Questions

Is it possible for IRS to provide the pricing schedule in Excel Format?

This is not possible. Our solicitation is currently on our own software.

Could the IRS please provide a list of current subcontractors/vendors utilized by the incumbent contractor?

This is the most accurate list of subcontractors for the Fresno Service Center.

Subcontractors are:

Phoenix Fire Protection 559-799-7569

San Joaquin Chemical559-994-9185
American Mobil Wash559-291-4802
Bank Company559-485-3456
Central Broiler559-625-5151

Advanced Welding & Fabrication 559-417-8152

A-Cal Concrete559-675-3000
All Valley Disposal559-277-1009

Central Boiler & Industrial Service 559-625-5151 Emerson 408-434-5330 Four CCCC’s A/C 559-237-3990 Fresno Waste Oil Services 800-359-2907 Fresno Tent and Awning 559-264-4771 Hobart 559-237-2118 Hyster 559-487-1160 Jerico Fire Protection 559-255-6446 Fresno Pipe & Supply 559-268-6241 Jorgensen Co. 559-268-6241 Lakos Solid Filtration 559-255-1601 L & H Airco 559-253-9660 Med Valley Distributors 559-485-2660 Power System Testing 559-275-2171 Red Wing Shoes 559-435-1555 Ama Plumbing 559-354-9630 San Joaquin Valley Air Pollution 559-230-6000

Would the Government consider removing the limitation on corporate experience and past performance to allow submission and evaluation of proposed subcontractor experience and references?

Limitations have been removed, please review amendment 0001.

Is this a hard bid?

No, this is a Request for Proposal. The propose contractor who offers the best value to the Government, based on price and technical considerations, will receive the award.

Is there a construction manager?

No, the Additional Services does not include this position in the current contract.

Was the Pre Bid Meeting mandatory?

Contractors were encouraged to attend the Site Survey on August 10, 2010. This was not a mandatory event.

If yes, will you be scheduling another?

There will not be another Site Survey.

Is there bonding required for this procurement?

Bonding is required for construction services. These services will be reflected in the category “Additional Services”.

Question regarding the Statement of Equivalent Wages – Please confirms that the Wage Determination 05-2045 is applicable vs. the Statement of Equivalent Wages.

For Service work the following wages would apply - Wage Determination Number 2005-2045, Revision 9, Dated 10/27/09 which applies for the Service Contract Act. For Construction work the following wages would apply -Davis Bacon General Decision Number CA 100029 03/19/2010 CA 29.

The PWS requires the incoming contractor to be responsible for all deficiency costs up to $500 per item. Is it reasonable to have the incoming contractor pay to make repairs which should have been covered by the previous contractor? If so then please provide a guideline on how to best estimate that cost.

Deficiencies are pointed out by the new O & M Contractor; we haven't turned in a building deficiency since the phase in period for the last contract. Deficiencies must not be confused with new and on going work orders. We do reserve the right to place 200 Service calls per month but have never came close to that number.

On SF 1449, on page 1, block 22 the unit for the Phase-In Period is given as “AJ.” This acronym or abbreviation is not listed in Technical Exhibit 8, Glossary of Terminology. Please explain meaning of “AJ.”

AJ means Adjustable. This CLIN would be considered two payments.

The AJ only applies to the Phase-In- Phase.

On SF 1449, on page 2, Item Number 0001 phase-In Period includes the statement “Due Date: 03/13/2010.” What does this mean?

Phase In period must be completed by 3/13/2010.

On page 122 of 143 under (8) B. Formatting and Layout, it says “type size must be 10 to 12 point font” but page 124 of 143, Written Proposal Format, B text, states “type size shall not be smaller than Microsoft Word font Times New Roman, 11point font”. Please clarify the font size and type.

This was a clerical error. The font should be “Times New Roman” and can type in the following font 10, 11 or 12 point font.

Technical Exhibit TE-3, on the bottom of page says the Government can order an additional 200 service calls to correct the deficiencies found in the Phase-In inspection. If all 200 service calls are ordered that would be a cost of $100,000 that the new contractor is responsible for. Is this correct and is the Government planning on using all 200 service calls?

That number depends directly on the incoming Contractor,. There are several from the last contractor that we deemed un-necessary.

