6/20
62BMech RoomOnDryTycoP2/6/20
91CBoiler RmOnDryFirematicIP Dialer1997F4/30/20IJO needed -Dry system is not operating consistently and may not activate during fire. system is 40 years old and should be upgraded.

- Dry pendants are over 10 years old and need to be sent out for testing or replaced

(NFPA 25 5.3.1.1.1.6)

91AShippingOnDryVikingIP Dialer2015P4/30/20
91BShippingOnDryVikingIP Dialer2015P4/30/20
119AMech RoomOnDryTycoIP DialerP5/26/20
121AExterior ClosetOnDryTyco DPV11986P11/3/20
121BBsmtOnDryViking F-1P5/29/20
162AOnDryFirelock?P4/1/20
162BOnDryFirelock?P4/1/20
163AAtticOnDryViking Quick Response2011P1/24/20
172Mech RoomOnDryVictalvic S/756P6/1/20
183AMech ClosetOnDryVikingP2/25/20
302AMain Entr Dr3OnDryTyco DPW-12011P3/31/20
302CNorth Bay - Dry System COnDryTyco DPW-22011P3/31/20
315OnDryTyco DS-1????2012P6/16/20
351AOnDry?IP DialerP8/22/20
355Loading DockOnDryViking F-1Local Alarm Only2002P12/11/20
407BMech ClosetOnDry4" Firelock NXTIP DialerP6/1/20
458AHigh BayOnDryVictaulic 768NP2/5/20new dry valve installed 2019
526OnDryP8/3/20
617OnDryVictaulic 768N2019P6/30/20
636Bay DoorOnDry3" Viking F-12018P10/2/20
636Cmech roomOnDry4" viking F-12018P10/2/20
647OnDryVictaulic 768N2019P6/17/20new dry valve installed 2019
807AOnDryvictaulic 768N2020P9/10/20new dry system installed in 2020
1610OnDryTyco DPV-1?2010P11/18/20compressor replaced 8-7-2020
3228BsmtOnDryTyco DPV-11992P10/5/20
3248Mech RoomOnDryReliableP7/29/20
3305Janitor ClosetOnDryTyco DPV-1P7/6/20
3316BHigh BayOnDryTyco DPV-1?P10/15/20
3411OnDryP9/15/20
3500OnDryVictaulic 756IP DialerP6/2/20
3518Mech ClosetOnDryTyco DPU-1P6/22/20
12AMain AreaOnDry ChemicalNotifier FM200 RP2002P5/11/20
44AFloor 6/TowerOnDry ChemicalFike FE2272014F5/14/20system powered down as per customer. Non operational
61Com Rm 140AOnDry ChemicalFenwal Novac 1230Fenwal Net 60002011P5/14/20
95AMain AreaOnDry ChemicalNotifier FM200 RP2002?F5/11/20Conduits to vault need to be sealed Two det. in vault on zone 5 does not cause discharge.
173Switch RmOnDry ChemicalAnsul CY90 AutoPulse 442RP5/11/20
173Battery RmOnDry ChemicalAnsul CY90 AutoPulse 442RP5/11/20
303Melt RoomOnDry ChemicalAutoman INDX ABC-XI-50AF5/7/20Automan INDX ABC XI -50A (3 tanks) due for 6 year. Ansul 101-30 Cartridge due for replacement. 4 Nozzles are blocked. Pull station cable is not run . 2 links are not accessible-high-Only 4 out of 6 were changed. No local Alarm and not tied into Fire Alarm
316Locker 4OnDry ChemicalPyrochem InD ABCP5/8/20
316Locker 6OnDry ChemicalPyrochem InD ABCP5/8/20
316Locker 5OnDry ChemicalPyrochem InD ABCP5/8/20
316Locker 1OnDry ChemicalPyrochem InD ABCP5/8/20
526Pav1OnDry ChemicalKidde2015P5/14/20
526Pav2OnDry ChemicalKidde2015P5/14/20
526Pav3OnDry ChemicalKidde2015P5/14/20
526Pav4OnDry ChemicalKidde2015P5/14/20
3013BMain AreaOnDry ChemicalNotifier FM200 RP2002?F5/11/20Air does not shut down
3100Flam StorageOnDry ChemicalPyrochem PCI 50P5/8/20
3310OnDry ChemicalWK Industrial?P5/14/20
3316OnDry ChemicalPyro Chem?P6/13/19fire dept refused due to Covid19
1MainFront EntrOnFire AlarmIP Dialer2019P4/15/20
2Main EntrOnFire AlarmFirelite MS-9050 UDCIP Dialer2012P1/14/20
3Main EntrOnFire AlarmFirelite MS9200 UDLSBosch C900 IPP1/13/20
614Main EntrOnFire AlarmGE/Edwards EST-3IP Dialer2011P2/5/20
7Main EntrOnFire AlarmSimplex 4100ESIP Dialer2013P3/30/20
8O/S Elec RmOnFire AlarmNotifier NFS-320IP Dialer2013P2/25/20
9Main Elec RmOnFire AlarmSiemens Firefinder-XLSIP Dialer2012P1/29/20
10BOnFire AlarmFire Lite MS9050 UDIP DialerP6/9/20
10Main Elec RmOnFire AlarmSiemens Firefinder-XLSIP Dialer2012P2/7/20
10AOnFire AlarmSiemens Firefinder-XLSIP DialerP5/26/20
11Main EntrOnFire AlarmSilent Knight 5208IP DialerP1/27/20
12Lab AreaOnFire AlarmFirelite MS-9200UDLSIP DialerP9/23/19
