Facility Maintenance and Repair – IRS Building Delegations
Technical Exhibit GEN-4
Preventive Maintenance Requirements
INTERNAL REVENUE SERVICE
Public Buildings Service Office of Real Property Management and Safety
PUBLIC BUILDINGS
PREVENTIVE
MAINTENANCE
GUIDES
March 2012
TABLE OF CONTENTS
1A-1 Air Dryer, Refrigerated or Regenerative Desiccant Type (Frequency: Semiannual)
3A-2 Unitary, Heating and Cooling Unit Application (Frequency: Annual)
5A-3 Humidification Systems (Frequency: Semiannual)
6A-4 Air Compressor (Frequency: Semiannual)
7A-5 Air Conditioning Machine; Split System (Frequency: Comfort – Annual, Special – Monthly)
9A-6 Air-Conditioning Machine Package Unit (Comfort Cooling) (Frequency: Annual)
11A-7 Air-Conditioning Machine, Package Unit (Special Purpose) (Frequency: Monthly)
13A-8 Air-Conditioning, Window Unit (Frequency: Annual)
15A-9 Air-Cooled Condenser (Frequency: Annual)
17A-10 Heat Pumps (Frequency: Annual)
19A-11 Air Handler Unit (Frequency: Annual)
21A-12 Glycol Dry Cooler (Frequency: Comfort – Annual, Special – Semiannual)
23A-13 Air Conditioning Unit, Ceiling/Wall Mounted (Frequency: Comfort – Annual, Special – Monthly)
25A-15 After-Cooler/Separator (Frequency: Semiannual)
26B-1 Battery Charger (Frequency: Quarterly)
27B-2 Boiler (Coal, Oil, and Gas) (Frequency: Annual)
28B-2A Boiler (Coal, Oil, and Gas)
29B-3 Burner, Gas (Frequency: Annual)
31B-4 Burner, Oil (Frequency: Annual)
33B-5 Boiler, Electric (Frequency: Annual)
34B-6 Boiler, Instruments/Controls (Frequency: Annual)
35B-7 Boiler, Internal Inspection and Hydrostatic Test (Frequency: Annual)
38B-8 Boiler, External Inspection (Frequency: Annual)
40BA-1
Battery Replacement, Restrooms (Frequency: Annual)
41C-1 Clocks, Central System (Frequency: Semiannual)
42C-2 Remote Air Intake Dampers (Frequency: Semiannual)
43C-3 Coils Preheat, Reheat, Etc. (Remote Locations) (Frequency: Annual)
44C-4 Central Mini-Computer, HVAC Systems (Frequency: Quarterly)
45C-5 Automatic Mixing Box Pneumatic or Electric (Frequency: Annual)
46C-6 Controls, Central System HVAC (Frequency: Annual)
47C-7 Condensate or Vacuum Pump (Frequency: Annual)
48C-8 Central Control Panel (Frequency: Annual)
49C-9 Cooling Tower, Maintenance (Frequency: Annual)
52C-10 Cooling Tower, Cleaning (Frequency: Quarterly)
55C-11 Evaporative Condenser (Frequency: Annual)
58C-13 Crane, Electric (Frequency: Quarterly)
59C-14 Chain Hoist and Trolley (Frequency: Annual)
60C-21 Carts and Scooters, Engine or Battery Powered (Frequency: Annual)
62C-24 Condensing Unit, Refrigeration (Frequency: Critical: Monthly, Comfort: Annual)
64D-1 Door, Power Operated (Frequency: Semiannual)
65D-3 Roof Drains, Downspout, and Gutter Inspection (Frequency: Annual)
66D-4 Door, Automatic Hydraulic Electric or Pneumatic Operated Main Entrance (Frequency: Quarterly)
67D-5 Doors, Main Entrance (Frequency: Semiannual)
68D-6 Drains, Areaway, Driveway, Storm (Frequency: Annual)
69D-9 Distiller, Water, Laboratory Use Only (Frequency: Annual)
70D-10 Door, Manual Overhead (Frequency: Annual)
71E-1 Elevators, Electric or Hydraulic (Frequency: Monthly)
73E-2 Elevators, Electric or Hydraulic (Frequency: Quarterly)
74E-3 Elevators, Electric or Hydraulic (Frequency: Semiannual)
75E-4 Elevators, Electric or Hydraulic (Frequency: Annual)
77E-5 Elevator, Electric, Inspection (Frequency: Semiannual)
79E-6 Elevator, Electric, Inspection (Frequency: Annual)
81E-7 Elevator, Electric, Inspection (Frequency: 5 Year)
91E-8 Elevator, Hydraulic, Inspection (Frequency: Semiannual)
93E-9 Elevator, Hydraulic, Inspection (Frequency: Annual)
102E-10 Escalators and Moving Walks, Inspection (Frequency: Annual)
104E-15 Escalator (Frequency: Weekly)
105E-16 Escalator (Frequency: Annual)
106E-17 Expansion Joints In Piping (Frequency: Annual)
107E-18 Emergency Lights, Wet Cell (Frequency: Quarterly)
108E-18A Emergency Lights (wet cell) (Frequency: Monthly)
109E-19 Emergency Lights, Closed Systems (Frequency: Quarterly)
110E-19A Emergency Lights, (Frequency: Monthly Closed System)
111E-20 Induction Disc Over Current Relay (Frequency: Annual)
113E-21 Over and/or Under Voltage Relay (Frequency: Annual)
115E-22 Thermal Over Current Relay (Frequency: Annual)
117E-23 Induction Disc – Directional Over Current Relay (Frequency: Annual)
119E-24 Power Factor Reverse Current or Watt Type Relay (Frequency: Annual)
120E-25 Ground Fault Type Transformer or Differential Relay (Frequency: Annual)
121E-25A Bolted Pressure Contact Switch (low voltage) Switch (low voltage) (Frequency: Ground Fault Operated: Annual, Stand Alone: Three Years
122E-26 Low Voltage Molded Case Circuit Breaker (Frequency: Three years)
123E-27 Low Voltage Power Air Circuit Breakers (Over 100 Amps) (Frequency: Three years)
125E-28 Motor Starters, 100 Hp and Greater (Frequency: Three years)
126E-29 High Voltage Oil Circuit Breaker (Frequency: Annual)
127E-30 Switchboards, Medium Voltage (Frequency: Three years)
129E-30A Switchboard, Low Voltage (Per Cubicle) (Frequency: Three Years)
131E-31 Network Protectors 600V Class (Frequency: Annual)
133E-32 High Voltage Network and Power Type Transformer (Oil Filled) (Frequency: Annual)
135E-33 High Voltage Network and Power Dry Type Transformers (Frequency: Annual)
136E-34 Disconnects (Isolating Switch; Per Switch 600 volts and above) (Frequency: Annual)
