T.S. Kings Pointer - Asbestos Survey Report - Sept. 2020 (Rev. 1).pdf
PDF 6 MB Posted
- Solicitation number
- 6933A224Q000010
About this file
This document is an Asbestos Survey Report for the Training Ship T.S. Kings Pointer located at the United States Merchant Marine Academy (USMMA) in Kings Point, NY. The survey was conducted on September 29, 2020 by Castle Hill Associates (Prime) and BSI Services and Solutions Inc. (Sub) for the U.S. Maritime Administration.
The key findings are that two types of asbestos-containing materials were identified - red and tan linoleum sheet flooring in various locations throughout the vessel. The total quantity of asbestos-containing materials is 110 square feet. The materials are in good condition and the recommended response action is Operations and Maintenance (O&M) until their removal at the time of renovation. No other asbestos-containing materials were detected during the survey.
View the file
Other files
Show 40 more
Latest 50 of 65 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS SURVEY REPORT
FOR
T.S. KINGS POINTER
AT
USMMA
300 STEAMBOAT ROAD
KINGS POINT, NY 11024
CLIENT:
U.S. MARITIME ADMINISTRATION
DIVISION OF ATLANTIC OPERATIONS
7737 HAMPTON BLVD. – BLDG. 19, STE 300
NORFOLK, VA 23505
ORDER # 6933A220P000062
INSPECTION DATE:
SEPTEMBER 29, 2020
PRIME CONTRACTOR:
CASTLE HILL ASSOCIATES, LLC
218-A MECHANIC ST.
WATERVILLE, OH 43566
567-952-0212
T.S. KINGS POINTER - USMMA
SEPTEMBER 2020
TABLE OF CONTENTS
1. ASBESTOS INSPECTION
• PROJECT SUMMARY
• INSPECTION OVERVIEW & FINDINGS
• INSPECTOR INFORMATION
• ASBESTOS BACKGROUND INFORMATION
• ASBESTOS CONTAINING MATERIAL PHOTOS
• ASBESTOS MATERIALS ASSESSMENT
• HOMOGENEOUS SAMPLING AREA DESCRIPTIONS
• ASBESTOS BULK SAMPLING DATA & LAB RESULTS
APPENDICES
Appendix A – Asbestos Sample Location Plans
Appendix B – Asbestos Laboratory Reports & Chain of Custody
Appendix C – Consultant Certifications
Appendix D – Laboratory Certifications
PROJECT SUMMARY
On September 29, 2020, Castle Hill Associates (Prime) and BSI Services and Solutions Inc.
(Sub) performed an asbestos survey of the Training Ship T.S. Kings Pointer located at the United States Merchant Marine Academy (USMMA) in Kings Point, NY in accordance with the SOW issued by the U.S. Maritime Administration. The intent was to identify the asbestos containing materials inside and outside the vessel including mechanical systems, structural components, and finishes.
Prior to this inspection, an interview was conducted with the Chief Engineer along with records of previous asbestos testing. According to previous testing, it was determined that the only asbestos containing materials identified in the vessel were linoleum sheet flooring.
Some of this flooring was reported to have been replaced as part of previous renovations to the vessel.
Vessel Background Information
Builder: Atlantic Marine Inc. Fort George Island, Florida Operator: USMMA Launched: October 01, 1980 Class and type: Solid Rocket Booster Recovery Vessel, School Ship Tonnage: 484 GRT Length: 176 ft Beam: 37 ft Height: 72 ft Draft: 12 ft Propulsion: 2 x 1450 hp GM EMD 12-645E6A Diesel Engines, 2 x 450 hp Detroit Diesel 8V71 engine driving bow and stern thrusters.
Speed: 15 knots Complement: 50 (6 crew, 44 cadets) on day voyage less than 12 hours. On voyages over 12 hours (9 crew, 31 cadets).