13Main LobbyOnFire AlarmSilent Knight 5208IP DialerP1/28/20
17OnFire AlarmFirelite MS-5UDF12/20/19
18BOnFire AlarmSiemensIP Comm2013P4/10/20
18COnFire AlarmSiemensIP Dialer2013P11/2/20
18Main EntrOnFire AlarmPyrotronics CP35Noti-Fire 911AF12/8/20IJO Needeed - Disconnect switch for preaction system does not work, horn strobes need to be synchronized
19Main EntrOnFire AlarmSimplex 4100UIP CommP5/9/20
20Coffee RmOnFire AlarmFirelite ES-200X(Stand Alone System)P6/30/20
21Main EntrOnFire AlarmFirelite MS9200Bosch V465 IPP9/11/20
25Bay 3OnFire AlarmNotifier 500IP DialerP11/20/20
30Mech RmOnFire AlarmSimplex 4100 ESNoti-Fire 911A2011P10/27/20
31Main LobbyOnFire AlarmNotifier AM 2020IP DialerF9/1/20IJO needed to provide strobe synchronization - additional IJO for multiple deficiencies needed
33Main EntrOnFire AlarmSimplex 4100 UNoti-Fire 911A2011P7/21/20
34Rear KitchenOnFire AlarmFirelite 9200 UDLSNoti-Fire 911AP6/3/20
44Boiler RmOnFire AlarmSimplex 4100ESFire Lite 411UD2014F1/22/20Follow up to add devices to Fire Pump / Gnerator Building
45OnFire AlarmSimplex4010 ESP9/15/20
59Main EntrOnFire AlarmFirelite MS9200IP DialerP3/17/20
60Bay 1OnFire AlarmFirelite MS5210 UDIP DialerP10/19/20
61Main EntrOnFire AlarmSiemens Fire FinderIP Dialer2011P9/12/19
62Main EntrOnFire AlarmFirelite MS 9200 UDLS?P3/2/20
63OnFire AlarmFireliteES-200XP10/8/19
64Main EntrOnFire AlarmFirelite MS5210 UDIP CommF7/22/20IJO needed to add protection to newly renovated office ares C-9 and extend voice evacuation to south side of building.
65Main EntrOnFire AlarmNotifier 5000IP DialerP12/30/19
67Main EntrOnFire AlarmFirelite 9050 UD?2011P3/9/20
68OnFire AlarmFireliteP6/30/20
79Main AreaOnFire AlarmSimplex 4001(NO DIALER)P7/23/20Per Fire Department inspection, install fire and smoke detectors on main floor and basement
84OnFire AlarmFireLite MS-5UDIP2016P3/5/20
91Main EntrOnFire AlarmSimplex 4100 UIP Dialer2011P2/20/20Existing notification devices operate properly, but they do not provide compliant coverage and are ineffective in many areas. IJO requested to install compliant coverage.
92LobbyOnFire AlarmFirelite Miniscan 4024IP Dialer2014P3/31/20
93Floor 1OnFire AlarmSiemens MXLIP DACTP1/31/20Initiating devices on floors 1 - 3 have a long delay prior to activating an alarm condition. This code violation requires an IJO to replace the system
94Front LobbyOnFire AlarmPyrotronics CP400411UD Dialerc. 1968P6/2/20IJO required for add'l notification devices and to replace panel
95Front EntrOnFire AlarmSimplex 4100 UIP Dialer2013F10/2/20IJO needed to replace sub-panel
110KitchenOnFire AlarmSimplex 4010?2010P5/20/20
118Utl Rm 14AOnFire AlarmFirelite Sensiscan 1000Ademco 4120XMP5/5/20
119Bsmt GarageOnFire AlarmFirelite MS 9200 UDLSIP DialerP7/28/20
120Main EntrOnFire AlarmGamewell Zans 400(Stand Alone System)F3/16/20IJO needed to replace panel and field devices in order to resolve inspection deficiencies
121Main EntrOnFire AlarmSilent Knight 5208IP DialerP7/23/20
121AMain EntrOnFire AlarmFirelite MS 9050 UDIP DialerP1/6/20
151Elec RmOnFire AlarmSimplex 4100 U ESIP Dialer2012P4/22/20
162OnFire AlarmSiemens XLS?P2/27/20
163OnFire AlarmFire Lite MS 9200 UDLSP3/11/20
169Elec RmOnFire AlarmSiemens FS 250Firewatch 411UDP6/25/20
172Front EntrOnFire AlarmSilent Knight 5208IP DialerP6/22/20
173Dispatch EntrOnFire AlarmFire Lite 9200 UDLSIP Dialer2017P4/14/20
174Main EntrOnFire AlarmSimplex 4001Noti-Fire 911AP3/13/20No Smoke Detection, only 2 Pull Stations
175Main EntrOnFire AlarmFirelite MS-9200 DLSIP DialerP9/12/20
176Main EntrOnFire AlarmEdwards 6616/6632IP DialerP10/26/20
183Media RmOnFire AlarmSilent Knight 5208IP DialerP4/8/20
217OnFire Alarm
