TE 2.4 Fire Detection Protection Spreadsheet_Rev1.xlsx
XLSX spreadsheet 84 KB Posted
- Attached to
- Picatinny Arsenal Base Operations (BASOPS) Federal contract opportunity
- Solicitation number
- W15QKN-21-R-5005
About this file
This document contains a federal contract opportunity notification for solicitation number W15QKN-21-R-5005 for base operations services at Picatinny Arsenal. The solicitation seeks to provide base operations services and will close for proposals on February 2, 2021 at 2:00 PM EST. The solicitation is issued by the Department of the Army Materiel Command Contracting Command Picatinny Arsenal for base operations requirements at Picatinny Arsenal. Interested offerors are notified of the opportunity to submit proposals for these services prior to the closing date.
View the file
Other files for this federal contract opportunity
Show all 50
Picatinny Arsenal Base Operations (BASOPS) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Detection & Protection Sys
| Building number | Sub Bldg | Sec | Location | Status | System type | Fire Panel Model | Dialer Model | Year Installed | Pass / Fail | Last Annual | Repairs Required |
| 526 | Pav | On | CO2 | Kidde Aegis | 2015 | F | 5/14/20 | Need to fix nitrogen lines to dampers, (4) and refill nitrogen cylinder. Dampers stuck closed right now. Lockout valve needs to be adjusted. Oderizer needs to be checked for proper position. Batteries need to be replaced. | |||
| 1 | Main | Front Closet | On | Dry | Victaulic 768N | 2019 | P | 3/30/20 | |||
| 1 | North | Mech Room | On | Dry | Victaulic 768N | 2019 | P | 3/30/20 | |||
| 1 | South | Closet | On | Dry | Victaulic 768N | 2019 | P | 3/30/20 | |||
| 9 | Mech Room | On | Dry | Viking | IP Dialer | 2012 | P | 12/8/20 | |||
| 10 | Mech Closet | On | Dry | Viking | IP Dialer | 2012 | P | 1/22/20 | |||
| 18 | C | Mech Room | On | Dry | Reliable - Model D | P | 10/30/20 | ||||
| 34 | HR Office | On | Dry | TYCO DVP-1 | P | 5/22/20 | |||||
| 45 | On | Dry | P | 5/20/20 | |||||||
| 61 | A | Mech Room | On | Dry | 4" Tyco | P | 10/8/20 | ||||
| 62 | A | Mech Room | On | Dry | Tyco | P | 2/6/20 | ||||
| 62 | B | Mech Room | On | Dry | Tyco | P | 2/6/20 | ||||
| 91 | C | Boiler Rm | On | Dry | Firematic | IP Dialer | 1997 | F | 4/30/20 | IJO needed -Dry system is not operating consistently and may not activate during fire. system is 40 years old and should be upgraded. |
- Dry pendants are over 10 years old and need to be sent out for testing or replaced
(NFPA 25 5.3.1.1.1.6)
| 91 | A | Shipping | On | Dry | Viking | IP Dialer | 2015 | P | 4/30/20 | ||
| 91 | B | Shipping | On | Dry | Viking | IP Dialer | 2015 | P | 4/30/20 | ||
| 119 | A | Mech Room | On | Dry | Tyco | IP Dialer | P | 5/26/20 | |||
| 121 | A | Exterior Closet | On | Dry | Tyco DPV1 | 1986 | P | 11/3/20 | |||
| 121 | B | Bsmt | On | Dry | Viking F-1 | P | 5/29/20 | ||||
| 162 | A | On | Dry | Firelock | ? | P | 4/1/20 | ||||
| 162 | B | On | Dry | Firelock | ? | P | 4/1/20 | ||||
| 163 | A | Attic | On | Dry | Viking Quick Response | 2011 | P | 1/24/20 | |||
| 172 | Mech Room | On | Dry | Victalvic S/756 | P | 6/1/20 | |||||
| 183 | A | Mech Closet | On | Dry | Viking | P | 2/25/20 | ||||
| 302 | A | Main Entr Dr3 | On | Dry | Tyco DPW-1 | 2011 | P | 3/31/20 | |||
| 302 | C | North Bay - Dry System C | On | Dry | Tyco DPW-2 | 2011 | P | 3/31/20 | |||
| 315 | On | Dry | Tyco DS-1 | ???? | 2012 | P | 6/16/20 | ||||
| 351 | A | On | Dry | ? | IP Dialer | P | 8/22/20 | ||||
| 355 | Loading Dock | On | Dry | Viking F-1 | Local Alarm Only | 2002 | P | 12/11/20 | |||
| 407 | B | Mech Closet | On | Dry | 4" Firelock NXT | IP Dialer | P | 6/1/20 | |||
| 458 | A | High Bay | On | Dry | Victaulic 768N | P | 2/5/20 | new dry valve installed 2019 | |||
| 526 | On | Dry | P | 8/3/20 | |||||||
| 617 | On | Dry | Victaulic 768N | 2019 | P | 6/30/20 | |||||
| 636 | Bay Door | On | Dry | 3" Viking F-1 | 2018 | P | 10/2/20 | ||||
| 636 | C | mech room | On | Dry | 4" viking F-1 | 2018 | P | 10/2/20 | |||
| 647 | On | Dry | Victaulic 768N | 2019 | P | 6/17/20 | new dry valve installed 2019 | ||||
| 807 | A | On | Dry | victaulic 768N | 2020 | P | 9/10/20 | new dry system installed in 2020 | |||
| 1610 | On | Dry | Tyco DPV-1 | ? | 2010 | P | 11/18/20 | compressor replaced 8-7-2020 | |||
| 3228 | Bsmt | On | Dry | Tyco DPV-1 | 1992 | P | 10/5/20 | ||||
| 3248 | Mech Room | On | Dry | Reliable | P | 7/29/20 | |||||
| 3305 | Janitor Closet | On | Dry | Tyco DPV-1 | P | 7/6/20 | |||||
| 3316 | B | High Bay | On | Dry | Tyco DPV-1 | ? | P | 10/15/20 | |||
| 3411 | On | Dry | P | 9/15/20 | |||||||
| 3500 | On | Dry | Victaulic 756 | IP Dialer | P | 6/2/20 | |||||
| 3518 | Mech Closet | On | Dry | Tyco DPU-1 | P | 6/22/20 | |||||
| 12 | A | Main Area | On | Dry Chemical | Notifier FM200 RP2002 | P | 5/11/20 | ||||
| 44 | A | Floor 6/Tower | On | Dry Chemical | Fike FE227 | 2014 | F | 5/14/20 | system powered down as per customer. Non operational | ||
| 61 | Com Rm 140A | On | Dry Chemical | Fenwal Novac 1230 | Fenwal Net 6000 | 2011 | P | 5/14/20 | |||
| 95 | A | Main Area | On | Dry Chemical | Notifier FM200 RP2002 | ? | F | 5/11/20 | Conduits to vault need to be sealed Two det. in vault on zone 5 does not cause discharge. | ||
| 173 | Switch Rm | On | Dry Chemical | Ansul CY90 AutoPulse 442R | P | 5/11/20 | |||||
| 173 | Battery Rm | On | Dry Chemical | Ansul CY90 AutoPulse 442R | P | 5/11/20 | |||||
| 303 | Melt Room | On | Dry Chemical | Automan INDX ABC-XI-50A | F | 5/7/20 | Automan INDX ABC XI -50A (3 tanks) due for 6 year. Ansul 101-30 Cartridge due for replacement. 4 Nozzles are blocked. Pull station cable is not run . 2 links are not accessible-high-Only 4 out of 6 were changed. No local Alarm and not tied into Fire Alarm | ||||
