Suggested_Product_-_Fan_Coil.pdf
PDF 1 MB Posted
- Attached to
- PEVI HVAC Replacement Federal contract opportunity
- Solicitation number
- 140P6425Q0103
About this file
This document is a detailed product data sheet for the Carrier FV4C Performance Series Fan Coil, covering sizes 002 through 006. The fan coil is a premium air handler designed with environmentally responsible Puron refrigerant (R-410A) and features an Electronically Commutated Motor (ECM) for enhanced efficiency. Key technical highlights include a factory-installed Thermostatic Expansion Valve (TXV), grooved tubing, louvered aluminum fins, and a rugged prepainted metal cabinet with high-density insulation. The unit offers multipoise installation, supports high and low voltage connections, and achieves low cabinet leakage rates (less than 2% at 0.5 inches W.C.) as tested per ASHRAE 193 standard.
The product data sheet provides comprehensive performance specifications, including airflow delivery charts for cooling and heating modes, cooling capacities under various temperature conditions, estimated sound power levels, and electrical data for different electric heater configurations. The document also details 14 accessory kits available for the fan coil, such as disconnect kits, downflow conversion kits, filter kits, air purifiers, and condensate drain trap kits. These accessories enhance installation flexibility, improve system performance, and provide additional features like air purification and water management. The fan coil is designed for residential heating and cooling applications, offering 30-40% more efficiency compared to standard systems.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6425Q0103_Amd_0002.pdf | ||
| Questions___Answers_0002.pdf | ||
| Mini_Split_Outdoor_Unit_Specs_0001.pdf | ||
| Air_Cooled_Heat_Pump_Specs_0001.pdf | ||
| Heat_Pump_Air_Handler_Schedule__Specs_0001.pdf | ||
| Mini_Split_Indoor_Unit__Specs_0001.pdf | ||
| Sol_140P6425Q0103_Amd_0001.pdf | ||
| Electric_Baseboard_Heat_Specs_0001.pdf | ||
| Combined_Synopsis.pdf | ||
| SCA_WD_-_Ottawa_County__OH.pdf | ||
| Price_Schedule.xlsx | XLSX spreadsheet | |
| Statement_of_Work.pdf | ||
| Suggested_Product_-_Mini_Split.pdf | ||
| Suggested_Product_-_Electric_Baseboard_Heater.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FV4C
Performance� Series Fan Coil Sizes 002 Thru 006
Product Data
PREMIUM ENVIRONMENTALLY
RESPONSIBLE FAN COIL
The FV4C is the premium air handler combining the proven technology of Carrier fan coils with environmentally balanced Puron� refrigerant. The FV4C achieves an operational advantage when the ECM (Electronically Commutated Motor) is combined with a Carrier Performance� heat pump with Puron� refrigerant.
With attention to quiet, efficient, and comfortable operation, Carrier has developed a new benchmark for superior indoor comfort and control.
Carrier’s heat pump and air conditioning systems now feature Puron� refrigerant (R−410A), the chlorine−free refrigerant that is the future for the residential heating and cooling industry. The FV4C using Puron� refrigerant maximizes performance for environmentally balanced systems. In addition to environmental safety, these systems are 30 to 40% more efficient than standard heating and cooling systems, thereby combining excellence in efficiency and environmental responsibility.
The FV4C provides these benefits due to Carrier’s command of ECM technology. These motors are extremely efficient at all speeds, and enable the FV4C to operate at the correct speed to deliver airflow precisely, ensuring proper performance across a wide range of duct static pressures. This adaptive efficiency also makes installation quality easier to achieve for today’s demanding homeowner.
Carrier’s command of ECM technology may be most evident in the comfort advantages that ECM can deliver. Operation set up steps on the Easy Select� Board provide the installing technician with alternatives to maximize comfort and efficiency. For true indoor comfort, the homeowner can achieve command of both temperature and humidity in cooling and heating modes.
Another feature which sets the FV4C apart is the factory−installed TXV, which enhances efficiency and provides compressor protecting operation at all recommended conditions. Grooved tubing, louvered aluminum fins, and the large face areas of the FV4C refrigerant coils also provide superior efficiency, for high SEER and HSPF performance. Carrier leads the way in condensate control, a hallmark of these multipoise fan coils. All of these featured components are protected within a rugged, prepainted metal cabinet lined with super thick, high density insulation. For neat, high quality installations the unit exterior features sweat refrigerant connections for simple leak free performance, and multiple electrical entry for both high and low voltage service.
Assembled at the factory compliant with low leak requirements of less than 2% cabinet leakage rate at 0.5 inches W.C. and 1.4% cabinet leakage rate at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.