E-34A Disconnects (Isolating Switch: Per Switch, less than 600 volts, greater than 200 amps) (Frequency: Annual 138E-35 Motor Control Center (MCC) (Frequency: Semiannual)
139E-36 Automatic Transfer Switch (Frequency: 3 Years)
141E-37 Bus Duct, Low Voltage, and Connectors (Frequency: Aluminum: Annual, Outdoors: Annual, Copper: 3 Years
144E-37A Bus Duct, Metal Enclosed, and Connectors (Frequency: Aluminum: Annual, Outdoors: Annual, Copper: 3 Years
146E-38 High Voltage Air Circuit Breaker (Frequency: Annual)
147E-39 Supervision Set (Frequency: Annual)
148E-40 Emergency Generators, Electric, Gasoline, or Natural Gas Engines (Frequency: Annual)
150E-41 Emergency Generators, Electric, Diesel Engines (Frequency: Quarterly)
151E-41A Emergency Generators, Electric, Diesel Engines (Frequency: Annual)
153E-42 Emergency Generators, Electric (Frequency: Weekly)
155E-42A Emergency Generators, Electric (Frequency: Monthly)
157E-42B Emergency Generators, Electric (Frequency: Quarterly)
158E-42C Emergency Generators, Electric (Frequency: Semiannual)
160E-43 Lead Acid Battery (Frequency: Quarterly)
162E-43A Lead Acid Battery – Sealed Type (Gell Cell) (Frequency: Quarterly)
163E-44 Nickel Cadmium Battery (Frequency: Quarterly)
164E-44A Primary Battery (Dry Cell) (Frequency: Monthly)
165E-46 Battery, Uninterruptible Power System (Frequency: Monthly)
167E-46A Battery, Uninterruptible Power System (Frequency: Quarterly)
168E-46B Battery, Uninterruptible Power System (Frequency: Annual)
169E-49 Emergency Pumps and Ventilators (Frequency: Annual)
170E-50 Emergency Pumps and Ventilators (Frequency: Quarterly)
171E-51 Motor Starter, Less than 100 Hp (Frequency: Annual)
172E-52 Auxiliary Protective Relays (Frequency: Annual)
173E-53 Exit Lights, Emergency (Frequency: Monthly)
174E-56 Dimmer and Control, Stage and General Lighting (Frequency: Quarterly)
175E-57 Low Voltage Dry Type Transformer (30 KVA or More, 600 Volts or Less) (Frequency: 3 years)
176E-58 Power Distribution Units (PDU) (Frequency: Semiannual)
178E-59 Uninterruptible Power Systems (UPS) (Frequency: Quarterly)
179E-60 Uninterruptible Power Systems (UPS) (Static) (Frequency: Annual)
181E-61 Uninterruptible Power Systems (UPS) Static (Frequency: Annual)1
182E-65 Uninterruptible Power Systems (UPS) (Frequency: Annual, Quarterly)
184E-66 Uninterruptible Power Systems (UPS) (Frequency: Annual, Semi-Annual)
191F-1 Alarm Check Valves and Accessories (Frequency: Monthly)
192F-1A Alarm Check Valves and Accessories (Frequency: Quarterly)
193F-2 Dry Pipe, Deluge and Preaction Valves (Frequency: Weekly)
195F-2B Dry Pipe, Deluge, and Preaction Valves (Frequency: Annual)
197F-3 Post Indicator Valves (Frequency: Annual)
198F-4 Fire Control Valves (Frequency: Monthly)
199F-4A Fire Control Valves (Frequency: Quarterly)
200F-4B Fire Control Valves (Frequency: Annual)
201F-5 Fire Pump – Diesel Engine Driven (Frequency: Weekly)
203F-5A Fire Pump – Diesel Engine Driven (Frequency: Monthly)
204F-5B Fire Pump – Diesel Engine Driven (Frequency: Quarterly)
205F-5C Fire Pump – Diesel Engine Driven (Frequency: Annual)
207F-6 Fire Pump – Electric Motor Driven (Frequency: Weekly)
208F-6A Fire Pump – Electric Motor Driven (Frequency: Monthly)
209F-6B Fire Pump – Electric Motor Driven (Frequency: Annual)
211F-8 Fire Hose – 1.5 in., Racked in Buildings (Frequency: Monthly)
212F-8A Fire Hose – 1.5 in. Racked in Buildings (Frequency: Annual)
213F-9 Fire Department Hose Connections – Standpipe Outlets (Frequency: Monthly)
214F-9A Fire Department Hose Connections – Standpipe Outlets (Frequency: Five Years)
215F-10 Fire Department Pumper Connections – Standpipe or Sprinkler (Frequency: Monthly)
216F-11 Fire Doors – Stairwells and Exitways, Swinging (Frequency: Quarterly)
217F-12 Fire Doors – Sliding and Vertical Rolling (Frequency: Quarterly)
218F-13 Fire Supervisory Signals – Testing (Frequency: Quarterly)
219F-14 Automatic Fire Detection – Smoke Detectors (Frequency: Annual)
221F-14B Automatic Fire Detection – Heat Detectors (Frequency: Annual)
223F-14C Smoke Control Systems – Operational Testing (Frequency: Semiannual)
224F-15 Fire Alarm Control Panel and Remote Annunciators (Frequency: Annual)
226F-15A Fire Alarm Control Panel – Special Systems (Frequency: Annual)
228F-15B Central Station Transmitter (Frequency: Annual)
229F-15C Central Station – Receiver and Re-Transmission Equipment (Frequency: Daily)
231F-16 Fire Alarm System – Recorder (Frequency: Weekly)
232F-16A Fire Alarm System – Event Printer (Frequency: Quarterly)
233F-16B Fire Alarm System – Audio Control Panel (Frequency: Annual)
234F-16C Fire Alarm System – Remote Controller (Frequency: Annual)
235F-16D Fire Alarm System – Remote Amplifier (Frequency: Annual)
236F-17 Manual Fire Alarm Stations – Coded and Uncoded (Frequency: Annual)
237F-18 Fire and Smoke Dampers (Frequency: Two Years)
238F-19 Fire Hydrants – Dry Barrel and Wet Barrel (Frequency: Semiannual)
239F-19A Fire Hydrant Flow Test- Dry Barrel and Wet Barrel (Frequency: Five Years)
241F-20 Sprinkler Heads – Sprinklered Areas (Frequency: Annual)
242F-20A Antifreeze Solution in Sprinkler Systems (Frequency: Annual)
244F-21 Water Spray Extinguishing Systems (Frequency: Monthly)
245F-21A Water Spray Extinguishing Systems (Frequency: Annual)
247F-22 Fire Extinguishers, Stored Pressure with Gauge (Frequency: Annual)
249F-22A Fire Extinguishers – Stored Pressure With Gauge (Non- Stainless Steel Shell) (Frequency: 6-years)