| 316 | Locker 4 | On | Dry Chemical | Pyrochem InD ABC | P | 5/8/20 | |||||
| 316 | Locker 6 | On | Dry Chemical | Pyrochem InD ABC | P | 5/8/20 | |||||
| 316 | Locker 5 | On | Dry Chemical | Pyrochem InD ABC | P | 5/8/20 | |||||
| 316 | Locker 1 | On | Dry Chemical | Pyrochem InD ABC | P | 5/8/20 | |||||
| 526 | Pav | 1 | On | Dry Chemical | Kidde | 2015 | P | 5/14/20 | |||
| 526 | Pav | 2 | On | Dry Chemical | Kidde | 2015 | P | 5/14/20 | |||
| 526 | Pav | 3 | On | Dry Chemical | Kidde | 2015 | P | 5/14/20 | |||
| 526 | Pav | 4 | On | Dry Chemical | Kidde | 2015 | P | 5/14/20 | |||
| 3013 | B | Main Area | On | Dry Chemical | Notifier FM200 RP2002 | ? | F | 5/11/20 | Air does not shut down | ||
| 3100 | Flam Storage | On | Dry Chemical | Pyrochem PCI 50 | P | 5/8/20 | |||||
| 3310 | On | Dry Chemical | WK Industrial | ? | P | 5/14/20 | |||||
| 3316 | On | Dry Chemical | Pyro Chem | ? | P | 6/13/19 | fire dept refused due to Covid19 | ||||
| 1 | Main | Front Entr | On | Fire Alarm | IP Dialer | 2019 | P | 4/15/20 | |||
| 2 | Main Entr | On | Fire Alarm | Firelite MS-9050 UDC | IP Dialer | 2012 | P | 1/14/20 | |||
| 3 | Main Entr | On | Fire Alarm | Firelite MS9200 UDLS | Bosch C900 IP | P | 1/13/20 | ||||
| 6 | 14 | Main Entr | On | Fire Alarm | GE/Edwards EST-3 | IP Dialer | 2011 | P | 2/5/20 | ||
| 7 | Main Entr | On | Fire Alarm | Simplex 4100ES | IP Dialer | 2013 | P | 3/30/20 | |||
| 8 | O/S Elec Rm | On | Fire Alarm | Notifier NFS-320 | IP Dialer | 2013 | P | 2/25/20 | |||
| 9 | Main Elec Rm | On | Fire Alarm | Siemens Firefinder-XLS | IP Dialer | 2012 | P | 1/29/20 | |||
| 10 | B | On | Fire Alarm | Fire Lite MS9050 UD | IP Dialer | P | 6/9/20 | ||||
| 10 | Main Elec Rm | On | Fire Alarm | Siemens Firefinder-XLS | IP Dialer | 2012 | P | 2/7/20 | |||
| 10 | A | On | Fire Alarm | Siemens Firefinder-XLS | IP Dialer | P | 5/26/20 | ||||
| 11 | Main Entr | On | Fire Alarm | Silent Knight 5208 | IP Dialer | P | 1/27/20 | ||||
| 12 | Lab Area | On | Fire Alarm | Firelite MS-9200UDLS | IP Dialer | P | 9/23/19 | ||||
| 13 | Main Lobby | On | Fire Alarm | Silent Knight 5208 | IP Dialer | P | 1/28/20 | ||||
| 17 | On | Fire Alarm | Firelite MS-5UD | F | 12/20/19 | ||||||
| 18 | B | On | Fire Alarm | Siemens | IP Comm | 2013 | P | 4/10/20 | |||
| 18 | C | On | Fire Alarm | Siemens | IP Dialer | 2013 | P | 11/2/20 | |||
| 18 | Main Entr | On | Fire Alarm | Pyrotronics CP35 | Noti-Fire 911A | F | 12/8/20 | IJO Needeed - Disconnect switch for preaction system does not work, horn strobes need to be synchronized | |||
| 19 | Main Entr | On | Fire Alarm | Simplex 4100U | IP Comm | P | 5/9/20 | ||||
| 20 | Coffee Rm | On | Fire Alarm | Firelite ES-200X | (Stand Alone System) | P | 6/30/20 | ||||
| 21 | Main Entr | On | Fire Alarm | Firelite MS9200 | Bosch V465 IP | P | 9/11/20 | ||||
| 25 | Bay 3 | On | Fire Alarm | Notifier 500 | IP Dialer | P | 11/20/20 | ||||
| 30 | Mech Rm | On | Fire Alarm | Simplex 4100 ES | Noti-Fire 911A | 2011 | P | 10/27/20 | |||
| 31 | Main Lobby | On | Fire Alarm | Notifier AM 2020 | IP Dialer | F | 9/1/20 | IJO needed to provide strobe synchronization - additional IJO for multiple deficiencies needed | |||
| 33 | Main Entr | On | Fire Alarm | Simplex 4100 U | Noti-Fire 911A | 2011 | P | 7/21/20 | |||
| 34 | Rear Kitchen | On | Fire Alarm | Firelite 9200 UDLS | Noti-Fire 911A | P | 6/3/20 | ||||
| 44 | Boiler Rm | On | Fire Alarm | Simplex 4100ES | Fire Lite 411UD | 2014 | F | 1/22/20 | Follow up to add devices to Fire Pump / Gnerator Building | ||
| 45 | On | Fire Alarm | Simplex | 4010 ES | P | 9/15/20 | |||||
| 59 | Main Entr | On | Fire Alarm | Firelite MS9200 | IP Dialer | P | 3/17/20 | ||||
| 60 | Bay 1 | On | Fire Alarm | Firelite MS5210 UD | IP Dialer | P | 10/19/20 | ||||
| 61 | Main Entr | On | Fire Alarm | Siemens Fire Finder | IP Dialer | 2011 | P | 9/12/19 | |||
| 62 | Main Entr | On | Fire Alarm | Firelite MS 9200 UDLS | ? | P | 3/2/20 | ||||
| 63 | On | Fire Alarm | Firelite | ES-200X | P | 10/8/19 | |||||
| 64 | Main Entr | On | Fire Alarm | Firelite MS5210 UD | IP Comm | F | 7/22/20 | IJO needed to add protection to newly renovated office ares C-9 and extend voice evacuation to south side of building. | |||
| 65 | Main Entr | On | Fire Alarm | Notifier 5000 | IP Dialer | P | 12/30/19 | ||||
| 67 | Main Entr | On | Fire Alarm | Firelite 9050 UD | ? | 2011 | P | 3/9/20 | |||
| 68 | On | Fire Alarm | Firelite | P | 6/30/20 | ||||||
| 79 | Main Area | On | Fire Alarm | Simplex 4001 | (NO DIALER) | P | 7/23/20 | Per Fire Department inspection, install fire and smoke detectors on main floor and basement | |||
| 84 | On | Fire Alarm | FireLite MS-5UD | IP | 2016 | P | 3/5/20 | ||||
| 91 | Main Entr | On | Fire Alarm | Simplex 4100 U | IP Dialer | 2011 | P | 2/20/20 | Existing notification devices operate properly, but they do not provide compliant coverage and are ineffective in many areas. IJO requested to install compliant coverage. | ||
| 92 | Lobby | On | Fire Alarm | Firelite Miniscan 4024 | IP Dialer | 2014 | P | 3/31/20 | |||
| 93 | Floor 1 | On | Fire Alarm | Siemens MXL | IP DACT | P | 1/31/20 | Initiating devices on floors 1 - 3 have a long delay prior to activating an alarm condition. This code violation requires an IJO to replace the system | |||
| 94 | Front Lobby | On | Fire Alarm | Pyrotronics CP400 | 411UD Dialer | c. 1968 | P | 6/2/20 | IJO required for add'l notification devices and to replace panel | ||
| 95 | Front Entr | On | Fire Alarm | Simplex 4100 U | IP Dialer | 2013 | F | 10/2/20 | IJO needed to replace sub-panel | ||
| 110 | Kitchen | On | Fire Alarm | Simplex 4010 | ? | 2010 | P | 5/20/20 | |||
| 118 | Utl Rm 14A | On | Fire Alarm | Firelite Sensiscan 1000 | Ademco 4120XM | P | 5/5/20 | ||||
| 119 | Bsmt Garage | On | Fire Alarm | Firelite MS 9200 UDLS | IP Dialer | P | 7/28/20 | ||||
