Q73 - Annual - Utility Building - 2023-09-25.pdf

PDF 1 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction - Miami - Project 546-20-120 Federal contract opportunity
Solicitation number
36C77624B0027
Issued by
Department of Veterans Affairs Technology Acquisition Center Austin

About this file

This document is a detailed inspection report for the fire and life safety systems at the VA Medical Center - Utility Building in Miami, Florida. The report covers inspections and testing of tamper switches, water flow devices, sprinkler system main drains, and fire department water supply connections, as required by NFPA 25 and Joint Commission standards.

The key details include:

  • The inspections were conducted on September 25, 2023 by Johnson Controls North America, the service provider.
  • The inspection found that most of the devices passed testing, except for one tamper switch that failed due to not activating the signal on the fire alarm control panel when tested.
  • The annual main drain test for the wet pipe sprinkler system was successfully completed, with no deficiencies noted.
  • The quarterly inspection of the fire department connection also passed, with all components found to be in good condition.
  • No changes to the occupancy, machinery, or fire protection systems were reported since the last inspection.

View the file

Other files for this federal contract opportunity

Other files attached to EHRM Infrastructure Upgrades Construction - Miami - Project 546-20-120, newest first.
File Type Posted
Wage Determination - Miami-Dade County 11-1-24.pdf PDF
36C77624B0027 0006.pdf PDF
36C77624B0027 0005.pdf PDF
Additional RFI responses - SOLICITATION 36C77624B0027 - Miami Project 546-20-120.pdf PDF
Online Bid Opening Meeting Info.docx DOCX document
36C77624B0027 0004.pdf PDF
36C77624B0027 0003.pdf PDF
52.222-33 NOTICE OF REQUIREMENT FOR PROJECT LABOR AGREEMENT.pdf PDF
RFI Responses - SOLICITATION 36C77624B0027 - Miami Project 546-20-120.pdf PDF
36C77624B0027 0002.pdf PDF
52.222-34 PROJECT LABOR AGREEMENT ALTERNATE I.pdf PDF
Q73 - Annual - Building 1 - 2023-09-29.pdf PDF
Q73 - Annual - Building 7 and 40 - 2023-09-26.pdf PDF
Q73 - Quarterly - Fisher House - 2023-12-05.pdf PDF
Data Racks By TR.pdf PDF
Q73 - Annual - Building 10 - 2023-09-26.pdf PDF
Wage Determination - Miami-Dade County 10-4-24.pdf PDF
Q73 - Annual - Shop Building - 2023-09-26.pdf PDF
EHRM Site Visit Sign-in Sheet.pdf PDF
Amendment 0001 9-18-2024 - 36C77624B0027 0001.pdf PDF
Brand Name Justifcation - Miami EHRM Construction_Redacted.pdf PDF
Miami RFI SUBMISSION SHEET - SOLICITATION 36C77624B0027.xlsx XLSX spreadsheet
IFB 36C77624B0027.pdf PDF
Wage Determination - Miami-Dade County 8-9-24.pdf PDF
21-147 100 Percent CD Dwgs.pdf PDF
Terracon Asbestos Report.pdf PDF
VHA PCRA 546-20-120 Signed.pdf PDF
Site Visit Instructions - Miami.pdf PDF
21-147 100 Percent CD Specs.pdf PDF
VAAR 852.219-75 Limitations on Subcontracting.docx DOCX document
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Johnson Controls is committed to serving our customers with the best-in-class services and technologies. Xaap is an advanced inspection reporting application that has been used by Johnson Controls on your inspections.

Xaap is a software-as-a-service (SaaS) solution that provides a streamlined and digitized approach for performing fire and life safety inspections and managing compliance reports in a single, centralized platform.

The application allows inspectors to capture data for fire and life safety systems and devices while generating the required compliance reports directly from their phones. It also provides facility managers, building managers and key stakeholders with a centralized view of all building systems and deficiency data. Users can easily access, download and share historical inspection reports through Xaap.