221Mech ShedOnFire AlarmFirelite MS-5UDIP Dialer2013P8/6/20Follow up order entered to replace dialer
225Fire AlarmStand Alone SystemLocal Alarm OnlyF5/15/20IJO to Install Monitored Fire Alarm System
237Control RmOnFire AlarmAuto Pulse Z-10Noti Fire 9112012F7/22/20No Dialer - No phone lines or IP comm's in building - Needs to be run to other building
240Main EntrFire AlarmStand Alone SystemLocal Alarm OnlyF5/15/20No fire protection in bldg, only bell controlled by switch - Recommend fire protection be installed in bldg
256Center EntrOnFire AlarmGamewell 7887IP Dialer2012P7/27/20
266Main EntrOnFire AlarmFirelite MS 10 UDP5/13/20Recommend heat detector in kitchen and horn strobes/detectors in back room - relocate zone 1 detectors
302Main Entr Dr3OnFire AlarmFirelite MS 9200 UDDACT2014P6/29/20
303OnFire AlarmSimplex 4100 ESPhone LinesP2/19/20
307Main EntrOnFire AlarmFirelite MS 9200 UDDATCP7/1/20
312319320319 Main EntrOnFire AlarmFirelite ES200XIP Dialer2020F6/17/20new Fire alarm installed 2020
315Main EntrOnFire AlarmFirelite MS 9200 UDLSDATC?P7/8/20
316Main EntrOnFire AlarmNotifier SFP1024Bosch B002568FP8/6/20recommend more notification devices to bring up to current code
318Main EntrOnFire AlarmFirelite MS 5210 UDNoti-Fire 911AP7/14/20
322Main CorrOnFire AlarmFire Lite MS9050 UDNoti-Fire 911A2012P9/15/20
323Mech RmOnFire AlarmSiemens Firefinder-XLS(Stand Alone System)2012P7/17/20
329Main EntrOnFire AlarmFirelite MS 9200Bosch B0025652P7/21/20
337Kitchen ExitOnFire AlarmFirelite 9200UDLSNoti-Fire 911AP12/11/20
351OnFire AlarmSimplex 4100ESIP Dialer2014P1/24/20
354Main LobbyOnFire AlarmFirelite Sensiscan 2000IP DialerF7/30/20IJO needed for panel replacement
355Main LobbyOnFire AlarmPyrontronics CP400IP DialerP5/15/20
382Main LobbyOnFire AlarmSilent Knight 5208P6/24/20
403OnFire AlarmFireliteMS9050P9/8/20
407E Wing Jan ClosetOnFire AlarmFCI FC-72IP DialerF7/20/20IJO needed - life span of smoke detectors is exceded, replacement of duct detectors is also needed
455Main EntrOffFire AlarmFirelite Sensiscan 1000IP DialerF7/7/20System has internal component failures. Panel is obsolete, parts are not available
458OnFire AlarmNotifierIP CommP11/17/20
472Main EntrOnFire AlarmNotifier SGL-404IP DialerP7/15/20
526Cntrl Rm 155OnFire AlarmSimplex 4100 UIP DialerP10/5/20
604EOnFire AlarmFirelite MS-10UD2013P7/9/20
611Main EntrOnFire AlarmFirelite MS 10UDIP DialerP8/19/20
617Main EntrOnFire AlarmFirelite 4050 UDIP Comm2010P7/20/20
617AOnFire AlarmP9/1/20
630BOnFire AlarmSF50IP DialerP8/25/20
647OnFire AlarmSimplex 4100ESIP DialerP9/6/20
660Main EntrOnFire AlarmFireliteBosch IPP8/31/20
660AOnFire AlarmSimplex 4010 ESP9/1/20
717OffFire AlarmF5/15/20not in service - IJO Required for demolition, engineering, and installation
800OnFire AlarmViking Par-3P7/9/20
806Fire AlarmStand Alone SystemLocal Alarm OnlyF5/15/20Bldg has local 120v pull station and A/V system only - IJO needed for new FACP
820northsideOnFire alarm2018P8/24/20new system installed 2018
908Elec Rm 3OnFire AlarmGamewell Zams 200P7/13/20
911Main AreaOnFire AlarmEdwards EFS-CP9/9/20
914Main AreaOnFire AlarmEdwards EFS-CP9/9/20
1029Main Elec RmOnFire AlarmFirelite MS-92004-DIS?P9/17/20
1053OnFire AlarmFirelite MS 521 UDIP Comm?P6/10/20
1090AOnFire AlarmFire Lite 9050 UD?2012P6/10/20
1090Main EntrOnFire AlarmSimplex 4100 ESIP Dialer2012P5/28/20
1136OnFire AlarmFirelite MS 5024 UD?P6/5/20
1176Main EntrOnFire AlarmSimplex 4100 ESIP Dialer2012P7/22/20
13011301
1308Room 146OnFire AlarmNotifier NFS 3030ND2013P10/25/19
1307Main AreaOnFire AlarmNotifier NFS 3030ND?2012P10/16/20
1403Control RmOnFire AlarmNotifier 5000(Stand Alone System)P11/16/20
1406Utility RmOnFire AlarmFirelite ES200XFirewatch 411UD2020P11/3/20new fire alarm installed 2020