FEATURES
Environmentally Balanced Refrigerant Technology � Puron�, chlorine−free, non−ozone depleting refrigerant
� Thermostatic Expansion Valve (TXV) designed to maximize performance with Puron� refrigerant
Energy Efficient Operation � Electronically Commutating Motor (ECM) operates efficiently at all speeds
� Maximizes efficiency of heating and cooling systems
� Ultra low power consumption during fan only operation
Indoor Weather Control � Warm, comfortable heating air temperatures
� Unmatched humidity control, especially with Carrier’s thermostat with relative humidity controls
Airflow and Sound Technology � Diffuser air discharge section for high airflow efficiency and quiet, smooth operation
� High duct static capability
� Design meets stringent regulations for cabinet air leakage of less than 2% when tested at 0.5 inches W.C., and cabinet air leakage less than
1.4% at 0.5 inches W.C. when tested in accordance with ASHRAE 193 standard.
Condensate Control and Disposal Technology � Minimal standing waterless microbial growth for improved IAQ and reduced condensate line clogging and related condensate leakage
� Condensate fittings relocated away from turbulent airflow patterns at the blower entrance for improved condensate control performance
� Overflow feature for slope coil units allows condensate to exit the unit without damage to product under clogged primary and secondary line conditions
� Tested for condensate disposal at conditions much more severe than those required by AHRI
� Primary and secondary drain connections to comply with HUD
� All pans constructed of an injection molded glass−filled polycarbonate engineered resin material, with brass drain connections.
� High density, super thick cabinetry insulation with vapor barrier
� Pre−painted galvanized sheet metal cabinet
Heat Transfer Technology � Grooved tubing
� Lanced sine wave aluminum fins
� Discreet refined counter−flow refrigerant circuitry
� Bi−flow hard shut−off TXV metering device
Quality Assisting, Ease of Installation and Service Features � All units multipoise
� Provision made for suspending from roof or ceiling joints
� Modular cabinet on 003 thru 006 units
� Sweat connections for leak free service
� Multiple electrical entry for application flexibility (high and low voltage)
� Low voltage terminal strip, to safely hold connections within the cabinet
� Cabinet construction features innovations designed to prevent cabinet sweating
Controls and Electrical Features � Easy Select� Board to maximize comfort, efficiency, and safe heater airflow operation
� Easy plug connection provided for quick installation of accessory heater packages
� 40VA 208/230v transformer
� Replaceable 5−amp blade−type auto fuse protects against transformer secondary short
Filter Features � Factory supplied filter
� Cleanable polyester filter media
� Filter “springs” out for easy access − no tools required
� Newly improved filter rack area − filter door insulation added for an improved air seal
MODEL NUMBER NOMENCLATURE
1 2 3 4 5 6 7 8 9 10 11 12
F V 4 C N B 0 0 3 0 0 0
Product
F = Fan Coil
Type
V = Puron� Refrigerant
Coil Type
Position T00 = Tin-plated
4 = Multipoise 000 = Copper
L00 = Aluminum
Series
C Capacity
002 = 18-36,000
Electrical 003 = 24-42,000
N = 208/230v, 1ph-60 Hz 005 = 30-48,000
006 = 30-60,000
Cabinet/Insulation
B = Modular
F = Single piece the environmentally sound refrigerant
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program For verification of certification for individual products, go to www.ahridirectory.org.
SPECIFICATIONS
MODEL FV4C 002 003 005 006
COIL
Refrigerant Metering Device Puron� Refrigerant (R-410A)
TXV Size 2 Ton 3 Ton 4 Ton 5 Ton
Rows/Fins Per In. 3 / 14.5
Face Area (Sq Ft) 3.46 5.93 7.42
Configuration A Slope A
BLOWER & MOTOR
Air Discharge Upflow, Downflow, Horizontal
CFM (Nominal Clg/Htg)
525 / 470 700 / 630 875 / 785 1050 / 945
700 / 630 875 / 785 1050 / 945 1225 / 1100
875 / 785 1050 / 945 1225 / 1100 1400 / 1260
1050 / 945 1225 / 1100 1400 / 1260 1750 / 1575
Motor HP (ECM) 1/2 3/4
FILTER CLEANABLE