SSeeee hhooww yyoouurr oorrggaanniizzaattiioonn ccaann lleevveerraaggee tthhiiss ssmmaarrtt tteecchhnnoollooggyy ffoorr yyoouurr iinntteerrnnaall iinnssppeeccttiioonnss VViissiitt iinnffoo..jjccii..ccoomm//xxaaaapp--ttjjcc TToo LLeeaarrnn MMoorree

TThhiiss rreeppoorrtt iiss ppoowweerreedd bbyy XXaaaapp,, tthhee BBuuiillddiinngg CCoommpplliiaannccee RReeppoorrttiinngg PPllaattffoorrmm uusseedd bbyy JJoohhnnssoonn CCoonnttrroollss..

TThhiiss ppaaggee iiss iinnffoorrmmaattiioonnaall oonnllyy aanndd nnoott ppaarrtt ooff TThhee JJooiinntt CCoommmmiissssiioonn RReeppoorrtt

TThhiiss rreeppoorrtt iiss ppoowweerreedd bbyy https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc https://info.jci.com/xaap-tjc

[This Page Intentionally Left Blank]

Inspection Summary

Customer Information

Name VA Medical Center (1201 NW 16th Street)

Building Information

Name VA Medical Center - Utility Building

Address 1201 N.W 16th Street, Miami, Florida 33125-1393

Contact Information

Name Veronica Allen

Role Administrative officer

E-Mail veronica.Allen3@va.gov

Phone 7867970136

Account Information

Service Provider Johnson Controls North America

Office Address 10550 Commerce Parkway, Miramar FL 33025

Office Phone 954-431-3700

Office License 80542700012002

Inspector Name Nestor De Four

Inspector License

FP122-000286

Inspection Information

Start Date 09/25/2023

Date 09/25/2023

Inspection Type Joint Commission

Work Order# 55004034

Timezone GMT-04:00

Inspection Summary

The following Tests and Inspections have been covered in this inspection

EP 2 - Tamper Switches and Water Flow Devices EP 9 - Sprinkler Systems Main Drain EP 10 - Fire Department Water Supply Connections

NFPA 25

General Inspection Notes

1. ANNUAL FIRE SPRINKLER INSPECTION

www.xaapbuildings.com

GENERAL DEFICIENCIES

DESCRIPTION IMAGES

1- (1) Missing 21/2” hose valve cap at 4”FSR East stair-2nd floor- Install —

2- Backflow #1 OS&Y valve tamper did not activate signal on FACP when tested-Troubleshoot alarm tech. —

3- Install (1)wall mounted FDC sign —

DEVICE DEFICIENCIES

TEST TO PERFORM LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE INSPECTOR / DATE IMAGES

EP2 Utility Bluilding, Outside

OUTSIDE

BACKFLOW N9:M1-7 Tamper Switch — — —

Nestor Roderick De Four

09/25/2023

FAILURE TYPE: Functional Failure FAILURE REASON: Did not activate signal on FACP when tested

INSPECTION RESULTS SUMMARY

CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS

TEST PERFORMED DEVICE TYPE TOTAL PASSED FAILED CANNOT INSPECT % INSPECTED TOTAL

EP2 Tamper Switch 29 28 1 0 100 29

EP2 Water Flow Switch 4 4 0 0 100 4

EP9 Main Drain - Wet Pipe Valve 1 1 0 0 100 1

EP10 Fire Dept. Connection 1 1 0 0 100 1

NFPA 25 City Connection Control Valve 2 2 0 0 100 2

NFPA 25 Wet System 1 1 0 0 100 1

TOTAL 38 37 1 0 100 38

TAMPER SWITCHES AND WATER FLOW DEVICES

CUSTOMER NAME: VA Medical Center (1201 NW 16th Street) BUILDING NAME: VA Medical Center - Utility Building BUILDING ADDRESS: 1201 N.W 16th Street, Miami, Florida 33125-1393

CONTACT NAME: Veronica Allen CONTACT E-MAIL: veronica.Allen3@va.gov CONTACT ROLE: Administrative officer

CONTACT PHONE: 7867970136

SERVICE PROVIDER: Johnson Controls North America OFFICE ADDRESS: 10550 Commerce Parkway, Miramar FL 33025