250F-22B Fire Extinguishers – Non rechargeable (Frequency: Annual)
251F-23 Fire Extinguishers, Gas Cartridge or Cylinder (No Gauge) (Frequency: Annual)
253F-24 Fire Extinguishers – Inspection (Frequency: Monthly)
254F-24 Fire Extinguishers – Inspection (Frequency: Monthly)
255F-25 Fire Extinguishers, Hydrostatic Testing of Carbon Dioxide, Stored Pressure and Cartridge Type (Frequency: 5 or 12 years)
257F-26 Fire Extinguishing Systems, Carbon Dioxide (High Pressure) Halon, Dry Chemical – Inspection (Frequency: Monthly)
258F-26A Fire Extinguishing Systems, Carbon Dioxide (High Pressure) Halon, Dry Chemical (Frequency: Semiannual)
260F-27 Fan, Centrifugal (Frequency: Annual)
261F-28 Filter, Movable Curtain, Oil Coated (Frequency: Quarterly)
262F-29 Filter, Roll Type, Disposable (Frequency: Quarterly)
263F-30 Filters, Viscous Type(Wire Mesh) (Frequency: Quarterly)
264F-31 Filter, Roll Type Disposable Media, Manual or Motor Driven (Frequency: Annual)
265F-31 Filter, Roll Type Disposable Media, Manual or Motor Driven (Frequency: Annual)
266F-32 Filter, Throw Away (Frequency: Quarterly)
267F-32A Filter, Throw Away (Frequency: Monthly)
268F-32H HEPA Filter, Throw Away (Frequency: Annual)
269F-33 Filters, Electrostatic (Frequency: Quarterly)
270F-36 Fans, Propeller, 24" Diameter or Larger (Frequency: Annual)
271F-38 Lightning Protection(Per Down Conductor) (Frequency: Annual)
272F-39 Cafeteria Exhaust Hood, Duct System (Frequency: Semiannual)
273F-40 Filter, Throw Away, Bag Type (Frequency: Semiannual)
274F-43 Filter, Charcoal (Frequency: Quarterly)
275F-44 Fountain, Memorial or Decorative (Frequency: Semiannual)
276F-46 Fireplace (Frequency: Monthly)
277F-47 Fireplace (Frequency: Quarterly)
278F-49 Filter, Control Air (Frequency: Quarterly)
279G-1 Fuel Oil Filter/Strainer (Frequency: Semiannual)
280G-2 Grease Traps (Frequency: Monthly)
281G-3 Fences and Gates, Security/Access (Frequency: Semiannual)
282H-1 Hot Water Converters (Steam) (Frequency: Annual)
283H-2 Hot Water Heater – Gas (Frequency: Annual)
284H-3 Hot Water Heater – Electric (Frequency: Annual)
285H-4 Plate Heat Exchanger (Frequency: Annual)
286H-5 Hot Water Heater – Steam Coil (Frequency: Annual)
287H-6 Hot Air Furnace (Frequency: Annual)
288H-12 Unit Heater, Fuel Oil (Frequency: Annual)
289H-15 Hoist, Electric (Frequency: Annual)
290I-2 Fan Coil Units, Under Window Type
291I-3 Induction Units, Under Window Type (Frequency: Annual)
292I-4 Fan Coil Unit, Ceiling Hung (Frequency: Annual)
293I-5 Fan Coil Unit, Ceiling Hung, VAV Box with Electric Reheat (Frequency: Annual)
294K-1 Play Structure, Surfacing, Location and Accessibility, Size, and Placement, and Storage Area, Maintenance Worksheet (Frequency: Monthly)
295K-2 Play Structure, Sliding Equipment (Frequency: Quarterly)
296K-3 Play Structure, Swing (Frequency: Monthly)
297K-4 Play Structure, Climbing Equipment (Frequency: Monthly)
299K-5 Play Structure, Rotating, Spring Rocking, and Seesaws (Frequency: Monthly)
300K-6 Play Structure, Sand and Water Play Equipment (Frequency: Monthly)
301K-7 Play Structure, Signs, Trees, and Pathways (Frequency: Semiannual)
302K-8 Play Structure, Playhouse, Garden, and Manipulatives (Frequency: Annual)
303K-9 Play Structure, Carriages and Buggies (Frequency: Annual)
304K-100 Kitchen Equipment, Dish/Tray, Busing Conveyor (Frequency: Quarterly)
305K-100A Kitchen Equipment, Dish/Tray, Busing Conveyor (Frequency: Semiannual)
306K-101 Kitchen Equipment, Dishwashing Machine (Frequency: Quarterly)
307K-101A Kitchen Equipment, Dishwashing Machine, Electric (Frequency: Semiannual)
308K-102 Kitchen Equipment, Fryer (Frequency: Quarterly)
309K-102A Kitchen Equipment, Fryer (Frequency: Semiannual)
310K-103 Kitchen Equipment, Grill (Frequency: Quarterly)
311K-103A Kitchen Equipment, Grill (Frequency: Semiannual)
312K-104 Kitchen Equipment, Ice Cream and Shake Maker (Frequency: Quarterly)
313K-104A Kitchen Equipment, Ice Cream and Shake Maker (Frequency: Semiannual)
314K-105 Kitchen Equipment, Ice Maker (Frequency: Quarterly)
315K-105A Kitchen Equipment, Ice Maker (Frequency: Semiannual)
316K-106 Kitchen Equipment, Kettle (Frequency: Quarterly)
317K-106A Kitchen Equipment, Kettle (Frequency: Semiannual)
318K-107 Kitchen Equipment, Oven (Frequency: Quarterly)
319K-107A Kitchen Equipment, Oven (Frequency: Semiannual)
320K-108 Kitchen Equipment, Range (Frequency: Quarterly)
321K-108A Kitchen Equipment, Range (Frequency: Semiannual)
322K-109 Kitchen Equipment, Refrigerators/Freezers (Walk-In Units) (Frequency: Quarterly)
323K-109A Kitchen Equipment, Refrigerators/Freezers (Walk-In Units) (Frequency: Semiannual)
324K-110 Kitchen Equipment, Boiler/Generator, Steam (Frequency: Quarterly)
325K-110A Kitchen Equipment, Boiler/Generator, Steam (Frequency: Semiannual)
326L-2 Loading Ramp, Adjustable (Frequency: Quarterly)
327L-3 Lighting, Special Fixture (Frequency: Annual)
328L-4 Lighting, Outside; Incandescent (Frequency: Semiannual), Fluorescent, Mercury Vapor Or High Pressure Sodium ( Frequency: Five Years)
329L-5 Lawn Sprinklers (Per Nozzle) (Frequency: Annual)
330L-5A Lawn Sprinklers, Seasonal Start Up (Frequency: Annual)
332L-8 Spotlights, Fixed And Portable (Frequency: Monthly)
333L-10 Lift, Electric, Stage Screen (Frequency: Semiannual)
334L-11 Leak Detection System, (Frequency: Semi-Annual Fuel Oil)
336L-11A Leak Detection System, (Frequency: Annual Water, Under Floor)