INSPECTION OVERVIEW & FINDINGS
SAMPLING OVERVIEW
A total of 15 asbestos bulk samples and sample layers analyzed in accordance with the State of New York regulations as follows:
• PLM NYS 198.1 Friable (7 layers)
• PLM NYS 198.6 NOB (10 layers)
• TEM NYS 198.4 NOB (9 layers)
All samples were collected in and on the vessel of suspect asbestos containing materials. All bulk sampling of suspected asbestos was based upon the appearance, texture, and location of the material in accordance with US EPA NESHAP regulations. All bulk samples were analyzed utilizing current EPA and NYS methods for PLM (Polarized Light Microscopy) and TEM (Transmission Electron Microscopy) by EMSL Analytical, Inc. in Cinnaminson, NJ. The laboratory is accredited by the NIST, NVLAP program (National Institute of Standards and Technology, National Voluntary Laboratory Accreditation Program), is an American Industrial Hygiene Association (AIHA) accredited laboratory, and is certified by the State of New York as an asbestos bulk sample laboratory.
FINDINGS:
Asbestos Containing
Material Locations Quantity Condition
Red linoleum sheet flooring Top of stairs to lower deck off Galley
6 sf Good – No Damage
Tan linoleum sheet flooring Lower deck – Forward hallway and passage hall to Engine room
104 sf Good – No Damage
INSPECTOR INFORMATION
The project manager for the survey was Brett Brumbaugh of Castle Hill Associates who is an EPA trained asbestos inspector, management planner, and project designer since 1987. He is a Registered Environmental Property Assessor (REPA) and Certified Environmental and Safety Officer (CESCO) through the NREP (National Registry of Environmental Professionals).
The NY certified asbestos inspector for the survey was Ryan Baksh who is certified by the NY Dept. of Labor, license #16-05688.
Chief Highlight
ASBESTOS BACKGROUND INFORMATION
The term asbestos describes six naturally occurring fibrous minerals found in certain types of rock formations. The minerals chrysotile, amosite, and crocidolite have been most commonly used in building products such as floor tile, pipe insulation, boiler insulation, asbestos cement materials, roofing materials, and plasters. The minerals anthophyllite, actinolite, and tremolite are not frequently found in ACBM.
Intact and undisturbed ACBM do not pose a health risk. They may, however, become a health hazard if they are damaged, disturbed, or deteriorate over time and release fibers into the air. If released into the air, asbestos fibers may be inhaled. After prolonged or intense exposure, inhaled asbestos fibers may cause various types of lung disease. The health risks associated with asbestos exposure are greater for those who smoke.
REGULATORY BACKGROUND INFORMATION
Federal Regulations The United States Environmental Protection Agency (EPA), the Occupational Safety and Health Administration (OSHA), and delegated states are responsible for regulating environmental exposure and protecting workers from asbestos exposure. OSHA is responsible for the health and safety of workers who may be exposed to asbestos in connection with their jobs (Occupational Exposure to Asbestos; Title 29, Code of Federal Regulations (CFR) Parts 1910.1001 and 1926.1101). The EPA and state regulators are responsible for developing and enforcing regulations necessary to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health.
In 1979, EPA began an asbestos technical assistance program for building owners, environmental groups, contractors, and industry. In May 1982, EPA issued the first regulation intended to control asbestos in schools under the authority of the Toxic Substances Control Act (TSCA); this regulation is known as the Asbestos-in-Schools Rule.
Two EPA regulations govern asbestos: The Asbestos Hazard Emergency Response Act (AHERA) and the National Emission Standards for Hazardous Air Pollutants (NESHAP).
AHERA
In 1986, Congress enacted AHERA (Title 40, CFR Part 763) which mandated a regulatory program to address the asbestos hazards in schools. A part of AHERA deals with the mandatory training and accreditation of persons who perform certain types of asbestos-related work in schools.
Subsequently, in 1990 Congress amended AHERA to extend some of the training and accreditation requirements to persons performing such work in public and commercial buildings.
