This document appears to be a Request for Proposal (RFP) for the EHRM Infrastructure Upgrades Construction - Miami - Project 546-20-120. The project is a competitive Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside, and the contractor will be required to provide all tools, equipment, materials, labor, and supervision to complete the construction project at the VA Miami health care Bruce W. Carter VA Medical Center. The project is being solicited by the Department of Veterans Affairs Technology Acquisition Center Austin. Key details include the location, the scope of work, the set-aside status, and the requirement for the contractor to provide all necessary resources to complete the project.
View the file
Other files for this federal contract opportunity
Show all 30
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Johnson Controls is committed to serving our customers with the best-in-class services and technologies. Xaap is an advanced inspection reporting application that has been used by Johnson Controls on your inspections.
Xaap is a software-as-a-service (SaaS) solution that provides a streamlined and digitized approach for performing fire and life safety inspections and managing compliance reports in a single, centralized platform.
The application allows inspectors to capture data for fire and life safety systems and devices while generating the required compliance reports directly from their phones. It also provides facility managers, building managers and key stakeholders with a centralized view of all building systems and deficiency data. Users can easily access, download and share historical inspection reports through Xaap.
SSeeee hhooww yyoouurr oorrggaanniizzaattiioonn ccaann lleevveerraaggee tthhiiss ssmmaarrtt tteecchhnnoollooggyy ffoorr yyoouurr iinntteerrnnaall iinnssppeeccttiioonnss VViissiitt iinnffoo..jjccii..ccoomm//xxaaaapp--ttjjcc TToo LLeeaarrnn MMoorree
TThhiiss rreeppoorrtt iiss ppoowweerreedd bbyy XXaaaapp,, tthhee BBuuiillddiinngg CCoommpplliiaannccee RReeppoorrttiinngg PPllaattffoorrmm uusseedd bbyy JJoohhnnssoonn CCoonnttrroollss..
TThhiiss ppaaggee iiss iinnffoorrmmaattiioonnaall oonnllyy aanndd nnoott ppaarrtt ooff TThhee JJooiinntt CCoommmmiissssiioonn RReeppoorrtt
TThhiiss rreeppoorrtt iiss ppoowweerreedd bbyy https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc
[This Page Intentionally Left Blank]
Inspection Summary
Customer Information
Name VA Medical Center (1201 NW 16th Street)
Building Information
Name VA Medical Center - Building 1 New
Address 1201 NW 16th Street, Miami, FL 33125
Contact Information
Name Veronica Allen
Role Administrative Officer
E-Mail veronica.allen3@va.gov
Phone 7867970136
Account Information
Service Provider Johnson Controls North America
Office Address 10550 Commerce Parkway, Miramar FL 33025
Office Phone 954-431-3700
Office License 80542700012002
Inspector Name Nestor De Four
Inspector License
FP122-000286
Inspection Information
Start Date 09/27/2023
Date 09/29/2023
Inspection Type Joint Commission
Work Order# 55004034
Timezone GMT-04:00
Inspection Summary
The following Tests and Inspections have been covered in this inspection
EP 2 - Tamper Switches and Water Flow Devices EP 5 - Emergency Services Notification Transmission Equipment EP 9 - Sprinkler Systems Main Drain EP 10 - Fire Department Water Supply Connections
NFPA 25
General Inspection Notes
1. ANNUAL FIRE SPRINKLER INSPECTION
www.xaapbuildings.com
GENERAL DEFICIENCIES
DESCRIPTION IMAGES
1- Replace (2) damage 11/4” ITV in Stair#1- Penthouse- (handles missing unable to operate) GENERAL DEFICIENCY IMAGES
APPENDIX 1
1- Address Stair#6-3rd (1) 3” Bfly valve & (1) 3” potter VSR flow Switch have no address and did not activate signal on FACP-troubleshoot alarm tech. GENERAL DEFICIENCY IMAGES
APPENDIX 2
3- Address-Lower (1) Tyco 1/2”x155deg QR pendt & install white semi-recess outer plate - 2 floor in corridor by Stair#7 by room#2B136 GENERAL DEFICIENCY IMAGES