1407Utility RmOnFire AlarmNotifier NFS 640Firewatch 411UD2013P11/19/20
1408Utility RmOnFire AlarmNFS 640Firewatch 411UD2013P11/4/20
1408CControl RmOnFire AlarmFirelite 9200 ULSFirewatch 411UD2013P11/6/20IJO need to provide IP Drop for central station and to Install Dialer and Program Central Station
1411Elec/Mech RmOnFire AlarmNotifier NFS 3030NDFirewatch 411UD2013F11/5/20Panel has Program courupt trouble. Replacement is rocommended
1412Control RmOnFire AlarmFire LiteMS-SLD2013P11/9/20
1417Elec Rm 338OnFire AlarmNotifier NFS 640Firewatch 411UD2013F11/10/20Follow up to Repair Dialer - IJO needed to replace panel
1461AUtility roomOnFire AlarmFirelite ES200X2019P9/26/19new system installed
1463Front ClosetOnFire AlarmHoneywell E32019P7/28/20
1501FACP RmOnFire AlarmFCI FC72(Stand Alone System)P9/9/19
1516Main EntrOnFire AlarmEST EST-3Fire Watch 4112013P7/15/20
1530OnFire AlarmFirelite MS 5210 UDIP DialerP7/15/20
1610OnFire AlarmFirelite MS 9050 UDIP Dialer2010P2/24/20
3002Main EntrOnFire AlarmSimplex 4100 UIP Dialer2010P5/22/20
3006OnFire AlarmStand Alone SystemLocal Alarm OnlyP6/12/20
3008Front EntrOnFire AlarmFirelite MS 9050 UDIP DialerP6/15/20
3021Main Elec RmOnFire AlarmFire-Lite MS-10UD-7IP DialerP7/24/19
3022Front vestibuleOnFire AlarmGameWell FCI E3/MNSIP Dialer1/8/20p1/8/20
3024Main EntrOnFire AlarmFaraday MPC 2000?F10/22/20IJO needed to Repair or replace existing dry pipe fire suppression system for building.
3028Elec Rm 139OnFire AlarmNotifier MD4Ademco 4120XM2019F11/29/19Disabled due to construction - system will be restored to normal and passed
3029Elec Rm 3OnFire AlarmSimplex 4002Firewatch 411UDF12/13/19IJO needed to interface fire alarm to B3028
3050Main EntrOnFire AlarmSiemensBosch C900V2P10/8/20
3100Main EntrOnFire AlarmNotifier 500Noti-Fire 911AF3/19/20IJO needed to replace panel and dialer
3114WarehouseOnFire AlarmFirelite MS9000UDLSBosch V465 IPP7/23/20
3124Main EntrOnFire AlarmFirelite MS9050UD2010P7/2/20
3128OnFire AlarmFirelite 9200 UDLSP3/6/20
3150Nautilus RmOnFire AlarmSimplex 4100ESIP Dialer2013P6/24/20
3153Room 115OnFire AlarmGamewell FCI 7100-2IP DialerP5/18/20
3156Mech Rm 115OnFire AlarmHoneywell FCI 7100IP DialerP9/12/20
3159Main EntrOffFire AlarmPotter PFC Series 4000Noti-Fire 911AF9/12/20new fire alarm being installed 2021
3173Bldg 3177OnFire AlarmSiemens Firefinder-XLSIP Dialer2012P8/11/20horn strobe needed above panel (completed on service order)
3208OnFire AlarmSimplex 4100ESIP Dialer2013P7/10/20
3215OnFire AlarmP7/10/20
3221Main EntrOnFire AlarmSimplex 4006DACTP5/12/20
3225Elec RmOnFire AlarmSecurtron Modul-R RMR2616BPhone LinesP6/16/20
3227Elec Rm Bld 2OnFire AlarmSimplex 4100 UNoti-Fire 911AP5/8/20
3228Main EntrOnFire AlarmFireLite 9200 UDLSIP Dialer2017P8/13/20
3248Stor RmOnFire AlarmSilent KnightIP Dialer2013P8/12/20
3305Main EntrOnFire AlarmFirelite MS 10UD(Stand Alone System)2013P8/7/20Need to replace outside bell
3306OnFire AlarmGamewell E3DACT at Node 1P2/18/20
3308OnFire AlarmGamewell E3(DACT at Node 1 in B3306)P2/11/20
3310OnFire AlarmGamewell E3(DACT at Node 1 in B3306)P2/12/20
3316Main AreaOnFire AlarmFirelite MS-92004DLSIP DialerP6/26/20
3324Main EntrOnFire AlarmSilent Knight 5208Noti-Fire 911AP9/15/20IJO recommended for additional strobe lights and smoke detectors
3328Main EntrOnFire AlarmSilent Knight 6820EUSNoti-Fire 911AP8/14/20
3329Main EntrOnFire AlarmSilent Knight 5208Fire Watch 411P1/2/20Warehouse section has no detection
3355OnFire AlarmSimplex 4100UDialer?P1/16/20
3356OnFire AlarmSimplex 4100UBosch C900?P1/15/20
3360OnFire AlarmSimplex 4100 U??P1/17/20
3409Rear EntrOnFire AlarmHoneywell 1000IP DialerP8/4/20
3410Main EntrOnFire AlarmFirelite MS-90200 UDLSIP DialerP8/3/20recommend replacing smoke detectors
3411OnFire AlarmSiemens MXLIQIP Comm2014P1/10/20