AHERA requires inspections of school buildings to determine the conditions of ACBM and preparation of management plans which recommend the best way to reduce the asbestos hazards. U.S.
government agencies have adopted many of the requirements of AHERA for surveys performed at federal facilities. The methods may include removal, encapsulation, enclosure, repair, and operations and maintenance to protect human health and the environment from ACBM.
NESHAP
The Clean Air Act (CAA) of 1970 required EPA to develop and enforce regulations to protect the general public from exposure to airborne contaminants that are known to be hazardous to human health; therefore, EPA promulgated NESHAP (Title 40, CFR Part 61) on April 6, 1973.
NESHAP is intended to minimize the release of asbestos fibers during certain activities (i.e., renovations, demolition, and installations). It specifies work practices to be followed during renovations of buildings (except apartment buildings that have no more than four dwelling units) which contain a specific amount of friable asbestos. NESHAP requires that buildings be inspected for ACBM prior to renovation/demolition projects.
NESHAP also requires owners and operators subject to the asbestos rules to notify delegated state and local agencies and/or the regional EPA offices before demolition or renovation activities begin. In addition, NESHAP requires the removal of all friable ACBM prior to demolition.
OSHA
OSHA began regulating workplace asbestos exposure in 1970, adopting a permissible exposure limit (PEL) to regulate worker exposure. The original asbestos standard has been revised several times to better protect workers. On August 10, 1994, OSHA issued a revised final standard regulating asbestos exposure in all industries. The newly revised standard for the construction industry lowers the PEL. The revised standard also establishes a new classification system for asbestos construction work, which clearly spells out mandatory work practices to follow to reduce worker exposures (see Occupational Exposure to Asbestos, Title 29, CFR 1926.1101).
State and Local Regulations New York state regulations are similar to the Federal regulations. In many instances state and local asbestos regulations are more stringent, therefore, it is recommended that the applicable state asbestos regulation(s) be reviewed before the start of any renovation/demolition projects.
State asbestos regulations include requirements for licensing and certification of personnel who will perform asbestos-related work activities. All personnel who engage in asbestos-related activities must comply with the state licensing/certification requirements as well as with all Federal requirements.
ANALYTICAL METHODS AND LIMITATIONS
Bulk Sampling Protocol EPA and OSHA define an ACBM as any material which contains greater than 1percent asbestos (some state regulations may be more stringent). The ACBM inspection and bulk sampling were performed in accordance with the methods outlined in the EPA guidance document titled Guidance for Controlling Asbestos-Containing Materials in Buildings (Document No. 560/5-85/024). In addition, bulk sampling of asbestos was performed in accordance with 40 CFR Part 763, AHERA requirements for number of samples and types of ACBM to be sampled. According to these requirements, materials are classified as either surfacing (e.g., decorative plaster, spray-applied fireproofing), thermal system insulation (e.g., pipe insulation, pipe fitting insulation, boiler insulation), or miscellaneous materials (e.g., floor tile, ceiling tile, plaster, wallboard, mastics).
The number of samples collected from each material varies based on the classification of the material and increases as the potential for a non-uniform mixture of asbestos in the material increases. Typically, regulations require a minimum number of samples to be collected from the different classifications of suspect ACBM, as follows:
• Surfacing Material
a) Three samples from homogeneous areas up to 1,000 square feet
b) Five samples from homogeneous areas between 1,000 and 5,000 square feet
c) Seven samples from homogeneous areas over 5,000 square feet
• Thermal System Insulation
a) Minimum of three samples per homogeneous area
• Miscellaneous Material
a) Minimum of one sample per homogeneous area, but must be sufficient to determine asbestos content based on the discretion of the inspector
EXPLANATION OF ASSESSMENT OF ACM’S
Asbestos inspection protocols are based on the Asbestos Hazard Emergency Response Act (AHERA), Environmental Protection Act’s (EPA’s) revised Asbestos Model Accreditation Plan (MAP) mandated by the Asbestos School Hazard Abatement Reauthorization Act (ASHARA). The tabular listing included in this report contains Room Number, Material Category (i.e., TSI, SM or MM), Material Type, quantity, a numerical priority ranking, condition, potential for damage, potential for human exposure, drawing number, hazard ranking, recommended response action and associated cost estimate for implementation of those response actions.