APPENDIX 3
DEVICE DEFICIENCIES
TEST TO PERFORM LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE INSPECTOR / DATE IMAGES
EP2 Building 1, Floor 1 2” Bfly valve Stair#4 3:M3-34 Tamper Switch — — —
Nestor Roderick De Four
09/28/2023
FAILURE TYPE: Functional Failure FAILURE REASON: Did not activate signal on FACP when tested-Troubleshoot Alarm tech
EP2 Building 1, Floor 1 2” Bfly valve Stair#4 3:M3-21 Tamper Switch — — —
Nestor Roderick De Four
09/28/2023
FAILURE TYPE: Functional Failure FAILURE REASON: Did not activate signal on FACP when tested
EP2 Building 1, Floor 14 STAIR 1 5:M4-74 Water Flow Switch — — —
Nestor Roderick De Four
09/29/2023
FAILURE TYPE: Visual Failure FAILURE REASON: Unable to locate on 14th Floor
EP2 Building 1, Floor 14 BLDG 1 STAIR 1 5:M4-73 Tamper Switch — — —
Nestor Roderick De Four
09/29/2023
FAILURE TYPE: Visual Failure FAILURE REASON: Unable to locate -on 14th floor
EP2 Building 1, Floor 2 21/2”Potter VSR- Stair#8 M2-6 -old Address Water Flow Switch — — —
Nestor Roderick De Four
09/28/2023
DEFICIENCY
IMAGES
APPENDIX 1.2
FAILURE TYPE: Functional Failure FAILURE REASON: Did not activate signal on FACP when tested- troubleshoot alarm tech
EP2 Building 1, Floor 2 21/2”Milwaukee Bfly valve Stair#7
4:M2-7 old Address Tamper Switch — — —
Nestor Roderick De Four
09/28/2023
DEFICIENCY
IMAGES
APPENDIX 1.1
FAILURE TYPE: Functional Failure FAILURE REASON: Did not activate signal on FACP when tested
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
TEST PERFORMED DEVICE TYPE TOTAL PASSED FAILED CANNOT INSPECT % INSPECTED TOTAL
EP2 Tamper Switch 141 137 4 0 100 141
EP2 Water Flow Switch 93 91 2 0 100 93
EP5 DACT Main/Central Station 1 1 0 0 100 1
EP9 Main Drain - Wet Pipe Valve 12 12 0 0 100 12
EP10 Fire Dept. Connection 3 3 0 0 100 3
TOTAL 250 244 6 0 100 250
TAMPER SWITCHES AND WATER FLOW DEVICES
CUSTOMER NAME: VA Medical Center (1201 NW 16th Street) BUILDING NAME: VA Medical Center - Building 1 New BUILDING ADDRESS: 1201 NW 16th Street, Miami, FL 33125
CONTACT NAME: Veronica Allen CONTACT E-MAIL: veronica.allen3@va.gov CONTACT ROLE: Administrative Officer
CONTACT PHONE: 7867970136
SERVICE PROVIDER: Johnson Controls North America OFFICE ADDRESS: 10550 Commerce Parkway, Miramar FL 33025
OFFICE PHONE: 954-431-3700
OFFICE LICENSE: 80542700012002
INSPECTOR: Nestor De Four
INSPECTOR LICENSE: FP122-000286
INSPECTION START DATE: 09/27/2023
INSPECTION END DATE: 09/29/2023
WORK ORDER: 55004034
TIMEZONE: GMT-04:00
INSPECTION RESULTS SUMMARY
CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS
DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT
Water Flow Switch 93 91 2 0 100 93
Tamper Switch 141 137 4 0 100 141
DEVICE DEFICIENCIES
LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES
Building 1, Floor 1 2” Bfly valve Stair#4 3:M3-34 Tamper Switch — — — 09/28/2023 FUNCTIONAL
FAILURE —
FAILURE REASON: Did not activate signal on FACP when tested-Troubleshoot Alarm tech
Building 1, Floor 1 2” Bfly valve Stair#4 3:M3-21 Tamper Switch — — — 09/28/2023 FUNCTIONAL
FAILURE —
FAILURE REASON: Did not activate signal on FACP when tested
Building 1, Floor 2 21/2”Milwaukee Bfly valve Stair#7
4:M2-7 old Address Tamper Switch — — — 09/28/2023 FUNCTIONAL
FAILURE
DEFICIENCY
IMAGES
APPENDIX 1.1
FAILURE REASON: Did not activate signal on FACP when tested
Building 1, Floor 2 21/2”Potter VSR- Stair#8 M2-6 -old Address Water Flow Switch — — — 09/28/2023 FUNCTIONAL
FAILURE
DEFICIENCY
IMAGES
APPENDIX 1.2
FAILURE REASON: Did not activate signal on FACP when tested- troubleshoot alarm tech
Building 1, Floor 14 BLDG 1 STAIR 1 5:M4-73 Tamper Switch — — — 09/29/2023 VISUAL FAILURE —
FAILURE REASON: Unable to locate -on 14th floor
Building 1, Floor 14 STAIR 1 5:M4-74 Water Flow Switch — — — 09/29/2023 VISUAL FAILURE —
FAILURE REASON: Unable to locate on 14th Floor
RETIRED DEVICES
No retired devices in this inspection.
