This document is a Limited Hazardous Material Survey Report for Building 1 of the Miami VA Medical Center located at 1201 NW 16th Street, Miami, FL. The survey was conducted by Terracon Consultants, Inc. from November 7-17, 2022 in preparation for a planned future renovation of the building. The report details the findings from the survey, which identified the presence of asbestos-containing materials (ACM) and lead-containing paint (LCP) in various building components. Specifically, the survey found ACM in 71 homogeneous areas, which will need to be properly abated prior to renovation activities. Additionally, LCP was detected in representative painted surfaces throughout the building. The report provides recommendations for managing the identified hazardous materials in accordance with applicable federal regulations, including the Asbestos NESHAP and OSHA lead standards. This information will be critical for planning and executing the upcoming renovation project at the Miami VA Medical Center.
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Facilities | Environmental | Geotechnical | Materials I
Limited Hazardous Material Survey Report Apogee – Miami VAMC – Bldg. 1
December 22, 2022 | Report Number: H8227118
5371 NW 33rd Avenue, Suite 201 Fort Lauderdale, Florida 33309 P (954) 741-8282
5371 NW 33rd Avenue, Ste 201 Ft. Lauderdale, FL 33309
P: (954) 741-8282
Terracon.com
Facilities | Environmental | Geotechnical | Materials I
December 22, 2022
Apogee Consulting Group, P.A.
201 East Main Street, Suite 480 Murfreesboro, TN 37130
Attn: Mr. John Foley, AIA, LEEP AP Senior Project Manager P 919.815.1285 E jfoley@acg-pa.com
RE: Limited Hazardous Material Survey Report VAMC Miami – Bldg. 1 1201 NW 16th Street Miami, Florida 33125 Terracon Project No. H8227118
Dear Mr. Foley, Terracon Consultants, Inc. (Terracon) is pleased to submit the attached report to Apogee Consulting Group, P.A. The purpose of this report is to present the results of a limited hazardous material survey performed on the 94 mechanical rooms located throughout building 1’s basement through 12th floor on November 7, 8, 9 and 17, 2022, at the above referenced location in Miami, Florida. This survey was conducted in general accordance with Terracon Proposal number PH8227118, dated September 2, 2022. We understand that this survey was requested due to the planned future renovation of building 1.
Based on the laboratory results, asbestos was detected in building materials assessed during our survey assessment. Please refer to the attached report for details.
Lead containing paint was detected above the laboratory reporting limit. Please refer to the attached report for details.
Terracon appreciates the opportunity to provide this service to Apogee Consulting Group, P.A. If you have any questions regarding this report, please contact us at (954) 741-8282.
Sincerely, Terracon Consultants, Inc.
Florida Asbestos Consulting Business License No. ZA337
Sergio A. Adasme
Project Industrial Hygienist
Mitch Reiber, PG, CIH
Principal
National Director
Wilson S. Bull, CIH
Tampa IH Group Manager
FL Licensed Asbestos Consultant AX92 https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAA9AxeetydteEMMdLDe3G1FxkGuHhOZzVh https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAA9AxeetydteEMMdLDe3G1FxkGuHhOZzVh https://na3.documents.adobe.com/verifier?tx=CBJCHBCAABAA9AxeetydteEMMdLDe3G1FxkGuHhOZzVh
Facilities | Environmental | Geotechnical | Materials i
TABLE OF CONTENTS
Page
1.0 Introduction
1.1 Project Objective
1.2 Reliance
2.0 Building Description
3.0 Field Activities
3.1 Asbestos
3.2 Lead Containing Paint
4.0 Regulatory Overview
4.1 Asbestos
4.2 Lead in Construction
5.0 Findings and Recommendations
5.1 Asbestos
5.2 Lead containing paint
6.0 General Comments
Appendices
Appendix A Asbestos Containing Materials Sample Summary
Appendix B Asbestos Analytical Laboratory Data
Appendix C LCP Analytical Laboratory Data
Appendix D Licenses and Certifications
Appendix E Sample Location Diagram
Appendix F Photographs
Limited Hazardous Material Survey Report Miami VAMC – Bldg. 1 | Miami, Florida
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 1
1.0 Introduction
Terracon Consultants, Inc. (Terracon) conducted a Limited Hazardous Material survey in Building 1 of the Veteran Affairs (VA) location at 1201 NW 16th Street Miami, Florida. The survey was conducted on November 7, 8, 9 and 17, 2022, by an Asbestos Hazard Emergency Response Act (AHERA)-accredited asbestos inspector in general accordance with a Terracon proposal PH8227118, dated September 2, 2022. The structure’s components, as designated by the site representative, were surveyed and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Additionally, Terracon obtained readily and safely accessible paint-chip samples from surfaces of the renovation areas to identify the presence and concentration of lead paint. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, in voids or in other concealed areas.