The material assessment categories of the ACM identified in the building is formatted in the following order for the summary tables enclosed in this report:
• Material Category - Surfacing Material (SUR); Thermal System Insulation (TSI); Miscellaneous (MM)
• Material Type - Friable (F); Non-Fable (NF)
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
• Physical Assessment - Low; Medium; High
• Recommended Response Action - 1 through 7
Material category is the type of material such as surfacing material (SUR), thermal system insulation (TSI), and miscellaneous (MM)
• Surfacing Material (SUR) - Surfacing ACM means surfacing material that is ACM. Surfacing material means material in a school building that is sprayed-on, troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.
• Thermal System Insulation (TSI) - Thermal system insulation ACM means thermal system insulation that is ACM. Thermal system insulation means material in a school building applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.
• Miscellaneous (MM) - Miscellaneous ACM means miscellaneous material that is ACM Miscellaneous material means interior building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.
Material type refers to the hardness of a material to be crumbled, pulverized, or reduced to powder by hand pressure as friable (F), and includes previously non-friable (NF) material after such previously non-friable material becomes damaged to the extent that when dry it may be crumbled, pulverized, or reduced to powder by hand pressure.
• Condition of Material - Good; Fair; Poor
• Potential for Damage - Low; Medium; High
• Physical Assessment - Low; Medium; High
Seven Categories define in the AHERA regulation one of which must be assigned to each friable surfacing and miscellaneous ACBM and each asbestos-containing TSI during the inspection/re-inspection.
1. Damaged or significantly damaged TSI ACBM - Damaged or significantly damaged thermal system insulation ACM means thermal system insulation ACM on pipes, boilers, tanks, ducts, and other thermal system insulation equipment where the insulation has lost its structural integrity, or its covering, in whole or in part, is crushed, water-stained, gouged, punctured, missing, or not intact such that it is not able to contain fibers. Damage may be further illustrated by occasional punctures, gouges or other signs of physical injury to ACM; occasional water damage on the protective coverings/jackets;
or exposed ACM ends or joints. Asbestos debris originating from the ACBM in question may also indicate damage.
2. Damaged friable surfacing ACBM - Damaged friable surfacing ACM means friable surfacing ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or which has delaminated such that its bond to the substrate (adhesion) is inadequate, or which, for any other reason, lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
3. Significantly damaged friable surfacing ACBM - Significantly damaged friable surfacing ACM means damaged friable surfacing ACM in a functional space where the damage is extensive and severe.
4. Damaged or significantly damaged friable miscellaneous ACBM - Damaged friable miscellaneous ACM means friable miscellaneous ACM which has deteriorated or sustained physical injury such that the internal structure (cohesion) of the material is inadequate or, if applicable, which has delaminated such that its bond to the substrate (adhesion) is inadequate or which for any other reason lacks fiber cohesion or adhesion qualities. Such damage or deterioration may be illustrated by the separation of ACM into layers; separation of ACM from the substrate; flaking, blistering, or crumbling of the ACM surface; water damage; significant or repeated water stains, scrapes, gouges, mars or other signs of physical injury on the ACM. Asbestos debris originating from the ACBM in question may also indicate damage.
5. ACBM with Potential for Damage - Potential damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
6. ACBM with potential for significant damaged - Potential significant damage means circumstances in which:
(1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.
(2) There are indications that there is a reasonable likelihood that the material or its covering will become significantly damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.