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023 Customer: VA Medical Center (1201 NW 16th Street) | Building: VA Medical Center - Building 1 New
Elements of Performance #2
At least semi-annually, the facility tests water-flow devices and at least semi-annually the facility tests supervisory valve tamper switches. The completion date of the tests is documented.
Valve Tamper Switches and Water Flow devices
For additional guidance on performing tests, see NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Device Test Method
Control Valve Tamper Switch:
14.4.2.2-14.(i).(1)
Valve shall be operated and signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacture's specifications
Mechanical, Electro-sonic, or Pressure-Type Water flow Device:
14.4.2.2-14.(j)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25.
A.1.1.1.2 There are times when a single inspection or test can meet the requirements of both NFPA 25 and NFPA 72 (e.g., operation of a tamper switch). This standard does not necessarily require that two separate inspections or tests be conducted on the same component, provided the inspection or test meets the requirements of both standards and the individual performing the inspection or test is qualified to perform the inspection or test required by both standards.
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
WATER FLOW SWITCH
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 1, Floor 1 1st floor Radiation Oncology back of reception 3:M4-20 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
2 Building 1, Floor 2 21/2”Potter VSR- Stair#8 M2-6 -old Address Water Flow Switch — Nestor Roderick De
Four 09/28/2023 Failed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
Reason for failure: (Functional Failure) Did not activate signal on FACP when tested- troubleshoot alarm tech
3 Building 1, Floor 1 A1 BOILER PUMP ROOM 3:M2-198 Water Flow Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 45sec
Open test connection/bypass. Did water flow activate the alarm? Yes
4 Building 1, Floor 1 A1 BOILER PUMP ROOM 3:M2-200 Water Flow Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 38sec
Open test connection/bypass. Did water flow activate the alarm? Yes
5 Building 1, Floor 1 A1 M1 3 1
MEA-19-Engineering Shop
3:M2-157 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 40sec
Open test connection/bypass. Did water flow activate the alarm? Yes
6 Building 1, Floor 1 A1 S1 STAIR 2 3:M2-181 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
7 Building 1, Floor 2 A1 STAIR #2 4:M1-31 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
8 Building 1, Floor 1 A2 SERVICE ELEVATOR LOBBY 3:M2-127 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
9 Building 1, Floor 2 A2 STAIR #8 4:M1-12 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
10 Building 1, Floor 3 A2 STAIR #8 4:M1-159 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
11 Building 1, Floor 1 A2 STAIRS 8 3:M2-145 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
12 Building 1, Floor 1 A2 STAIRS S1 8 3:M2-210 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
13 Building 1, Floor 5 (A) S1 STAIR 2 5:M4-38 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
14 Building 1, Floor 4 (A) S4 STAIR 2 5:M4-36 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
15 Building 1, Floor 5 (A) S5 STAIR 1 5:M4-56 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 41sec
Open test connection/bypass. Did water flow activate the alarm? Yes
16 Building 1, Floor 5 (A) S5 STAIR 8 5:M4-76 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 36sec
Open test connection/bypass. Did water flow activate the alarm? Yes
17 Building 1, Floor 6 (A) S6 STAIR 2 5:M4-40 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 41sec
Open test connection/bypass. Did water flow activate the alarm? Yes
18 Building 1, Floor 7 (A) S7 STAIR 2 5:M4-42 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 28Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
19 Building 1, Floor 8 (A) S8 2 STAIR 5:M4-44 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
20 Building 1, Floor 9 (A) S9 STAIR 2 5:M4-46 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
21 Building 1, Floor 11 (A) S11 STAIR 2 5:M4-50 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
22 Building 1, Floor 12 (A) S12 STAIR 2 5:M4-52 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 25sec
Open test connection/bypass. Did water flow activate the alarm? Yes