| 120 | Main Entr | On | Fire Alarm | Gamewell Zans 400 | (Stand Alone System) | F | 3/16/20 | IJO needed to replace panel and field devices in order to resolve inspection deficiencies | |||
| 121 | Main Entr | On | Fire Alarm | Silent Knight 5208 | IP Dialer | P | 7/23/20 | ||||
| 121 | A | Main Entr | On | Fire Alarm | Firelite MS 9050 UD | IP Dialer | P | 1/6/20 | |||
| 151 | Elec Rm | On | Fire Alarm | Simplex 4100 U ES | IP Dialer | 2012 | P | 4/22/20 | |||
| 162 | On | Fire Alarm | Siemens XLS | ? | P | 2/27/20 | |||||
| 163 | On | Fire Alarm | Fire Lite MS 9200 UDLS | P | 3/11/20 | ||||||
| 169 | Elec Rm | On | Fire Alarm | Siemens FS 250 | Firewatch 411UD | P | 6/25/20 | ||||
| 172 | Front Entr | On | Fire Alarm | Silent Knight 5208 | IP Dialer | P | 6/22/20 | ||||
| 173 | Dispatch Entr | On | Fire Alarm | Fire Lite 9200 UDLS | IP Dialer | 2017 | P | 4/14/20 | |||
| 174 | Main Entr | On | Fire Alarm | Simplex 4001 | Noti-Fire 911A | P | 3/13/20 | No Smoke Detection, only 2 Pull Stations | |||
| 175 | Main Entr | On | Fire Alarm | Firelite MS-9200 DLS | IP Dialer | P | 9/12/20 | ||||
| 176 | Main Entr | On | Fire Alarm | Edwards 6616/6632 | IP Dialer | P | 10/26/20 | ||||
| 183 | Media Rm | On | Fire Alarm | Silent Knight 5208 | IP Dialer | P | 4/8/20 | ||||
| 217 | On | Fire Alarm | |||||||||
| 221 | Mech Shed | On | Fire Alarm | Firelite MS-5UD | IP Dialer | 2013 | P | 8/6/20 | Follow up order entered to replace dialer | ||
| 225 | Fire Alarm | Stand Alone System | Local Alarm Only | F | 5/15/20 | IJO to Install Monitored Fire Alarm System | |||||
| 237 | Control Rm | On | Fire Alarm | Auto Pulse Z-10 | Noti Fire 911 | 2012 | F | 7/22/20 | No Dialer - No phone lines or IP comm's in building - Needs to be run to other building | ||
| 240 | Main Entr | Fire Alarm | Stand Alone System | Local Alarm Only | F | 5/15/20 | No fire protection in bldg, only bell controlled by switch - Recommend fire protection be installed in bldg | ||||
| 256 | Center Entr | On | Fire Alarm | Gamewell 7887 | IP Dialer | 2012 | P | 7/27/20 | |||
| 266 | Main Entr | On | Fire Alarm | Firelite MS 10 UD | P | 5/13/20 | Recommend heat detector in kitchen and horn strobes/detectors in back room - relocate zone 1 detectors | ||||
| 302 | Main Entr Dr3 | On | Fire Alarm | Firelite MS 9200 UD | DACT | 2014 | P | 6/29/20 | |||
| 303 | On | Fire Alarm | Simplex 4100 ES | Phone Lines | P | 2/19/20 | |||||
| 307 | Main Entr | On | Fire Alarm | Firelite MS 9200 UD | DATC | P | 7/1/20 | ||||
| 312 | 319 | 320 | 319 Main Entr | On | Fire Alarm | Firelite ES200X | IP Dialer | 2020 | F | 6/17/20 | new Fire alarm installed 2020 |
| 315 | Main Entr | On | Fire Alarm | Firelite MS 9200 UDLS | DATC | ? | P | 7/8/20 | |||
| 316 | Main Entr | On | Fire Alarm | Notifier SFP1024 | Bosch B002568F | P | 8/6/20 | recommend more notification devices to bring up to current code | |||
| 318 | Main Entr | On | Fire Alarm | Firelite MS 5210 UD | Noti-Fire 911A | P | 7/14/20 | ||||
| 322 | Main Corr | On | Fire Alarm | Fire Lite MS9050 UD | Noti-Fire 911A | 2012 | P | 9/15/20 | |||
| 323 | Mech Rm | On | Fire Alarm | Siemens Firefinder-XLS | (Stand Alone System) | 2012 | P | 7/17/20 | |||
| 329 | Main Entr | On | Fire Alarm | Firelite MS 9200 | Bosch B0025652 | P | 7/21/20 | ||||
| 337 | Kitchen Exit | On | Fire Alarm | Firelite 9200UDLS | Noti-Fire 911A | P | 12/11/20 | ||||
| 351 | On | Fire Alarm | Simplex 4100ES | IP Dialer | 2014 | P | 1/24/20 | ||||
| 354 | Main Lobby | On | Fire Alarm | Firelite Sensiscan 2000 | IP Dialer | F | 7/30/20 | IJO needed for panel replacement | |||
| 355 | Main Lobby | On | Fire Alarm | Pyrontronics CP400 | IP Dialer | P | 5/15/20 | ||||
| 382 | Main Lobby | On | Fire Alarm | Silent Knight 5208 | P | 6/24/20 | |||||
| 403 | On | Fire Alarm | Firelite | MS9050 | P | 9/8/20 | |||||
| 407 | E Wing Jan Closet | On | Fire Alarm | FCI FC-72 | IP Dialer | F | 7/20/20 | IJO needed - life span of smoke detectors is exceded, replacement of duct detectors is also needed | |||
| 455 | Main Entr | Off | Fire Alarm | Firelite Sensiscan 1000 | IP Dialer | F | 7/7/20 | System has internal component failures. Panel is obsolete, parts are not available | |||
| 458 | On | Fire Alarm | Notifier | IP Comm | P | 11/17/20 | |||||
| 472 | Main Entr | On | Fire Alarm | Notifier SGL-404 | IP Dialer | P | 7/15/20 | ||||
| 526 | Cntrl Rm 155 | On | Fire Alarm | Simplex 4100 U | IP Dialer | P | 10/5/20 | ||||
| 604 | E | On | Fire Alarm | Firelite MS-10UD | 2013 | P | 7/9/20 | ||||
| 611 | Main Entr | On | Fire Alarm | Firelite MS 10UD | IP Dialer | P | 8/19/20 | ||||
| 617 | Main Entr | On | Fire Alarm | Firelite 4050 UD | IP Comm | 2010 | P | 7/20/20 | |||
| 617 | A | On | Fire Alarm | P | 9/1/20 | ||||||
| 630 | B | On | Fire Alarm | SF50 | IP Dialer | P | 8/25/20 | ||||
| 647 | On | Fire Alarm | Simplex 4100ES | IP Dialer | P | 9/6/20 | |||||
| 660 | Main Entr | On | Fire Alarm | Firelite | Bosch IP | P | 8/31/20 | ||||
| 660 | A | On | Fire Alarm | Simplex 4010 ES | P | 9/1/20 | |||||
| 717 | Off | Fire Alarm | F | 5/15/20 | not in service - IJO Required for demolition, engineering, and installation | ||||||
| 800 | On | Fire Alarm | Viking Par-3 | P | 7/9/20 | ||||||
| 806 | Fire Alarm | Stand Alone System | Local Alarm Only | F | 5/15/20 | Bldg has local 120v pull station and A/V system only - IJO needed for new FACP | |||||
| 820 | northside | On | Fire alarm | 2018 | P | 8/24/20 | new system installed 2018 | ||||
| 908 | Elec Rm 3 | On | Fire Alarm | Gamewell Zams 200 | P | 7/13/20 | |||||
| 911 | Main Area | On | Fire Alarm | Edwards EFS-C | P | 9/9/20 | |||||
| 914 | Main Area | On | Fire Alarm | Edwards EFS-C | P | 9/9/20 | |||||
| 1029 | Main Elec Rm | On | Fire Alarm | Firelite MS-92004-DIS | ? | P | 9/17/20 | ||||