OFFICE PHONE: 954-431-3700

OFFICE LICENSE: 80542700012002

INSPECTOR: Nestor De Four

INSPECTOR LICENSE: FP122-000286

INSPECTION START DATE: 09/25/2023

INSPECTION END DATE: 09/25/2023

WORK ORDER: 55004034

TIMEZONE: GMT-04:00

INSPECTION RESULTS SUMMARY

CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT

Water Flow Switch 4 4 0 0 100 4

Tamper Switch 29 28 1 0 100 29

DEVICE DEFICIENCIES

LOCATION DESCRIPTION ADDRESS DEVICE MAKE MODEL BARCODE DATE OF TEST TYPE IMAGES

Utility Bluilding, Outside

OUTSIDE

BACKFLOW N9:M1-7 Tamper Switch — — — 09/25/2023 FUNCTIONAL

FAILURE —

FAILURE REASON: Did not activate signal on FACP when tested

RETIRED DEVICES

No retired devices in this inspection.

Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Tamper Switches and Water Flow Devices | 09/25/2023 Customer: VA Medical Center (1201 NW 16th Street) | Building: VA Medical Center - Utility Building

Elements of Performance #2

At least semi-annually, the facility tests water-flow devices and at least semi-annually the facility tests supervisory valve tamper switches. The completion date of the tests is documented.

Valve Tamper Switches and Water Flow devices

For additional guidance on performing tests, see NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2

Device Test Method

Control Valve Tamper Switch:

14.4.2.2-14.(i).(1)

Valve shall be operated and signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacture's specifications

Mechanical, Electro-sonic, or Pressure-Type Water flow Device:

14.4.2.2-14.(j)

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25.

A.1.1.1.2 There are times when a single inspection or test can meet the requirements of both NFPA 25 and NFPA 72 (e.g., operation of a tamper switch). This standard does not necessarily require that two separate inspections or tests be conducted on the same component, provided the inspection or test meets the requirements of both standards and the individual performing the inspection or test is qualified to perform the inspection or test required by both standards.

Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Tamper Switches and Water Flow Devices | 09/25/2023

TAMPER SWITCH

# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Utility Building , 1st Floor BY ELEVATOR LOBBY N9:M1-21 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

2 Utility Building , 1st Floor

BY FIRE ALARM

CONTROL PANEL N9:M1-2 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

3 Utility Building , 2nd Floor

BY FIRE PUMP

ROOM 20344 N9:M1-41 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

4 Utility Building , 2nd Floor

BY FIRE PUMP

ROOM 20344 N9:M1-42 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

5 Utility Building , 2nd Floor

IN BOILER ROOM

20444 ENTRANCE N9:M1-37 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

6 Utility Building , 2nd Floor

IN BOILER ROOM

20444 ENTRANCE N9:M1-38 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

7 Utility Building , 4th Floor IN ELEVATOR LOBBY 11:M1-136 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

8 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-49 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

9 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-50 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

10 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-51 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

11 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-52 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

12 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-54 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

13 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-53 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

14 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-55 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

15 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-56 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

16 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-57 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

17 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-58 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Tamper Switches and Water Flow Devices | 09/25/2023

TAMPER SWITCH

18 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-59 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

19 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-60 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

20 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-61 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

21 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-73 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

22 Utility Building , 2nd Floor

IN FIRE PUMP ROOM

20344 N9:M1-74 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

23 Utility Building , 4th Floor IN STAIR #1 N9:M1-71 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

24 Utility Building , 1st Floor IN STAIR #2 N9:M1-5 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

25 Utility Building , 2nd Floor IN STAIR #2 N9:M1-34 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

26 Utility Building , 3rd Floor IN STAIR #2 N9:M1-64 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

27 Utility Bluilding, Outside OUTSIDE BACKFLOW N9:M1-7 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Failed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

Reason for failure: (Functional Failure) Did not activate signal on FACP when tested

28 Utility Bluilding, Outside OUTSIDE BACKFLOW N9:M1-8 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

29 Utility Bluilding, Outside OUTSIDE PIV N9:M1-6 Tamper Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is tamper switch free of damage with its electrical connections secure? Yes

WATER FLOW SWITCH

# LOCATION DESCRIPTION ADDRESS DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Utility Building , 4th Floor IN STAIR #1 N9:M1-72 Water Flow Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes

What was the number of seconds that the water flow signal was delayed 35sec

Open test connection/bypass. Did water flow activate the alarm? Yes

2 Utility Building , 1st Floor IN STAIR #2 N9:M1-4 Water Flow Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes

What was the number of seconds that the water flow signal was delayed 30sec

Open test connection/bypass. Did water flow activate the alarm? Yes

Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Tamper Switches and Water Flow Devices | 09/25/2023

WATER FLOW SWITCH

3 Utility Building , 2nd Floor IN STAIR #2 N9:M1-33 Water Flow Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes

What was the number of seconds that the water flow signal was delayed 35sec

Open test connection/bypass. Did water flow activate the alarm? Yes

4 Utility Building , 3rd Floor IN STAIR #2 N9:M1-63 Water Flow Switch — Nestor Roderick De

Four 09/25/2023 Passed

Quarterly Visual Inspection Only - Is flow switch free of damage with its electrical connections secure? Yes

What was the number of seconds that the water flow signal was delayed 36sec

Open test connection/bypass. Did water flow activate the alarm? Yes

Inspector Signature

Inspector Name Nestor De Four Date 09/25/2023

Signature of the

Electric Supervisor

Printed name of the Electric

Supervisor Valdes Juan F Date 09/25/2023

Element of Performance - EP-2 NFPA 72-2010: Table 14.4.5 and NFPA 25-2011: Table 5.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 2 EP -2

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Tamper Switches and Water Flow Devices | 09/25/2023

SPRINKLER SYSTEMS MAIN DRAIN

BUILDING NAME: VA Medical Center - Utility Building BUILDING ADDRESS: 1201 N.W 16th Street, Miami, Florida 33125-1393

CONTACT NAME: Veronica Allen CONTACT E-MAIL: veronica.Allen3@va.gov CONTACT ROLE: Administrative officer

CONTACT PHONE: 7867970136

SERVICE PROVIDER: Johnson Controls North America OFFICE ADDRESS: 10550 Commerce Parkway, Miramar FL 33025

OFFICE PHONE: 954-431-3700

OFFICE LICENSE: 80542700012002

INSPECTOR: Nestor De Four

INSPECTOR LICENSE: FP122-000286

INSPECTION START DATE: 09/25/2023

INSPECTION END DATE: 09/25/2023

WORK ORDER: 55004034

TIMEZONE: GMT-04:00

INSPECTION RESULTS SUMMARY

CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT

Main Drain - Wet Pipe Valve 1 1 0 0 100 1

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

RETIRED DEVICES

No retired devices in this inspection.

Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1

Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Sprinkler Systems Main Drain | 09/25/2023

Elements of Performance #9

Every 12 months the facility tests the main drains at the system low point or at all system risers. A main drain test shall be conducted annually at each system riser and any time the valve is closed at each system riser or feed main after the control valve has been closed to determine whether there has been a change in the condition of the water supply piping and control valves. The completion date of the tests is documented.

Main Drain

For additional guidance on performing the annual / quarterly tests, see NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1

Device Test Method

Main Drain 1. Record the pressure indicated by the supply water gauge.

2. Close the alarm control valve on alarm valves.

3. Fully open the main drain valve.

4. After the flow has stabilized, record the residual (flowing) pressure indicated by the water supply gauge.

5. Close the main drain valve slowly.

6. Record the time taken for the supply water pressure to return to the original static (non-flowing) pressure.

7. Open the alarm control valve.

** 13.2.5.1 In systems where the sole water supply is through a backflow preventer and/or pressure reducing valves, the main drain test of at least one system downstream of the device shall be conducted on a quarterly basis.

Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1

Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Sprinkler Systems Main Drain | 09/25/2023

MAIN DRAIN - WET PIPE VALVE

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Utility Building , 1st Floor

Main Drain - Wet Pipe Valve 1

Main Drain - Wet Pipe Valve — Nestor Roderick De

Four 09/25/2023 Passed

Test Pipe Located? North Stair

Size of Test Pipe? 1”

Previous Main Drain Test Date 06/20/2023

Previous Main Drain Static Pressure 165

Previous Main Drain Residual Pressure 90

Static Supply Pressure? 165

Residual Pressure? 90

Time to return to Normal System Pressure? 3sec

Static Pressure after completion of test? 165

Main Drain-PSI Comparable Yes

Main drain opened & free of obstruction discoloration? Yes

Inspector Signature

Inspector Name Nestor De Four Date 09/25/2023

Signature of the

Electric Supervisor

Printed name of the Electric

Supervisor Valdes Juan F Date 09/25/2023

Element of Performance - EP-9 NFPA 25-2011: 13.2.5; 13.3.3.4; Table 13.1.1.2; Table 13.8.1

Joint Commission Standard EC.02.03.05 Element of Performance 9 EP -9

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Sprinkler Systems Main Drain | 09/25/2023

FIRE DEPARTMENT WATER SUPPLY CONNECTIONS

BUILDING NAME: VA Medical Center - Utility Building BUILDING ADDRESS: 1201 N.W 16th Street, Miami, Florida 33125-1393

CONTACT NAME: Veronica Allen CONTACT E-MAIL: veronica.Allen3@va.gov CONTACT ROLE: Administrative officer

CONTACT PHONE: 7867970136

SERVICE PROVIDER: Johnson Controls North America OFFICE ADDRESS: 10550 Commerce Parkway, Miramar FL 33025

OFFICE PHONE: 954-431-3700

OFFICE LICENSE: 80542700012002

INSPECTOR: Nestor De Four

INSPECTOR LICENSE: FP122-000286

INSPECTION START DATE: 09/25/2023

INSPECTION END DATE: 09/25/2023

WORK ORDER: 55004034

TIMEZONE: GMT-04:00

INSPECTION RESULTS SUMMARY

CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT

Fire Dept. Connection 1 1 0 0 100 1

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

RETIRED DEVICES

No retired devices in this inspection.

Element of Performance - EP-10 NFPA 25-2011: 13.7; Table 13.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 10 EP -1

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Fire Department Water Supply Connections | 09/25/2023

Elements of Performance #10

Every quarter the facility inspects all fire department water supply connections. The completion date of the tests is documented.

Fire Department Connections

For additional guidance on performing the tests, see NFPA 25-2011: 13.7; Table 13.1.1.2

Device Test Method

Fire Department Connections

1. The fire department connections are visible and accessible.

2. Couplings or swivels are not damaged and rotate smoothly.

3. Plugs or caps are in place and undamaged.

4. Gaskets are in place and in good condition.

5. Identification signs are in place.

6. The check valve is not leaking.

7. The automatic drain valve is in place and operating properly.

8. The fire department connection clapper(s) is in place and operating properly.

Element of Performance - EP-10 NFPA 25-2011: 13.7; Table 13.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 10 EP -1

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Fire Department Water Supply Connections | 09/25/2023

FIRE DEPT. CONNECTION

1 Floor 01 By Test Header Fire Dept. Connection — Nestor Roderick De Four 09/25/2023 Passed

FDC Quarterly Questions

Is FDC Visible / Accessible? Yes

Are Couplings / Swivels / Plugs / Caps in place? Yes

Identification Signs In Place? Yes

Check Valve Not Leaking / Gaskets In Good Condition / Ball Drip and Clapper in Place and Operating Properly Yes

FDC Hydrostatic Test Date 06/14/2022

FDC Check Valves Internal Inspection Date 11/22/2022

Notes:

• FDC- outside north Images: DEVICE NOTES IMAGES APPENDIX 1.1

Inspector Signature

Inspector Name Nestor De Four Date 09/25/2023

Signature of the

Electric Supervisor

Printed name of the Electric

Supervisor Valdes Juan F Date 09/25/2023

Element of Performance - EP-10 NFPA 25-2011: 13.7; Table 13.1.1.2

Joint Commission Standard EC.02.03.05 Element of Performance 10 EP -1

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | Fire Department Water Supply Connections | 09/25/2023

NFPA 25

BUILDING NAME: VA Medical Center - Utility Building BUILDING ADDRESS: 1201 N.W 16th Street, Miami, Florida 33125-1393

CONTACT NAME: Veronica Allen CONTACT E-MAIL: veronica.Allen3@va.gov CONTACT ROLE: Administrative officer

CONTACT PHONE: 7867970136

SERVICE PROVIDER: Johnson Controls North America OFFICE ADDRESS: 10550 Commerce Parkway, Miramar FL 33025

OFFICE PHONE: 954-431-3700

OFFICE LICENSE: 80542700012002

INSPECTOR: Nestor De Four

INSPECTOR LICENSE: FP122-000286

INSPECTION START DATE: 09/25/2023

INSPECTION END DATE: 09/25/2023

WORK ORDER: 55004034

TIMEZONE: GMT-04:00

INSPECTION RESULTS SUMMARY

CURRENT INSPECTION RESULTS PREVIOUS INSPECTION RESULTS

DEVICE TYPE INVENTORY COUNT PASSED FAILED CANNOT INSPECT % INSPECTED INVENTORY COUNT

City Connection Control Valve 2 2 0 0 100 2

Wet System 1 1 0 0 100 1

DEVICE DEFICIENCIES

No device deficiencies in this inspection.

RETIRED DEVICES

No retired devices in this inspection.

NFPA 25, Edition 2011

N

FP

A

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | NFPA 25 | 09/25/2023

CITY CONNECTION CONTROL VALVE

1 Backflow City Connection Valve

1 ; OS&Y

City Connection Control Valve — Nestor Roderick De

Four 09/25/2023 Passed

Is This A Main System, Sub System, Or Auxiliary Control Valve? Main

What Size Is This Control Valve? 8”

Easily Accessible? Yes

Signs? Yes

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Locked, Supervised

Free from External Leaks Yes

Control Valve - Annual Questions

Control Valve Fully Exercised? Yes

2 Backflow City Connection Valve

2 ; OS&Y

City Connection Control Valve — Nestor Roderick De

Four 09/25/2023 Passed

Is This A Main System, Sub System, Or Auxiliary Control Valve? Main

What Size Is This Control Valve? 8”