23 Building 1, Floor 2 A STAIR #2 4:M1-26 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
24 Building 1, Floor 3 A STAIR #2 4:M1-191 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
25 Building 1, Floor 3 A STAIR #2 4:M1-193 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
26 Building 1, Floor 10 (A) STAIR 2 5:M4-48 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 25sec
Open test connection/bypass. Did water flow activate the alarm? Yes
27 Building 1, Floor 1 A STAIR 3 3:M2-188 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
28 Building 1, Floor 2 A STAIR #3 4:M1-36 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
29 Building 1, Floor 2 A STAIR #3 4:M1-49 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 33sec
Open test connection/bypass. Did water flow activate the alarm? Yes
30 Building 1, Basement
BASEMENT CENTER
SOUTH 3:M2-67 Water Flow Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
31 Building 1, Basement
BASEMENT
ELEVATOR LOBBY 3:M2-76 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
32 Building 1, Basement
BASEMENT FHC -
Mail room 3:M2-5 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
33 Building 1, Floor 5 (B) S5 STAIR 6 5:M4-129 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
34 Building 1, Floor 6 (B) S6 STAIR 1 5:M4-58 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
35 Building 1, Floor 7 (B) S7 STAIR 1 5:M4-60 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
36 Building 1, Floor 8 (B) S8 1 STAIR#1 5:M4-62 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 31sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
37 Building 1, Floor 9 (B) S9 STAIR 1 5:M4-64 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
38 Building 1, Floor 10 (B) S10 STAIR 1 5:M4-66 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 40sec
Open test connection/bypass. Did water flow activate the alarm? Yes
39 Building 1, Floor 11 (B) S11 STAIR 1 5:M4-68 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
40 Building 1, Floor 12 (B) S12 STAIR 1 5:M4-70 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30
Open test connection/bypass. Did water flow activate the alarm? Yes
41 Building 1, Floor 4 (B) STAIR #1 5:M4-54 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 36sec
Open test connection/bypass. Did water flow activate the alarm? Yes
42 Building 1, Floor 1 By-roomE-16 above ceiling 3:M4-27 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 38sec
Open test connection/bypass. Did water flow activate the alarm? Yes
43 Building 1, Floor 1
C1 HAC 1C115-
Spinal Cord Housekeeping
3:M1-171 Water Flow Switch — Nestor Roderick De Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 25Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
44 Building 1, Floor 3 C1 STAIR #1 4:M1-132 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
45 Building 1, Floor 3 C1 STAIR #1 4:M1-134 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
46 Building 1, Floor 1 C1 STAIR 6 3:M-159 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 38sec
Open test connection/bypass. Did water flow activate the alarm? Yes
47 Building 1, Floor 1 C1 STAIR 7 3:M1-144 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 36sec
Open test connection/bypass. Did water flow activate the alarm? Yes
48 Building 1, Floor 3 C2 STAIR 6 4:M2-129 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 25sec
Open test connection/bypass. Did water flow activate the alarm? Yes
49 Building 1, Floor 3 C2 STAIR #6 4:M2-131 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 32sec
Open test connection/bypass. Did water flow activate the alarm? Yes
50 Building 1, Floor 2 C2 STAIR 6 4:M3-48 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20sec
Open test connection/bypass. Did water flow activate the alarm? Yes
51 Building 1, Floor 2 C2 STAIR #6 4:M3-50 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
52 Building 1, Floor 2 C2 STAIR #6 4:M3-52 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
53 Building 1, Floor 3 C2 STAIR 7 4:M2-143 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 31sec
Open test connection/bypass. Did water flow activate the alarm? Yes
54 Building 1, Floor 3 C2 STAIR #7 4:M2-151 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 32sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
55 Building 1, Floor 2 C3 C2 7-1 CORR-above ceiling Stair#5 4:M3-89 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 38sec