7. Any remaining friable ACBM or Friable Suspected ACBM
CONCLUSION/RECOMMENDATIONS
An operations and maintenance (O&M) program should be developed for the positively identified ACBM in the vessel. Any renovation/demolition work which may impact these positive materials should be conducted in accordance with the O&M program and all applicable Federal, state, and local regulations by appropriately trained and approved personnel and contractors. Since demolition was not performed as part of the inspection, certain areas such as pipe chases and areas above fixed permanent ceilings were not inspected or tested.
Prior to renovation and alteration work which could impact these areas, Castle Hill recommends that exploratory demolition be performed and a qualified inspector be utilized to examine the areas and collect samples as needed.
Respectfully Submitted:
Brett L. Brumbaugh – Project Manager
TABLE 1
LIST OF ACRONYMS
ACBM Asbestos Containing Building Material ACM Asbestos Containing Material AHERA Asbestos Hazard Emergency Response Act AIHA American Industrial Hygiene Association CAA Clean Air Act CFR Code of Federal Regulations EPA United States Environmental Protection Agency HazCom Hazard Communication HEPA High Efficiency Particulate Air Filter HVAC Heating, Ventilation, and Air Conditioning MISC Miscellaneous Asbestos Containing Material NESHAP National Emission Standards for Hazardous Air Pollutants NIOSH National Institute for Occupational Safety and Health NIST National Institute of Standards and Technology NOB Non-friable Organically Bound NVLAP National Voluntary Laboratory Accreditation Program OSHA Occupational Safety and Health Administration PAT AIHA Proficiency Analytical Testing Program PCM Phase Contrast Microscopy PEL Permissible Exposure Limit PLM Polarized Light Microscopy TEM Transmission Electron Microscopy TSCA Toxic Substances Control Act TSI Thermal Systems Insulation Castle Hill Castle Hill Associates, LLC XRD X-Ray Diffraction
TABLE 2
REMOVAL PRIORITY PROTOCOLS
HAZARD
RANK
REMOVAL
PRIORITY
AHERA
CATEGORY
RESPONSE ACTION
RECOMMENDATION
7 1 Significantly Damaged
Evacuate or isolate the area.
Remove or repair if feasible.
O&M for all friable ACM.
6 2 Damaged with potential for significant damage
Evacuate or isolate the area.
Remove, encapsulate, or repair if feasible. O&M for all friable
ACM.
5 3 Damaged with potential for damage
Remove, encapsulate, or repair. O&M for all friable ACM.
4 4 Damaged Remove, encapsulate, or repair. O&M for all friable ACM.
3 5 Potential for significant damage
Take steps to reduce potential for damage. O&M for all friable
ACM.
2 6 Potential for damage O&M for all friable ACM.
1 7 No problem O&M for all friable ACM.
ASBESTOS CONTAINING MATERIAL PHOTOS
PHOTOGRAPHS OF ASBESTOS MATERIALS
Photo A-1 Red linoleum sheet flooring at top of stairs from main deck galley to lower deck
Photo A-2
Tan linoleum sheet flooring in passage hallway to
Engine Room under carpet runner and 12” self-stick floor tile
Photo A-3 Tan linoleum sheet flooring in forward hallway by quarters in lower deck
ASBESTOS MATERIALS ASSESSMENT
T.S. Kings Pointer
USMMA - Kings Point, NY
Asbestos Assessments and Cost Estimates
September 2020
Asbestos Material Locations Quantity
AHERA
Category Friability
AHERA
Assessment Recommendation
Removal
Priority
Repair Cost
Estimate
Removal Cost
Estimate
Red Linoleum sheet flooring Main Deck - Stair landing to lower deck off of
Galley 6 SF MISC Non-friable 1 O&M; Remove at renovation 7 No damage $1,500
Tan Linoleum sheet flooring Lower deck – Forward hallway and passage hall to Engine room 104 SF MISC Non-friable 1 O&M; Remove at renovation 7 No damage $4,000
TOTAL $5,500
HOMOGENEOUS SAMPLING AREA DESCRIPTIONS
ASBESTOS HOMOGENEOUS SAMPLING AREA DESCRIPTIONS
HOMOG.