3500FoyerOnFire AlarmFirelite 5210 UDIP DialerP7/24/20
3501Main EntrOnFire AlarmSilent Knight 5208IP DialerP8/17/20
3510Main EntrOnFire AlarmSilent Knight 5208IP DialerP8/18/20
3518Conf RmOnFire AlarmFirelite MS 5024 UDIP DialerP8/10/20recommend office by IT room have a smoke detector/lab area should have more notification devices
3720OnFire AlarmStand Alone SystemISD Only2013P5/19/20
3721OnFire AlarmStand Alone SystemISD Only2013P5/19/20
3722OnFire AlarmStand Alone SystemISD Only2013P5/19/20
807AOnFire AlarmSilent Knight2020P9/17/20Alarm system installed 2020
810OnFire alarmFirelite ES-200-X2020P10/1/20new fire alarm installed 2020 10/2020
12CPU Lab AreaOnFM2002018P5/14/20
31AARMAGOnFM200?IP Dialer2018F11/15/18No testing since 2018 comissioning
34ClosetOnHoodKidde WHDRP5/6/20
34Pizza SideOnHoodKidde WHDRP5/6/20
34Main kitchenOnHoodAnsul R1022012F5/6/20Actuation gas line needs a safety vent relief / Alarm not functioning / Multiple duct nozzles need bracing
121By Ice ChestOnHoodKidde WHDRP5/7/20
169Kitchen LeftOnHoodAnsul R102P6/13/19fire dept refused due to Covid19
175LeftOnHoodPyrochem PCL240F5/7/20NL nozzles need changing / Electric shut off not functioning not tied to FACP
337Behind FridgeOnHoodKidde WHDRP5/7/20
1176LeftOnHoodPyrochem PCL460IP DialerP5/7/20
3153RightOnHoodAnsul R102P5/6/20
3156Rm 102OnHoodAnsul R102P5/6/20
3156FrontOnHoodAnsul R102F5/6/20Needs module for alarm contacts (FCI Gamewell panel)
3225LeftOnHoodBadgerF5/6/20No makeup air shutdown / electrci range does not shutdown
3227RightOnHoodAnsul R102P5/6/20
7Room 130OnHS DelugePyrotechIP DialerP6/16/20
217OffHS Deluge20187/9/20
237RM 1OnHS DelugeTFS2012P6/17/20
237Rm 2OnHS DelugeTFS2012P6/17/20
238OnHS DelugeTFS2012P6/17/20
252OnHS DelugeF7/20/20Repair HSD valve 1 zone 7 room 8
427Room 6OnHS Deluge?P6/15/20
427Room 20OnHS Deluge?F6/15/20Detector 2 in fault
526Panel 2Room 125OnHS DelugeReliable Model F12019P6/8/20
526Panel 2Room 127OnHS DelugeReliable Model F12019P6/8/20
526Panel 2Room 156OnHS DelugeReliable Model F12019P6/8/20
526Panel 2Room 157OnHS DelugeReliable Model F12019P6/8/20
526Panel 2Room 158OnHS DelugeReliable Model F12019P6/8/20
526Panel 1Room 120OnHS DelugeReliable Model F12019P6/8/20
526Panel 1Room 160OnHS DelugeReliable Model F12019P6/8/20
526Panel 1Room 162OnHS DelugeReliable Model F12019P6/8/20
526Panel 1Room 109OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 135OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 136OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 137OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 138OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 139OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 140OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 145OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 146OnHS DelugeReliable Model F12019P6/8/20
526Panel 3Room 147OnHS DelugeReliable Model F12019P6/8/20
604COnHS DelugePyrotech CPF 74F7/6/20room 7 detector 2 needs to be replaced
617GOnHS DelugePyrotech CPF 74F7/6/20Nozzle 12 in zone 5 needs repair
636FOnHS DelugePyrotechP7/1/20
636GOnHS DelugePyrotechP7/6/20
810OnHS Deluge?P6/18/20
816Rm 5, 6, 7OnHS Deluge?P9/10/20
1301Panel BOnHS Deluge?P6/24/20
1301Panel AOnHS Deluge?F6/24/20Panel needs to be replaced internal ground fault
1301Panel DOnHS Deluge?P6/29/20
1301Panel COnHS Deluge?P6/24/20
1403Control RmOnHS Deluge?P6/23/20
1408COnHS DelugeP6/1/20new panel installed 2020
1408OnHS DelugeP6/23/20
1411OnHS DelugeF6/23/20need to repair Trouble shoot room 323 Zones 6,7,8 and 9. Detectors in fault.
1417BOnHS Deluge?P6/24/20
1516OnHS DelugeF6/16/20Follow up - 1) Building 1516 needs all high speed valve replaced and nozzles relocated to provide proper coverage.