Suspect ACM samples were collected in general accordance with the sampling protocols outlined in EPA regulation 40 CFR 763 (AHERA). Asbestos samples were delivered to an accredited laboratory for analysis. Suspect ACM samples were analyzed by Polarized Light Microscopy.
Suspect lead containing paint samples were obtained from representative surfaces potentially containing lead paint coatings. Lead paint samples were delivered to an accredited laboratory for analysis by Flame Atomic Absorption.
1.1 Project Objective
We understand this hazardous material survey was requested due to the planned future renovation of Building 1. EPA regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP), prohibits the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated ACM (RACM) be identified, classified, and quantified prior to planned renovation or demolition activities.
In addition, suspect lead containing paint (LCP) samples were obtained to identify potential exposure sources, regulated by the Occupational Safety and Health Administration (OSHA) 29 CFR
1926.62 and other applicable EPA regulations that could develop if coatings are disturbed during planned renovation activities.
1.2 Reliance
This report is for the exclusive use of Apogee Consulting Group, P.A. for the project being discussed. Reliance by any other party on this report is prohibited without written authorization of Terracon and Apogee Consulting Group, P.A. Reliance on this report by Apogee Consulting Group, P.A. and all authorized parties will be subject to the terms, conditions, and limitations stated in the proposal, this report and the existing agreement between Apogee Consulting Group, P.A. and Terracon. The limitations of liability defined in Terracon’s Agreement for Services is the aggregate limit of Terracon’s liability to Apogee Consulting Group, P.A.
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 2
2.0 Building Description
According to the Miami-Dade Property Appraiser, building 1 of the Miami VA Medical Center was constructed in 1959 with additions made in 1980. Building 1 has an estimated square footage of 340,000 square feet. Building 1 consisted of a built-up roof, stucco exterior walls atop a concrete slab. Interior finishes consisted of perimeter and interior drywall walls, lay-in ceiling tiles, with ceramic and vinyl floor tiles.
3.0 Field Activities
The survey was conducted by AHERA-accredited asbestos inspector, Mr. Ryan Nanan. The survey was conducted in general accordance with the sample collection protocols established in EPA regulation 40 CFR 763 (AHERA). Paint chip sampling for lead was conducted on observed painted surfaces located within the surveyed areas. Copies of the applicable licenses and certifications are included in Appendix C. Asbestos analytical laboratory data is included as Appendix B. Lead containing paint analytical laboratory data is included as Appendix C.
3.1 Asbestos
Our survey activities began with visual observations of accessible interior areas to identify homogeneous areas of suspect ACM. A homogeneous area consists of building materials that appear similar throughout in terms of color, texture, and date of application. The assessment was conducted throughout visually accessible areas of Building 1. Materials identified as glass, wood, metal, or rubber were not considered suspect ACM. The survey did not include the exterior of the building.
A physical assessment of each homogeneous area of suspect ACM was conducted to assess the friability and condition of the materials. A friable material is defined by the EPA as a material which can be crumbled, pulverized, or reduced to powder by hand pressure when dry. Friability was assessed by physically touching suspect materials.
Based on results of the visual observation, bulk samples of suspect ACM were collected in general accordance with AHERA sampling protocols. Random samples of suspect materials were collected in each homogeneous area. Samples were collected bulk samples using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
A total of 208 bulk samples were collected from 71 homogeneous areas of suspect ACM during the survey completed on November 7, 8, 9 and 17, 2022. A table of laboratory-identified ACM sampled during this survey is provided in Appendix A.
Bulk samples were submitted under chain of custody to Eurofins EPK Built Environment Testing, LLC (Eurofins EPK) in Chantilly, Virginia for analysis by PLM per EPA methodology EPA/600/R- 93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. Eurofins EPK is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP Accreditation No. 600331-0).
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 3
3.2 Lead Containing Paint
Terracon performed a visual assessment of the interior of the building to identify, locate and assess predominant painted surfaces for lead. Representative paint chip samples were chosen from each unique combination of paint color, component, and substrate.
