Unfortunately, the provided file "Technical Exhibit K - Division 26 - Electrical.pdf" was not actually included in the message. Without the actual file contents, I cannot provide a detailed summary. The related federal contract opportunity indicates this is for a paving IDIQ (Indefinite Delivery/Indefinite Quantity) contract at Joint Base Lewis-McChord in Washington, involving roadway and airfield paving construction, removal, replacement, and repair services. However, the specific electrical technical exhibit details cannot be analyzed without the file itself being present.
View the file
Other files for this federal contract opportunity
Show all 28
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USACE / NAVFAC / AFCEC UFGS- 26 56 00 ( August 2021)
Pr epar i ng Act i v i t y: NAVFAC Super sedi ng UFGS- 26 56 00 ( May 2020)
UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS
Ref er ences ar e i n agr eement wi t h UMRL dat ed Apr i l 2024
SECTI ON TABLE OF CONTENTS
DI VI SI ON 26 - ELECTRI CAL
SECTI ON 26 56 00
EXTERI OR LI GHTI NG
08/ 21
PART 1 GENERAL
1. 1 REFERENCES
1. 2 RELATED REQUI REMENTS
1. 3 DEFI NI TI ONS
1. 4 SUBMI TTALS
1. 5 QUALI TY ASSURANCE
1. 5. 1 Dr awi ng Requi r ement s
1. 5. 1. 1 Lumi nai r e Dr awi ngs
1. 5. 1. 2 Pol e Dr awi ngs
1. 5. 2 Lumi nai r e Desi gn Dat a
1. 5. 3 ANSI / I ES LM- 79 Test Repor t
1. 5. 4 ANSI / I ES LM- 80 Test Repor t
1. 5. 5 ANSI / I ES TM- 21 Test Repor t
1. 5. 6 Test s f or Fi ber gl ass Pol es
1. 5. 7 Pr essur e Tr eat ed Wood Pol e Qual i t y
1. 5. 8 Phot omet r i c Pl an
1. 5. 9 Test Labor at or i es
1. 5. 10 Regul at or y Requi r ement s
1. 5. 11 St andar d Pr oduct s
1. 5. 11. 1 Al t er nat i ve Qual i f i cat i ons
1. 5. 11. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
1. 6 DELI VERY, STORAGE, AND HANDLI NG OF POLES
1. 6. 1 Al umi num Pol es
1. 6. 2 St eel Pol es
1. 6. 3 Wood Pol es
1. 6. 4 Fi ber gl ass Pol es
1. 6. 5 Concr et e Pol es
1. 7 WARRANTY
1. 7. 1 Lumi nai r e War r ant y
1. 7. 2 Li ght i ng Cont r ol s War r ant y
1. 7. 3 Pol e War r ant y
1. 8 OPERATI ON AND MAI NTENANCE MANUALS
1. 8. 1 Li ght i ng Syst em
SECTI ON 26 56 00 Page 1
1. 8. 2 Ext er i or Li ght i ng Cont r ol Syst em
PART 2 PRODUCTS
2. 1 PRODUCT COORDI NATI ON
2. 2 LUMI NAI RES
2. 2. 1 Lumi nai r e Sampl es
2. 2. 2 Lumi nai r es
2. 2. 3 Obst r uct i on Mar ker Lumi nai r es
2. 3 LI GHT SOURCES
2. 3. 1 LED Li ght Sour ces
2. 4 LED DRI VERS
2. 4. 1 Remot e LED Dr i ver s
2. 5 LI GHTI NG CONTROLS
2. 5. 1 Syst em
2. 5. 1. 1 Rel ay Panel
2. 5. 1. 2 Di mmi ng Panel
2. 5. 1. 3 Net wor ked Li ght i ng Cont r ol Syst em
2. 5. 1. 4 Gat eway
2. 5. 2 Devi ces
2. 5. 2. 1 Ti me Cl ock
2. 5. 2. 2 Phot osensor s
2. 5. 2. 3 Mot i on Sensor s
2. 5. 2. 4 Li ght i ng Cont act or
2. 6 POLES
2. 6. 1 Al umi num Pol es
2. 6. 2 St eel Pol es
2. 6. 3 Wood Pol es
2. 6. 4 Fi ber gl ass Pol es
2. 6. 5 Concr et e Pol es
2. 6. 5. 1 St eel Rei nf or ci ng
2. 6. 5. 2 Tensi oned Rei nf or ci ng
2. 6. 5. 3 Coat i ng and Sl eeves f or Rei nf or ci ng Member s
2. 6. 5. 4 St r engt h Requi r ement
2. 6. 5. 5 Shaf t Pr epar at i on
2. 6. 6 Br acket s and Suppor t s
2. 6. 7 Pol e Foundat i ons
2. 7 EQUI PMENT I DENTI FI CATI ON
2. 7. 1 Manuf act ur er ' s Namepl at e
2. 7. 2 Label s
2. 8 FACTORY APPLI ED FI NI SH
PART 3 EXECUTI ON
3. 1 I NSTALLATI ON
3. 1. 1 Lumi nai r es
3. 1. 2 LED Dr i ver s
3. 1. 2. 1 Remot e LED Dr i ver s
3. 1. 3 Fi el d- Appl i ed Pai nt i ng
3. 1. 4 Wood Pol es
3. 1. 5 Concr et e Pol es
3. 1. 6 Fi ber gl ass Pol es
3. 1. 7 Al umi num and St eel Pol es
3. 1. 8 Pol e Set t i ng
3. 1. 9 Li ght i ng Cont r ol s
3. 1. 9. 1 Phot osensor s
3. 1. 9. 2 Mot i on Sensor s
3. 1. 10 Gr oundi ng
3. 2 FI ELD QUALI TY CONTROL
SECTI ON 26 56 00 Page 2
3. 2. 1 Test s
3. 2. 1. 1 Li ght i ng Cont r ol Ver i f i cat i on Test
3. 3 CLOSEOUT ACTI VI TI ES
3. 3. 1 Tr ai ni ng
3. 3. 1. 1 Mai nt enance St af f Tr ai ni ng
3. 3. 1. 2 End- User Tr ai ni ng
- - End of Sect i on Tabl e of Cont ent s - -
SECTI ON 26 56 00 Page 3
USACE / NAVFAC / AFCEC UFGS- 26 56 00 ( August 2021)
Pr epar i ng Act i v i t y: NAVFAC Super sedi ng UFGS- 26 56 00 ( May 2020)
UNI FI ED FACI LI TI ES GUI DE SPECI FI CATI ONS
Ref er ences ar e i n agr eement wi t h UMRL dat ed Apr i l 2024
SECTI ON 26 56 00
EXTERI OR LI GHTI NG
08/ 21
NOTE: Thi s gui de speci f i cat i on cover s l i ght i ng and l i ght i ng cont r ol syst em r equi r ement s f or ext er i or i nst al l at i ons.
Thi s speci f i cat i on does not cover al l possi bl e met hods or r equi r ement s f or ext er i or l i ght i ng;
t her ef or e, desi gner shoul d add speci al i nf or mat i on r equi r ed t o sui t a speci f i c pr oj ect . I ndust r y publ i cat i ons exi st t o ai d t he desi gner i n choosi ng t he best l i ght i ng syst em f or t he pr oj ect .
Publ i cat i ons i ncl ude, but ar e not l i mi t ed t o, t he I l l umi nat i ng Engi neer i ng Soci et y ( I ES) ' Li ght i ng Handbook, 10t h Edi t i on' and RP- 8, ' Recommended Pr act i ce f or Roadway Li ght i ng. '
Adher e t o UFC 1- 300- 02 Uni f i ed Faci l i t i es Gui de Speci f i cat i ons ( UFGS) For mat St andar d when edi t i ng t hi s gui de speci f i cat i on or pr epar i ng new pr oj ect speci f i cat i on sect i ons. Edi t t hi s gui de speci f i cat i on f or pr oj ect speci f i c r equi r ement s by addi ng, del et i ng, or r evi s i ng t ext . For br acket ed i t ems, choose appl i cabl e i t em( s) or i nser t appr opr i at e i nf or mat i on.
Remove i nf or mat i on and r equi r ement s not r equi r ed i n r espect i ve pr oj ect , whet her or not br acket s ar e pr esent .