Easily Accessible? Yes

Signs? Yes

Valve in the Appropriate Open or Closed Position? Yes

Sealed, Locked, and/or Supervised Supervised, Locked

Free from External Leaks Yes

Control Valve - Annual Questions

Control Valve Fully Exercised? Yes

WET SYSTEM

# LOCATION DESCRIPTION DEVICE TYPE BARCODE INSPECTOR DATE OF TEST RESULT

1 Stair#1&2, Utility Bldg

Wet System (4)-21/ 2”floor Systems &

(2)4”FSR

Wet System — Nestor Roderick De

Four 09/25/2023 Passed

Wet Systems - Weekly - Monthly Questions

Make and Model (4)21/2”floor Systems

What Size Is This Wet Pipe Valve 2.5

Hydraulic Name Plate Present No

Gauges Reading Normal PSI Yes

Date of Check Valves Internal Inspection 11/22/2022

Date the internal pipe inspection was performed? 11/22/2022

Date of Gauges Replacement 11/22/2022

Wet Systems Quarterly - Semi Annual - Annual - Questions

Did check valves, water flow alarm devices, and retards test satisfactorily? Yes

Inspector's Test Valve Opened & Free Of Obstruction / Discoloration? Yes

NFPA 25, Edition 2011

N

FP

A

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | NFPA 25 | 09/25/2023

NFPA 25

NFPA 25 Questions

1. Has there been any changes in the occupancy classification, machinery or operations since the last inspection? No

2. Has there been any changes or repairs to the fire protection systems since the last inspection? No

3. Have you had an internal pipe inspection performed in the last 5 years? Yes

4. Date the internal pipe inspection was performed? 11/22/2022

5. Date Backflow Devices Were Tested 12/16/2022

6. Number Of Water Gauges? (12) -2022

7. Are all Tanks, Fire Pumps, and Fire Department Connections Inspected and Tested Per NFPA 25? Yes

8. Date That The Private Fire Main Been Flow Tested? 11/22/2022

9. All Systems Restored To Normal? Yes

Control Valves

1. Are all sprinkler system main control valves and all other valves in the appropriate open or closed position? Yes

2. Are all control valves sealed, locked, or supervised, in the appropriate open or closed position? Yes

Water Supplies

1. What type of water supply does this sprinkler system use? Pressure Fire Pump and City

Alarms

1. Did the electric alarms operate during testing? Yes

2. Did the supervisory alarms operate during testing? Yes

Sprinklers and Piping

1. Were All Sprinklers Made After 1920 Yes

2. Do sprinklers generally appear to be free of corrosion, paint, or loading visible obstructions? Yes

3. Is the buildings sprinklers inventory list located within the sprinkler spare head cabinet? Yes

4. Are appropriate number of extra sprinklers and sprinkler wrenches available on the premises? Yes

5. Does there appear to be proper clearance between the top of all storage and the sprinkler deflector? Yes

6. Does the exposed exterior condition of piping, drain valves, check valves, hangers, pressure gauges, open sprinklers and strainers appear to be satisfactory 1st floor piping in area of service elevator disconnected.

Yes

Inspector Signature

Inspector Name Nestor De Four Date 09/25/2023

Signature of the

Electric Supervisor

Printed name of the Electric

Supervisor Valdes Juan F Date 09/25/2023

NFPA 25, Edition 2011

N

FP

A

3a919b32-e4a8-48ce-80e8-d59e6b81ae43 | NFPA 25 | 09/25/2023

Terms And Conditions

1. Limitation of Liability; Limitations Of Remedy. It is understood and agreed by the Customer that Company is not an insurer and that insurance coverage, if any, shall be obtained by the Customer and that amounts payable to Company hereunder are based upon the value of the services and the scope of liability set forth in this agreement and are unrelated to the value of the Customer's property and the property of others located on the premises. Customer agrees to look exclusively to the Customer's insurer to recover for injuries or damage in the event of any loss or injury and that Customer releases and waives all right of recovery against Company arising by way of subrogation. Company makes no guaranty or Warranty, including any implied warranty of merchantability or fitness for a particular purpose that equipment or services supplied by Company will detect or avert occurrences or the consequences there from that the equipment or service was designed to detect or avert.<br />It is impractical and extremely difficult to fix the actual damages, if any, which may proximately result from failure on the part of Company to perform any of its obligations under this agreement. Accordingly, Customer agrees that, Company shall be exempt from liability for any loss, damage or injury arising directly or indirectly from occurrences, or the consequences therefrom, which the equipment or service was designed to detect or avert. Should Company be found liable for any loss, damage or injury arising from a failure of the equipment or service in any respect, Company's liability shall be limited to an amount equal to the agreement price (as increased by the price for any additional work) or where the time and material payment term is selected, Customer's time and material payments to Company. Where this agreement covers multiple sites, liability shall be limited to the amount of the payments allocable to the site where the incident occurred. Such sum shall be complete and exclusive. If Customer desires Company to assume greater liability, the parties shall amend this agreement by attaching a rider setting forth the amount of additional liability and the additional amount payable by the Customer for the assumption by Company of such greater liability, provided however that such rider shall in no way be interpreted to hold Company as an insurer. IN NO EVENT SHALL COMPANY BE LIABLE FOR ANY DAMAGE, LOSS, INJURY, OR ANY OTHER CLAIM ARISING FROM ANY SERVICING, ALTERATIONS, MODIFICATIONS, CHANGES, OR MOVEMENTS OF THE COVERED SYSTEM(S) OR ANY OF ITS COMPONENT PARTS BY THE CUSTOMER OR ANY THIRD PARTY. COMPANY SHALL NOT BE LIABLE FOR INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND, INCLUDING BUT NOT LIMITED TO DAMAGES ARISING FROM THE USE, LOSS OF THE USE, PERFORMANCE, OR FAILURE OF THE COVERED SYSTEM(S) TO PERFORM. The limitations of liability set forth in this agreement shall inure to the benefit of all parents, subsidiaries and affiliates of Company, whether direct or indirect, Company's employees, agents, officers and directors.