AREA
MATERIAL
ASBESTOS
MATERIAL
A Gray duct seam mastic No B Red pattern linoleum sheet flooring YES C Linoleum mastic (yellow) No D Black vinyl cove base No E Brown mastic No F Gray pattern linoleum sheet flooring No G Linoleum mastic (yellow) No H Tan pattern linoleum sheet flooring YES I Linoleum mastic (yellow) No J Diesel exhaust flue block insulation No K Diesel exhaust flue block insulation No L Diesel exhaust flue block insulation No M Interior window frame caulking No
ASBESTOS BULK SAMPLING DATA
ASBESTOS BULK SAMPLE DESCRIPTIONS & RESULTS
Vessel: T.S. Kings Pointer Location: USMMA – Kings Point, NY Sampling Date: September 29, 2020 Analysis Dates: October 6-7, 2020 Laboratory: EMSL Analytical, Inc. – Cinnaminson, NJ Certification: NVLAP Lab Code 101048-0, NY Accredited PLM Laboratory Methods: PLM (NYS 198.1 Friable; 198.6 VCM; 198.6 NOB) TEM by NYS 198.4 NOB)
SAMPLE
# HA SAMPLE LOCATION MATERIAL DESCRIPTION LABORATORY RESULTS
A Main Level forward storage exhaust duct Gray duct seam mastic No Asbestos Detected
2a B Stair landing – Main level
Red linoleum sheet flooring 3.90% Chrysotile Asbestos
2b C “” Linoleum mastic (yellow) No Asbestos Detected
3a D Stair landing – Main level
Black vinyl cove base No Asbestos Detected
3b E “” Brown mastic No Asbestos Detected
4a F Lower deck hallway – Aft Gray pattern linoleum sheet flooring <1% Chrysotile Asbestos
4b G “” Linoleum mastic (yellow) No Asbestos Detected
5a H Lower deck hallway - Forward
Tan linoleum sheet flooring 2.40% Chrysotile Asbestos
5b I “” Linoleum mastic (yellow) No Asbestos Detected
6 J Detroit diesel engine 1 Diesel exhaust flue block insulation No Asbestos Detected
7 J Detroit diesel engine 2 Diesel exhaust flue block insulation No Asbestos Detected
8 J Main engine 1 Diesel exhaust flue block insulation No Asbestos Detected
9 J Main engine 2 Diesel exhaust flue block insulation No Asbestos Detected
10 K Engine in passage to thruster room
Diesel exhaust flue block insulation No Asbestos Detected
11 L Bow thruster engine room – 14” exhaust pipe
Diesel exhaust flue block insulation No Asbestos Detected
12 L Bow thruster engine room – 30” exhaust pipe
Diesel exhaust flue block insulation No Asbestos Detected
13a D Forecastle deck hallway Black vinyl cove base No Asbestos Detected
13b E “” Brown mastic <1% Chrysotile Asbestos
14 M Bridge window Interior window frame caulking No Asbestos Detected
15a F Bridge deck Gray pattern linoleum sheet flooring No Asbestos Detected
15b G “” Linoleum mastic (yellow) No Asbestos Detected
Notes:
1. Asbestos containing materials are defined by the EPA as containing greater than 1% asbestos
2. HA = Homogeneous Sampling Area (includes areas with homogeneous building materials)
APPENDIX A
ASBESTOS SAMPLE LOCATION PLANS
APPENDIX B
ASBESTOS LABORATORY ANALYTICAL REPORTS
EMSL Analytical, Inc.