2) The system response time exceeds 100 milliseconds new deluge valves will correct issue.

3) System does not automatically reset. Pilot lines need to be reconfigured.

3022Lab COnHS DelugeP6/15/20
2Sprink RmOnPreactionNotifier RP-1001IP Dialer2012P1/23/20
8Mech RmOnPreactionFirelockP3/10/20
12BUtil ClosetOnPreactionViking E-11997P6/25/20
18BOnPreactionFirematic1993P10/30/20
31ARoom 402OnPreactionViking E-1IP Dialer2001P6/23/20
31HRoom 301OnPreactionViking E-1IP DialerP6/24/20
31DRoom 23OnPreactionViking E-1IP Dialer2003P6/24/20
31BRoom 104OnPreactionViking E-1IP Dialer2002P6/24/20
31CRoom 208OnPreactionViking E-1IP Dialer2001P6/30/20
44ABoiler RmOnPreactionViking E-12002P5/21/20
59Front HallwayOnPreactionTyco Dry2011P5/20/20
95CNorthOnPreactionVikingP7/29/20
95Optics LabOptics LabOnPreactionVictaulic Fire Lock NXTP7/29/20
95BSouthOnPreactionViking1997P7/29/20
236OffPreaction?F10/8/20The sprinkler system is partially demolished, turned off, and unmonitored. The system was inherited in this state. The corrective action would be to completely demo and rebuild a suppression system rated for its environment. An alarm system is also needed for monitoring.
329Bldg FrontOnPreactionViking1999P6/8/20
351NCOverhead DrOnPreactionViking E-1IP Dialer1997P8/22/20
351SBSide of BldgOnPreactionViking E-1IP Dialer1996P8/22/20
407AUtil ClosetOnPreactionViking E-1IP Dialer1987P6/1/20
717OffPreactionViking1995F12/11/20System out of service - cannot perform inspection. System requires complete replacement.
800OnPreactionViking E-11994P6/8/20
1090OnPreactionTyco TY-B?2012P4/28/20
3024BSprink RmOnPreactionViking E-11997P8/5/20
3029Riser RmOnPreactionViking E-11995P7/29/20
1530OffSuppressionIP Dialerdry system removed, no sprinkler system 5/21/2014
3316OnSuppression
1MainBasementOnWetShotgun valve2019P3/30/20
1AnnexMech RoomOnWetShotgun valve2019P3/30/20
614Mech RmOnWetTyco AV-1P2/25/20
7BBldg FrontOnWetViking H-2IP DialerP2/10/20
9Mech RoomOnWetVikingIP Dialer2012P12/8/20
10Mech ClosetOnWetEasy Check RiserIP Dialer2012P1/22/20
11OnWetAutomaticP12/11/20
12AMech RmOnWetAutomatic1977P6/19/20
13AProcurementOnWetVikingIP DialerP3/16/20
13BLunch RmOnWetAutomaticIP DialerP3/16/20
15fire pump roomOffWetnew system installed 2021
17OnWetVictavillicP9/14/20
18CMechOnWetP9/14/20
18AOnWetFirematic1993P10/30/20
18BMech RoomOnWetEasy CheckP11/2/20
25OnWetViking2000P11/20/20
31GHigh BayOnWetViking J-1IP DialerP6/23/20
31EChiller BldgOnWetViking J-1IP Dialer2001P6/24/202/4/00
31FRoom 15OnWetViking J-1IP Dialer2003P6/24/20
60Corner WhseOnWetTycoP7/1/20
61BMech RoomOnWet6" Riser ManifoldP10/8/20
61CMezz AreaOnWet4" Riser ManifoldP10/8/20
67OnWetVictaulic?2011P2/10/20
84OnWetFirelock 747P2/12/20
95AOnWetVictraulicP7/29/20
95DHigh bay warehouseOnWetGrinnell Model A1959P7/29/20
119BMech RoomOnWetIP DialerP5/26/20
121ABsmtOnWetReliable Model E1986P5/29/20
162COnWetVictaulic?P4/1/20
163BFirst FloorOnWetViking MICROFAST2011P1/24/20
169Mech RoomOnWetVictaulicP10/13/20
172Mech RoomOnWetEasy Check Mod EP6/1/20
175Mech RmOnWet4" CSC1997P9/15/20
183BMech RoomOnWetVikingIP Dialer2002P2/25/20
217AOnWet6" Victaulic 751201810/6/20
221OnWetVikingP7/1/20
238Bldg FrontOnWetVictaulic 7512012F7/1/20IJO needed to Install Fire Alarm Panel to interface and monitor sprinkler system
252OnWetTyco2005P7/1/20
256Center EntrOnWetReliableP7/1/20
302BNorth BayOnWetVictaulic2011P3/31/20
303OnWetFirematicP2/3/20
307Mach ShopOnWetP6/16/20
316OnWetViking1999P6/16/20
318Main EntrOnWetP6/17/20
217BOnWet4" Firelock NXT 768201810/6/20
325RearOffWetViking2020new system installed 2020
427BRoom 7OnWetVictaulic 751P6/30/20
427ARoom 24OnWetAutomaticP6/30/20
429AOnWetAUTOMATIC1966P6/30/20
429BBack LabOnWetAUTOMATIC1966P6/30/20
436OffWetVictaulic2000F3/17/20System is off due to no heat
458BPump RoomOnWetRiser onlyP2/5/20
458CPump RoomOnWetRiser onlyP2/5/20