Open test connection/bypass. Did water flow activate the alarm? Yes
56 Building 1, Basement
CENTER SOUTH
BASEMENT 3:M2-55 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 50sec
Open test connection/bypass. Did water flow activate the alarm? Yes
57 Building 1, Floor 4 (C) S4 STAIR 6 5:M4-127 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 25sec
Open test connection/bypass. Did water flow activate the alarm? Yes
58 Building 1, Floor 6 (C) S6 STAIR 6 5:M4-131 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 40sec
Open test connection/bypass. Did water flow activate the alarm? Yes
59 Building 1, Floor 7 (C) S7 STAIR 6 5:M4-133 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
60 Building 1, Floor 8 (C) S8 6 STAIR#6 5:M4-135 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
61 Building 1, Floor 9 (C) S9 STAIR 6 5:M4-137 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
62 Building 1, Floor 10 (C) S10 STAIR 6 5:M4-139 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
63 Building 1, Floor 11 (C) S11 STAIR 6 5:M4-141 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
64 Building 1, Floor 12 (C) S12 STAIR 6 5:M4-143 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 40
Open test connection/bypass. Did water flow activate the alarm? Yes
65 Building 1, Floor 2 C STAIR #1 4:M3-5 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 33sec
Open test connection/bypass. Did water flow activate the alarm? Yes
66 Building 1, Floor 2 C STAIR #4 4:M3-26 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 40sec
Open test connection/bypass. Did water flow activate the alarm? Yes
67 Building 1, Floor 3 C STAIR #4 4:M3-150 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
68 Building 1, Floor 3 C STAIR #4 4:M3-178 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20sec
Open test connection/bypass. Did water flow activate the alarm? Yes
69 Building 1, Floor 3 C STAIR #4 4:M3-180 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 25sec
Open test connection/bypass. Did water flow activate the alarm? Yes
70 Building 1, Floor 2 D1 STAIR #13 4:M3-79 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
71 Building 1, Floor 1 D2 PATIENT ESCORT MECHANICAL ROOM 3:M1-33 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 55sec
Open test connection/bypass. Did water flow activate the alarm? Yes
72 Building 1, Floor 1 D2 S1 STAIR 13 3:M1-19 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
73 Building 1, Floor 1 D3 STAIR 14 3:M1-189 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
74 Building 1, Floor 2 D3 STAIR #14 4:M2-26 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 32sec
Open test connection/bypass. Did water flow activate the alarm? Yes
75 Building 1, Floor 2 D3 STAIR #14 4:M2-78 Water Flow Switch — Nestor Roderick De Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
76 Building 1, Floor 2 D STAIR #12 4:M3-66 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 42sec
Open test connection/bypass. Did water flow activate the alarm? Yes
77 Building 1, Floor 3 D STAIR #13 4:M2-29 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 37sec
Open test connection/bypass. Did water flow activate the alarm? Yes
78 Building 1, Floor 1 In ceiling in Stairwell#5 3:M3-42 Water Flow Switch — Nestor Roderick De
Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 50sec
Open test connection/bypass. Did water flow activate the alarm? Yes
79 Building 1, Floor 1 In corridor by room 100 above ceiling 3:M4-18 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
80 Building 1, Floor 1 Radiation oncology back of reception 3:M4-20 Water Flow Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
81 Building 1, Basement
SOUTHWEST
BASEMENT 3:M2-66 Water Flow Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
82 Building 1, Floor 1 stair#1 3:M3-6 Water Flow Switch — Nestor Roderick De Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 32sec
Open test connection/bypass. Did water flow activate the alarm? Yes
83 Building 1, Floor 1 stair#1 3:M3-8 Water Flow Switch — Nestor Roderick De Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 40sec
Open test connection/bypass. Did water flow activate the alarm? Yes
84 Building 1, Floor 13 STAIR 1 5:M4-72 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
85 Building 1, Floor 14 STAIR 1 5:M4-74 Water Flow Switch — Nestor Roderick De Four 09/29/2023 Failed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Reason for failure: (Visual Failure) Unable to locate on 14th Floor