Comment s, suggest i ons and r ecommended changes f or t hi s gui de speci f i cat i on ar e wel come and shoul d be submi t t ed as a Cr i t er i a Change Request ( CCR) .
NOTE: For suppl ement al i nf or mat i on r egar di ng UFGS 26 56 00, i ncl udi ng PDF and CAD downl oads of l umi nai r e pl at es, go t o:
ht t p: / / www. wbdg. or g/ f f c/ dod/ uni f i ed- f aci l i t i es- gui de- speci f i cat i ons- uf gs/ uf gs- 26- 56- 00
SECTI ON 26 56 00 Page 4
NOTE: Thi s sect i on cont ai ns t he f ol l owi ng l umi nai r e pl at es ( al so r ef er r ed t o as ' sket ches' or ' det ai l s ' . ) These ar e avai l abl e i n met r i c ( SI ) and U. S. Cust omar y ( I P) syst em di mensi ons. Pl at e t i t l es and st y l e number s ar e unchanged f or bot h uni t s.
Do not i ncl ude l i s t of pl at es, of pl at es t hemsel ves, i n pr oj ect speci f i cat i ons. Use l umi nai r e pl at es as det ai l s on dr awi ngs whenever possi bl e. I f speci al f eat ur es ar e r equi r ed, do not modi f y pl at es, but i ndi cat e t hese changes as not es i n l umi nai r e schedul e. The " XL" st y l e number s and dat es must r emai n on t he dr awi ng det ai l s. I f addi t i onal l umi nai r e t ypes ar e needed t hat ar e not cover ed i n pl at es, pr ovi de addi t i onal sket ches or det ai l s on dr awi ngs, but do not l abel as XL pl at e t ype.
PLATE
NUMBER
Ti t l e
XL- 1 LED ROADWAY LUMI NAI RE
XL- 2 LED AREA LUMI NAI RE
XL- 3 LED PEDESTRI AN LUMI NAI RE
XL- 4 LED I LLUMI NATED BOLLARD
XL- 5 LED PARKI NG LOT LUMI NAI RE
XL- 6 LED PARKI NG GARAGE LUNI NAI RE
XL- 7 LED EXTERI OR STEP LI GHT
XL- 8 LED EXTERI OR WALL SCONCE
XL- 9 LED EXTERI OR DECORATI VE WALL SCONCE
XL- 10 LED WALL PACK
XL- 11 EXTERI OR RECESSED DOWNLI GHT
XL- 12 LED LI NEAR WALL WASH
XL- 13 AVI ATI ON OBSTRUCTI ON LUMI NAI RE
XL- 14 LED FLOOD LUMI NAI RE
XL- 15 DI RECT- SET FI BERGLASS POLE
XL- 16 DI RECT- SET CONCRETE POLE
XL- 17 DI RECT- SET STEEL/ ALUMI NUM POLE
SECTI ON 26 56 00 Page 5
PLATE
NUMBER
Ti t l e
XL- 18 ANCHOR BASE FI BERGLASS POLE
XL- 19 ANCHOR BASE STEEL/ ALUMI NUM POLE
XL- 20 ANCHOR BASE CONCRETE POLE
XL- 21 ANCHOR BASE POLE FOUNDATI ON
XL- 22 DI RECT SET POLE GROUNDI NG DETAI L
XL- 23 LUMI NAI RE MOUNTI NG ARM DETAI LS
XL- 24 LUMI NAI RE MOUNTI NG ARM DETAI LS
XL- 25 LUMI NAI RE MOUNTI NG BRACKET DETAI LS
XL- 26 LUMI NAI RE MOUNTI NG BRACKET DETAI LS
NOTE: Do not i ncl ude t hi s i ndex i n pr oj ect speci f i cat i on.
NOTE: I ncl ude t he f ol l owi ng i nf or mat i on on t he pr oj ect dr awi ngs:
1. Lumi nai r e schedul e i ndi cat i ng l umi nai r e symbol ;
l umi nai r e t ype; XL pl at e number and t ype desi gnat i on; l i ght sour ce; vol t age; i nput wat t s;
del i ver ed l umen out put ; ef f i cacy; CCT; CRI ; LED dr i ver ; di mmi ng; mount i ng; NEMA di st r i but i on i f appl i cabl e; BUG r at i ng i f appl i cabl e; and any ot her appl i cabl e opt i ons or not es.
2. Locat i on and mount i ng hei ght of al l l umi nai r es and r equi r ed accessor i es such as, mount i ng br acket s and pol es.
3. Ref er enced XL pl at e number or det ai l ( i f no XL pl at e i s avai l abl e) f or each l umi nai r e t ype pr ovi ded.
4. Al l accessor i es r equi r ed, such as mount i ng har dwar e, mount i ng br acket s, ar ms, NEMA 7- pi n r ecept acl es, r emot e dr i ver s, emer gency back- up, sensor s and cont r ol equi pment , and cent r al emer gency syst em component s.
5. Cont r ol st r at egy descr i pt i on f or each gi ven ar ea.
6. Ext ent and l ocat i on of t he wor k t o be accompl i shed wi t h wi r i ng and equi pment necessar y f or
SECTI ON 26 56 00 Page 6 a compl et e i nst al l at i on.
NOTE: Demol i t i on wor k t hat i nvol ves di sposal of f l uor escent and HI D l i ght sour ces and bal l ast s wi l l r equi r e t he use of Sect i on 02 84 16 HANDLI NG OF LI GHTI NG BALLASTS AND LAMPS CONTAI NI NG PCBs AND
MERCURY.
PART 1 GENERAL
1. 1 REFERENCES
NOTE: Thi s par agr aph i s used t o l i s t t he publ i cat i ons c i t ed i n t he t ext of t he gui de speci f i cat i on. The publ i cat i ons ar e r ef er r ed t o i n t he t ext by basi c desi gnat i on onl y and l i s t ed i n t hi s par agr aph by or gani zat i on, desi gnat i on, dat e, and t i t l e.
Use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e when you add a Ref er ence I dent i f i er ( RI D) out si de of t he Sect i on' s Ref er ence Ar t i c l e t o aut omat i cal l y pl ace t he r ef er ence i n t he Ref er ence Ar t i c l e. Al so use t he Ref er ence Wi zar d' s Check Ref er ence f eat ur e t o updat e t he i ssue dat es.
Ref er ences not used i n t he t ext wi l l aut omat i cal l y be del et ed f r om t hi s sect i on of t he pr oj ect speci f i cat i on when you choose t o r econci l e r ef er ences i n t he publ i sh pr i nt pr ocess.
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
ALLI ANCE FOR TELECOMMUNI CATI ONS I NDUSTRY SOLUTI ONS ( ATI S)
ATI S ANSI O5. 1 ( 2017) Wood Pol es - - Speci f i cat i ons & Di mensi ons
AMERI CAN ASSOCI ATI ON OF STATE HI GHWAY AND TRANSPORTATI ON OFFI CI ALS
( AASHTO)
AASHTO LTS ( 2013; Er r at a 2013) St andar d Speci f i cat i ons f or St r uct ur al Suppor t s f or Hi ghway Si gns, Lumi nai r es and Tr af f i c Si gnal s
AMERI CAN SOCI ETY OF CI VI L ENGI NEERS ( ASCE)
ASCE 7- 16 ( 2017; Er r at a 2018; Supp 1 2018) Mi ni mum Desi gn Loads and Associ at ed Cr i t er i a f or Bui l di ngs and Ot her St r uct ur es
SECTI ON 26 56 00 Page 7
AMERI CAN WOOD PROTECTI ON ASSOCI ATI ON ( AWPA)
AWPA U1 ( 2023) Use Cat egor y Syst em: User Speci f i cat i on f or Tr eat ed Wood
ASTM I NTERNATI ONAL ( ASTM)
ASTM A123/ A123M ( 2017) St andar d Speci f i cat i on f or Zi nc ( Hot - Di p Gal vani zed) Coat i ngs on I r on and St eel Pr oduct s
ASTM A153/ A153M ( 2023) St andar d Speci f i cat i on f or Zi nc Coat i ng ( Hot - Di p) on I r on and St eel Har dwar e
ASTM B108/ B108M ( 2019) St andar d Speci f i cat i on f or Al umi num- Al l oy Per manent Mol d Cast i ngs
ASTM B117 ( 2019) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us
ASTM C1089 ( 2013) St andar d Speci f i cat i on f or Spun Cast Pr est r essed Concr et e Pol es
ASTM G154 ( 2023) St andar d Pr act i ce f or Oper at i ng Fl uor escent Ul t r avi ol et ( UV) Lamp Appar at us f or Exposur e of Mat er i al s
CALI FORNI A ENERGY COMMI SSI ON ( CEC)
CEC Ti t l e 24 ( 2016) Bui l di ng Ener gy Ef f i c i ency St andar ds For Resi dent i al and Nonr esi dent i al Bui l di ngs
EUROPEAN UNI ON ( EU)
Di r ect i ve 2011/ 65/ EU ( 2011) Rest r i ct i on of t he Use of Cer t ai n Hazar dous Subst ances i n El ect r i cal and El ect r oni c Equi pment
I LLUMI NATI NG ENGI NEERI NG SOCI ETY ( I ES)
ANSI / I ES LM- 79 ( 2019) Appr oved Met hod: El ect r i cal and Phot omet r i c Measur ement s of Sol i d St at e Li ght i ng Pr oduct s
ANSI / I ES LM- 80 ( 2020) Appr oved Met hod: Measur i ng Lumi nous Fl ux and Col or Mai nt enance of LED Packages, Ar r ays and Modul es
ANSI / I ES LP- 11 ( 2020) Li ght i ng Pr act i ce: Envi r onment al Consi der at i ons f or Out door Li ght i ng
ANSI / I ES LS- 1 ( 2020) Li ght i ng Sci ence: Nomencl at ur e and Def i ni t i ons f or I l l umi nat i ng Engi neer i ng
ANSI / I ES RP- 8 ( 2018; Addenda 1 2020; Er r at a 1- 2 2021) Recommended Pr act i ce f or Desi gn and Mai nt enance of Roadway and Par ki ng
SECTI ON 26 56 00 Page 8
Faci l i t y Li ght i ng
ANSI / I ES TM- 15 ( 2020) Techni cal Memor andum: Lumi nai r e Cl assi f i cat i on Syst em f or Out door Lumi nai r es
ANSI / I ES TM- 21 ( 2021) Techni cal Memor andum: Pr oj ect i ng Long- Ter mLumi nous, Phot on, and Radi ant Fl ux Mai nt enance of LED Li ght Sour ces
I ES Li ght i ng Li br ar y I ES Li ght i ng Li br ar y
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE 100 ( 2000; Ar chi ved) The Aut hor i t at i ve Di ct i onar y of I EEE St andar ds Ter ms
I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)
ANSI C136. 3 ( 2020) Roadway and Ar ea Li ght i ng Equi pment
- Lumi nai r e At t achment s
ANSI C136. 13 ( 2020) Roadway and Ar ea Li ght i ng Equi pment
- Met al Br acket s f or Wood Pol es
ANSI C136. 21 ( 2014) Amer i can Nat i onal St andar d f or Roadway and Ar ea Li ght i ng Equi pment - Ver t i cal Tenons Used wi t h Post - Top- Mount ed Lumi nai r es
ANSI C136. 41 ( 2013) Roadway and Ar ea Li ght i ng Equi pment - Di mmi ng Cont r ol Bet ween an Ext er nal Locki ng Type Phot ocont r ol and Bal l ast or Dr i ver
NEMA 250 ( 2020) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)
NEMA ANSLG C78. 377 ( 2017) El ect r i c Lamps— Speci f i cat i ons f or t he Chr omat i c i t y of Sol i d St at e Li ght i ng Pr oduct s
NEMA C82. 77- 10 ( 2020) Har moni c Emi ssi on Li mi t s - Rel at ed Power Qual i t y Requi r ement s
NEMA C136. 10 ( 2023) Amer i can Nat i onal St andar d f or Roadway and Ar ea Li ght i ng Equi pment - Locki ng- Type Phot ocont r ol Devi ces and Mat i ng Recept acl es- - Physi cal and El ect r i cal I nt er changeabi l i t y and Test i ng
NEMA C136. 20 ( 2012; R 2021) Roadway and Ar ea Li ght i ng Equi pment - Fi ber Rei nf or ced Composi t e ( FRC) Li ght i ng Pol es
SECTI ON 26 56 00 Page 9
NEMA C136. 31 ( 2023) Roadway and Ar ea Li ght i ng Equi pment
- Lumi nai r e Vi br at i on
NEMA I CS 2 ( 2000; R 2020) I ndust r i al Cont r ol and Syst ems Cont r ol l er s, Cont act or s, and Over l oad Rel ays Rat ed 600 V
NEMA I CS 6 ( 1993; R 2016) I ndust r i al Cont r ol and Syst ems: Encl osur es
NEMA I EC 60529 ( 2004) Degr ees of Pr ot ect i on Pr ovi ded by Encl osur es ( I P Code)
NEMA SSL 1 ( 2016) El ect r oni c Dr i ver s f or LED Devi ces, Ar r ays, or Syst ems
NEMA SSL 3 ( 2011) Hi gh- Power Whi t e LED Bi nni ng f or Gener al I l l umi nat i on
NEMA WD 7 ( 2011; R 2016; R 2021) Occupancy Mot i on Sensor s St andar d
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 70 ( 2023; ERTA 7 2023; TI A 23- 15) Nat i onal El ect r i cal Code
U. S. DEPARTMENT OF AGRI CULTURE ( USDA)
RUS Bul l 1728F- 700 ( 2011) Speci f i cat i on f or Wood Pol es, St ubs, and Anchor Logs
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
47 CFR 15 Radi o Fr equency Devi ces
UNDERWRI TERS LABORATORI ES ( UL)
UL 773 ( 2016; Repr i nt Jul 2020) UL St andar d f or Saf et y Pl ug- I n, Locki ng Type Phot ocont r ol s f or Use wi t h Ar ea Li ght i ng
UL 773A ( 2016; Repr i nt Jan 2024) UL St andar d f or Saf et y Noni ndust r i al Phot oel ect r i c Swi t ches f or Li ght i ng Cont r ol
UL 916 ( 2015; Repr i nt Oct 2021) UL St andar d f or Saf et y Ener gy Management Equi pment
UL 924 ( 2016; Repr i nt Dec 2022) UL St andar d f or Saf et y Emer gency Li ght i ng and Power Equi pment
UL 1310 ( 2018; Repr i nt Jun 2022) UL St andar d f or Saf et y Cl ass 2 Power Uni t s
UL 1598 ( 2021; Repr i nt Jan 2024) UL St andar d f or Saf et y Lumi nai r es
SECTI ON 26 56 00 Page 10
UL 8750 ( 2015; Repr i nt Sep 2021) UL St andar d f or Saf et y Li ght Emi t t i ng Di ode ( LED) Equi pment f or Use i n Li ght i ng Pr oduct s
1. 2 RELATED REQUI REMENTS
NOTE: Sel ect appl i cabl e t r i - ser vi ce, Ar my, Navy, Ai r For ce, or NASA speci f i cat i on sect i on r ef er ence( s) .
For t he pur pose of t hi s document , ext er i or l umi nai r es i ncl ude l umi nai r es mount ed i n ext er i or envi r onment s t hat ar e not at t ached t o t he bui l di ng.
Lumi nai r es at t ached t o t he ext er i or of t he bui l di ng ar e speci f i ed i n Sect i on 26 51 00 I NTERI OR LI GHTI NG.
Mat er i al s not consi der ed t o be l umi nai r es, l umi nai r e accessor i es, or l i ght i ng equi pment ar e speci f i ed i n Sect i on( s) [ 33 71 02 UNDERGROUND
ELECTRI CAL DI STRI BUTI ON] [ 33 71 01. 00 40 OVERHEAD TRANSMI SSI ON AND
DI STRI BUTI ON] [ 33 71 01 OVERHEAD TRANSMI SSI ON AND DI STRI BUTI ON] .
Lumi nai r es and accessor i es i nst al l ed i n i nt er i or of bui l di ngs or at t ached t o t he ext er i or of a bui l di ng ar e speci f i ed i n Sect i on 26 51 00 I NTERI OR LI GHTI NG. Cyber secur i t y r equi r ement s ar e speci f i ed i n Sect i on 25 05 11. [ _____] CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS. Commi ssi oni ng r equi r ement s ar e speci f i ed i n Sect i on 01 91 00. 15 BUI LDI NG COMMI SSI ONI NG.
1. 3 DEFI NI TI ONS
a. Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons and on t he dr awi ngs must be as def i ned i n I EEE 100 and ANSI / I ES LS- 1.
b. For LED l umi nai r e l i ght sour ces, " Usef ul Li f e" i s t he oper at i ng hour s bef or e r eachi ng 70 per cent of t he i ni t i al r at ed l umen out put ( L70) wi t h no cat ast r ophi c f ai l ur es under nor mal oper at i ng condi t i ons. Thi s i s al so known as 70 per cent " Rat ed Lumen Mai nt enance Li f e" as def i ned i n ANSI / I ES LM- 80.
c. For LED l umi nai r es, " Lumi nai r e Ef f i cacy" ( LE) i s t he appr opr i at e measur e of ener gy ef f i c i ency, measur ed i n l umens/ wat t . Thi s i s gat her ed f r om LM- 79 dat a f or t he l umi nai r e, i n whi ch absol ut e phot omet r y i s used t o measur e t he l umen out put of t he l umi nai r e as one ent i t y, not t he sour ce separ at el y and t hen t he sour ce and housi ng t oget her .
d. Tot al Har moni c Di st or t i on ( THD) i s t he Root Mean Squar e ( RMS) of al l t he har moni c component s di v i ded by t he t ot al f undament al cur r ent .
e. The " Gr oundl i ne Sect i on" of wood pol es i s t hat por t i on of t he pol e bet ween 305 mm one f oot above, and 610 mm 2 f eet bel ow t he gr oundl i ne.
1. 4 SUBMI TTALS
NOTE: Revi ew Submi t t al Descr i pt i on ( SD) def i ni t i ons i n Sect i on 01 33 00 SUBMI TTAL PROCEDURES and edi t
SECTI ON 26 56 00 Page 11 t he f ol l owi ng l i s t , and cor r espondi ng submi t t al i t ems i n t he t ext , t o r ef l ect onl y t he submi t t al s r equi r ed f or t he pr oj ect . The Gui de Speci f i cat i on t echni cal edi t or s have cl assi f i ed t hose i t ems t hat r equi r e Gover nment appr oval , due t o t hei r compl exi t y or cr i t i cal i t y, wi t h a " G. " Gener al l y, ot her submi t t al i t ems can be r evi ewed by t he Cont r act or ' s Qual i t y Cont r ol Syst em. Onl y add a " G" t o an i t em i f t he submi t t al i s suf f i c i ent l y i mpor t ant or compl ex i n cont ext of t he pr oj ect .
For Ar my pr oj ect s, f i l l i n t he empt y br acket s f ol l owi ng t he " G" c l assi f i cat i on, wi t h a code of up t o t hr ee char act er s t o i ndi cat e t he appr ovi ng aut hor i t y. Codes f or Ar my pr oj ect s usi ng t he Resi dent Management Syst em ( RMS) ar e: " AE" f or Ar chi t ect - Engi neer ; " DO" f or Di st r i ct Of f i ce ( Engi neer i ng Di v i s i on or ot her or gani zat i on i n t he Di st r i ct Of f i ce) ; " AO" f or Ar ea Of f i ce; " RO" f or Resi dent Of f i ce; and " PO" f or Pr oj ect Of f i ce. Codes f ol l owi ng t he " G" t ypi cal l y ar e not used f or Navy and Ai r For ce pr oj ect s.
The " S" c l assi f i cat i on i ndi cat es submi t t al s r equi r ed as pr oof of compl i ance f or sust ai nabi l i t y Gui di ng Pr i nci pl es Val i dat i on or Thi r d Par t y Cer t i f i cat i on and as descr i bed i n Sect i on 01 33 00 SUBMI TTAL
PROCEDURES.
Choose t he f i r st br acket ed i t em f or Navy and Ai r For ce pr oj ect s, or choose t he second br acket ed i t em f or Ar my pr oj ect s.
NOTE: Lumi nai r e shop dr awi ngs ar e r equi r ed f or cust om l umi nai r es, l umi nai r es speci f i ed t o a speci f i c cust om l engt h, or l i near l umi nai r es wi t h l engt hs gr eat er t han 2. 5 met er s 8 f eet .
Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" or " S" c l assi f i cat i on. Submi t t al s not havi ng a " G" or " S" c l assi f i cat i on ar e [ f or Cont r act or Qual i t y Cont r ol appr oval . ] [ f or i nf or mat i on onl y. When used, a code f ol l owi ng t he " G" c l assi f i cat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . ] Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Lumi nai r e Dr awi ngs; G[ , [ _____] ]
Pol e Dr awi ngs; G[ , [ _____] ]
Cont r ol Syst em One- Li ne Di agr am; G[ , [ _____] ]
Sequence of Oper at i on f or Ext er i or Li ght i ng Cont r ol Syst em; G[ , SECTI ON 26 56 00 Page 12
SD- 03 Pr oduct Dat a
Lumi nai r es; G[ , [ _____] ]
Li ght Sour ces; G[ , [ _____] ]
LED Dr i ver s; G[ , [ _____] ]
Lumi nai r e War r ant y; G[ , [ _____] ]
Li ght i ng Cont r ol s War r ant y; G[ , [ _____] ]
Pol e War r ant y; G[ , [ _____] ]
Di mmi ng Panel ; G[ , [ _____] ]
Mot i on Sensor s; G[ , [ _____] ]
Phot osensor s; G[ , [ _____] ]
Ti me Cl ock; G[ , [ _____] ]
Li ght i ng Cont act or ; G[ , [ _____] ]
Pol es; G[ , [ _____] ]
Br acket s
Obst r uct i on Mar ker Lumi nai r es; G[ , [ _____] ]
[ SD- 04 Sampl es
Lumi nai r e Sampl es; G[ , [ _____] ]
] SD- 05 Desi gn Dat a
Lumi nai r e Desi gn Dat a; G[ , [ _____] ]
Phot omet r i c Pl an; G[ , [ _____] ]
SD- 06 Test Repor t s
ANSI / I ES LM- 79 Test Repor t ; G[ , [ _____] ]
ANSI / I ES LM- 80 Test Repor t ; G[ , [ _____] ]
ANSI / I ES TM- 21 Test Repor t ; G[ , [ _____] ]
Pr essur e Tr eat ed Wood Pol e Qual i t y; G[ , [ _____] ]
Test s f or Fi ber gl ass Pol es; G[ , [ _____] ]
SD- 08 Manuf act ur er ' s I nst r uct i ons
Pol es
SD- 10 Oper at i on and Mai nt enance Dat a
Li ght i ng Syst em, Dat a Package 5; G[ , [ _____] ]
SECTI ON 26 56 00 Page 13
Ext er i or Li ght i ng Cont r ol Syst em, Dat a Package 5; G[ , [ _____] ]
Mai nt enance St af f Tr ai ni ng Pl an; G[ , [ _____] ]
End- User Tr ai ni ng Pl an; G[ , [ _____] ]
1. 5 QUALI TY ASSURANCE
Dat a, dr awi ngs, and r epor t s must empl oy t he t er mi nol ogy, c l assi f i cat i ons and met hods pr escr i bed by t he I ES Li ght i ng Li br ar y as appl i cabl e, f or t he l i ght i ng syst em speci f i ed.
1. 5. 1 Dr awi ng Requi r ement s
1. 5. 1. 1 Lumi nai r e Dr awi ngs
NOTE: EPA and wei ght must be i ncl uded i n t he l umi nai r e dr awi ngs f or pol e- mount ed l umi nai r es.
Ai mi ng di agr ams ar e r equi r ed f or appl i cat i ons wi t h di r ect i onal l umi nai r es, such as adj ust abl e l andscape and t r ee l i ght i ng, spor t s l i ght i ng, and wal l wash appl i cat i ons.
I ncl ude di mensi ons, [ ef f ect i ve pr oj ect ed ar ea ( EPA) , wei ght , ] accessor i es, and i nst al l at i on and const r uct i on det ai l s. Phot omet r i c dat a, i ncl udi ng CRI , CCT, TM- 15- 11 BUG r at i ng, LED dr i ver t ype, [ ai mi ng di agr am, ] zonal l umen dat a, and candl epower di st r i but i on dat a per LM- 79 must accompany shop dr awi ngs.
1. 5. 1. 2 Pol e Dr awi ngs
NOTE: Wi nd l oads f or r oadway l umi nai r es ar e def i ned by AASHTO LTS. For ot her non- r oadway pol es, use
ASCE 7- 16.
I ncl ude di mensi ons, wi nd l oad det er mi ned i n accor dance wi t h [ AASHTO LTS] [ ASCE 7- 16] , pol e def l ect i on, pol e c l ass, and ot her appl i cabl e i nf or mat i on. [ For concr et e pol es, i ncl ude: sect i on and det ai l s t o i ndi cat e quant i t i es and posi t i on of pr est r essi ng st eel , spi r al st eel , i nser t s, and t hr ough hol es; i ni t i al pr est r essi ng st eel t ensi on; and concr et e st r engt hs at r el ease and at 28 days. ]
1. 5. 2 Lumi nai r e Desi gn Dat a
a. Pr ovi de di st r i but i on dat a accor di ng t o I ES cl assi f i cat i on t ype as def i ned i n I ES Li ght i ng Li br ar y and ANSI / I ES RP- 8.
b. B. U. G. r at i ng f or t he i nst al l ed posi t i on as def i ned by ANSI / I ES TM- 15 and shi el di ng as def i ned by ANSI / I ES RP- 8.
c. Pr ovi de saf et y cer t i f i cat i on and f i l e number f or t he l umi nai r e f ami l y. I ncl ude l i s t i ng, l abel i ng and i dent i f i cat i on i n accor dance wi t h NFPA 70 ( NEC) . Appl i cabl e t est i ng bodi es ar e det er mi ned by t he
SECTI ON 26 56 00 Page 14
US Occupat i onal Saf et y Heal t h Admi ni st r at i on ( OSHA) as Nat i onal l y Recogni zed Test i ng Labor at or i es ( NRTL) and i ncl ude: CSA ( Canadi an St andar ds Associ at i on) , ETL ( Edi son Test i ng Labor at or y) , and UL ( Under wr i t er s Labor at or i es) .
d. Pr ovi de l ong t er m l umen mai nt enance pr oj ect i ons f or each LED l umi nai r e i n accor dance wi t h ANSI / I ES TM- 21. Dat a used f or pr oj ect i ons must be obt ai ned f r om t est i ng i n accor dance wi t h ANSI / I ES LM- 80.
e. Pr ovi de wi nd l oadi ng cal cul at i ons f or l umi nai r es mount ed on pol es.
Wei ght and ef f ect i ve pr oj ect ed ar ea ( EPA) of l umi nai r es and mount i ng br acket s must not exceed maxi mum r at i ng of pol e as i nst al l ed i n par t i cul ar wi nd zone ar ea.
1. 5. 3 ANSI / I ES LM- 79 Test Repor t
Submi t t est r epor t on manuf act ur er ' s st andar d pr oduct i on model of speci f i ed l umi nai r e. Test i ng must be per f or med at t he same oper at i ng dr i ve cur r ent as speci f i ed l umi nai r e. I ncl ude al l appl i cabl e and r equi r ed dat a as out l i ned under " 14. 0 Test Repor t " i n ANSI / I ES LM- 79.
1. 5. 4 ANSI / I ES LM- 80 Test Repor t
Submi t r epor t on manuf act ur er ' s st andar d pr oduct i on LED l i ght sour ce ( package, ar r ay, or modul e) of speci f i ed l umi nai r e. Test i ng must be per f or med at t he same oper at i ng dr i ve cur r ent as speci f i ed l umi nai r e.
I ncl ude al l appl i cabl e and r equi r ed dat a as out l i ned under " 8. 0 Test Repor t " i n ANSI / I ES LM- 80.
1. 5. 5 ANSI / I ES TM- 21 Test Repor t
Submi t t est r epor t on manuf act ur er ' s st andar d pr oduct i on LED l i ght sour ce ( package, ar r ay or modul e) of speci f i ed l umi nai r e. Test i ng must be per f or med at t he same oper at i ng dr i ve cur r ent as speci f i ed l umi nai r e.
I ncl ude al l appl i cabl e and r equi r ed dat a, as wel l as r equi r ed i nt er pol at i on i nf or mat i on as out l i ned under " 7. 0 Repor t " i n ANSI / I ES TM- 21.
1. 5. 6 Test s f or Fi ber gl ass Pol es
a. Ul t r avi ol et r esi st ance t est s: Per f or m accor di ng t o ASTM G154 usi ng a UV- B l i ght sour ce havi ng a 313 nanomet er wavel engt h, oper at ed at 54 degr ees C 130 degr ees F, cycl i ng t he l i ght sour ce on f or 4 hour s and of f f or 4 hour s f or a t ot al t est per i od of 1500 hour s mi ni mum wi t h t he f ol l owi ng r esul t s:
Fi ber exposur e: None
Cr azi ng: None
Checki ng: None
Chal ki ng: None
Col or : May dul l s l i ght l y
b. Fl exur al st r engt h and def l ect i on t est : Test l oadi ng must be as a cant i l ever beam wi t h pol e but t as f i xed end and a f or ce s i mul at i ng wi nd l oad at t he f r ee end.
SECTI ON 26 56 00 Page 15
1. 5. 7 Pr essur e Tr eat ed Wood Pol e Qual i t y
Ensur e t he qual i t y of pr essur e t r eat ed wood pol es. Fur ni sh an i nspect i on r epor t ( f or wood pol es) of an i ndependent i nspect i on agency, appr oved by t he Cont r act i ng Of f i cer , st at i ng t hat of f er ed pr oduct s compl y wi t h AWPA U1 and RUS Bul l 1728F- 700 st andar ds. The RUS appr oved Qual i t y Mar k " WQC" on each pol e wi l l be accept ed, i n l i eu of i nspect i on r epor t s, as evi dence of compl i ance wi t h appl i cabl e AWPA t r eat ment st andar ds.
[ 1. 5. 8 Phot omet r i c Pl an
NOTE: Requi r e phot omet r i c pl ans and desi gn cr i t er i a t o be submi t t ed i f t he pr oj ect i s a Desi gn- Bui l d pr oj ect and wi l l not have an engi neer or desi gner pr oduci ng phot omet r i cs dur i ng desi gn.
Sel ect ANSI / I ES RP- 8 f or r oadway and par ki ng f aci l i t i es phot omet r i c pl ans and ANSI / I ES LP- 11 f or al l ot her ext er i or envi r onment scenar i os.
For r oadway desi gns, r equi r e aver age mai nt ai ned l umi nance.
For [ r oadways] [ par ki ng l ot s] [ i nt er sect i ons] [ _____] i ncl ude comput er - gener at ed phot omet r i c anal ysi s of t he " desi gned t o" val ues i n accor dance wi t h [ ANSI / I ES RP- 8] [ ANSI / I ES LP- 11] f or t he " end of usef ul l i f e" of t he l umi nai r e i nst al l at i on usi ng a l i ght l oss f act or of 0. 81.
Pr ovi de phot omet r i c pl ans t hat meet cr i t er i a i n t he Basi s of Desi gn i n t he pr oj ect pl ans. I ncl ude t he f ol l owi ng i n t he submi t t al :
a. Hor i zont al i l l umi nance measur ement s at f i ni shed gr ade, t aken at a maxi mum gr i d s i ze of 3050 mm 10 f eet by 3050 mm 10 f eet .
b. Ver t i cal i l l umi nance measur ement s at 1500 mm 5 f eet above f i ni shed gr ade at al l s i dewal ks and cr osswal ks, t aken at a maxi mum of 3050 mm 10 f eet .
c. Mi ni mum and maxi mum l ux f oot candl e l evel s.
d. Aver age mai nt ai ned l ux f oot candl e l evel .
e. Maxi mum t o mi ni mum r at i o f or hor i zont al i l l umi nance onl y.
[ f . Aver age mai nt ai ned l umi nance i n candel a per squar e met er .
] ] 1. 5. 9 Test Labor at or i es
Test l abor at or i es f or t he ANSI / I ES LM- 79 and ANSI / I ES LM- 80 t est r epor t s must be one of t he f ol l owi ng:
a. Nat i onal Vol unt ar y Labor at or y Accr edi t at i on Pr ogr am ( NVLAP) accr edi t ed f or sol i d- st at e l i ght i ng t est i ng as par t of t he Ener gy- Ef f i c i ent Li ght i ng Pr oduct s l abor at or y accr edi t at i on pr ogr am.
b. One of t he qual i f i ed l abs l i s t ed on t he Depar t ment of Ener gy - Ener gy Ef f i c i ency & Renewabl e Ener gy, Sol i d- St at e Li ght i ng web si t e.
SECTI ON 26 56 00 Page 16
c. One of t he EPA- Recogni zed Labor at or i es l i s t ed at f or LM- 80 t est i ng.
1. 5. 10 Regul at or y Requi r ement s
Equi pment , mat er i al s, i nst al l at i on, and wor kmanshi p must be i n accor dance wi t h t he mandat or y pr ovi s i ons of NFPA 70 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed or i ndi cat ed. Pr ovi de l umi nai r es and assembl ed component s t hat ar e appr oved by and bear t he l abel of UL f or t he appl i cabl e l ocat i on and condi t i ons unl ess ot her wi se speci f i ed.
1. 5. 11 St andar d Pr oduct s
Pr ovi de mat er i al s and equi pment t hat ar e pr oduct s of manuf act ur er s r egul ar l y engaged i n t he pr oduct i on of such pr oduct s whi ch ar e of equal mat er i al , desi gn and wor kmanshi p. Pr oduct s must have been i n sat i sf act or y commer ci al or i ndust r i al use f or s i x mont hs pr i or t o bi d openi ng. The si x- mont h per i od must i ncl ude appl i cat i ons of equi pment and mat er i al s under s i mi l ar c i r cumst ances and of s i mi l ar s i ze. The pr oduct must have been on sal e on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es dur i ng t he si x- mont h per i od. Wher e t wo or mor e i t ems of t he same cl ass of equi pment ar e r equi r ed, t hese i t ems must be pr oduct s of a s i ngl e manuf act ur er ; however , t he component par t s of t he i t em need not be t he pr oduct s of t he same manuf act ur er unl ess st at ed i n t hi s sect i on.
1. 5. 11. 1 Al t er nat i ve Qual i f i cat i ons
Pr oduct s havi ng l ess t han a s i x- mont h f i el d ser vi ce r ecor d wi l l be accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on f or not l ess t han 6000 hour s, excl usi ve of t he manuf act ur er s ' f act or y or l abor at or y t est s, i s f ur ni shed.
1. 5. 11. 2 Mat er i al and Equi pment Manuf act ur i ng Dat e
Do not use pr oduct s manuf act ur ed mor e t han si x mont hs pr i or t o dat e of del i ver y t o s i t e, unl ess speci f i ed ot her wi se.
1. 6 DELI VERY, STORAGE, AND HANDLI NG OF POLES
1. 6. 1 Al umi num Pol es
Do not st or e pol es on gr ound. Suppor t pol es so t hey ar e at l east 305 mm one f oot above gr ound l evel and gr owi ng veget at i on. Do not r emove f act or y- appl i ed pol e wr appi ngs unt i l j ust bef or e i nst al l i ng pol e.
1. 6. 2 St eel Pol es
Do not st or e pol es on gr ound. Suppor t pol es so t hey ar e at l east 305 mm one f oot above gr ound l evel and gr owi ng veget at i on. Do not r emove f act or y- appl i ed pol e wr appi ngs unt i l j ust bef or e i nst al l i ng pol e.
1. 6. 3 Wood Pol es
Do not st or e pol es on gr ound. St ack pol es st or ed f or mor e t han 2 weeks on decay- r esi st i ng ski ds ar r anged t o suppor t t he pol es wi t hout pr oduci ng not i ceabl e di st or t i on. St or e pol es t o per mi t f r ee c i r cul at i on of ai r ; t he bot t om pol es i n t he st ack must be at l east 305 mm one f oot above gr ound l evel and gr owi ng veget at i on. Do not per mi t decayed or decayi ng wood t o
SECTI ON 26 56 00 Page 17 r emai n under neat h st or ed pol es. Do not dr ag t r eat ed pol es al ong t he gr ound. Do not use pol e t ongs, cant hooks, and ot her poi nt ed t ool s capabl e of pr oduci ng i ndent at i on mor e t han 25 mm one i nch i n dept h i n handl i ng t he pol es. Do not appl y t ool s t o t he gr oundl i ne sect i on of any pol e.
1. 6. 4 Fi ber gl ass Pol es
Do not st or e pol es on gr ound. Suppor t pol es so t hey ar e at l east 305 mm one f oot above gr ound l evel and gr owi ng veget at i on. Do not r emove f act or y- appl i ed pol e wr appi ngs unt i l j ust bef or e i nst al l i ng pol e.
1. 6. 5 Concr et e Pol es
Do not st or e pol es on gr ound. Suppor t pol es so t hey ar e at l east 305 mm one f oot above gr ound l evel and gr owi ng veget at i on.
1. 7 WARRANTY
Suppor t al l equi pment i t ems by ser vi ce or gani zat i ons whi ch ar e r easonabl y conveni ent t o t he equi pment i nst al l at i on i n or der t o r ender sat i sf act or y ser vi ce t o t he equi pment on a r egul ar and emer gency basi s dur i ng t he war r ant y per i od of t he cont r act .
1. 7. 1 Lumi nai r e War r ant y
Pr ovi de and t r ansf er t o t he gover nment t he or i gi nal LED l umi nai r e manuf act ur er s st andar d commer ci al war r ant y f or each di f f er ent l umi nai r e manuf act ur er used i n t he pr oj ect .
a. Pr ovi de a wr i t t en f i ve year mi ni mum r epl acement war r ant y f or mat er i al , l umi nai r e f i ni sh, and wor kmanshi p. Pr ovi de wr i t t en war r ant y document t hat cont ai ns al l war r ant y pr ocessi ng i nf or mat i on needed, i ncl udi ng cust omer ser vi ce poi nt of cont act , whet her or not a r et ur n aut hor i zat i on number i s r equi r ed, r et ur n shi ppi ng i nf or mat i on, and cl osest r et ur n l ocat i on t o t he l umi nai r e l ocat i on.
( 1) Fi ni sh war r ant y must i ncl ude f ai l ur e and subst ant i al det er i or at i on such as bl i st er i ng, cr acki ng, peel i ng, chal k i ng, or f adi ng.
( 2) Mat er i al war r ant y must i ncl ude:
( a) Al l LED dr i ver s and i nt egr al cont r ol equi pment .
( b) Repl acement when mor e t han 15 per cent of LED sour ces i n any l i ght bar or subassembl y( s) ar e def ect i ve, non- st ar t i ng, or oper at i ng bel ow 70 per cent of speci f i ed l umen out put .
b. War r ant y per i od must begi n i n accor dance wi t h t he manuf act ur er ' s st andar d war r ant y st ar t i ng dat e.
c. Pr ovi de r epl acement s t hat ar e pr ompt l y shi pped, wi t hout char ge, t o t he usi ng Gover nment f aci l i t y poi nt of cont act and t hat ar e i dent i cal t o or an i mpr ovement upon t he or i gi nal equi pment . Al l r epl acement s must i ncl ude t est i ng of new component s and i nst al l at i on.
1. 7. 2 Li ght i ng Cont r ol s War r ant y
Pr ovi de and t r ansf er t o t he gover nment t he or i gi nal l i ght i ng cont r ol s
SECTI ON 26 56 00 Page 18 manuf act ur er s st andar d commer ci al war r ant y f or each di f f er ent l i ght i ng cont r ol s manuf act ur er used i n t he pr oj ect . War r ant y cover age must begi n f r om dat e of f i nal syst em commi ssi oni ng or t hr ee mont hs f r om dat e of del i ver y, whi chever i s t he ear l i est . War r ant y ser vi ce must be per f or med by a f act or y- t r ai ned engi neer or t echni c i an.
a. Unl ess ot her wi se not ed, pr ovi de a wr i t t en f i ve year mi ni mum war r ant y on t he compl et e syst em f or al l syst ems wi t h f act or y commi ssi oni ng.
Pr ovi de war r ant y t hat cover s 100 per cent of t he cost of any r epl acement par t s and ser vi ces r equi r ed over t he f i ve year s whi ch ar e di r ect l y at t r i but abl e t o t he pr oduct f ai l ur e. Fai l ur es i ncl ude, but ar e not l i mi t ed t o, t he f ol l owi ng:
( 1) Sof t war e: Fai l ur e of i nput / out put t o execut e swi t chi ng or di mmi ng commands.
( 2) Damage of el ect r oni c component s due t o t r ansi ent vol t age sur ges.
( 3) Fai l ur e of cont r ol devi ces, i ncl udi ng but not l i mi t ed t o phot osensor s and mot i on sensor s.
b. Pr ovi de a wr i t t en f i ve year mi ni mum war r ant y on al l i nput devi ces agai nst def ect i n wor kmanshi p or mat er i al s pr ovi ded by devi ce manuf act ur er .
c. Pr ovi de a wr i t t en f i ve year mi ni mum war r ant y on al l cont r ol component s at t ached t o l umi nai r es agai nst def ect i n wor kmanshi p or mat er i al s.
1. 7. 3 Pol e War r ant y
NOTE: Thr ee year pol e war r ant y i s pr ef er r ed.
Sel ect one year when t hr ee year s i s not avai l abl e.
Pr ovi de and t r ansf er t o t he gover nment t he or i gi nal pol e manuf act ur er s st andar d commer ci al war r ant y f or each di f f er ent pol e manuf act ur er used i n t he pr oj ect . War r ant y cover age must begi n f r om dat e of f i nal syst em commi ssi oni ng or t hr ee mont hs f r om dat e of del i ver y, whi chever i s t he ear l i est . Pr ovi de a wr i t t en [ 3] [ one] year mi ni mum r epl acement war r ant y f or mat er i al , l umi nai r e f i ni sh, and wor kmanshi p. War r ant y ser vi ce must be per f or med by a f act or y- t r ai ned engi neer or t echni c i an.
1. 8 OPERATI ON AND MAI NTENANCE MANUALS
1. 8. 1 Li ght i ng Syst em
Pr ovi de oper at i on and mai nt enance manual s f or t he l i ght i ng syst em i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA t hat pr ovi de basi c dat a r el at i ng t o t he desi gn, oper at i on, and mai nt enance of t he l i ght i ng syst em. Addi t i onal O&M Manual r equi r ement s f or t he Ar my ar e pr ovi ded i n Sect i on 01 78 24. 00 10 FACI LI TY DATA REQUI REMENTS. Addi t i onal r equi r ement s f or t he Navy ar e pr ovi ded i n Sect i on 01 78 24. 00 20 FACI LI TY DATA WORKBOOK ( FDW) . I ncl ude t he f ol l owi ng:
a. Manuf act ur er s ' oper at i ng and mai nt enance manual s.
b. Lumi nai r e shop dr awi ngs f or modi f i ed and cust om l umi nai r es.
SECTI ON 26 56 00 Page 19
c. Lumi nai r e Manuf act ur er s ' st andar d commer ci al war r ant y i nf or mat i on as speci f i ed i n par agr aph LUMI NAI RE WARRANTY.
1. 8. 2 Ext er i or Li ght i ng Cont r ol Syst em
Pr ovi de oper at i on and mai nt enance manual s f or t he ext er i or l i ght i ng cont r ol syst em i n accor dance wi t h Sect i on 01 78 23 OPERATI ON AND MAI NTENANCE DATA t hat pr ovi de basi c dat a r el at i ng t o t he desi gn, oper at i on, and mai nt enance of t he ext er i or l i ght i ng cont r ol syst em.
I ncl ude t he f ol l owi ng:
a. Cont r ol Syst em One- Li ne Di agr am
b. Pr oduct dat a f or al l devi ces, i ncl udi ng i nst al l at i on and pr ogr ammi ng i nst r uct i ons.
c. Tr ai ni ng mat er i al s, such as v i deos or i n- dept h manual s, t hat cover basi c oper at i on of t he l i ght i ng cont r ol syst em and i nst r uct i ons on modi f y i ng t he cont r ol syst em. Tr ai ni ng mat er i al s must i ncl ude cal i br at i on, adj ust ment , t r oubl eshoot i ng, mai nt enance, r epai r , and r epl acement .
[ d. Mot i on sensor cover age l ayout .
] PART 2 PRODUCTS
2. 1 PRODUCT COORDI NATI ON
2. 2 LUMI NAI RES
NOTE: Onl y r equi r e t he acqui s i t i on of sampl es f or l umi nai r e i nst al l at i ons t hat war r ant mock- ups, such as wal l gr azi ng uni que mat er i al s, or f or appl i cat i ons wher e aest het i cs ar e of hi gh pr i or i t y.
UL 1598, NEMA C82. 77- 10. Pr ovi de l umi nai r es as i ndi cat ed i n t he l umi nai r e schedul e and XL pl at es or det ai l s on pr oj ect pl ans, compl et e wi t h l i ght sour ce, wat t age, and l umen out put i ndi cat ed. Al l l umi nai r es of t he same t ype must be pr ovi ded by t he same manuf act ur er . Lumi nai r es must be speci f i cal l y desi gned f or use wi t h t he LED dr i ver and l i ght sour ce pr ovi ded.
[ 2. 2. 1 Lumi nai r e Sampl es
NOTE: Onl y r equi r e t he acqui s i t i on of sampl es f or l umi nai r e i nst al l at i ons t hat war r ant mock- ups, such as wal l gr azi ng uni que mat er i al s, f or cust om l umi nai r es, or f or appl i cat i ons wher e aest het i cs ar e of hi gh pr i or i t y.
Submi t one sampl e of each l umi nai r e t ype [ _____] , compl et e wi t h l i ght sour ce and LED dr i ver r at ed f or 120 V oper at i on, and 2 met er s 6 f eet pi gt ai l wi t h 3- pr ong Edi son pl ug. Sampl e wi l l be r et ur ned t o t he Cont r act or f or i nst al l at i on i n t he pr oj ect wor k.
SECTI ON 26 56 00 Page 20
] 2. 2. 2 Lumi nai r es
NOTE: 40 degr ees C 104 degr ees F i s " st andar d" upper l evel r at i ng of most LED l umi nai r es. Choose hi gher 50 degr ees C 122 degr ees F r at i ng when an i nst al l at i on l ocat i on war r ant s a hi gher ambi ent t emper at ur e r at i ng and t he addi t i onal cost i t i ncur s.
Pr ovi de desi gn i nf or mat i on i ncl udi ng del i ver ed l umen out put , L70 l umen mai nt enance dat a, and l umi nai r e ef f i cacy i n l umi nai r e schedul e on pr oj ect pl ans.
UL 8750, ANSI / I ES LM- 79, ANSI / I ES LM- 80. For al l l umi nai r es, pr ovi de:
a. Compl et e syst em wi t h LED dr i ver s and l i ght sour ces.
b. Housi ng const r uct ed of non- cor r osi ve mat er i al s. Al l new al umi num housi ngs must be anodi zed or powder - coat ed. Al l new st eel housi ngs must be t r eat ed t o be cor r osi on r esi st ant .
c. ANSI / I ES TM- 21, ANSI / I ES LM- 80. Mi ni mum L70 l umen mai nt enance val ue of 50, 000 hour s unl ess ot her wi se i ndi cat ed i n t he l umi nai r e schedul e.
Lumi nai r e dr i ve cur r ent val ue must be i dent i cal t o t hat pr ovi ded by t est dat a f or l umi nai r e i n quest i on.
d. Mi ni mum ef f i cacy as speci f i ed i n t he l umi nai r e schedul e. Theor et i cal model s of i ni t i al l amp l umens per wat t ar e not accept abl e. I f ef f i cacy val ues ar e not l i s t ed i n t he l umi nai r e schedul e, pr ovi de l umi nai r es t hat meet t he f ol l owi ng mi ni mum val ues:
Lumi nai r e St yl e Mi ni mum Lumi nai r e Ef f i cacy
Ar ea and Roadway ( pol e mount ed, ar m mount ed)
119 LPW
Pedest r i an Post - Top ( pol e mount ed, ar m mount ed)
97 LPW
Bol l ar d 45 LPW
Accent ( adj ust abl e l andscape, s i gn l i ght i ng) 35 LPW
Li near Accent ( f acade, wal l wash) 80 LPW
Ext er i or Wal l Sconce 50 LPW
St epl i ght 30 LPW
Par ki ng Gar age Lumi nai r e 113 LPW
e. Pr oduct r at ed f or oper at i on wi t hi n an ambi ent t emper at ur e r ange of mi nus 30 degr ees C mi nus 22 degr ees F t o[ 40 degr ees C 104 degr ees F] [ 50 degr ees C 122 degr ees F] .
f . UL l i s t ed f or wet l ocat i ons. [ Opt i cal compar t ment f or LED l umi nai r es must be seal ed and r at ed a mi ni mum of I P65 per NEMA I EC 60529. ]
SECTI ON 26 56 00 Page 21
g. I ES Li ght i ng Li br ar y. Li ght di st r i but i on and NEMA f i el d angl e c l assi f i cat i ons as i ndi cat ed i n l umi nai r e schedul e on pr oj ect pl ans.
h. Housi ng f i ni sh t hat i s baked- on enamel , anodi zed, or baked- on powder coat pai nt . Fi ni sh must be capabl e of sur vi v i ng ASTM B117 sal t f og envi r onment t est i ng f or 2500 hour s mi ni mum wi t hout bl i st er i ng or peel i ng.
i . LED dr i ver and l i ght sour ce package, ar r ay, or modul e ar e accessi bl e f or ser vi ce or r epl acement wi t hout r emoval or dest r uct i on of l umi nai r e.
j . ANSI / I ES TM- 15. Does not exceed t he BUG r at i ngs as l i s t ed i n t he l umi nai r e schedul e. I f BUG r at i ngs ar e not l i s t ed i n t he l umi nai r e schedul e, pr ovi de l umi nai r es t hat meet t he f ol l owi ng mi ni mum val ues f or each appl i cat i on and mount i ng condi t i ons:
Li ght i ng Appl i cat i on Mount i ng Condi t i ons BUG Rat i ng
Ar ea and Roadway Al l B3- U0- G3
Pedest r i an Post - Top Al l B2- U1- G1
Ext er i or Wal l Sconce Above 1. 2 met er s 4 f eet AFF B1- U0- G2
Ext er i or Wal l Sconce Bel ow or at 1. 2 met er s 4 f eet AFF B4- U0- G4
St epl i ght Above 1. 2 met er s 4 f eet AFF B1- U1- G2
St epl i ght Bel ow or at 1. 2 met er s 4 f eet AFF B4- U1- G4
Par ki ng Gar age Lumi nai r e Cei l i ng mount ed B4- U4- G3
k. Ful l y assembl ed and el ect r i cal l y t est ed pr i or t o shi pment f r om f act or y.
l . Fi ni sh col or i s as i ndi cat ed i n t he l umi nai r e schedul e or det ai l on t he pr oj ect pl ans.
m. Lenses const r uct ed of [ c l ear ] [ f r ost ed] t emper ed gl ass or UV- r esi st ant acr yl i c. [ Pr ovi de pol ycar bonat e vandal - r esi st ant l enses. ]
n. Al l f act or y el ect r i cal connect i ons ar e made usi ng cr i mp, l ocki ng, or l at chi ng st y l e connect or s. Twi st - st y l e wi r e nut s ar e not accept abl e.
o. NEMA C136. 31. Compl y wi t h 3G vi br at i on t est i ng.
[ p. Lumi nai r e ar m bol t s const r uct ed f r om 304 st ai nl ess st eel or z i nc- pl at ed st eel .
] [ q. Wi r i ng compar t ment on pol e- mount ed, st r eet and ar ea l umi nai r es i s accessi bl e wi t hout t he use of hand t ool s t o mani pul at e smal l scr ews, bol t s, or har dwar e.
] [ r . I ncor por at e modul ar el ect r i cal connect i ons, and const r uct l umi nai r es t o al l ow r epl acement of al l or any par t of t he opt i cs, heat s i nks, LED dr i ver s, sur ge suppr essor s and ot her el ect r i cal component s usi ng onl y a s i mpl e t ool , such as a manual or cor dl ess el ect r i c scr ewdr i ver .
SECTI ON 26 56 00 Page 22
] [ s. ANSI C136. 3. For al l r oadway and ar ea l umi nai r es, pr ovi de pr oduct s wi t h an i nt egr al t i l t adj ust ment of pl us or mi nus 5 degr ees t o al l ow t he uni t t o be l evel ed.
] [ 2. 2. 3 Obst r uct i on Mar ker Lumi nai r es
NOTE: Do not use LED obst r uct i on l umi nai r es f or Ai r For ce pr oj ect s. See Ai r For ce ETL 11- 29 " Use of Li ght - Emi t t i ng Di ode ( LED) Fi xt ur es i n Ai r f i el d Li ght i ng Syst ems on Ai r For ce I nst al l at i ons and Endur i ng/ Cont i ngency Locat i ons" f or mor e i nf or mat i on.
Pr ovi de obst r uct i on mar ker l umi nai r es f or f aci l i t i es as r equi r ed by t he FAA and i n accor dance wi t h Sect i on 26 56 20 AI RFI ELD AND HELI PORT LI GHTI NG
AND VI SUAL NAVI GATI ON AI DS.
] 2. 3 LI GHT SOURCES
NEMA ANSLG C78. 377, NEMA SSL 3. Pr ovi de t ype, l umen r at i ng, and wat t age as i ndi cat ed i n l umi nai r e schedul e on pr oj ect pl ans.
2. 3. 1 LED Li ght Sour ces
NOTE: A col or t emper at ur e of 3000 K i s st andar d f or most appl i cat i ons. When speci f i cal l y desi r ed by t he desi gner , a nomi nal col or t emper at ur e of 2700 K, 3500 K, or 4000 K may be sel ect ed. The hi ghest al l owabl e CCT i s 4100 K.
For ar ea and r oadway pr oj ect s wher e col or det ect i on i s not of hi gh i mpor t ance, sel ect a CRI of 70.
Pr ovi de LED l i ght sour ces t hat meet t he f ol l owi ng r equi r ement s:
a. NEMA ANSLG C78. 377. Emi t whi t e l i ght and have a nomi nal Cor r el at ed Col or Temper at ur e ( CCT) of [ 3000] [ 2700] [ 3500] [ 4000] Kel v i n.
b. Mi ni mum Col or Render i ng I ndex ( CRI ) of [ 80] [ 70] .
c. Di r ect i ve 2011/ 65/ EU. Rest r i ct i on of Hazar dous Subst ances ( RoHS) compl i ant .
d. Li ght sour ce col or consi st ency by ut i l i z i ng a bi nni ng t ol er ance wi t hi n a 4- st ep McAdam el l i pse.
2. 4 LED DRI VERS
NOTE: 40 degr ees C 104 degr ees F i s " st andar d" upper l evel r at i ng of most LED l umi nai r es. Choose hi gher 50 degr ees C 122 degr ees F r at i ng when an i nst al l at i on l ocat i on war r ant s a hi gher ambi ent t emper at ur e r at i ng and t he addi t i onal cost i t i ncur s.
Requi r e a di mmabl e dr i ver f or al l ext er i or l i ght i ng
SECTI ON 26 56 00 Page 23 t hat wi l l be r educed at cur f ew i n accor dance wi t h t he l i ght i ng cont r ol st r at egi es i n t he pr oj ect pl ans.
NEMA SSL 1, UL 1310. Pr ovi de LED Dr i ver s t hat ar e el ect r oni c, UL Cl ass 1 or Cl ass 2, const ant - cur r ent t ype and meet t he f ol l owi ng r equi r ement s:
a. The combi ned LED dr i ver and LED l i ght sour ce syst em i s gr eat er t han or equal t o t he mi ni mum l umi nai r e ef f i cacy val ues as l i s t ed i n t he l umi nai r e schedul e pr ovi ded.
b. Oper at e at a vol t age of [ 120- 277] [ 120] [ 277] vol t s at 50/ 60 her t z, wi t h i nput vol t age f l uct uat i ons of pl us or mi nus 10 per cent .
c. Power Fact or ( PF) gr eat er t han or equal t o 0. 90 at f ul l i nput power and acr oss speci f i ed di mmi ng r ange.
d. Maxi mum Tot al Har moni c Di st or t i on ( THD) l ess t han or equal t o 20 per cent at f ul l i nput power and acr oss speci f i ed di…
This is the start of the file's text. The full file is on GovTribe.