337M-1 Manhole, Electrical (Frequency: Annual)
338M-2 Manholes, Sewer (Frequency: Quarterly)
339M-3 Motors, Preventive Maintenance (Frequency: Annual)
340M-3A Motors, Predictive Maintenance (Frequency: Annual)
342M-4 Manhole (Water, Steam, and Fuel Oil) (Frequency: Semiannual)
343M-5 Material Handling Equipment, Electric Lift Trucks (Frequency: Monthly)
345M-5A Material Handling Equipment, Electric Lift Trucks (Frequency: Annual)
346M-6 Material Handling Equipment, Engine Driven (Frequency: Semiannual)
347M-7 Material Handling Equipment, Non-Power Operated (Frequency: Annual)
348M-9 Mobile Equipment (Frequency: Annual)
349M-10 Motor Controller Unit, 600 Volts or 200 Hp and Above (Frequency: Annual)
351M-11 Motors, 3-Ph, 600 Volts or 200 Hp and Above. (Frequency: Annual)
353P-4 Pump, Centrifugal (Frequency: Annual)
355P-6 Pump, Vacuum (Frequency: Semiannual)
356P-08, PA/Music/White sound (Frequency: Monthly)
357P-9 Asphalt Parking Lot Inspection (Frequency: Semiannual)
358R-1 Radiator, Heating (Frequency: Five Years)
359R-2 Roof Inspection, Built Up Type (Frequency: Semiannual)
360R-2A Roof Inspection, Shingle Type (Frequency: Semiannual)
367R-3 Refrigeration Machine, Absorption Unit (Frequency: Annual)
370R-4 Central Chilled Water Package Unit: Comfort Cooling or Drinking Water (Frequency: Annual), Special Purpose or Computer Cooling (Frequency: Quarterly)
372R-5 Refrigeration Machine, Centrifugal (Frequency: Annual)
374R-6 Refrigeration Machine, Reciprocating and Scroll (Frequency: Annual)
376R-7 Refrigeration Machine, Rotary Screw (Frequency: Semiannual)
378R-8 Control Panel, Central Refrigeration Unit (Frequency: Annual)
379R-9 Radiation – Baseboards/Convectors (Steam, Hot Water, or Electric, per Linear Foot) (Frequency: 2 Years)
380R-11 Refrigeration Controls, Central System (Frequency: Annual)
381R-13 Non-Destructive Chiller Tube Analysis (Frequency: Three Years)
382R-14 High Efficiency Purge Units (Frequency: Annual)
384R-15 Refrigerant Monitor (Frequency: Monthly)
385S-1 Separator, Oil and Water (Frequency: Semi-Annual)
386S-2 Sewage Ejector (Pneumatic Tank Type Ejectors) (Frequency: Annual)
387S-5 Sweeper (Frequency: Semiannual)
388S-6 Sewage Ejector, Sump Type (Frequency: Annual)
389S-7 Sump Pump (Frequency: Annual)
390S-8 Strainer, Y-Type (Frequency: Annual)
391S-9 Strainer, Bolted Flange Type (Water and Steam) (Frequency: Annual)
392S-10 Scrubbing Machine (Battery or Propane Powered) (Frequency: Quarterly)
393S‑11 Snow Blower (Frequency: Annual)
394S-14 Dual Strainer (Frequency: Annual)
395S-15 Backwash Strainer (Frequency: Annual)
397T‑1 Tanks, Water, (All Types) (Frequency: 3 Years)
398T‑2 Tank, Air/Refrigerant/LP Gas (Frequency: Annual)
399T‑3 Tanks, Fuel Oil Storage (Frequency: 4 Years)
400T-4 Underground Storage Tank (UST) (Frequency: Monthly)
401T‑5 Trash Compactor (Frequency: Annual)
402T‑6 Tank, Chemical (Frequency: Annual)
403T‑8 Traps (All Types) (Frequency: Low Press: —Every 5 Years, High Press: Annual)
404U‑1 Unit Heaters (Steam and Hot Water) (Frequency: Annual)
405U‑2 Unit Heater (Gas and Oil Fired) (Frequency: Annual)
406V‑2 Valve, Safety Relief (Frequency: Monthly)
407V‑3 Valves, Regulating (Frequency: Annual)
408V-4 Valves, Fire System – Pressure Regulating Type (Frequency: Monthly)
409V-4A Valves, Fire System – Pressure Regulating Type (Frequency: Annual)
411V-4B Valves, Fire System – Pressure Regulating Type (Frequency: Five Years)
413V‑5 Valve, Manually Operated (Frequency: Main Line or Critical – Annual, Other Over Two Inches — 5 years)
414V‑6 Valve, Motor Operated (Frequency: Annual)
415V-7 Valve, Hydraulic/Pneumatic/Electric (Frequency: Annual)
416V‑8 Check Valve, Critical (Frequency: Annual)
417V-9 Backflow Preventer (Frequency: Annual)
419V‑10 Vacuum System, Centralized (Frequency: Annual)
420V-11 Mixing valve (Frequency: Annual)
421W‑1 Drinking Water Filter Systems (Frequency: Quarterly)
422W‑2 Wash, Emergency (Frequency: Weekly)
423W‑3 Water Softener (Frequency: Semiannual)
424W‑4 Filter, Water (Frequency: Semiannual)
425W-5 Window Washing Scaffold, Power Operated (Frequency: Annual)
426W‑7 Wheelchair Lift (Frequency: Monthly)
427W-8 Water Treatment for Cooling Systems (Frequency: Monthly)
429W-8 Water Treatment for Cooling Towers (Frequency: Monthly)
430W-9 Water Treatment for Heating Systems (Frequency: Monthly)
431W-10 Drinking Water Fountain (Frequency: Annual)
432X‑21 Key Card System (Frequency: Quarterly)
433X‑22 Electric Flag Pole (Frequency: Quarterly)
434X‑23 Unit Heater, Electric (Frequency: Semiannual)
435X‑26 Solar Heating System (Frequency: Semiannual)
436X‑26A Solar Heating System, (Solar Collectors) (Frequency: Annual)
437X‑29 Chemical Feeder (Frequency: Semiannual)
438X‑32 Parking Arm Gates (Frequency: Annual)
439X‑37 Emergency Shower (Frequency: Annual)
440X‑39 Septic Tank (Frequency: Annual)
441X‑41 Tractor, Diesel (Frequency: Monthly, Semiannual, Annual)
442X-50 Variable Speed Frequency Drive (VFD) (Frequency: Annual)
443X-50A Frequency Drive (VFD) (Frequency: Semi-annual)
A-1 Air Dryer, Refrigerated or Regenerative Desiccant Type (Frequency: Semiannual)
Application:
This guide card applies to refrigerated or regenerative desiccant type air dryers with a capacity of 10 SCFM or greater. Those units with a capacity of less than 10 SCFM will be maintained in conjunction with the air compressor that they are associated with.
Special Instructions:
1.