| 1053 | On | Fire Alarm | Firelite MS 521 UD | IP Comm | ? | P | 6/10/20 | ||||
| 1090 | A | On | Fire Alarm | Fire Lite 9050 UD | ? | 2012 | P | 6/10/20 | |||
| 1090 | Main Entr | On | Fire Alarm | Simplex 4100 ES | IP Dialer | 2012 | P | 5/28/20 | |||
| 1136 | On | Fire Alarm | Firelite MS 5024 UD | ? | P | 6/5/20 | |||||
| 1176 | Main Entr | On | Fire Alarm | Simplex 4100 ES | IP Dialer | 2012 | P | 7/22/20 | |||
| 1301 | 1301 |
| 1308 | Room 146 | On | Fire Alarm | Notifier NFS 3030ND | 2013 | P | 10/25/19 | |||||
| 1307 | Main Area | On | Fire Alarm | Notifier NFS 3030ND | ? | 2012 | P | 10/16/20 | ||||
| 1403 | Control Rm | On | Fire Alarm | Notifier 5000 | (Stand Alone System) | P | 11/16/20 | |||||
| 1406 | Utility Rm | On | Fire Alarm | Firelite ES200X | Firewatch 411UD | 2020 | P | 11/3/20 | new fire alarm installed 2020 | |||
| 1407 | Utility Rm | On | Fire Alarm | Notifier NFS 640 | Firewatch 411UD | 2013 | P | 11/19/20 | ||||
| 1408 | Utility Rm | On | Fire Alarm | NFS 640 | Firewatch 411UD | 2013 | P | 11/4/20 | ||||
| 1408 | C | Control Rm | On | Fire Alarm | Firelite 9200 ULS | Firewatch 411UD | 2013 | P | 11/6/20 | IJO need to provide IP Drop for central station and to Install Dialer and Program Central Station | ||
| 1411 | Elec/Mech Rm | On | Fire Alarm | Notifier NFS 3030ND | Firewatch 411UD | 2013 | F | 11/5/20 | Panel has Program courupt trouble. Replacement is rocommended | |||
| 1412 | Control Rm | On | Fire Alarm | Fire Lite | MS-SLD | 2013 | P | 11/9/20 | ||||
| 1417 | Elec Rm 338 | On | Fire Alarm | Notifier NFS 640 | Firewatch 411UD | 2013 | F | 11/10/20 | Follow up to Repair Dialer - IJO needed to replace panel | |||
| 1461 | A | Utility room | On | Fire Alarm | Firelite ES200X | 2019 | P | 9/26/19 | new system installed | |||
| 1463 | Front Closet | On | Fire Alarm | Honeywell E3 | 2019 | P | 7/28/20 | |||||
| 1501 | FACP Rm | On | Fire Alarm | FCI FC72 | (Stand Alone System) | P | 9/9/19 | |||||
| 1516 | Main Entr | On | Fire Alarm | EST EST-3 | Fire Watch 411 | 2013 | P | 7/15/20 | ||||
| 1530 | On | Fire Alarm | Firelite MS 5210 UD | IP Dialer | P | 7/15/20 | ||||||
| 1610 | On | Fire Alarm | Firelite MS 9050 UD | IP Dialer | 2010 | P | 2/24/20 | |||||
| 3002 | Main Entr | On | Fire Alarm | Simplex 4100 U | IP Dialer | 2010 | P | 5/22/20 | ||||
| 3006 | On | Fire Alarm | Stand Alone System | Local Alarm Only | P | 6/12/20 | ||||||
| 3008 | Front Entr | On | Fire Alarm | Firelite MS 9050 UD | IP Dialer | P | 6/15/20 | |||||
| 3021 | Main Elec Rm | On | Fire Alarm | Fire-Lite MS-10UD-7 | IP Dialer | P | 7/24/19 | |||||
| 3022 | Front vestibule | On | Fire Alarm | GameWell FCI E3/MNS | IP Dialer | 1/8/20 | p | 1/8/20 | ||||
| 3024 | Main Entr | On | Fire Alarm | Faraday MPC 2000 | ? | F | 10/22/20 | IJO needed to Repair or replace existing dry pipe fire suppression system for building. | ||||
| 3028 | Elec Rm 139 | On | Fire Alarm | Notifier MD4 | Ademco 4120XM | 2019 | F | 11/29/19 | Disabled due to construction - system will be restored to normal and passed | |||
| 3029 | Elec Rm 3 | On | Fire Alarm | Simplex 4002 | Firewatch 411UD | F | 12/13/19 | IJO needed to interface fire alarm to B3028 | ||||
| 3050 | Main Entr | On | Fire Alarm | Siemens | Bosch C900V2 | P | 10/8/20 | |||||
| 3100 | Main Entr | On | Fire Alarm | Notifier 500 | Noti-Fire 911A | F | 3/19/20 | IJO needed to replace panel and dialer | ||||
| 3114 | Warehouse | On | Fire Alarm | Firelite MS9000UDLS | Bosch V465 IP | P | 7/23/20 | |||||
| 3124 | Main Entr | On | Fire Alarm | Firelite MS9050UD | 2010 | P | 7/2/20 | |||||
| 3128 | On | Fire Alarm | Firelite 9200 UDLS | P | 3/6/20 | |||||||
| 3150 | Nautilus Rm | On | Fire Alarm | Simplex 4100ES | IP Dialer | 2013 | P | 6/24/20 | ||||
| 3153 | Room 115 | On | Fire Alarm | Gamewell FCI 7100-2 | IP Dialer | P | 5/18/20 | |||||
| 3156 | Mech Rm 115 | On | Fire Alarm | Honeywell FCI 7100 | IP Dialer | P | 9/12/20 | |||||
| 3159 | Main Entr | Off | Fire Alarm | Potter PFC Series 4000 | Noti-Fire 911A | F | 9/12/20 | new fire alarm being installed 2021 | ||||
| 3173 | Bldg 3177 | On | Fire Alarm | Siemens Firefinder-XLS | IP Dialer | 2012 | P | 8/11/20 | horn strobe needed above panel (completed on service order) | |||
| 3208 | On | Fire Alarm | Simplex 4100ES | IP Dialer | 2013 | P | 7/10/20 | |||||
| 3215 | On | Fire Alarm | P | 7/10/20 | ||||||||
| 3221 | Main Entr | On | Fire Alarm | Simplex 4006 | DACT | P | 5/12/20 | |||||
| 3225 | Elec Rm | On | Fire Alarm | Securtron Modul-R RMR2616B | Phone Lines | P | 6/16/20 | |||||
| 3227 | Elec Rm Bld 2 | On | Fire Alarm | Simplex 4100 U | Noti-Fire 911A | P | 5/8/20 | |||||
| 3228 | Main Entr | On | Fire Alarm | FireLite 9200 UDLS | IP Dialer | 2017 | P | 8/13/20 | ||||
| 3248 | Stor Rm | On | Fire Alarm | Silent Knight | IP Dialer | 2013 | P | 8/12/20 | ||||
| 3305 | Main Entr | On | Fire Alarm | Firelite MS 10UD | (Stand Alone System) | 2013 | P | 8/7/20 | Need to replace outside bell | |||
| 3306 | On | Fire Alarm | Gamewell E3 | DACT at Node 1 | P | 2/18/20 | ||||||
| 3308 | On | Fire Alarm | Gamewell E3 | (DACT at Node 1 in B3306) | P | 2/11/20 | ||||||
| 3310 | On | Fire Alarm | Gamewell E3 | (DACT at Node 1 in B3306) | P | 2/12/20 | ||||||
| 3316 | Main Area | On | Fire Alarm | Firelite MS-92004DLS | IP Dialer | P | 6/26/20 | |||||
| 3324 | Main Entr | On | Fire Alarm | Silent Knight 5208 | Noti-Fire 911A | P | 9/15/20 | IJO recommended for additional strobe lights and smoke detectors | ||||
| 3328 | Main Entr | On | Fire Alarm | Silent Knight 6820EUS | Noti-Fire 911A | P | 8/14/20 | |||||
| 3329 | Main Entr | On | Fire Alarm | Silent Knight 5208 | Fire Watch 411 | P | 1/2/20 | Warehouse section has no detection | ||||
| 3355 | On | Fire Alarm | Simplex 4100U | Dialer | ? | P | 1/16/20 | |||||
| 3356 | On | Fire Alarm | Simplex 4100U | Bosch C900 | ? | P | 1/15/20 | |||||