200 Route 130 North Cinnaminson, NJ 08077
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042023925EMSL Order:
Customer ID: CHAS42
Customer PO:
Project ID:
Attention: Phone:Brett Brumbaugh (567) 952-0212
Fax:Castle Hill Associates, LLC
Received Date:218-A Mechanic St. 10/01/2020 9:30 AM
Analysis Date:Waterville, OH 43566 10/06/2020 - 10/07/2020
Collected Date: 09/29/2020
Project: TV Kings Pointer - USMMA
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 1 Description - Gray Duct Seam Mastic
042023925-0001 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Gray Inconclusive: None Detected10/06/2020 100.00% Other
TEM NYS 198.4 NOB Gray None Detected10/07/2020 100.00% Other
Sample ID 2 Description - Red Linoleum
042023925-0002 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Red10/06/2020 None 100.00% Other Inconclusive : <1% Chrysotile
TEM NYS 198.4 NOB Red10/07/2020 None 96.10% Other 3.90% Chrysotile
Sample ID 3-Cove Base Description - Black Cove Base
042023925-0003 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Gray Inconclusive: None Detected10/06/2020 100.00% Other
TEM NYS 198.4 NOB Gray None Detected10/07/2020 100.00% Other
Sample ID 3-Mastic Description - Mastic
042023925-0003A Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Yellow Inconclusive: None Detected10/06/2020 100.00% Other
TEM NYS 198.4 NOB Yellow None Detected10/07/2020 100.00% Other
Sample ID 4 Description - Gray Linoleum
042023925-0004 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Gray Inconclusive: None Detected10/06/2020 100.00% Other
TEM NYS 198.4 NOB Gray10/07/2020 None 100.00% Other <1% Chrysotile
Initial report from: 10/07/2020 12:34:05
Page 1 of 4ASB_198x_0009 - 1.71 Printed 10/7/2020 11:47:35PM
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042023925EMSL Order:
Customer ID: CHAS42
Customer PO:
Project ID:
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 5 Description - Tan Linoleum
042023925-0005 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Tan10/06/2020 None 97.60% Other 2.40% Chrysotile
TEM NYS 198.4 NOB Not Analyzed
Sample ID 6 Description - Exhaust Breeching Insulation
042023925-0006 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray None Detected10/06/2020 30.00% Min. Wool 70.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 7 Description - Exhaust Breeching Insulation
042023925-0007 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray None Detected10/06/2020 5.00% Cellulose 95.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 8 Description - Exhaust Breeching Insulation
042023925-0008 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray None Detected10/06/2020 10.00% Cellulose 90.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 9 Description - Exhaust Breeching Insulation
042023925-0009 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray None Detected10/06/2020 10.00% Cellulose 90.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 10 Description - Exhaust Breeching Insulation
042023925-0010 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray None Detected10/06/2020 10.00% Cellulose 90.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Page 2 of 4ASB_198x_0009 - 1.71 Printed 10/7/2020 11:47:35PM
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042023925EMSL Order:
Customer ID: CHAS42
Customer PO:
Project ID:
Test Report:Asbestos Analysis of Bulk Material
Test Color
Analyzed
Date Fibrous Non-Fibrous Asbestos
Non-Asbestos
Sample ID 11 Description - Exhaust Breeching Insulation
042023925-0011 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray None Detected10/06/2020 10.00% Cellulose 90.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 12 Description - Exhaust Breeching Insulation
042023925-0012 Homogeneity Homogeneous