A total of 37 paint chips samples were collected and submitted to Eurofins EPK of Tustin, California for analysis. The paint chips were analyzed by Flame Atomic Absorption Spectrometry (AAS) by NIOSH 7082 and EPA method 7000B Modified. Eurofins EPK is accredited under the Environmental Lead Laboratory Accreditation Program (AIHA-LAP, Accreditation No. 178697).
Analytical laboratory data for LCP samples taken during this survey are provided in Appendix C.
4.0 Regulatory Overview
4.1 Asbestos
The asbestos NESHAP (40 CFR Part 61, Subpart M) regulates asbestos fiber emissions and asbestos waste disposal practices. It also requires the identification and classification of existing materials prior to demolition or renovation activity. Under NESHAP, ACM are classified as either friable, Category I non-friable or Category II non-friable ACM. Friable materials are those that, when dry, may be crumbled, pulverized, or reduced to powder by hand pressure. Category I non-friable ACM includes packings, gaskets, resilient floor coverings and asphalt roofing products containing more than 1% asbestos. Category II non-friable ACM are any non-friable materials other than non-friable Category I materials that contain more than 1% asbestos.
Friable ACM, Category I and Category II non-friable ACM which is in poor condition and has become friable or which will be subjected to drilling, sanding, grinding, cutting, or abrading and which could be crushed or pulverized during anticipated renovation or demolition activities are considered RACM.
The NESHAP regulations include an option for Friable materials or potential RACM that are found to contain less than 10% asbestos to be “point-counted” or analyzed by similar, advanced analytical methods, such as Transmission Electron Microscopy (TEM), to confirm the asbestos concentrations. If the additional “point-counting” or TEM analysis is not implemented then the materials are required to be categorized as ACM (>1% asbestos content) even if the initial, estimated laboratory results are reported “trace” or less than 1% (<1%) asbestos content.
In the State of Florida, asbestos activities are regulated by the Florida Department of Environmental Protection (FDEP), which is enforced locally by the Miami-County Division of Environmental Resources Management, which is located at 701 NW 1st Court, Suite 400 Miami, FL 33324. RACM must be removed prior to renovation or demolition activities which will disturb the materials. The owner or operator must provide the FDEP with written notification of planned removal activities at least 10 working days prior to the commencement of asbestos abatement activities. Removal of ACM and/or RACM must be conducted by a State of Florida-licensed asbestos abatement contractor.
The OSHA Asbestos standard for construction (29 CFR 1926.1101) regulates workplace exposure to asbestos. The OSHA standard requires that employee exposure to airborne asbestos fibers be maintained below 0.1 asbestos fibers per cubic centimeter of air (0.1 f/cc) for an 8-hour exposure
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 4 and 1.0 f/cc for a peak exposure, 30-minute timeframe. The OSHA standard classifies construction and maintenance activities which could disturb ACM and specifies work practices and precautions which employers must follow when engaging in each class of regulated work. In addition, OSHA requires that activities where workers disturb materials with even “trace” amounts of asbestos content (< 1%) are still regulated and require compliance with certain elements of the regulation.
4.2 Lead in Construction
Lead is regulated by the EPA, HUD, FDEP and OSHA. The EPA and FDEP regulate lead use, removal, and disposal, and OSHA regulates lead exposure to workers. The EPA and HUD, with their small child-safety focus, define Lead-Based Paint (LBP) as paint, varnish, stain, or other applied coating that contains lead equal to or greater than 1.0 mg/cm2, 5,000 mg/kg, or 0.5% by dry weight as determined by laboratory analysis.
However, for the purpose of the OSHA lead standard, with its focus on the safety/exposure of construction workers, paint-containing lead includes any detectable concentrations of metallic lead, all inorganic lead compounds, and organic lead soaps. A synopsis of the OSHA regulations (29 CFR 1926.62) and the applicability are as follows:
The OSHA Lead Standard for Construction (29 CFR 1926.62) applies to all construction work where an employee may be occupationally exposed to lead. All work related to construction, alteration, or repair (including painting and decorating) is included. The lead-in-construction standard applies to any detectable concentration of lead in paint, as even small concentrations of lead can result in unacceptable employee exposures depending upon on the method of removal and other workplace conditions.