Schedule this maintenance in conjunction with the maintenance on the associated air compressor.
2.
Review manufacturer's instructions.
3.
Review the Standard Operating Procedure for "Controlling Hazardous Energy Sources."
4.
De-energize, lock and tag electrical circuits.
5.
Comply with the latest provisions of the Clean Air Act and Environmental Protection Agency (EPA) regulations as they apply to protection of stratospheric ozone.
6.
No intentional venting of refrigerants is permitted. During the servicing, maintenance, and repair of refrigeration equipment, the refrigerant must be recovered.
7.
Whenever refrigerant is added or removed from equipment, record the quantities on the appropriate forms.
8.
Recover, recycle, or reclaim the refrigerant as appropriate.
9.
If disposal of the equipment item is required, follow regulations concerning removal of refrigerants and disposal of the item.
10.
If materials containing refrigerants are discarded, comply with EPA regulations as applicable.
11.
Refrigerant oils to be removed for disposal must be analyzed for hazardous waste and handled accordingly.
12.
For refrigerant type units, closely follow all safety procedures described in the Material Safety Data Sheet (MSDS) for the refrigerant and all labels on refrigerant containers.
Checkpoints:
1.
Lubricate valves and replace packing, if necessary.
2.
Check dryer operating cycle.
3.
Inspect and clean heat exchanger.
4.
Check outlet dew point.
5.
Clean and lubricate blower.
6.
Check automatic blow down devices.
7.
Inspect and replace or reinstall inlet filters.
8.
Refrigerated Type:
a.
Check traps.
b.
Check refrigerant level and moisture content. If low level or moisture is indicated, check for refrigerant leaks using a halogen leak detector or similar device. If leaks are not able to be stopped or corrected, report leak status to supervisor.
c.
Clean and lubricate condenser fan motor.
9.
Desiccant Type:
a.
Replace filter cartridges, both prefilter and afterfilter.
b.
Check the inlet flow pressure, temperature and purge rate.
c.
Check the desiccant and replace if necessary.
d.
Inspect and clean solenoids, purge valves, and strainers.
Recommended Tools, Materials, and Equipment:
1.
Tool Group A
2.
Cleaning equipment, lubricants, approved refrigerants if applicable, and materials. Consult the Material Safety Data Sheets (MSDS) and container labels for hazardous ingredients and proper personal protective equipment (PPE).
3.
Filter cartridges (for desiccant type dryer)
4.
Gasket and packing material
5.
Fin comb
6.
Self sealing quick disconnect refrigerant hose fittings
7.
Refrigerant recovery/recycle unit
8.
EPA/DOT approved refrigerant storage tanks
A-2 Unitary, Heating and Cooling Unit Application (Frequency: Annual)
This guide card applies to self-contained heating and cooling units containing a complete cooling system and heating unit (gas or oil burner). These are normally installed on rooftops, but can be in other locations. They are also referred to as climate changers, roof packs, etc.
Special Instructions:
1.
Schedule shutdowns with operating personnel, as needed.
2.
Review manufacturer's instructions.
3.
Review the Standard Operating Procedure for "Controlling Hazardous Energy Sources."
4.
De-energize, lock and tag electrical circuits.
5.
Comply with the latest provisions of the Clean Air Act and Environmental Protection Agency (EPA) regulations as they apply to protection of stratospheric ozone.
6.
No intentional venting of refrigerants is permitted. During the servicing, maintenance, and repair of refrigeration equipment, the refrigerant must be recovered.
7.
Whenever refrigerant is added or removed from equipment, record the quantities on the appropriate forms.
8.
Recover, recycle, or reclaim the refrigerant as appropriate.
9.
If disposal of the equipment item is required, follow regulations concerning removal of refrigerants and disposal.
10.
If materials containing refrigerants are discarded, comply with EPA regulations as applicable.
11.
Refrigerant oils to be removed for disposal must be analyzed for hazardous waste and handled accordingly.
12.
Closely follow all safety procedures described in the
13.
Material Safety Data Sheet (MSDS) for the refrigerant and all labels on refrigerant containers.
Checkpoints:
1.
Remove debris from air screen and clean underneath unit.
2.
Inspect gaskets. Look for leaks between unit and structure, caulk as necessary.
3.
Clean condenser, cooling coil fins, and fans.
4.
Remove dirt or dust from all interior parts.
5.
Replace filter.
6.
Inspect and adjust damper.
7.
Lubricate motor and fan bearings.
8.
Check fan RPM to design specifications.
9.
Check bearing collar set screws on fan shaft to make sure they are tight.
10.
Check dampers for dirt accumulations. Check felt. Repair or replace as necessary.
11.
Check damper motors and linkage for proper operation.
12.
Lubricate mechanical connections of dampers sparingly.
13.
Clean coils by brushing, blowing, vacuuming or pressure washing.
14.
Check coils for leaking, tightness of fittings:
a.
Check for refrigerant leaks using a halogen detector or similar testing device. If leaks are not able to be stopped or corrected, report leak status to supervisor. Consult the Material Safety Data Sheets (MSDS) for disposal requirements. Reclaimed and recycled CFCs are exempt from hazardous waste regulations (Consult 40 CFR Part 261).
b.
Check refrigerant levels and recharge if needed.
15.
Use fin comb to straighten coil fins.
16.
Flush and clean condensate pans and drains.
17.
Check belts for wear, adjust tension or alignment and replace belts when necessary. Multi-belt drives should be replaced with matched sets.
18.
Check rigid couplings for alignment on direct drives and for tightness of assembly. Check flexible couplings for alignment and wear.
19.
Check electrical connections for tightness.
20.
Check mounting for tightness.
21.
Check for corrosion.
22.
Check mounting bolts and tighten if needed.
23.
Check and adjust, or replace if necessary, vibration eliminators.
24.
Compressor.
a.
Check compressor oil level.
b.
Run machine, check action of controls, relays, switches, etc., to see that:
1) compressor(s) run at proper settings.
2) reheat coils activate properly.
3) crankcase heater is operating properly.
4) suction and discharge pressures are proper.
5) discharge air temperature is set properly.
25.
Heating Unit.
a.
Gas and/or oil fired (if equipped).
1) Check burner for flashback and tight shutoff of fuel.
2) Check operation of controls. Clean and adjust if necessary.
3) Clean burner, chamber, thermocouple and control. (Use a high suction vacuum and/or brush.) Check combustion chamber for cracks, holes, or other defects.
4) Adjust pilot or electric ignition device.
5) Inspect vent and damper operation.
6) Operate unit and adjust burner.
7) Check operation of safety pilot, gas shutoff valve, and other burner safety devices.
8) Check temperature differential and controls.
9) Check frame of unit with ohmmeter for proper electric ground.
10) Replace covers (if any) and clean area.
b.
Electrical (if equipped).
1) Visually inspect for broken parts, contact arcing or any evidence of overheating. Inspect all wiring for deterioration.