PLM NYS 198.1 Friable Gray None Detected10/06/2020 10.00% Cellulose 90.00% Non-fibrous (other)
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Not Analyzed
TEM NYS 198.4 NOB Not Analyzed
Sample ID 13-Cove Base Description - Black Cove Base
042023925-0013 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Gray Inconclusive: None Detected10/06/2020 100.00% Other
TEM NYS 198.4 NOB Gray None Detected10/07/2020 100.00% Other
Sample ID 13-Mastic Description - Mastic
042023925-0013A Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Yellow10/06/2020 None 100.00% Other Inconclusive : <1% Chrysotile
TEM NYS 198.4 NOB Yellow10/07/2020 None 100.00% Other <1% Chrysotile
Sample ID 14 Description - Inter. Window Frame Caulk
042023925-0014 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Gray Inconclusive: None Detected10/06/2020 100.00% Other
TEM NYS 198.4 NOB Gray None Detected10/07/2020 100.00% Other
Sample ID 15 Description - Gray Linoleum
042023925-0015 Homogeneity Homogeneous
PLM NYS 198.1 Friable Not Analyzed
PLM NYS 198.6 VCM Not Analyzed
PLM NYS 198.6 NOB Gray Inconclusive: None Detected10/06/2020 100.00% Other
TEM NYS 198.4 NOB Gray None Detected10/07/2020 100.00% Other
Page 3 of 4ASB_198x_0009 - 1.71 Printed 10/7/2020 11:47:35PM
Tel/Fax: (800) 220-3675 / (856) 786-5974 http://www.EMSL.com / cinnasblab@EMSL.com
042023925EMSL Order:
Customer ID: CHAS42
Customer PO:
Project ID:
Test Report:Asbestos Analysis of Bulk Material
Analyst(s):
John Witcraft PLM NYS 198.1 Friable (2) Sarah Kleinbrahm PLM NYS 198.1 Friable (5)
Sarah Kleinbrahm PLM NYS 198.6 NOB (10) Diane Turcios TEM NYS 198.4 NOB (9)
Samples reviewed and approved by:
Samantha Rundstrom, Laboratory Manager or Other Approved Signatory
NOB = Non Friable Organically Bound N/A = Not Applicable VCM = Vermiculite Containing Material
-In New York State, TEM is currently the only method that can be used to determine if NOB materials can be considered or treated as non-asbestos containing.
All samples examined for the presence of vermiculite when analyzed via NYS 198.1.
-NYS Guidelines for Vermiculite containing samples are available at http://www.wadsworth.org/labcert/elapcert/forms/VermiculiteInterimGuidance_Rev070913.pdf EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by
EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client.
Samples were received in good condition unless otherwise noted.
This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. This report may contain data that is not covered by the NVLAP accreditation.
Samples analyzed by EMSL Analytical, Inc. Cinnaminson, NJ NYS ELAP 10872, PA ID# 68-00367
Page 4 of 4ASB_198x_0009 - 1.71 Printed 10/7/2020 11:47:35PM
OrderID: 042023925
OrderID: 042023925
APPENDIX C
CONSULTANT CERTIFICATIONS
Brett Brumbaugh
State Asbestos Licenses
State License/Cert Number License/Training
Ohio ES3488 Asbestos Hazard Evaluation Specialist
Ohio PD60095 Asbestos Project Designer
Indiana 192916010 Asbestos Inspector, Mgt. Planner, and Project Designer
Illinois 100-09972 Asbestos Inspector
Michigan A3686 Asbestos Inspector, Mgt. Planner, and Project Designer
Minnesota AI14402 Asbestos Inspector
Missouri 7136041420MOII21053 Asbestos Inspector
Pennsylvania 49043 Asbestos Inspector
Pennsylvania 49043 Asbestos Project Designer
Kentucky 62525 Asbestos Project Designer
Kentucky 62524 Asbestos Inspector & Mgt. Planner
Virginia 3303004018 Asbestos Inspector
Virginia 3305001292 Asbestos Project Designer
West Virginia AI010074 Asbestos Inspector
North Carolina 12411 Asbestos Inspector
Iowa 19-3383 & 19-3384 Asbestos Inspector & Mgt. Planner
Tennessee A-I-46297-78155 Asbestos Inspector
South Dakota 8517 Asbestos Inspector
South Dakota 8517 Asbestos Mgt. Planner
South Dakota 8571 Asbestos Project Designer
APPENDIX D
LABORATORY CERTIFICATIONS