Under this standard, construction includes, but is not limited to, the following:
Demolition or salvage of structures where lead or materials containing lead are present
Removal or encapsulation of materials containing lead
New construction, alteration, repair, or renovation of structures, substrates, or portions containing lead, or materials containing lead
Installation of products containing lead
Lead contamination/emergency clean-up
Transportation, disposal, storage, or containment of lead or materials containing lead on the site or location at which construction activities are performed
Maintenance operations associated with construction activities described above
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 5
5.0 Findings and Recommendations
5.1 Asbestos
Asbestos was detected in samples collected during this site inspection in the following homogenous areas:
Black Mastic (2%-8% Chrysotile) associated with the HVAC Ducts (HA-3) The material measures approximately 315 square feet combined and is located on the HVAC Ducts in rooms B5, A129, A208H, T23, B427, B614A, C409D, and C1002.
Black Mastic (2%-8% Chrysotile) associated with the Brown 9"x9" Vinyl Floor Tiles
(HA-9)
The material measures approximately 245 square feet combined and is located on the floors of rooms T11, E22, T21, T214, T23, T24, T41, and T42.
Black/Yellow Mastic (2%-5% Chrysotile) associated with the Brown 12"x15" Vinyl Floor Tiles (HA-11) The material measures approximately 100 square feet and is located on the floor of room A129.
Black/Yellow Mastic (2% Chrysotile) associated with the White/Grey 12"x12" Vinyl Floor Tiles (HA-14) The material measures approximately 200 square feet and is located on the floor of room B110E.
Black Mastic (2% Chrysotile) associated with the Black Floor Mastic (HA-15) The material measures approximately 120 square feet combined and is located on the floors of rooms T134, T1A12, T2A13 and T2E11.
Black/Yellow Mastic (2%-3% Chrysotile) associated with the Beige 15"x15" Vinyl Floor Tile and Brown Glue over Brown 12"x12" Vinyl Floor Tile (HA-17) The material measures approximately 200 square feet and is located on the floor of room 1B141K.
Tan Mastic (2% Chrysotile) associated with the Mastic on Metal HVAC Ducts (HA-21) The material measures approximately 340 square feet combined and is located along the HVAC ducts in rooms T1C7, T1C6, 1A158C, and A204L.
Black/Yellow Mastic (2% Chrysotile) associated with the Light/Dark Brown 12"x12" Vinyl Floor Tile (HA-25) The material measures approximately 220 square feet combined and is located on the floors of rooms 1A15BC, and CLC261.
Black Mastic (2%-5% Chrysotile) associated with the Brown with Orange Strips 12"x12" Vinyl Floor Tile (HA-26) The material measures approximately 120 square feet and is located on the floor of room
CLC161.
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 6
Black Mastic (2%-3% Chrysotile) associated with the Brown with Large Brown strips 12"x12" Vinyl Floor Tile (HA-29) The material measures approximately 670 square feet combined and is located on the floors of rooms 127, T21, 305, 321, CLC361, CLC461, and B706B.
Black/Yellow Mastic (5% Chrysotile) associated with the White with Orange and Green Strips Pattern 12"x12" Vinyl Floor Tile (HA-31) The material measures approximately 200 square feet and is located on the floor of room A208H.
Black Mastic (5% Chrysotile) associated with the Brown Wood Pattern Vinyl Floor Sheeting and Brown Glue over White 12"x12" Vinyl Floor Tile (HA-36) The material measures approximately 100 square feet and is located on the floor of room 2A150C4.
Black Mastic (5% Chrysotile) associated with the Grey 12” x 12” Vinyl Floor Tile and Brown Glue over White 12"x12" Vinyl Floor Tile (HA-41) The material measures approximately 200 square feet and is located on the floor of room 2E109B.
Black/Yellow Mastic (3% Chrysotile) associated with the Brown 12"x12" Vinyl Floor Tile and Brown Glue over Brown 12"x12" Vinyl Floor Tile (HA-44) The material measures approximately 250 square feet and is located on the floor of room 2C147A.
Black Mastic (5% Chrysotile) associated with the White with Multi color 9"x9" Vinyl Floor Tile (HA-45) The material measures approximately 100 square feet and is located on the floor of room 2B126.
Black Mastic (2% Chrysotile) associated with the Light Brown with Large Dark Brown strips 12"x12" Vinyl Floor Tile and Brown Glue over Green 12"x12" Vinyl Floor Tile
(HA-47)
The material measures approximately 80 square feet and is located on the floor of room
SPC3081.
Black Mastic (3% Chrysotile) associated with the Blue 9"x9" Vinyl Floor Tile (HA-48) The material measures approximately 85 square feet combined and is located on the floors of rooms SPT351, T122, and T121.