| 3360 | On | Fire Alarm | Simplex 4100 U | ? | ? | P | 1/17/20 | |||||
| 3409 | Rear Entr | On | Fire Alarm | Honeywell 1000 | IP Dialer | P | 8/4/20 | |||||
| 3410 | Main Entr | On | Fire Alarm | Firelite MS-90200 UDLS | IP Dialer | P | 8/3/20 | recommend replacing smoke detectors | ||||
| 3411 | On | Fire Alarm | Siemens MXLIQ | IP Comm | 2014 | P | 1/10/20 | |||||
| 3500 | Foyer | On | Fire Alarm | Firelite 5210 UD | IP Dialer | P | 7/24/20 | |||||
| 3501 | Main Entr | On | Fire Alarm | Silent Knight 5208 | IP Dialer | P | 8/17/20 | |||||
| 3510 | Main Entr | On | Fire Alarm | Silent Knight 5208 | IP Dialer | P | 8/18/20 | |||||
| 3518 | Conf Rm | On | Fire Alarm | Firelite MS 5024 UD | IP Dialer | P | 8/10/20 | recommend office by IT room have a smoke detector/lab area should have more notification devices | ||||
| 3720 | On | Fire Alarm | Stand Alone System | ISD Only | 2013 | P | 5/19/20 | |||||
| 3721 | On | Fire Alarm | Stand Alone System | ISD Only | 2013 | P | 5/19/20 | |||||
| 3722 | On | Fire Alarm | Stand Alone System | ISD Only | 2013 | P | 5/19/20 | |||||
| 807 | A | On | Fire Alarm | Silent Knight | 2020 | P | 9/17/20 | Alarm system installed 2020 | ||||
| 810 | On | Fire alarm | Firelite ES-200-X | 2020 | P | 10/1/20 | new fire alarm installed 2020 10/2020 | |||||
| 12 | CPU Lab Area | On | FM200 | 2018 | P | 5/14/20 | ||||||
| 31 | A | ARMAG | On | FM200 | ? | IP Dialer | 2018 | F | 11/15/18 | No testing since 2018 comissioning | ||
| 34 | Closet | On | Hood | Kidde WHDR | P | 5/6/20 | ||||||
| 34 | Pizza Side | On | Hood | Kidde WHDR | P | 5/6/20 | ||||||
| 34 | Main kitchen | On | Hood | Ansul R102 | 2012 | F | 5/6/20 | Actuation gas line needs a safety vent relief / Alarm not functioning / Multiple duct nozzles need bracing | ||||
| 121 | By Ice Chest | On | Hood | Kidde WHDR | P | 5/7/20 | ||||||
| 169 | Kitchen Left | On | Hood | Ansul R102 | P | 6/13/19 | fire dept refused due to Covid19 | |||||
| 175 | Left | On | Hood | Pyrochem PCL240 | F | 5/7/20 | NL nozzles need changing / Electric shut off not functioning not tied to FACP | |||||
| 337 | Behind Fridge | On | Hood | Kidde WHDR | P | 5/7/20 | ||||||
| 1176 | Left | On | Hood | Pyrochem PCL460 | IP Dialer | P | 5/7/20 | |||||
| 3153 | Right | On | Hood | Ansul R102 | P | 5/6/20 | ||||||
| 3156 | Rm 102 | On | Hood | Ansul R102 | P | 5/6/20 | ||||||
| 3156 | Front | On | Hood | Ansul R102 | F | 5/6/20 | Needs module for alarm contacts (FCI Gamewell panel) | |||||
| 3225 | Left | On | Hood | Badger | F | 5/6/20 | No makeup air shutdown / electrci range does not shutdown | |||||
| 3227 | Right | On | Hood | Ansul R102 | P | 5/6/20 | ||||||
| 7 | Room 130 | On | HS Deluge | Pyrotech | IP Dialer | P | 6/16/20 | |||||
| 217 | Off | HS Deluge | 2018 | 7/9/20 | ||||||||
| 237 | RM 1 | On | HS Deluge | TFS | 2012 | P | 6/17/20 | |||||
| 237 | Rm 2 | On | HS Deluge | TFS | 2012 | P | 6/17/20 | |||||
| 238 | On | HS Deluge | TFS | 2012 | P | 6/17/20 | ||||||
| 252 | On | HS Deluge | F | 7/20/20 | Repair HSD valve 1 zone 7 room 8 | |||||||
| 427 | Room 6 | On | HS Deluge | ? | P | 6/15/20 | ||||||
| 427 | Room 20 | On | HS Deluge | ? | F | 6/15/20 | Detector 2 in fault | |||||
| 526 | Panel 2 | Room 125 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 2 | Room 127 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 2 | Room 156 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 2 | Room 157 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 2 | Room 158 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 1 | Room 120 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 1 | Room 160 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 1 | Room 162 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 1 | Room 109 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 135 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 136 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 137 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 138 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 139 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 140 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 145 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 146 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 526 | Panel 3 | Room 147 | On | HS Deluge | Reliable Model F1 | 2019 | P | 6/8/20 | ||||
| 604 | C | On | HS Deluge | Pyrotech CPF 74 | F | 7/6/20 | room 7 detector 2 needs to be replaced | |||||
| 617 | G | On | HS Deluge | Pyrotech CPF 74 | F | 7/6/20 | Nozzle 12 in zone 5 needs repair | |||||
| 636 | F | On | HS Deluge | Pyrotech | P | 7/1/20 | ||||||
| 636 | G | On | HS Deluge | Pyrotech | P | 7/6/20 | ||||||
| 810 | On | HS Deluge | ? | P | 6/18/20 | |||||||
| 816 | Rm 5, 6, 7 | On | HS Deluge | ? | P | 9/10/20 | ||||||
| 1301 | Panel B | On | HS Deluge | ? | P | 6/24/20 | ||||||
| 1301 | Panel A | On | HS Deluge | ? | F | 6/24/20 | Panel needs to be replaced internal ground fault | |||||
| 1301 | Panel D | On | HS Deluge | ? | P | 6/29/20 | ||||||
| 1301 | Panel C | On | HS Deluge | ? | P | 6/24/20 | ||||||
| 1403 | Control Rm | On | HS Deluge | ? | P | 6/23/20 | ||||||
| 1408 | C | On | HS Deluge | P | 6/1/20 | new panel installed 2020 | ||||||
| 1408 | On | HS Deluge | P | 6/23/20 | ||||||||
| 1411 | On | HS Deluge | F | 6/23/20 | need to repair Trouble shoot room 323 Zones 6,7,8 and 9. Detectors in fault. | |||||||
| 1417 | B | On | HS Deluge | ? | P | 6/24/20 | ||||||
| 1516 | On | HS Deluge | F | 6/16/20 | Follow up - 1) Building 1516 needs all high speed valve replaced and nozzles relocated to provide proper coverage. |
2) The system response time exceeds 100 milliseconds new deluge valves will correct issue.
3) System does not automatically reset. Pilot lines need to be reconfigured.
| 3022 | Lab C | On | HS Deluge | P | 6/15/20 | ||||||
| 2 | Sprink Rm | On | Preaction | Notifier RP-1001 | IP Dialer | 2012 | P | 1/23/20 | |||
| 8 | Mech Rm | On | Preaction | Firelock | P | 3/10/20 | |||||
| 12 | B | Util Closet | On | Preaction | Viking E-1 | 1997 | P | 6/25/20 | |||
| 18 | B | On | Preaction | Firematic | 1993 | P | 10/30/20 | ||||
| 31 | A | Room 402 | On | Preaction | Viking E-1 | IP Dialer | 2001 | P | 6/23/20 | ||
| 31 | H | Room 301 | On | Preaction | Viking E-1 | IP Dialer | P | 6/24/20 | |||
| 31 | D | Room 23 | On | Preaction | Viking E-1 | IP Dialer | 2003 | P | 6/24/20 | ||
| 31 | B | Room 104 | On | Preaction | Viking E-1 | IP Dialer | 2002 | P | 6/24/20 | ||
| 31 | C | Room 208 | On | Preaction | Viking E-1 | IP Dialer | 2001 | P | 6/30/20 | ||
| 44 | A | Boiler Rm | On | Preaction | Viking E-1 | 2002 | P | 5/21/20 | |||
| 59 | Front Hallway | On | Preaction | Tyco Dry | 2011 | P | 5/20/20 | ||||
| 95 | C | North | On | Preaction | Viking | P | 7/29/20 | ||||
| 95 | Optics Lab | Optics Lab | On | Preaction | Victaulic Fire Lock NXT | P | 7/29/20 | ||||
| 95 | B | South | On | Preaction | Viking | 1997 | P | 7/29/20 | |||
| 236 | Off | Preaction | ? | F | 10/8/20 | The sprinkler system is partially demolished, turned off, and unmonitored. The system was inherited in this state. The corrective action would be to completely demo and rebuild a suppression system rated for its environment. An alarm system is also needed for monitoring. | |||||
| 329 | Bldg Front | On | Preaction | Viking | 1999 | P | 6/8/20 | ||||
| 351 | N | C | Overhead Dr | On | Preaction | Viking E-1 | IP Dialer | 1997 | P | 8/22/20 | |
| 351 | S | B | Side of Bldg | On | Preaction | Viking E-1 | IP Dialer | 1996 | P | 8/22/20 | |
| 407 | A | Util Closet | On | Preaction | Viking E-1 | IP Dialer | 1987 | P | 6/1/20 | ||
| 717 | Off | Preaction | Viking | 1995 | F | 12/11/20 | System out of service - cannot perform inspection. System requires complete replacement. | ||||
| 800 | On | Preaction | Viking E-1 | 1994 | P | 6/8/20 | |||||
| 1090 | On | Preaction | Tyco TY-B | ? | 2012 | P | 4/28/20 | ||||
| 3024 | B | Sprink Rm | On | Preaction | Viking E-1 | 1997 | P | 8/5/20 | |||
| 3029 | Riser Rm | On | Preaction | Viking E-1 | 1995 | P | 7/29/20 | ||||
| 1530 | Off | Suppression | IP Dialer | dry system removed, no sprinkler system 5/21/2014 | |||||||
| 3316 | On | Suppression | |||||||||
| 1 | Main | Basement | On | Wet | Shotgun valve | 2019 | P | 3/30/20 | |||
| 1 | Annex | Mech Room | On | Wet | Shotgun valve | 2019 | P | 3/30/20 | |||
| 6 | 14 | Mech Rm | On | Wet | Tyco AV-1 | P | 2/25/20 | ||||
| 7 | B | Bldg Front | On | Wet | Viking H-2 | IP Dialer | P | 2/10/20 | |||
| 9 | Mech Room | On | Wet | Viking | IP Dialer | 2012 | P | 12/8/20 | |||
| 10 | Mech Closet | On | Wet | Easy Check Riser | IP Dialer | 2012 | P | 1/22/20 | |||
| 11 | On | Wet | Automatic | P | 12/11/20 | ||||||
| 12 | A | Mech Rm | On | Wet | Automatic | 1977 | P | 6/19/20 | |||
| 13 | A | Procurement | On | Wet | Viking | IP Dialer | P | 3/16/20 | |||
| 13 | B | Lunch Rm | On | Wet | Automatic | IP Dialer | P | 3/16/20 | |||
| 15 | fire pump room | Off | Wet | new system installed 2021 | |||||||
| 17 | On | Wet | Victavillic | P | 9/14/20 | ||||||
| 18 | C | Mech | On | Wet | P | 9/14/20 | |||||
| 18 | A | On | Wet | Firematic | 1993 | P | 10/30/20 | ||||
| 18 | B | Mech Room | On | Wet | Easy Check | P | 11/2/20 | ||||
| 25 | On | Wet | Viking | 2000 | P | 11/20/20 | |||||
| 31 | G | High Bay | On | Wet | Viking J-1 | IP Dialer | P | 6/23/20 | |||
| 31 | E | Chiller Bldg | On | Wet | Viking J-1 | IP Dialer | 2001 | P | 6/24/20 | 2/4/00 | |
| 31 | F | Room 15 | On | Wet | Viking J-1 | IP Dialer | 2003 | P | 6/24/20 | ||
| 60 | Corner Whse | On | Wet | Tyco | P | 7/1/20 | |||||
| 61 | B | Mech Room | On | Wet | 6" Riser Manifold | P | 10/8/20 | ||||
| 61 | C | Mezz Area | On | Wet | 4" Riser Manifold | P | 10/8/20 | ||||
| 67 | On | Wet | Victaulic | ? | 2011 | P | 2/10/20 | ||||
| 84 | On | Wet | Firelock 747 | P | 2/12/20 | ||||||
| 95 | A | On | Wet | Victraulic | P | 7/29/20 | |||||
| 95 | D | High bay warehouse | On | Wet | Grinnell Model A | 1959 | P | 7/29/20 | |||
| 119 | B | Mech Room | On | Wet | IP Dialer | P | 5/26/20 | ||||
| 121 | A | Bsmt | On | Wet | Reliable Model E | 1986 | P | 5/29/20 | |||
| 162 | C | On | Wet | Victaulic | ? | P | 4/1/20 | ||||
| 163 | B | First Floor | On | Wet | Viking MICROFAST | 2011 | P | 1/24/20 | |||
| 169 | Mech Room | On | Wet | Victaulic | P | 10/13/20 | |||||
| 172 | Mech Room | On | Wet | Easy Check Mod E | P | 6/1/20 | |||||
| 175 | Mech Rm | On | Wet | 4" CSC | 1997 | P | 9/15/20 | ||||
| 183 | B | Mech Room | On | Wet | Viking | IP Dialer | 2002 | P | 2/25/20 | ||
| 217 | A | On | Wet | 6" Victaulic 751 | 2018 | 10/6/20 | |||||
| 221 | On | Wet | Viking | P | 7/1/20 | ||||||
| 238 | Bldg Front | On | Wet | Victaulic 751 | 2012 | F | 7/1/20 | IJO needed to Install Fire Alarm Panel to interface and monitor sprinkler system | |||
| 252 | On | Wet | Tyco | 2005 | P | 7/1/20 | |||||
| 256 | Center Entr | On | Wet | Reliable | P | 7/1/20 | |||||
| 302 | B | North Bay | On | Wet | Victaulic | 2011 | P | 3/31/20 | |||
| 303 | On | Wet | Firematic | P | 2/3/20 | ||||||
| 307 | Mach Shop | On | Wet | P | 6/16/20 | ||||||
| 316 | On | Wet | Viking | 1999 | P | 6/16/20 | |||||
| 318 | Main Entr | On | Wet | P | 6/17/20 | ||||||
| 217 | B | On | Wet | 4" Firelock NXT 768 | 2018 | 10/6/20 | |||||
| 325 | Rear | Off | Wet | Viking | 2020 | new system installed 2020 | |||||
| 427 | B | Room 7 | On | Wet | Victaulic 751 | P | 6/30/20 | ||||
| 427 | A | Room 24 | On | Wet | Automatic | P | 6/30/20 | ||||
| 429 | A | On | Wet | AUTOMATIC | 1966 | P | 6/30/20 | ||||
| 429 | B | Back Lab | On | Wet | AUTOMATIC | 1966 | P | 6/30/20 | |||
| 436 | Off | Wet | Victaulic | 2000 | F | 3/17/20 | System is off due to no heat | ||||
| 458 | B | Pump Room | On | Wet | Riser only | P | 2/5/20 | ||||
| 458 | C | Pump Room | On | Wet | Riser only | P | 2/5/20 | ||||