2) Check nameplate for current rating and controller manufacturer's recommended heater size. (Heater size shall not be changed without the regional design engineer's approval.)
3) Check line and load connections and heater mounting screws for tightness.
Recommended Tools, Materials, and Equipment:
1.
Tool Group A
2.
Tachometer
3.
Grease gun and oiler
4.
Pressure washer
5.
Vacuum
6.
Fin comb
7.
Cleaning tools, approved refrigerant, and materials. Consult the MSDS for hazardous ingredients and proper personal protective equipment.
8.
Safety goggles and gloves.
9.
CO2 analyzer
10.
Self sealing quick disconnect refrigerant hose fittings
11.
Refrigerant recovery/recycle unit
12.
EPA/DOT approved refrigerant storage tanks.
A-3 Humidification Systems (Frequency: Semiannual)
Special Instructions.
1.
Review manufacturer's instructions.
2.
Review the Standard Operating Procedure for "Selection, Care, and Use of Respiratory Protection."
3.
Turn off water supply.
4.
Secure electrical service before servicing humidification system, if applicable.
5.
Use of work gloves may be necessary due to caustic residual mineral deposits.
Checkpoints.
1.
Operate humidistat through its throttling range to verify activation, or deactivation of humidifier.
2.
Clean and flush condensate pans, drains, water pans, etc. Remove corrosion, and repaint as needed. If a corrosion preventive chemical is used, ensure that it does not become a part of the indoor air by creating large amounts of volatile organic compounds or irritants. Check the Material Safety Data Sheet (MSDS) to see what hazardous products are present. If hazardous products are present rinse very well before the system is returned to use. Ensure that the paint lead level is 0.06% or less.
3.
Check condition of heating element. Clean steam coils.
4.
Clean steam/water spray nozzles. Adjust/replace as needed.
5.
Chemically clean exterior of coil to remove scale and encrustations.
6.
Inspect steam trap for proper operation.
7.
Inspect pneumatic controller for air leaks.
8.
Inspect water lines for leaks and corrosion. Tighten all connections and repair leaks.
Recommended Tools, Materials, and Equipment.
1.
Tool Group A
2.
Psychrometer
3.
Coil cleaning chemical. Consult the MSDS for hazardous ingredients and proper personal protective equipment (PPE).
4.
Work gloves
5.
Safety goggles
6.
Respirator
A-4 Air Compressor (Frequency: Semiannual)
Special Instructions:
1.
Review manufacturer's instructions and equipment history record.
2.
Coordinate motor PM on an annual basis. See Guide M-3.
3.
Tank should be inspected and tested by qualified inspector.
4.
De-energize, tag, and lock out circuits. Review the Standard Operating Guide on "Controlling Hazardous Energy Sources".
Checkpoints:
1.
Perform normal tour checks and operations. Perform a visual inspection of the air system, noting any obvious leaks or portions of the air distribution network that may be subject to physical damage.
2.
Change compressor crankcase oil.
3.
Clean or replace air intake filter.
4.
Check air dryer, automatic condensate drains, and air tank for proper operation. Clean condenser coils and cover grills.
5.
Inspect belt alignment and condition. Adjust or replace belts as required.
6.
Check for corrosion and scale on water cooled units.
7.
Clean heat exchange surfaces.
8.
Check accuracy of gauges with calibrated test gauge.
9.
On two stage compressor, check intermediate pressure.
10.
Test relief valves, replace if leaking or the relief range is incorrect. Do not readjust safety relief valves in the field.
11.
Check operation of compressor unloaders, repair or replace if not loading and unloading properly.
12.
Check compressor suction and discharge valves for proper operation. Replace leaking valves.
13.
Check cut in and cut out of compressor pressure controller, readjust if necessary for proper air pressure requirements. Do not exceed ASME maximum tank pressure.
14.
Check to make sure belt guard is installed prior to putting air compressor back in service.
15.
No pressure vessel is to have its hand hole or manhole covers removed unless the vessel is at atmospheric pressure.
16.
Check if air compressor is running excessively or frequently cycling on and off (possible leaks). Log hour meter readings.
17.
Perform an air leak check of the compressor and air distribution network in the equipment room, using an appropriate ultrasonic scanning device. Check hoses, hose connections, hose fittings, quick couplers, filters, regulators and lubricators. Correct or schedule repair as a work item. Tag location and date of leaks.
Recommended Tools, Materials, and Equipment:
1.
Standard Tools – Basic
2.
Belts
3.
Lubricants. Consult the Material Safety Data Sheets (MSDS) for hazardous ingredients and proper personal protective equipment (PPE).
4.
Fin comb
5.
Vacuum cleaner commercial type
6.Test gauge
7.
Ultrasonic scanner with trisonic and contact scanning modes.
A-5 Air Conditioning Machine; Split System (Frequency: Comfort – Annual, Special – Monthly)
Application:
This guide card applies to those packaged type air conditioning machines that are equipped with chilled water coils or direct expansion coils on split systems. The other portion of the split system, i.e., a refrigeration condensing unit (PM Guide C-24), or a packaged type chilled water unit (PM Guide R-4), is to be serviced in conjunction with this PM activity.
Special Instructions:
1.
Review manufacturer's instructions.
2.
A/C machine maintenance should be scheduled to coincide with condensing unit or package chiller maintenance as noted above.
3.
Comply with the latest provisions of the Clean Air Act and Environmental Protection Agency (EPA) regulations as they apply to protection of stratospheric ozone.
4.
No intentional venting of refrigerants is permitted. During the servicing, maintenance, and repair of refrigeration equipment, the refrigerant must be recovered.
5.
Whenever refrigerant is added or removed from equipment, record the quantities on the appropriate forms.
6.
Recover, recycle, or reclaim the refrigerant as appropriate.
7.
If disposal of the equipment item is required, follow regulations concerning removal of refrigerants and disposal.
8.
If materials containing refrigerants are discarded, comply with EPA regulations as applicable.
9.
Refrigerant oils to be removed for disposal must be analyzed for hazardous waste and handled accordingly.
10.
Closely follow all safety procedures described in the Material Safety Data Sheet (MSDS) for the refrigerant and all labels on refrigerant containers.
Checkpoints:
1.
Thoroughly inspect and clean interior and exterior of machine with vacuum (remove panels).
2.
Clean drain pan and note excessive corrosion. Treat rusted areas with rust inhibitor. Ensure that the rust inhibitor chemical does not add volatile organic compounds or contaminants to the drain pan. If possible, rinse well after application or choose a less hazardous material. Consult the chemicals Material Safety Data Sheet (MSDS) for this information.
3.
Perform checks according to the type of unit.
a.
Chilled water units:
1) Check for chilled water leaks on all lines, valves, strainers, coils, etc. If leaks are not able to be stopped or correctedf, report leak status to supervisor.
2) Clean strainer on chilled water unit.
b.