Black Mastic (2%-3% Chrysotile) associated with the Grey with Blue/Pink spots 12"x12" Vinyl Floor Tile and Brown Glue over White 12"x12" Vinyl Floor Tile (HA-55) The material measures approximately 200 square feet and is located on the floor of room B427.
Black Mastic (3% Chrysotile) associated with the White with Green Strips 9"x9" Vinyl Floor Tile (HA-56) The material measures approximately 395 square feet and is located on the floors of rooms T61, T71, and T122.
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 7
Black Mastic (2% Chrysotile) associated with the White with Purple /Blue Spots 12"x12" Vinyl Floor Tile and Brown Glue over White 12"x12" Vinyl Floor Tile (HA-59) The material measures approximately 210 square feet and is located on the floors of rooms T62, C611A, C409D, and C714.
Black Mastic (5% Chrysotile) associated with the White with Orange /Green/Black Dots 12"x12" Vinyl Floor Tile and Brown Glue over White 12"x12" Vinyl Floor Tile
(HA-71)
The material measures approximately 100 square feet and is located on the floor of room C1201B.
A table of laboratory-identified ACM sampled during this survey is provided in Appendix A.
The results of this assessment should be communicated to the renovation contractor and other subcontractors working in the building and a copy of the survey should be on-site during renovation or demolition activities. In addition, a 10-day renovation/demolition notice may need to be sent to Miami-Dade County, Division of Environmental Resources Management. We recommend that a call be made to (305) 372-6925 to confirm their regulatory requirements.
Any concealed building materials discovered during renovation activities not identified in this report, which are suspected to contain asbestos, should be sampled by a Florida Licensed Asbestos Consultant and analyzed by a NVLAP-accredited laboratory to confirm the presence or absence of asbestos prior to disturbing such materials. If the materials are found to contain asbestos, various regulations (EPA NESHAP, FDEP and OSHA) will apply. In addition, direct contact with the FDEP is recommended to confirm their actual regulatory requirements.
5.2 Lead containing paint
Quantifiable concentrations of lead were identified in samples of the following paint collecting during Terracon’s assessment:
Sample # Description Substrate Lead
Results (ppm)
L1 Green Wood Plywood wall – 1st Floor Wood 1600 ppm
L4 Light Brown Metal Door Frame – 1st Floor Metal 1100 ppm
L15 Light Brown Wood Door – 2nd Floor Wood 370 ppm
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 8
L20 Blue Plywood Wall – 2nd Floor Wood 1300 ppm
L22 Light Brown Metal Door – 3rd Floor Metal 650 ppm
L23 Light Brown Metal Door Frame – 3rd Floor Metal 680 ppm
L24 Lime Green Plywood Wall – 3rd Floor Wood 43,000 ppm
L26 White Drywall and Joint Compound Wall – 3rd Floor Drywall 44 ppm
L27 Light Brown Wood Door – 3rd Floor Wood 110 ppm
L30 Light Brown Metal Door Frame – 4th Floor Metal 48 ppm
L32 Cream Colored Plywood Wall – 4th Floor Wood 1600 ppm
L33 Light Brown Wood Door – 4th Floor Wood 260 ppm
L34 Cream Colored Plywood Wall – 6th Floor Wood 2200 ppm
L35 Light Brown Metal Door Frame – 6th Floor Metal 200 ppm
Since lead was detected in paint in the building, proper notification to the contractors as to the presence of lead coating so that the proper controls, training, work practices, etc., as delineated in the OSHA Lead in Construction standard (29 CFR 1926.62) can be implemented. In addition, the contractor should also be made aware that the disposal of lead-containing construction components may require Toxicity Characteristic Leaching Procedure (TCLP) testing. Likewise, direct contact with the FDEP Southeast District is recommended to confirm their actual regulatory requirements.
December 22, 2022 | Terracon Report No. H8227118
Facilities | Environmental | Geotechnical | Materials 9
It should be noted that the Lime Green paint (sample #L24) found on plywood walls on the 3rd floor is greater than 5000 ppm and is therefor classified as lead-based paint. Additional precautions may be warranted when impacting this paint.
Any concealed building painted surfaces discovered during renovation activities not identified in this report which are suspected to contain lead, should be sampled, and analyzed.
The results of this assessment should be communicated to the renovation contractor and other subcontractors working in the building and a copy of the survey should be on-site during the renovation activities.
6.0 General Comments
It should be noted that suspect asbestos materials other than those identified during our survey may exist in locations outside of the designated surveyed areas. Should suspect materials other than those which were identified during this survey be uncovered prior to renovation activities, those materials should be assumed asbestos-containing, until sampling and analysis can confirm or deny their asbestos content.