2. Limited Warranty. COMPANY WARRANTS THAT ITS WORKMANSHIP AND MATERIAL FURNISHED UNDER THIS AGREEMENT WILL BE FREE FROM DEFECTS FOR A PERIOD OF NINETY

(90) DAYS FROM THE DATE OF FURNISHING. Where Company provides product or equipment of others, Company will warrant the product or equipment only to the extent warranted by such third party. EXCEPT AS EXPRESSLY SET FORTH HEREIN, COMPANY DISCLAIMS ALL WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE WITH RESPECT TO THE SERVICES PERFORMED OR THE PRODUCTS, SYSTEMS OR EQUIPMENT, IF ANY, SUPPORTED HEREUNDER. COMPANY MAKES NO WARRANTY OR REPRESENTATION, AND UNDERTAKES NO OBLIGATION TO ENSURE BY THE SERVICES PERFORMED UNDER THIS AGREEMENT, THAT COMPANY'S PRODUCTS OR THE SYSTEMS OR EQUIPMENT OF THE CUSTOMER WILL CORRECTLY HANDLE THE PROCESSING OF CALENDAR DATES BEFORE OR

AFTER DECEMBER 31, 1999.

3. Indemnity. Customer agrees to indemnify, hold harmless and defend Company against any and all losses, damages, costs, including expert fees and costs, and expenses including reasonable defense costs, arising from any and all third party claims for personal injury, death, property damage or economic loss, including specifically any damages resulting from the exposure of workers to Hazardous Conditions whether or not Customer pre-notifies Company of the existence of said hazardous conditions, arising in any way from any act or omission of Customer or Company relating in any way to this agreement, including but not limited to the Services under this agreement, whether such claims are based upon contract, warranty, tort (including but not limited to active or passive negligence), strict liability or otherwise. Company reserves the right to select counsel to represent it in any such action.

4. Hazardous Materials. Customer represents that, except to the extent that Company has been given written notice of the following hazards prior to the execution of this agreement, to the best of Customer's knowledge there is no:

a. "permit confined space," as defined by OSHA, or space in which work must be performed that, because of its construction, location, contents or work activity therein, accumulation of a hazardous gas, vapour, dust or fume or the creation of a risk of infectious disease

b. need for air monitoring, respiratory protection, or other medical risk

c. asbestos, asbestos-containing material, formaldehyde or other potentially toxic or otherwise hazardous material contained in or on the surface of the floors, walls, ceilings, insulation or other structural components of the area of any building

d. All of the above are hereinafter referred to as "Hazardous Conditions". Company shall have the right to rely on the representations listed above. If hazardous conditions are encountered by Company during the course of Company's work, the discovery of such conditions shall constitute an event beyond Company's control and Company shall have no obligation to further perform in the area where the hazardous conditions exist until the area has been made safe by Customer as certified in writing by an independent testing agency, and Customer shall pay disruption expenses and re-mobilization expenses as determined by Company. This agreement does not provide for the cost of capture, containment or disposal of any hazardous waste materials, or hazardous materials, encountered in any of the Covered System(s) and/or during performance of the Services. Said materials shall at all times remain the responsibility and property of Customer. Company shall not be responsible for the testing, removal or disposal of such hazardous materials.

5. Equipment Disconnections. This represents Company's notice to you that the system(s)/device(s) listed on the face of this agreement as temporarily or permanently disconnected are no longer in service and, thus, cannot detect, perform and/or report

6. General. Unless otherwise specified, work shall be performed during company's regular business hours,, exclusive of Saturdays, Sundays and Company holidays. All work is subject to review and rebilling in accordance with the terms and conditions of Customer's agreement/contract with Company, if one is in effect. Company shall not be responsible for failure to render services due to causes beyond its control, including but not limited to material shortages, work stoppages, fires, civil disobedience or unrest, severe weather, fire or any other cause beyond the control of Company. Customer is aware that the Limitation of Liability and other provisions set forth in any existing agreement/contract, if one is in effect, or set forth above, apply to services performed and materials supplied. The terms of this agreement shall govern notwithstanding any inconsistent or additional terms and conditions in any purchase order or other document submitted by Customer.

Joint Commission Report | Date: 09/25/2023 Page 4 of 5

DEVICE NOTE IMAGE APPENDICES

EP10

LOCATION DESCRIPTION DEVICE BARCODE IMAGES

Floor 01 By Test Header Fire Dept. Connection — DEVICE NOTES IMAGES APPENDIX 1.1 Notes:

• FDC- outside north

Joint Commission Report | Date: 09/25/2023 Page 5 of 5