477Mech RoomOnWetAutomatic1945F6/30/20IJO needed to add FACP - not monitored by central station
526Mech RoomOnWetTyco AV-1P8/3/20
604CSect BOnWetTYCO AV-1P7/1/20
604CSect AOnWetTYCO AV-1P7/1/20
607A-Afront doorOnWet2" riser check2018P10/15/18
607A-Bfront doorOnWetreliable DDX 2" deluge valve2018P10/15/18
617GRoom 2OnWetTYCO AV-12008P8/19/20
623GPump HouseOnWetSwing checkP7/1/20
631Chiller RoomOffWetTYCO2008F10/8/20Riser access is blocked
636Amech roomOnWet4" Viking F-12018P10/2/20
636Bmech roomOnwet4" Viking J-12018P10/2/20
636Emech roomOnWet4" Tyco CV-1F2018P10/2/20
636Fmech roomOnWet4" Viking F-12018P10/2/20
636GMech RoomOnWet4" Viking F-12018P10/2/20
660APump RoomOffWetAUTOMATICP7/24/2012/14/2020 no heat
660Mech RmOffWetVikingP7/24/2012/14/2020 no heat
809OnWetTyco2013F6/19/20IJO Required for Installation work to Interface WF & Tmprs to FACP
810Aelevator mechnical roomOnWetVictualic S751F6/18/20IJO Requested to replace WF Bell and to integrate horn strobes
810Bfront of bldgOnWetVictaulic Fire lockF6/18/20IJO Requested to replace WF Bell and to integrate horn strobes
813Bldg FrontOnWetTyco AV-1F6/18/20
816ABldg FrontOnWetTyco AV-1P8/16/20
816BOnWetTyco2005P8/16/20
820OnWetVikingP6/15/20
900OnWetHedgmen1949P7/22/20
908Mech RoomOnWetVictaulicP7/22/20
1029Bldg FrontOnWetVictaulic 7512007P7/2/20
1090AOnWetTyco TY-B?2012P4/28/20
1301Mech RoomOnWetTycoP11/13/20
1307Mech RoomOnWetTycoP7/28/20
1403Back LabOnWetGem1944P9/11/20
1406OnWetTycoP9/30/20
1407Mech RoomOnWetTycoP9/11/20
1408CMech RoomOnWetTycoP7/28/20
1408OnWetTycoP7/28/20
1411Mech RoomOnWetTycoP7/28/20
1417Mech RoomOnWetTycoP6/30/20
1461AUtility roomOnWet2019Pnew system installed
1463AOnWetReliable1996P11/23/20
1516Mech RoomOnWetTyco?P7/24/20
1530OnWetTycoP7/24/20
3022AMech RmOnWetAutomatic1976P8/5/20
3022BMech RmOnWetAutomatic1977P8/5/20
3024ASprink RmOnWetFirematic Model L1997P8/5/20
3028Riser RmOnWetAUTOMATIC AP8/19/20
3050AGarageOnWetVictaulic2017P8/4/20
3050BGarageOnWetVictaulic2017P8/4/20
3106GarageOnWetP10/8/20
3109GarageOnWetP10/8/20
3111Back of BldgOnWetP10/1/20
3124OnWet2010P6/17/20
3145OnWetP10/1/20
3150DGymOnWetCentral2013P4/29/20UL testing passed test again in 2025
3150BFront LeftOnWetCentral2013P4/29/20UL testing passed test again in 2025
3150CFront CenterOnWetCentral2013P4/29/20UL testing passed test again in 2025
3150AL Rear CornerOnWetCentral2013P4/29/20UL testing passed test again in 2025
3150FRear CenterOnWetCentral2013P4/29/20UL testing passed test again in 2025
3150EShippingOnWetCentral2013P4/29/20UL testing passed test again in 2025
3153Mech RoomOnWetVictaulicP4/28/20
3156Mech RmOnWetVisctaulic S/751P4/28/20
3159fire sprinkler roomOffWetnew Fire sprinkler system installed 2021
3225Elec RmOnWetRASCO 4" 705A2001P4/28/20
3306OnWetVictraulic?P12/10/20
3308OnWetVictraulic?P12/21/20
3310OnWetVictraulic?P2/13/20
3316AHigh BayOnWetTyco AV-1?P10/15/20
3328OnWetVictaulicSystem Sensor 2-WT-B2016P6/17/20
3329Rear EntrOnWetGem Model F2001F12/9/20Bay Area Missing Coverage. 8 Pendent Heads need to be removed / Changes to the bldg layout requires a redesign
3355APump HouseOnWetP11/15/20
3355Mech RoomOnWetTyco??P11/15/20
3356OnWetTycoP11/12/20
3360OnWetTycoP11/12/20
3409BsmtOnWetRASCO Model EIP Dialer1992P6/19/20
3410Sprink RmOnWetCentralIP Dialer1992P7/24/20
3411OnWet-P9/15/20
3501Behind GateOnWetVictaulic CVBIP DialerP6/22/20
3510Util ClosetOnWetAUTOMATICIP DialerP6/22/20
Systems in Green are currently ON
Systems in Yellow are ON and operational but are OVERDUE FOR INSPECTION
Systems in Orange are ON and operational but REQUIRE REPAIRES
Systems in Red are currently OFF
Systems in Gray are OFF and are UNDER CONSTRUCTION
Systems in Blue are OFF and Not Required
**Note: P/F markings indicate whether the system passed or failed the most recent inspection and have no effect on the system's status