The asbestos and LCP survey was conducted in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the building. The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions at a later date.
This report has been prepared on behalf of and exclusively for use by the Client. for specific application to their project as discussed. This report is not a bidding document. Contractors or consultants reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information which may have been used in the preparation of this report. No warranty, express or implied is made.
Facilities | Environmental | Geotechnical | Materials
Appendix A
Asbestos Containing Materials Sample Summary
Asbestos Containing Materials Sample Summary
HA
Number Sample Number
Material Description Material Location
Square Footage
Lab Results
Black Mastic on HVAC Ducts
Room B5 40 ft²
Black Mastic
2%-8% Chrysotile
2 Room A129 15 ft²
Room A208H
65 ft²
4 Room T23 40 ft²
5 Room B427 60 ft²
Room B614A
30 ft²
Room C409D
25 ft²
Room C1002 40 ft²
Brown 9"x9" Vinyl Floor Tile and Black Mastic
Room T11 40 ft²
Black Mastic
2%-8% Chrysotile
2 Room E22 30 ft²
3 Room T21 30 ft²
4 Room T214 30 ft²
Rooms T23, T24 60 ft²
6 Room T41 25 ft²
7 Room T42 30 ft²
1 Brown 12"x15" Vinyl Floor Tile and
Brown /Back Mastic Room A129 100 ft²
Black/Yellow Mastic
2%-5% Chrysotile2
1 White/Grey 12"x12" Vinyl Floor Tile and
Brown/Black Mastic Room B110E 200 ft²
Black/Yellow Mastic 2% Chrysotile2
Black Floor Mastic
Room T134 30 ft²
Black Mastic
2% Chrysotile
2 Room T1A12 30 ft²
3 Room T2A13 30 ft²
4 Room T2E11 30 ft²
1 Beige 15"x15" Vinyl Floor Tile and
Brown Glue over Brown 12"x12" Vinyl Floor Tile and Black Mastic
Room 1B141K
200 ft² Black/Yellow Mastic
2%-3% Chrysotile2
Brown Mastic on Metal HVAC Ducts
Room T1C7 85 ft²
Tan Mastic
2% Chrysotile
2 Room T1C6 85 ft²
Room
1A158C 85 ft²
Room
A204L 85 ft²
Light/Dark Brown 12"x12" Vinyl Floor Tile and Brown /Black Mastic
Room
1A15BC
100 ft² Black/Yellow Mastic
2% Chrysotile
Room
CLC261
120 ft²
HA
Number
Sample Number
Material Description Material Location
Square Footage
Lab Results
1 Brown with Orange Strips 12"x12"
Vinyl Floor Tile and Black Mastic Room
CLC161
120 ft²
Black/Yellow Mastic 2%-5% Chrysotile2
Brown with Large Brown strips 12"x12" Vinyl Floor Tile and Black Mastic
Room
130 ft²
Black Mastic
2%-3% Chrysotile
Room
T21 30 ft²
Room
100 ft²
Room
150 ft²
Room
CLC361
80 ft²
Room
CLC461
100 ft²
Room
B760B 80 ft²
1 White with Orange and Green Strips
Pattern 12”x12” Vinyl Floor Tile and Brown /Black Mastic
Room A208H
200 ft² Black/Yellow Mastic
5% Chrysotile2
1 Brown Wood Pattern Vinyl Floor Sheeting and Brown Glue over White
12"x12" Vinyl Floor Tile and Black Mastic
Room 2A150C4
100 ft² Black Mastic
5% Chrysotile2
1 Grey 12"x12" Vinyl Floor Tile and
Brown Glue over White 12"x12" Vinyl Floor Tile and Brown Black and Mastic
Room 2E109B
200 ft² Black Mastic
5% Chrysotile2
1 Brown 12”x12” Vinyl Floor Tile and Brown Glue over Brown 12"x12” Vinyl
Floor Tile and Brown/Black Mastic
Room 2C147A
250 ft² Black/Yellow Mastic
3% Chrysotile
1 White with Multi color 9”x9" Vinyl Floor
Tile and Black Mastic Room 2B126 100 ft²
Black Mastic
5% Chrysotile2
1 Light Brown with Large Dark Brown strips 12”x12” Vinyl Floor Tile and Brown Glue over Green 12"x12" Vinyl
Floor Tile and Black Mastic
Room
SPC3081
80 ft² Black Mastic
2% Chrysotile2
Blue 9"x9” Vinyl Floor Tile and Black
Mastic
Room
SPT351
30 ft² Black Mastic
3% Chrysotile2 Room T122 30 ft²
Room T121 25 ft²
1 Grey with Blue/Pink spots 12"x12" Vinyl Floor Tile and Brown Glue over White 12"x12" Vinyl Floor Tile and
Black Mastic
Room B427 200 ft² Black Mastic
2%-3% Chrysotile
HA
Number
Sample Number
Material Description Material Location
Square Footage
Lab Results
White with Green Strips 9"x9" Vinyl Floor Tile and Black Mastic
Room T61 30 ft²
Black Mastic
3% Chrysotile
2 Room T71 30 ft²
3 Room T122 25 ft²
Room B707 35 ft²
Room T72 30 ft²
Room T81 20 ft²
Room T82 25 ft²