86 Building 1, Floor 13 STAIR 1 5:M4-82 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 37sec
Open test connection/bypass. Did water flow activate the alarm? Yes
87 Building 1, Floor 1 Stair#4 3M3-33 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 28Sec
Open test connection/bypass. Did water flow activate the alarm? Yes
88 Building 1, Floor 1 Stair#4 3M3-20 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 40sec
Open test connection/bypass. Did water flow activate the alarm? Yes
89 Building 1, Floor 1 Stair#6 3:M1-159 Water Flow Switch — Nestor Roderick De Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 32sec
Open test connection/bypass. Did water flow activate the alarm? Yes
90 Building 1, Floor 4 STAIR 6 (C) 5:M4-145 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 20sec
Open test connection/bypass. Did water flow activate the alarm? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
91 Building 1, Floor 4 STAIR 6 (C) 5:M4-147 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 33sec
Open test connection/bypass. Did water flow activate the alarm? Yes
92 Building 1, Floor 1 Stair11 3:M3-38 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 30sec
Open test connection/bypass. Did water flow activate the alarm? Yes
93 Building 1, Floor 1 Stair12 3:M3-58 Water Flow Switch — Nestor Roderick De Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes
What was the number of seconds that the water flow signal was delayed 35sec
Open test connection/bypass. Did water flow activate the alarm? Yes
TAMPER SWITCH
# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT
1 Building 1, Floor 1 2” Bfly valve Stair#4 3:M3-34 Tamper Switch — Nestor Roderick De Four 09/28/2023 Failed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Reason for failure: (Functional Failure) Did not activate signal on FACP when tested-Troubleshoot Alarm tech
2 Building 1, Floor 1 2” Bfly valve Stair#4 3:M3-21 Tamper Switch — Nestor Roderick De Four 09/28/2023 Failed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Reason for failure: (Functional Failure) Did not activate signal on FACP when tested
3 Building 1, Floor 2 21/2”Milwaukee Bfly valve Stair#7 4:M2-7 old Address Tamper Switch — Nestor Roderick De
Four 09/28/2023 Failed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Reason for failure: (Functional Failure) Did not activate signal on FACP when tested
4 Building 1, Floor 1 A1 BOILER PUMP ROOM 3:M2-201 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
5 Building 1, Floor 1 A2 STAIRS 8 BY RECEIVING 3:M2-209 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
6 Building 1, Floor 1 BLDG. 1 1FL A1 BOILER PUMP RM 3:M2-199 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
7 Building 1, Floor 1 BLDG. 1 1FL A1 M1 3 1 MEA-19 3:M2-158 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
8 Building 1, Floor 1 BLDG. 1 1FL A1 MEA-24 M1 2 1 3:M2-160 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
9 Building 1, Floor 1 BLDG. 1 1FL A1 MEA-24 M1 2 1 3:M2-161 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2
Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2
2a281e75-0f6a-433f-9191-386d805b40e3 | Tamper Switches and Water Flow Devices | 09/29/2023
TAMPER SWITCH
10 Building 1, Floor 1 BLDG. 1 1FL A1 MEA-24 M1 2 1 3:M2-162 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
11 Building 1, Floor 1 BLDG. 1 1FL A1 STAIRS 2 3:M2-180 Tamper Switch — Nestor Roderick De
Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
12 Building 1, Floor 1 BLDG. 1 1FL A2 REC ELEV MACH RM 3:M2-139 Tamper Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
13 Building 1, Floor 1 BLDG. 1 1FL A2 SERV ELEV LOB 3:M2-128 Tamper Switch — Nestor Roderick De
Four 09/29/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
14 Building 1, Floor 1 BLDG. 1 1FL A2 STAIRS 8 3:M2-144 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
15 Building 1, Floor 1 BLDG. 1 1FL A STAIRS 3 3:M2-187 Tamper Switch — Nestor Roderick De
Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
16 Building 1, Floor 1 BLDG. 1 1FL C1 STAIRS 6 3:M1-160 Tamper Switch — Nestor Roderick De
Four 09/27/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
17 Building 1, Floor 1 BLDG. 1 1FL C1 STAIRS 7 3:M1-145 Tamper Switch — Nestor Roderick De
Four 09/28/2023 Passed
Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes
18 Building 1, Floor 1 BLDG. 1 1FL C2 HAC 1C115 3:M1-170 Tamper Switch — Nestor Roderick De
Four…