Direct expansion units: Check for refrigeration leaks on all lines, valves, fittings, coils, etc., using a halogen leak detector or similar testing device. If leaks are not able to be stopped or corrected, report leak status to supervisor.
4.
Check condition of cooling and reheat coils. Use fin comb if need to straighten fins.
5.
Clean coils. Use detergent solution and warm water if coil is heavily soiled.
6.
Drain and clean humidifier pan or pad, whichever applies. Replace pad if required. Remove corrosion as needed.
7.
Clean and lubricate motor and squirrel cage fan(s). Check alignment of motor and fan. Check bearings for excessive wear.
8.
Check belt tension and condition. Adjust or replace as required.
9.
Replace pre-filters if needed.
10.
Replace final filter if needed.
11.
Run machine, check action of controls, relays, switches, etc., to see that:
a.
Chilled water units:
1) Chilled water valve(s) are operating properly.
2) Reheat coils activate properly.
3) Humidistat activates humidifier.
4) Valves regulating water pressure are proper on cooling.
5) Discharge air temperature is set properly.
6) Check and record chilled water inlet and outlet temperatures.
b.
Direct expansion units:
1) Humidistat activates humidifier.
2) Reheat coils activate properly.
3) Discharge air temperature is set properly.
12.
Check and adjust vibration eliminator mountings if equipped. Repair or replace if required.
Recommended Tools, Materials, and Equipment:
1.
Tool Group A
2.
Cleaning tools, grease gun, oil and materials. Consult the MSDS for hazardous ingredients and proper personal protective equipment (PPE).
3.
Vacuum
4.
Fin comb
5.
Filters
6.
Spare V-belts
7.
Self-sealing quick disconnect refrigerant hose fittings, if applicable.
8.
Refrigerant recovery/recycling unit, if applicable.
9.
EPA/DOT approved refrigerant storage tanks.
10.
Safety goggles
11.
Gloves
12.
Approved refrigerant.
13.
Electronic leak detector.
A-6 Air-Conditioning Machine Package Unit (Comfort Cooling) (Frequency: Annual)
Application:
This PM guide applies to units that may have the evaporator, compressor, fan unit components, and condenser within a single housing or may have the condenser separate from the housing. If the condenser is separate, perform the PM on the condensing unit using PM Guide A-9 at the same time.
Special Instructions:
1. Review manufacturer's instructions.
2. De-energize, lockout, and tag the electrical circuits.
3. Comply with the latest provisions of the Clean Air Act and Environmental Protection Agency (EPA) regulations as they apply to protection of stratospheric ozone.
4. No intentional venting of refrigerants is permitted. During the servicing, maintenance, and repair of refrigeration equipment, the refrigerant must be recovered.
5. Whenever refrigerant is added or removed from equipment, record the quantities on the appropriate forms.
6. Recover, recycle, or reclaim the refrigerant as appropriate.
7. If disposal of the equipment item is required, follow regulations concerning removal of refrigerants and disposal of the appliance.
8. If materials containing refrigerants are discarded, comply with EPA regulations as applicable.
9. Refrigerant oils to be removed for disposal must be analyzed for hazardous waste and handled accordingly.
10. Closely follow all safety procedures described in the Material Safety Data Sheet (MSDS) for the refrigerant and all labels on refrigerant containers.
Checkpoints:
1. Thoroughly inspect and clean interior and exterior of machine with vacuum cleaner, (remove panels).
2. Clean drain pan and note excessive corrosion, prepare metal and paint as necessary. Consult the Material Safety Data Sheet (MSDS) to ensure that the paint lead level is 0.06% or less.
3. Check for refrigerant leaks using a halogen detector or similar testing device. Repair all leaks before recharging unit. If leaks are not able to be stopped or corrected, report leak status to supervisor. Consult the MSDS for disposal requirements. Reclaimed and recycled CFCs are exempt from hazardous waste regulations (Consult 40 CFR Part 261).
4. Check refrigerant levels for proper charge and recharge as needed.
5. Check condition of cooling and reheat coils. Use fin comb if needed to straighten fins.
6. Clean coils, use coil cleaner detergent solution and high pressure water.
7. Check belts for wear, adjust tension or alignment, and replace when necessary.
8. Drain and clean humidifier drip pan, if applicable. Remove corrosion; prime, and paint as needed.
9. Lubricate motor and fan bearings, if not sealed. Check alignment of motor and fan.
10. Replace prefilters if needed.
11. Replace final filters if needed.
12. Check compressor oil level, if compressor has an oil sight glass.
13. Run machine, check action of controls, relays, switches, etc., to see that:
a. compressor(s) run at proper settings.
b. reheat coils activate properly.
c. humidistat activates humidifier.
d. suction and discharge pressures are proper.
e. discharge air pressure is set properly.
14. Check and tighten any loose unit electrical terminals, disconnect switches, or connectors.
15. Check and adjust vibration eliminators. Replace if required.
16. Remove all trash or debris from work area. Consult the MSDS for proper personal protective equipment (PPE).
Recommended Tools, Materials, and Equipment:
1. Tool Group A
2. Cleaning tools and materials, vacuum wet/dry, fin comb, grease gun and oil, filters and prefilters, spare belts.
3. Approved refrigerant.
4. Paint and brushes as required. Consult the MSDS to ensure that the paint lead level is 0.06% or less.
5. Self sealing quick disconnect refrigerant hose fittings
6. Refrigerant recovery/recycle unit
7. EPA/DOT approved refrigerant storage tanks.
8. Safety goggles.
9. Gloves.
10. Electronic leak detector.
A-7 Air-Conditioning Machine, Package Unit (Special Purpose) (Frequency: Monthly)
Application:
This equipment is typically found in computer rooms, CAD rooms, laboratories, etc. It is identical in design and configuration to the A-6 unit for comfort cooling. One difference is that it may use a glycol dry cooler during favorable outside air conditions.
Special Instructions:
1. Review manufacturer's instructions and the Standard Operating Procedure for "Controlling Hazardous Energy Sources."
2. De-energize, lock out, and tag electrical circuits.
3. Perform any required drycooler or air cooled condenser maintenance simultaneously with this PM.
4. Comply with the latest provisions of the Clean Air Act and Environmental Protection Agency (EPA) regulations as they apply to protection of stratospheric ozone.
5. No intentional venting of refrigerants is permitted. During the servicing, maintenance, and repair of refrigeration equipment, the refrigerant must be recovered.
6. Whenever refrigerant is added or removed from equipment, record the quantities on the appropriate forms.
7. Recover, recycle, or reclaim the refrigerant as appropriate.
8. If disposal of the equipment item is required, follow regulations concerning removal of refrigerants and disposal of the equipment.
9. If materials containing refrigerants are discarded, comply with EPA regulations as applicable.
10. Refrigerant oils to be removed for disposal must be analyzed for hazardous waste and handled accordingly.
11. Closely follow all safety procedures described in the Material Safety Data Sheet (MSDS) for the refrigerant and all labels on refrigerant containers.