Room T91 25 ft²
Room T92 25 ft²
Room T102 25 ft²
Room T111 25 ft²
Room B1107 100 ft²
White with Purple /Blue Spots 12"x12" Vinyl Floor Tile and Brown Glue over White 12"x12" Vinyl Floor Tile and
Black Mastic
Room T62 30 ft²
Black Mastic
2% Chrysotile
Room C611A
80 ft²
Room C409D
65 ft²
Room C714 35 ft²
1 White with Orange /Green/Black Dots
12"x12" Vinyl Floor Tile and Brown Glue over White 12"x12" Vinyl Floor
Tile and Black Mastic
Room C1201B
100 ft² Black Mastic
5% Chrysotile2
Appendix B
Asbestos Analytical Laboratory Data
Approved by:
Approved Signatory Virginia Jones
Report for:
Mr. Sergio Adasme Terracon - Fort Lauderdale, FL 5371 NW 33rd Ave.
Suite 201 Fort Lauderdale, FL 33309
Regarding:
Eurofins EPK Built Environment Testing, LLC Project: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
EML ID: 3088513
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the samples as received and tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
Eurofins EPK Built Environment Testing, LLC ("the Company"), a member of the Eurofins Built Environment Testing group of companies, shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:
Asbestos PLM: 11-21-2022 to 11-23-2022
Service SOPs: Asbestos PLM (EPA 40CFR App E to Sub E of Part 763 & EPA METHOD 600/R-93-116, SOP EM-AS-S-1267) NVLAP Lab Code 600331-0
EMLab ID: 3088513, Page 1 of 63Eurofins EPK Built Environment Testing, LLC
Eurofins EPK Built Environment Testing, LLC 4460 Brookfield Corporate Drive, Suite A, Chantilly, VA 20151
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Total Samples Submitted: 208 Total Samples Analyzed: 203
Total Samples with Layer Asbestos Content > 1%: 59
Location: 1-1, White 2'x2' Worm Ceiling Tile Lab ID-Version‡: 14909071-1
Sample Layers Asbestos Content White Coating ND
Tan Ceiling Tile ND Composite Non-Asbestos Content: 60% Cellulose
20% Mineral Wool Sample Composite Homogeneity: Good
Location: 1-3, White 2'x2' Worm Ceiling Tile Lab ID-Version‡: 14909072-1
Sample Layers Asbestos Content White Coating ND
Tan Ceiling Tile ND Composite Non-Asbestos Content: 60% Cellulose
20% Mineral Wool Sample Composite Homogeneity: Good
Location: 1-10, White 2'x2' Worm Ceiling Tile Lab ID-Version‡: 14909073-1
Sample Layers Asbestos Content White Coating ND
Tan Ceiling Tile ND Composite Non-Asbestos Content: 60% Cellulose
20% Mineral Wool Sample Composite Homogeneity: Good
Location: 1-18, White 2'x2' Worm Ceiling Tile Lab ID-Version‡: 14909074-1
Sample Layers Asbestos Content White Coating ND
Tan Ceiling Tile ND Composite Non-Asbestos Content: 60% Cellulose
20% Mineral Wool Sample Composite Homogeneity: Good
EMLab ID: 3088513, Page 2 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 1-23, White 2'x2' Worm Ceiling Tile Lab ID-Version‡: 14909075-1
Sample Layers Asbestos Content White Coating ND
Tan Ceiling Tile ND Composite Non-Asbestos Content: 60% Cellulose
20% Mineral Wool Sample Composite Homogeneity: Good
Location: 2-1, White Mastic on HVAC Ducts Lab ID-Version‡: 14909076-1
Sample Layers Asbestos Content White Foam ND
Silver Foil with Yellow Mastic ND Black Mastic ND Brown Paper ND
Composite Non-Asbestos Content: 10% Cellulose 10% Glass Fibers 2% Wollastonite
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
Location: 2-2, White Mastic on HVAC Ducts Lab ID-Version‡: 14909077-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Glass Fibers 8% Wollastonite
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
EMLab ID: 3088513, Page 3 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 2-3, White Mastic on HVAC Ducts Lab ID-Version‡: 14909078-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Glass Fibers 8% Wollastonite
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
EMLab ID: 3088513, Page 4 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 2-4, White Mastic on HVAC Ducts Lab ID-Version‡: 14909079-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Glass Fibers 8% Wollastonite