Fire Protection and Detection Systems Picatinny Arsenal, NJ

Fire Protection and Detection Systems Picatinny Arsenal, NJ

Fire Protection and Detection Systems Picatinny Arsenal, NJ

Fire Protection and Detection Systems Picatinny Arsenal, NJ

Fire Protection and Detection Systems Picatinny Arsenal, NJ

08/16/2013

06/12/2012

06/12/2012

06/12/2012

&D

Fire Pumps

BUILDING NUMBER-4493458623630B660A80813013029C3355A
PUMP MFR-PEERLESSAURORAPATTERSONAC FIRE PUMPITT A-CAURORAFLOWAYFAIRBANKS MORSE
SHAFT TYPE-HORIZONTALHORIZONTALCENTRIFICALHORIZONTALHORIZONTALVERTICALHORIZONTALFromSubjectReceivedSizeCategories
MODEL #-6AEF16N481-SF6X5X17SSC07-05059100481 BG18MKL-FP2823AFAmami, Robert M CIV USARMY ID-SUSTAINMENT (USA)FW: ICE | https://ice.disa.mil/index.cfm?fa=site&site_id=401 (UNCLASSIFIED)11:20 AM17 KB
SHOP OR SERIAL #-56297279-67809FP-C096 46479-01-01 / QKE66103-123456-01-01/QK000112-2202501F55467-1-1K4D1025110
GPM-10001500100020003000150030002500
RATED HEAD/FT-1961151612816369323352185
RATED PSI-855070122160140152.41680
RATED RPM-17801750178017851785177017602100
DRIVER MFR-US ELECTRICMARATHONWEGEMERSONWEGCATERPILLARCUMMINS
TYPE-ELECTRICELECTRICELECTRICELECTRICELECTRICDIESELDIESEL
MODEL #-AD03JM364060180P3E 364TSAR54444/5TS34066BTA59F1
SHOP OR SERIAL #-F04-AD03-M965383-11/13-31007183237D200EZFS10138834026TB2275345244744
RATED VOLTS-230/460230/460230/460460460460N/AN/A
OPER. VOLTS-208460460460460N/AN/A
HORSE POWER-756030200400200430208
RATED RPM-17851775178017851750178021002100
DRIVER RATED AMPS-1727570.2235225N/AN/A???
PHASE-333333N/AN/A
AMPS AT 150%-000N/AN/AN/A
CYCLES-6060606060N/AN/A
SERVICE FACTOR-1.151.151.151.151.15N/AN/A
CONTROLLER MFR-FIRETROLJOSLYN CLARKLMR EATONMETRONJOSLYN CLARKJOSLYN CLARKFIRETROL
MODEL #-FTA 1000G2C184-53RFT90-60D-L1MP700-200-480C63C234-53RA10710FTA1100-EL12N
SHOP OR SERIAL #-101802-002-01-0134092816BK836ENA-07M36482-11344062254661159419
AUTO START PSI-4075120651309060
STOP PSI-N/A140N/AN/A145N/AN/A
JOCKEY PUMP START-90N/A130120145127100
JOCKEY PUMP STOP-110N/A160150160165145
CITY SUPPLY-N/A96psi80psiN/AN/AN/A32psi
CONNECTION SIZE-8"8"8"10"8"10"12"
TANK SUPPLY-YESN/AN/AYESYESN/AN/A
TANK HEIGHT-22'N/AN/A16'26'N/AN/A
TANK CAPACITY-0N/AN/A6 TANKS @ 55K100000POND SUPPLYN/A
INSPECTION DATE-Sep-20Sep-20Sep-20Sep-20Sep-20Sep-20Sep-20Sep-20Sep-20Sep-20
INSPECTION STAUS-PASSPASSPASSPASSPASSPASSPASSPASSPASSPASS
tank water level gauge broken SAME ISSUE AS 5/2/12 & 5/10/13 INSPECTIONS, settings need to be changed, casing relief valve needs replacement, os&y valve needs replacement (YELLOW TAGGED)
Pump-2014-05-13P05/13/2014bypass valves are shut but cannot be left open, no jockey pump, need to cut in a 5" butterfly valve on test header SAME ISSUES AS 5/2/12 & 5/10/13 INSPECTIONS (YELLOW TAGGED)ARDEC
44BOnFire PumpPeerless 6AEF16NPump-2014-05-13P05/13/2014transducer needs replacement (GREEN TAGGED)ARDEC
93OnFire PumpAurora 481-SFPump-2014-05-14P05/14/2014negative pressure on intake, display unit is blank, need to check timer OVERDUE INSPECTION (NO ACCESS)ARDECGordon James, X2729637 admin, not incl. visitors
458OnFire PumpPatterson 6X5X17SSCIP DialerPump-2012-05-24P05/24/20122011 new system installed OVERDUE INSPECTION (NO ACCESS)DPW
623OnFire PumpAC FIRE PUMP 07-0505?2011-?jockey pump discharge piping incorrect, sensing lines for pump and jockey pump need to be corrected, angle hose valve is split (YELLOW TAGGED)
630BOffFire PumpITT A-C 9100?2013Pump-2014-05-16P05/16/2014not in service - IJO Required for demolition and installARDEC
660AOnFire PumpAurora 481 BG?2016-07F07/01/2016gauges need to be replaced both lines (YELLOW TAGGED)ARDEC
717OffFire Pump?Pump-2014-05-16P05/16/2014sensing lines are steel and do not have check valves but have control valves, SAME ISSUES AS 5/4/12 & 5/10/13 INSPECTIONS pump settings should be changed (YELLOW TAGGED)ARDEC
808OnFire PumpFloway 18MKL-FPPump-2014-05-13P05/13/2014gauges are over 5yrs old, bypass needs to be installed properly or removed (YELLOW TAGGED)DPW
3029COnFire PumpFairbanks Morse 2823AFPump-2014-05-13P05/13/2014OVERDUE INSPECTIONCommissary
3355OnFire PumpITT-AC 8X6X12F?-?acts a a service pump but should be serviced and inspected the same way as a FP. Need to determine adding to Chugach contract - forwarded to Mr. Havrisko for review.