Checkpoints:
1. Thoroughly inspect and clean interior and exterior of machine with wet/ dry vacuum, (remove panels).
2. Clean drain pan and note excessive corrosion, prepare and paint necessary. Consult the Material Safety Data Sheet (MSDS) to ensure that the paint lead level is 0.06% or less.
3. Check for refrigerant leaks using a halogen detector or similar testing device. If leaks are not able to be stopped or corrected, report leak status to supervisor.
4. Check refrigerant levels and recharge if needed. Consult the MSDS for disposal requirements. Reclaimed and recycled CFCs are exempt from hazardous waste regulations (Consult 40 CFR Part 261).
5. Check condition of cooling and reheat coils. Use fin comb if needed to straighten fins.
6. A dirty coil surface can be cleaned using a coil cleaner solution and warm water.
7. Drain and clean humidifier drip pan, replace pan if applicable. Remove scale and paint if necessary.
8. Lubricate motor and fan bearings, if not sealed. Check alignment of motor and fan. Clean fan or blower.
9. Check belt tension and condition. Adjust or replace as required.
10. Replace prefilters if needed.
11. Replace final filters if needed.
12. Check compressor oil level if compressor has a sight glass.
13. Run machine, check action of controls, relays, switches, etc. to see that:
a. compressor(s) run at proper settings.
b. reheat coils activate properly.
c. humidistat activates humidifier.
d. suction and discharge pressures are proper.
e. discharge air temperature is set properly.
14. Check and adjust vibration eliminators. Replace if required.
15. Check and tighten all electrical terminals, connections, and disconnect switches.
16. Remove all trash or debris from work area. Consult the MSDS for proper personal protective equipment (PPE).
Recommended Tools, Materials, and Equipment:
1. Tool Group A
2. Cleaning tools and materials, vacuum, fin comb, grease gun and oil, filters and prefilters, spare belts.
3. Clamp meter (volt-ohm-amp meter).
4. Paint and brushes as required. Consult the MSDS to ensure that the paint lead level is 0.06% or less.
5. Self sealing quick disconnect refrigerant hose fittings
6. Refrigerant recovery/recycle unit
7. EPA/DOT approved refrigerant storage tanks.
8. Safety goggles.
9. Gloves.
10. Electronic leak detector.
A-8 Air-Conditioning, Window Unit (Frequency: Annual)
Special Instructions:
1. Disconnect electric cord to unit.
2. Review manufacturer's instructions.
3. Comply with the latest provisions of the Clean Air Act and Environmental Protection Agency (EPA) regulations as they apply to protection of stratospheric ozone.
4. No intentional venting of refrigerants is permitted. During the servicing, maintenance, and repair of refrigeration equipment, the refrigerant must be recovered.
5. Whenever refrigerant is added or removed from equipment, record the quantities on the appropriate forms.
6. Recover, recycle, or reclaim the refrigerant as appropriate.
7. If disposal of the equipment item is required, follow regulations concerning removal of refrigerants and disposal of the equipment.
8. If materials containing refrigerants are discarded, comply with EPA regulations as applicable.
9. Refrigerant oils to be removed for disposal must be analyzed for hazardous waste and handled accordingly.
10. Closely follow all safety procedures described in the Material Safety Data Sheet (MSDS) for the refrigerant and all labels on refrigerant containers.
Checkpoints:
1. Clean condenser, cooling coil fins, drain pan, and fans. Slime or mold found on the cooling coil or drain pan should be cleaned with an appropriate EPA approved solution. Place an EPA approved biocide tablet in the drain pan.
2. Inspect fins. Straight with a fin comb as required.
3. Remove dirt, or rust from all interior parts, repaint as necessary.
4. Replace or clean filter.
5. Inspect and adjust fresh air damper.
6. Lubricate motor and fan bearings.
7. Inspect gaskets. Look for leaks between unit and window, caulk as necessary.
8. Check for refrigerant leaks with halogen leak detector and soap bubbles. If leaks are not able to be stopped or corrected, report leak status to supervisor. Consult the Material Safety Data Sheets (MSDS) for disposal requirements. Reclaimed and recycled CFCs are exempt from hazardous waste regulations (Consult 40 CFR Part 261).
9. Start unit and observe operation.
10. Check temperature differential between air entering evaporator and leaving the evaporator.
11. Check frame of unit with ohmmeter for proper electric ground.
12. Replace covers, clean filter and front filter grill.
13. Clean up the work area.
Recommended Tools, Materials, and Equipment:
1. Tool Group A
2. Cleaning tools and materials. Consult the MSDS for hazardous ingredients and proper personal protective equipment (PPE).
3. Lubricants. Consult the MSDS for hazardous ingredients and proper PPE.
4. Vacuum cleaner wet/dry type.
5. Fin comb
6. Filters
7. Self sealing quick disconnect refrigerant hose fittings
8. Refrigerant recovery/recycle unit
9. EPA/DOT approved refrigerant storage tanks.
10. Safety goggles
11. Gloves
12. Approved refrigerant
13. Electronic leak detector
A-9 Air-Cooled Condenser (Frequency: Annual)
Application:
This PM guide applies to equipment which has the condenser, fan(s), and fan motor(s) enclosed within the same housing. The compressor and other components are at a separate location. PM of these other devices should be scheduled simultaneously with the units serviced by the condenser. If the condenser motor(s) is/are rated at 1 HP or higher, schedule PM of motor(s) with this PM.
Special Instructions:
1. Review manufacturer's instructions.
2. Review the Standard Operating Procedure for "Controlling Hazardous Energy Sources."
3. Review the Standard Operating Procedure for "Selection, Care, and Use of Respiratory Protection".
4. De-energize, lock out, and tag electrical circuit breaker.
5. Comply with the latest provisions of the Clean Air Act and Environmental Protection Agency (EPA) regulations as they apply to protection of stratospheric ozone.
6. No intentional venting of refrigerants is permitted. During the servicing, maintenance, and repair of refrigeration equipment, the refrigerant must be recovered.
7. Whenever refrigerant is added or removed from equipment, record the quantities on the appropriate forms.
8. Recover, recycle, or reclaim the refrigerant as appropriate.
9. If disposal of the equipment item is required, follow regulations concerning removal of refrigerants and disposal of the equipment.
10. If materials containing refrigerants are discarded, comply with EPA regulations as applicable.
11. Refrigerant oils to be removed for disposal must be analyzed for hazardous waste and handled accordingly.
12. Closely follow all safety procedures described in the Material Safety Data Sheet (MSDS) for the refrigerant and all labels on refrigerant containers.
Checkpoints:
1. Remove debris from air screen and clean underneath unit.
2. Pressure wash coil with coil cleaning solution.
3. Straighten fin tubes with fin comb.
4. Check electrical connections for tightness.
5. Check mounting for tightness.
6. Check for and remove all corrosion or rust from unit and supporting steel, prime and paint as necessary.