Sample Composite Homogeneity: Poor
Location: 2-5, White Mastic on HVAC Ducts Lab ID-Version‡: 14909080-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Glass Fibers 8% Wollastonite
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
Location: 2-6, White Mastic on HVAC Ducts Lab ID-Version‡: 14909081-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Wollastonite 5% Glass Fibers
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
EMLab ID: 3088513, Page 5 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 2-7, White Mastic on HVAC Ducts Lab ID-Version‡: 14909082-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Glass Fibers 8% Wollastonite
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
EMLab ID: 3088513, Page 6 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 2-8, White Mastic on HVAC Ducts Lab ID-Version‡: 14909083-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Glass Fibers 8% Wollastonite
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
Location: 2-9, White Mastic on HVAC Ducts Lab ID-Version‡: 14909084-1
Sample Layers Asbestos Content Beige Foam ND
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
8% Glass Fibers 8% Wollastonite
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
Location: 3-1, Black Mastic on HVAC Ducts Lab ID-Version‡: 14909085-1
Sample Layers Asbestos Content Black Mastic 3% Chrysotile
Silver Foil with Yellow Mastic ND Brown Paper ND
Composite Non-Asbestos Content: 10% Cellulose 5% Glass Fibers
Sample Composite Homogeneity: Poor Comments: Some layers in the sample were inseparable without cross contamination.
EMLab ID: 3088513, Page 7 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 3-2, Black Mastic on HVAC Ducts Lab ID-Version‡: 14909086-1
Sample Layers Asbestos Content Black Mastic 5% Chrysotile
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 15% Glass Fibers
10% Cellulose Sample Composite Homogeneity: Poor
Comments: Some layers in the sample were inseparable without cross contamination.
EMLab ID: 3088513, Page 8 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 3-3, Black Mastic on HVAC Ducts Lab ID-Version‡: 14909087-1
Sample Layers Asbestos Content Black Mastic 5% Chrysotile
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
5% Glass Fibers Sample Composite Homogeneity: Poor
Comments: Some layers in the sample were inseparable without cross contamination.
Location: 3-4, Black Mastic on HVAC Ducts Lab ID-Version‡: 14909088-1
Sample Layers Asbestos Content Black Mastic 5% Chrysotile
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 10% Cellulose
10% Glass Fibers Sample Composite Homogeneity: Poor
Comments: Some layers in the sample were inseparable without cross contamination.
Location: 3-5, Black Mastic on HVAC Ducts Lab ID-Version‡: 14909089-1
Sample Layers Asbestos Content Black Mastic 2% Chrysotile
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 15% Cellulose
5% Glass Fibers Sample Composite Homogeneity: Poor
Comments: Some layers in the sample were inseparable without cross contamination.
EMLab ID: 3088513, Page 9 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is
(866) 871-1984 www.eurofinsus.com/BuiltClient: Terracon - Fort Lauderdale, FL C/O: Mr. Sergio Adasme Re: Apogee- Miami VAMC; 1201 NW 16th Street Miami, FL
Date of Sampling: 11-17-2022 Date of Receipt: 11-18-2022 and 11-21-2022 Date of Report: 11-23-2022
ASBESTOS PLM REPORT
Location: 3-6, Black Mastic on HVAC Ducts Lab ID-Version‡: 14909090-1
Sample Layers Asbestos Content Black Mastic 8% Chrysotile
Silver Foil with Yellow Mastic ND Brown Paper ND
Yellow Insulation ND Composite Non-Asbestos Content: 15% Glass Fibers
10% Cellulose Sample Composite Homogeneity: Poor
EMLab ID: 3088513, Page 10 of 63Eurofins EPK Built Environment Testing, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by any agency of the federal government. The Company reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is