| 477 | Mech Room | On | Wet | Automatic | 1945 | F | 6/30/20 | IJO needed to add FACP - not monitored by central station | |||
| 526 | Mech Room | On | Wet | Tyco AV-1 | P | 8/3/20 | |||||
| 604 | C | Sect B | On | Wet | TYCO AV-1 | P | 7/1/20 | ||||
| 604 | C | Sect A | On | Wet | TYCO AV-1 | P | 7/1/20 | ||||
| 607 | A-A | front door | On | Wet | 2" riser check | 2018 | P | 10/15/18 | |||
| 607 | A-B | front door | On | Wet | reliable DDX 2" deluge valve | 2018 | P | 10/15/18 | |||
| 617 | G | Room 2 | On | Wet | TYCO AV-1 | 2008 | P | 8/19/20 | |||
| 623 | G | Pump House | On | Wet | Swing check | P | 7/1/20 | ||||
| 631 | Chiller Room | Off | Wet | TYCO | 2008 | F | 10/8/20 | Riser access is blocked | |||
| 636 | A | mech room | On | Wet | 4" Viking F-1 | 2018 | P | 10/2/20 | |||
| 636 | B | mech room | On | wet | 4" Viking J-1 | 2018 | P | 10/2/20 | |||
| 636 | E | mech room | On | Wet | 4" Tyco CV-1F | 2018 | P | 10/2/20 | |||
| 636 | F | mech room | On | Wet | 4" Viking F-1 | 2018 | P | 10/2/20 | |||
| 636 | G | Mech Room | On | Wet | 4" Viking F-1 | 2018 | P | 10/2/20 | |||
| 660 | A | Pump Room | Off | Wet | AUTOMATIC | P | 7/24/20 | 12/14/2020 no heat | |||
| 660 | Mech Rm | Off | Wet | Viking | P | 7/24/20 | 12/14/2020 no heat | ||||
| 809 | On | Wet | Tyco | 2013 | F | 6/19/20 | IJO Required for Installation work to Interface WF & Tmprs to FACP | ||||
| 810 | A | elevator mechnical room | On | Wet | Victualic S751 | F | 6/18/20 | IJO Requested to replace WF Bell and to integrate horn strobes | |||
| 810 | B | front of bldg | On | Wet | Victaulic Fire lock | F | 6/18/20 | IJO Requested to replace WF Bell and to integrate horn strobes | |||
| 813 | Bldg Front | On | Wet | Tyco AV-1 | F | 6/18/20 | |||||
| 816 | A | Bldg Front | On | Wet | Tyco AV-1 | P | 8/16/20 | ||||
| 816 | B | On | Wet | Tyco | 2005 | P | 8/16/20 | ||||
| 820 | On | Wet | Viking | P | 6/15/20 | ||||||
| 900 | On | Wet | Hedgmen | 1949 | P | 7/22/20 | |||||
| 908 | Mech Room | On | Wet | Victaulic | P | 7/22/20 | |||||
| 1029 | Bldg Front | On | Wet | Victaulic 751 | 2007 | P | 7/2/20 | ||||
| 1090 | A | On | Wet | Tyco TY-B | ? | 2012 | P | 4/28/20 | |||
| 1301 | Mech Room | On | Wet | Tyco | P | 11/13/20 | |||||
| 1307 | Mech Room | On | Wet | Tyco | P | 7/28/20 | |||||
| 1403 | Back Lab | On | Wet | Gem | 1944 | P | 9/11/20 | ||||
| 1406 | On | Wet | Tyco | P | 9/30/20 | ||||||
| 1407 | Mech Room | On | Wet | Tyco | P | 9/11/20 | |||||
| 1408 | C | Mech Room | On | Wet | Tyco | P | 7/28/20 | ||||
| 1408 | On | Wet | Tyco | P | 7/28/20 | ||||||
| 1411 | Mech Room | On | Wet | Tyco | P | 7/28/20 | |||||
| 1417 | Mech Room | On | Wet | Tyco | P | 6/30/20 | |||||
| 1461 | A | Utility room | On | Wet | 2019 | P | new system installed | ||||
| 1463 | A | On | Wet | Reliable | 1996 | P | 11/23/20 | ||||
| 1516 | Mech Room | On | Wet | Tyco | ? | P | 7/24/20 | ||||
| 1530 | On | Wet | Tyco | P | 7/24/20 | ||||||
| 3022 | A | Mech Rm | On | Wet | Automatic | 1976 | P | 8/5/20 | |||
| 3022 | B | Mech Rm | On | Wet | Automatic | 1977 | P | 8/5/20 | |||
| 3024 | A | Sprink Rm | On | Wet | Firematic Model L | 1997 | P | 8/5/20 | |||
| 3028 | Riser Rm | On | Wet | AUTOMATIC A | P | 8/19/20 | |||||
| 3050 | A | Garage | On | Wet | Victaulic | 2017 | P | 8/4/20 | |||
| 3050 | B | Garage | On | Wet | Victaulic | 2017 | P | 8/4/20 | |||
| 3106 | Garage | On | Wet | P | 10/8/20 | ||||||
| 3109 | Garage | On | Wet | P | 10/8/20 | ||||||
| 3111 | Back of Bldg | On | Wet | P | 10/1/20 | ||||||
| 3124 | On | Wet | 2010 | P | 6/17/20 | ||||||
| 3145 | On | Wet | P | 10/1/20 | |||||||
| 3150 | D | Gym | On | Wet | Central | 2013 | P | 4/29/20 | UL testing passed test again in 2025 | ||
| 3150 | B | Front Left | On | Wet | Central | 2013 | P | 4/29/20 | UL testing passed test again in 2025 | ||
| 3150 | C | Front Center | On | Wet | Central | 2013 | P | 4/29/20 | UL testing passed test again in 2025 | ||
| 3150 | A | L Rear Corner | On | Wet | Central | 2013 | P | 4/29/20 | UL testing passed test again in 2025 | ||
| 3150 | F | Rear Center | On | Wet | Central | 2013 | P | 4/29/20 | UL testing passed test again in 2025 | ||
| 3150 | E | Shipping | On | Wet | Central | 2013 | P | 4/29/20 | UL testing passed test again in 2025 | ||
| 3153 | Mech Room | On | Wet | Victaulic | P | 4/28/20 | |||||
| 3156 | Mech Rm | On | Wet | Visctaulic S/751 | P | 4/28/20 | |||||
| 3159 | fire sprinkler room | Off | Wet | new Fire sprinkler system installed 2021 | |||||||
| 3225 | Elec Rm | On | Wet | RASCO 4" 705A | 2001 | P | 4/28/20 | ||||
| 3306 | On | Wet | Victraulic | ? | P | 12/10/20 | |||||
| 3308 | On | Wet | Victraulic | ? | P | 12/21/20 | |||||
| 3310 | On | Wet | Victraulic | ? | P | 2/13/20 | |||||
| 3316 | A | High Bay | On | Wet | Tyco AV-1 | ? | P | 10/15/20 | |||
| 3328 | On | Wet | Victaulic | System Sensor 2-WT-B | 2016 | P | 6/17/20 | ||||
| 3329 | Rear Entr | On | Wet | Gem Model F2001 | F | 12/9/20 | Bay Area Missing Coverage. 8 Pendent Heads need to be removed / Changes to the bldg layout requires a redesign | ||||
| 3355 | A | Pump House | On | Wet | P | 11/15/20 | |||||
| 3355 | Mech Room | On | Wet | Tyco | ? | ? | P | 11/15/20 | |||
| 3356 | On | Wet | Tyco | P | 11/12/20 | ||||||
| 3360 | On | Wet | Tyco | P | 11/12/20 | ||||||
| 3409 | Bsmt | On | Wet | RASCO Model E | IP Dialer | 1992 | P | 6/19/20 | |||
| 3410 | Sprink Rm | On | Wet | Central | IP Dialer | 1992 | P | 7/24/20 | |||
| 3411 | On | Wet | - | P | 9/15/20 | ||||||
| 3501 | Behind Gate | On | Wet | Victaulic CVB | IP Dialer | P | 6/22/20 | ||||
| 3510 | Util Closet | On | Wet | AUTOMATIC | IP Dialer | P | 6/22/20 |
| Systems in Green are currently ON |
| Systems in Yellow are ON and operational but are OVERDUE FOR INSPECTION |
| Systems in Orange are ON and operational but REQUIRE REPAIRES |
| Systems in Red are currently OFF |
| Systems in Gray are OFF and are UNDER CONSTRUCTION |
| Systems in Blue are OFF and Not Required |
| **Note: P/F markings indicate whether the system passed or failed the most recent inspection and have no effect on the system's status |
Fire Protection and Detection Systems Picatinny Arsenal, NJ