PWS 3.10.1 Phase-In Planning/Staffing, lists several positions and the number of days for which the position “shall be filled and the individuals shall be on-site prior to the contract start date.” Will this requirement be filled if the incoming contractor commits to hiring the incumbent personnel for these positions, but they remain employees of the outgoing contractor until the last day of the current contract? Please clarify.

Contractors should price it as though they would be hiring new employees and if they happen to hire incumbents that worked for IAP until the beginning of the new contract the Offeror should then give us a credit for all phase-in staffing not provided.

PWS 3.10.7, Phase-Out, states “The Contractor shall prepare and submit to the COTR any changes to the Phase-out plan submitted as part of the original proposal.” In addition, TE-6 refers to a Revised Phase-out Plan (emphasis added) being due 60 days before contract termination. However, the Phase-out Plan does not appear to be mentioned as part of the proposal contents in the PWS discussions for proposal preparation starting on page 119 of 143. Please clarify proposal requirements.

Phase out period is going to be incorporated into the last option year of the contract. This should be no extra charge.

The proposal instructions also state that there is no page limit for Volume I: Technical Proposal (page 123 of 143). However, there is a note after item 10 in the Corporate Experience Summary Sheet that states: "Note: If additional space is required to answer, in detail, any of the above questions please provide one separate page with the question number(s) and your response. Only one additional page will be accepted..." Is there a page limit for each Corporate Experience Summary Sheet? If there is a page limit for each Corporate Experience Summary Sheet, could the additional information be provided at each appropriate response item in the Summary Sheet instead of being referred to a third sheet, so long as the overall page limit per Summary Sheet is not exceeded?

There is no page limit. This statement has been omitted off the Corporate Experience Summary Form. Amendment 0003 will reflect a new revised Corporate Experience Summary Form.

18. Can you tell me who has contract now?

IAP Worldwide Services What are the terms of that contract? Is this information public information? Can I see a copy?

Yes, this information is public. If you would like to get a copy of this contract, you must submit your request in writing. Please note, this is a long process.

Technical exhibits state 1881 calls last year. Average 20 calls per day. 4.

Another place it says 5000 calls per year. Just want to clear what number I should use for planning purposed.

Numbers were based on FY2003 averages, 200 S/C per month is the maximum that O & M contract can receive per month. We are averaging about 80 per month. The contractor should be advised that the S/C numbers are very seasonal; also if the building is operated correctly the numbers go down.

Other files

File Type Posted
TIRWR10R00009-A0008[1].rtf RTF text file
TE-6_reports-august 26.pdf PDF
TIRWR10R00009[1]-revised August 24.rtf RTF text file
Davis Bacon 6-2010.pdf PDF
Fresno Wage Determination Aug25.pdf PDF
TIRWR10R00009-A0007.rtf RTF text file
Fresno Wage 6-2010.rtf RTF text file
Davis Bacon 6-2010.pdf PDF
TIRWR10R00009-A0006.pdf PDF
TIRWR10R00009-A0004.rtf RTF text file
TIRWR10R00009-A3.rtf RTF text file
Corporate Experience Summary Form 2.pdf PDF
TIRWR10R00009-A0002[1].pdf PDF
site survey sign in sheet.pdf PDF
post synopsis.rtf RTF text file
TIRWR10R00009[1]-revised August 9.pdf PDF
TIRWR10R00009-A0001[1].pdf PDF
TE-12 EMS Fresno Territory.pdf PDF
Past Performance Questionnaire-Fresno.pdf PDF
TE11 Certification Test-Schedule CA October 07.pdf PDF
Fresno Wage Determination[1].pdf PDF
Contract - QASP AUGUST 2010.pdf PDF
TE-6_reports-august 2010.pdf PDF
Corporate Experience Summary Form.pdf PDF
Freseno Davis Bacon[1].pdf PDF
TE-2, New PWS-aug 10.pdf PDF
TIRWR10R00009[1].pdf PDF
post synopsis.pdf PDF
te_8_terminology.revised.pdf PDF
TE-3_New PWS_12_9_09.pdf PDF
TE-5 Final 3-27-09.xls XLS spreadsheet
TE-7 Government Furnished Facilities.pdf PDF
te-4_preventive_AUGUST 2010.pdf PDF
te-9_standards_and_regulations_1_14_2008.pdf PDF
HSPD_12_PIV_Procedures_Manual.pdf PDF
te-10_infrared.pdf PDF
TE-1 Facility Location Data AUGUST 2010.pdf PDF
Show all 37

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .