(TE 14) Container Standoff and Separation Distances.pdf
PDF 286 KB Posted
- Solicitation number
- W911SG25RA009
About this file
This document is a technical exhibit (TE 14) from UFC 4-010-01 detailing standards for container standoff and separation distances for Department of Defense (DoD) buildings. The document provides comprehensive guidelines for positioning trash containers and equipment enclosures, including specific requirements for:
- Standoff distances from building exteriors, with precise measurements for new and existing buildings
- Enclosure design specifications, such as maximum opening sizes of 6 inches (150 mm)
- Security measures to prevent unauthorized access to trash containers
- Alternative methods for mitigating potential explosive risks, including building hardening and enclosure design
- Recommendations for enclosure construction, including pitched tops for opaque enclosures and options for transparent vertical surfaces
The accompanying figures (B-1 and B-2) illustrate standoff distance configurations for scenarios with and without controlled perimeters, showing the placement of trash containers, parking areas, roadways, and different building types in relation to each other.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
(TE 14) CONTAINER STANDOFF AND SEPARATION DISTANCES
(From B-1 of UFC 4-010-01)
B-1.1 Standard 1. Standoff Distances.
The standoff distances apply to all new and existing (when triggered) DoD buildings required to comply with these standards. They address standoff distances to controlled perimeters, parking areas, roadways, and trash containers. The standoff distances are presented in Tables B-1 and B- 2 and illustrated in Figures B-1 and B-2 for new buildings and Figures B-3 and B-4 for existing buildings.
B-1.1.14 Location of Trash Containers.
For buildings that are required to comply with these standards, provide standoff distances from the nearest points of trash containers or trash container enclosures to the closest points on the building exteriors or inhabited portions of the buildings or to specific building components in accordance with the conventional construction standoff distance from trash containers in Tables B-1 and B-2. Where the applicable conventional construction standoff distance is not available, analyze the building and apply building hardening as necessary to mitigate the effects of the explosives indicated for trash containers in Table B-1 at the achievable standoff distance to the appropriate level of protection.
Alternatively, harden trash enclosures to mitigate the direct blast effects and secondary fragment effects of the explosive on the building if the applicable level of protection can be proven by analysis or testing.
As an additional alternative, if trash containers or enclosures are secured to preclude introduction of objects 6-inches (150 mm) or greater in height or width into them by unauthorized personnel, they may be located closer to the building as long as they do not violate the unobstructed space provisions of Standard 2. Openings in screening materials and gaps between the ground and screens or walls making up an enclosure must not be greater than 6 inches (150 mm).
B-1.2.3 Equipment and Trash Container Enclosures.
If walls or other screening devices with more than two sides are placed around trash containers that have been secured, hardened, or located in accordance with the paragraph above, entitled, “Location of Trash Containers” or around electrical, mechanical, or other equipment within the unobstructed space, enclose the trash containers or equipment on all four sides and the top.
Openings in screening materials and gaps between the ground and screens or walls making up an enclosure will not be greater than 6 inches (150 mm). Secure any surfaces of the enclosures that can be opened so that unauthorized personnel cannot gain access through them. Where opaque top enclosures are provided, they will have a pitch of at least 1 vertical to 2 horizontal to increase visibility of objects thrown onto them and to increase the likelihood that the objects will slide off. Alternatively, if the vertical surfaces of the enclosures are transparent and at least 7 feet (2.1 meters) high, a top enclosure is not required.