Fire Protection and Detection Systems Picatinny Arsenal, NJ
Fire Protection and Detection Systems Picatinny Arsenal, NJ
Fire Protection and Detection Systems Picatinny Arsenal, NJ
Fire Protection and Detection Systems Picatinny Arsenal, NJ
08/16/2013
06/12/2012
06/12/2012
06/12/2012
&D
Fire Pumps
| BUILDING NUMBER | - | 44 | 93 | 458 | 623 | 630B | 660A | 808 | 1301 | 3029C | 3355A | |||||||
| PUMP MFR | - | PEERLESS | AURORA | PATTERSON | AC FIRE PUMP | ITT A-C | AURORA | FLOWAY | FAIRBANKS MORSE | |||||||||
| SHAFT TYPE | - | HORIZONTAL | HORIZONTAL | CENTRIFICAL | HORIZONTAL | HORIZONTAL | VERTICAL | HORIZONTAL | From | Subject | Received | Size | Categories | |||||
| MODEL # | - | 6AEF16N | 481-SF | 6X5X17SSC | 07-0505 | 9100 | 481 BG | 18MKL-FP | 2823AF | Amami, Robert M CIV USARMY ID-SUSTAINMENT (USA) | FW: ICE | https://ice.disa.mil/index.cfm?fa=site&site_id=401 (UNCLASSIFIED) | 11:20 AM | 17 KB | |||||
| SHOP OR SERIAL # | - | 562972 | 79-67809 | FP-C096 464 | 79-01-01 / QKE661 | 03-123456-01-01/QK0001 | 12-2202501 | F55467-1-1 | K4D1025110 | |||||||||
| GPM | - | 1000 | 1500 | 1000 | 2000 | 3000 | 1500 | 3000 | 2500 | |||||||||
| RATED HEAD/FT | - | 196 | 115 | 161 | 281 | 6369 | 323 | 352 | 185 | |||||||||
| RATED PSI | - | 85 | 50 | 70 | 122 | 160 | 140 | 152.416 | 80 | |||||||||
| RATED RPM | - | 1780 | 1750 | 1780 | 1785 | 1785 | 1770 | 1760 | 2100 | |||||||||
| DRIVER MFR | - | US ELECTRIC | MARATHON | WEG | EMERSON | WEG | CATERPILLAR | CUMMINS | ||||||||||
| TYPE | - | ELECTRIC | ELECTRIC | ELECTRIC | ELECTRIC | ELECTRIC | DIESEL | DIESEL | ||||||||||
| MODEL # | - | AD03 | JM364 | 060180P3E 364TS | AR54 | 444/5TS | 3406 | 6BTA59F1 | ||||||||||
| SHOP OR SERIAL # | - | F04-AD03-M | 965383-11/13-3 | 1007183237 | D200EZFS | 1013883402 | 6TB22753 | 45244744 | ||||||||||
| RATED VOLTS | - | 230/460 | 230/460 | 230/460 | 460 | 460 | 460 | N/A | N/A | |||||||||
| OPER. VOLTS | - | 208 | 460 | 460 | 460 | 460 | N/A | N/A | ||||||||||
| HORSE POWER | - | 75 | 60 | 30 | 200 | 400 | 200 | 430 | 208 | |||||||||
| RATED RPM | - | 1785 | 1775 | 1780 | 1785 | 1750 | 1780 | 2100 | 2100 | |||||||||
| DRIVER RATED AMPS | - | 172 | 75 | 70.2 | 235 | 225 | N/A | N/A | ??? | |||||||||
| PHASE | - | 3 | 3 | 3 | 3 | 3 | 3 | N/A | N/A | |||||||||
| AMPS AT 150% | - | 0 | 0 | 0 | N/A | N/A | N/A | |||||||||||
| CYCLES | - | 60 | 60 | 60 | 60 | 60 | N/A | N/A | ||||||||||
| SERVICE FACTOR | - | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | N/A | N/A | ||||||||||
| CONTROLLER MFR | - | FIRETROL | JOSLYN CLARK | LMR EATON | METRON | JOSLYN CLARK | JOSLYN CLARK | FIRETROL | ||||||||||
| MODEL # | - | FTA 1000 | G2C184-53R | FT90-60D-L1 | MP700-200-480C | 63C234-53R | A10710 | FTA1100-EL12N | ||||||||||
| SHOP OR SERIAL # | - | 101802-002-01-01 | 340928 | 16BK836E | NA-07M36482-11 | 344062 | 254661 | 159419 | ||||||||||
| AUTO START PSI | - | 40 | 75 | 120 | 65 | 130 | 90 | 60 | ||||||||||
| STOP PSI | - | N/A | 140 | N/A | N/A | 145 | N/A | N/A | ||||||||||
| JOCKEY PUMP START | - | 90 | N/A | 130 | 120 | 145 | 127 | 100 | ||||||||||
| JOCKEY PUMP STOP | - | 110 | N/A | 160 | 150 | 160 | 165 | 145 | ||||||||||
| CITY SUPPLY | - | N/A | 96psi | 80psi | N/A | N/A | N/A | 32psi | ||||||||||
| CONNECTION SIZE | - | 8" | 8" | 8" | 10" | 8" | 10" | 12" | ||||||||||
| TANK SUPPLY | - | YES | N/A | N/A | YES | YES | N/A | N/A | ||||||||||
| TANK HEIGHT | - | 22' | N/A | N/A | 16' | 26' | N/A | N/A | ||||||||||
| TANK CAPACITY | - | 0 | N/A | N/A | 6 TANKS @ 55K | 100000 | POND SUPPLY | N/A | ||||||||||
| INSPECTION DATE | - | Sep-20 | Sep-20 | Sep-20 | Sep-20 | Sep-20 | Sep-20 | Sep-20 | Sep-20 | Sep-20 | Sep-20 | |||||||
| INSPECTION STAUS | - | PASS | PASS | PASS | PASS | PASS | PASS | PASS | PASS | PASS | PASS | |||||||
| tank water level gauge broken SAME ISSUE AS 5/2/12 & 5/10/13 INSPECTIONS, settings need to be changed, casing relief valve needs replacement, os&y valve needs replacement (YELLOW TAGGED) | ||||||||||||||||||
| Pump-2014-05-13 | P | 05/13/2014 | bypass valves are shut but cannot be left open, no jockey pump, need to cut in a 5" butterfly valve on test header SAME ISSUES AS 5/2/12 & 5/10/13 INSPECTIONS (YELLOW TAGGED) | ARDEC | ||||||||||||||
| 44 | B | On | Fire Pump | Peerless 6AEF16N | Pump-2014-05-13 | P | 05/13/2014 | transducer needs replacement (GREEN TAGGED) | ARDEC | |||||||||
| 93 | On | Fire Pump | Aurora 481-SF | Pump-2014-05-14 | P | 05/14/2014 | negative pressure on intake, display unit is blank, need to check timer OVERDUE INSPECTION (NO ACCESS) | ARDEC | Gordon James, X2729 | 637 admin, not incl. visitors | ||||||||
| 458 | On | Fire Pump | Patterson 6X5X17SSC | IP Dialer | Pump-2012-05-24 | P | 05/24/2012 | 2011 new system installed OVERDUE INSPECTION (NO ACCESS) | DPW | |||||||||
| 623 | On | Fire Pump | AC FIRE PUMP 07-0505 | ? | 2011 | - | ? | jockey pump discharge piping incorrect, sensing lines for pump and jockey pump need to be corrected, angle hose valve is split (YELLOW TAGGED) | ||||||||||
| 630 | B | Off | Fire Pump | ITT A-C 9100 | ? | 2013 | Pump-2014-05-16 | P | 05/16/2014 | not in service - IJO Required for demolition and install | ARDEC | |||||||
| 660 | A | On | Fire Pump | Aurora 481 BG | ? | 2016-07 | F | 07/01/2016 | gauges need to be replaced both lines (YELLOW TAGGED) | ARDEC | ||||||||
| 717 | Off | Fire Pump | ? | Pump-2014-05-16 | P | 05/16/2014 | sensing lines are steel and do not have check valves but have control valves, SAME ISSUES AS 5/4/12 & 5/10/13 INSPECTIONS pump settings should be changed (YELLOW TAGGED) | ARDEC | ||||||||||
| 808 | On | Fire Pump | Floway 18MKL-FP | Pump-2014-05-13 | P | 05/13/2014 | gauges are over 5yrs old, bypass needs to be installed properly or removed (YELLOW TAGGED) | DPW | ||||||||||
| 3029 | C | On | Fire Pump | Fairbanks Morse 2823AF | Pump-2014-05-13 | P | 05/13/2014 | OVERDUE INSPECTION | Commissary | |||||||||
| 3355 | On | Fire Pump | ITT-AC 8X6X12F | ? | - | ? | acts a a service pump but should be serviced and inspected the same way as a FP. Need to determine adding to Chugach contract - forwarded to Mr. Havrisko for review. | |||||||||||