21-1/2” (546 mm) by 16-3/8” (417 mm) 19-7/8” (505 mm) 23-5/16” (585 mm)
CABINET CONFIGURATION OPTIONS
1 Piece 1 Piece or Modular Modular
D
IM
E N
SI
O
N S
U N
IT
S
IZ
E
A B
C D
E H
J in m m in m m in m m in m m in m m in m m in m m
F V
C
N B
/1
/8
/4
/8
/1
/1
F V
C
N B
/1
/8
/4
/8
/1
/1
F
V
C N
B
/1
/1
/4
/1
/4
/1
F
V
C N
F
/1
/8
/4
/8
/4
F
V
C N
F
/1
/8
/4
/8
/1
F V
C
N F
/1
/8
/4
/8
/2
D
IM
E N
SI
O
N S
U N
IT
S
IZ
E
F G
C O
IL
T
Y P
E S
H
IP
P
IN
G W
E
IG
H T in m m in m m lb k g
F V
C
N B
/1
/2
S
L O
P E
F V
C
N B
/1
/2
A
F V
C
N B
/1
/8
A
F V
C
N F
/1
/4
A
F V
C
N F
/1
/2
S
L O
P E
F V
C
N F
/4
/1
A
PERFORMANCE DATA
FV4C ADVANCED FAN COIL AIRFLOW DELIVERY CHART (CFM)
OPERATING MODE
UNIT SIZE
OUTDOOR
UNIT
CAPACITY
SINGLE—SPEED
APPLICATION
TWO—SPEED APPLICATION FAN ONLY
Nominal A/C
Cooling
A/C Cooling
Dehumidity
High Speed Low Speed
Lo Med High Nominal
A/C Cooling
A/C Cooling
Dehumidity
Nominal A/C
Cooling
A/C Cooling
Dehumidity
018 525 420 — — — — 350 420 525
024 700 560 700 560 560 450 350 560 700
030 875 700 — — — — 440 700 875
036 1050 840 1050 840 840 670 525 840 1050
024 700 560 700 560 560 450 415 560 700
030 875 700 — — — — 440 700 875
036 1050 840 1050 840 840 670 525 840 1050
042 1225 980 — — — — 610 980 1225
030 875 700 — — — — 440 700 875
036 1050 840 1050 840 840 670 525 840 1050
042 1225 980 — — — — 610 980 1225
048 1400 1120 1400 1120 1120 895 700 1120 1400
036 1050 840 1050 840 840 670 540 840 1050
042 1225 980 — — — — 610 980 1225
048 1400 1120 1400 1120 1120 895 700 1120 1400
060 1750 1400 1750 1400 1400 1120 875 1400 1750
NOTES:
1. The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM.
2. Air flow can be adjusted +15% or -10% by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kW heater and filter installed.
4. Airflows shown are at standard air conditions.
*Consult ARI ratings before matching outdoor unit with FV4C fan coil.
FV4C ADVANCED FAN COIL AIRFLOW DELIVERY CHART (CFM)
OPERATING MODE
UNIT SIZE
OUTDOOR
UNIT
CAPACITY
SINGLE—SPEED
APPLICATION
TWO—SPEED APPLICATION FAN ONLY
Heat Pump Comfort
Heat Pump Efficiency
High Speed Low Speed
Lo Med HighHeat Pump Comfort
Heat Pump Efficiency
Heat Pump Comfort
Heat Pump Efficiency
018 470 525 — — — — 350 380 470
024 630 700 630 700 505 560 350 505 630
030 785 875 — — — — 390 630 785
036 945 1050 945 1050 755 840 470 755 945
024 630 700 630 700 415 560 415 505 630
030 785 875 — — — — 415 630 785
036 945 1050 945 1050 755 840 470 755 945
042 1100 1225 — — — — 550 880 1100
030 785 875 — — — — 425 630 785
036 945 1050 945 1050 755 840 470 755 945
042 1100 1225 — — — — 550 880 1100
048 1260 1400 1260 1400 1010 1120 630 1010 1260
036 945 1050 945 1050 755 840 540 755 945
042 1100 1225 — — — — 550 880 1100
048 1260 1400 1260 1400 1010 1120 630 1010 1260
060 1575 1750 1575 1750 1260 1400 785 1260 1575
NOTES:
1. The above airflows result with the AC, HP CFM ADJUST select jumper set on NOM.
2. Air flow can be adjusted +15% or -10% by selecting HI or LO respectively for all modes except fan only.
3. Dry coil at 230 volts and with 10kW heater and filter installed.
4. Airflows shown are at standard air conditions.
PERFORMANCE DATA (cont)
AIRFLOW DELIVERY CHART (CFM) — ELECTRIC HEATING MODES
FAN
UNIT SIZE
OUTDOOR
UNIT
CAPACITY
BTUH
ELECTRIC HEATER kW RANGE
0-5 0-10 0-15 0-20
Lo Nom High Lo Nom High Lo Nom High Lo Nom High
18,000 625 625 625 675 675 - - - - - - -
24,000 650 725 835 - 725 835 875 875 875 - - -
30,000 815 905 1040 - 905 1040 900 900 1040 1100 1100 1100
36,000 980 1085 1250 980 1085 1250 980 1085 1250 1100 1100 1250
24,000 675 725 835 875 875 - - - - - - -
30,000 815 905 1040 875 905 1040 1100 1100 1100 - - -
36,000 980 1085 1250 980 1085 1250 1100 1100 1250 1225 1225 1250
42,000 1140 1270 1460 1140 1270 1460 1140 1270 1460 1225 1270 1460
FAN
UNIT SIZE
OUTDOOR
UNIT
CAPACITY
BTUH
ELECTRIC HEATER kW RANGE
0-10 0-15 0-20 0-30
Lo Nom High Lo Nom High Lo Nom High Lo Nom High
30,000 975 975 1040 1100 1100 1100 - - - - - -
36,000 980 1085 1250 1100 1100 1250 1250 1250 1250 - - -
42,000 1140 1270 1460 1140 1270 1460 1250 1270 1460 - - -
48,000 1305 1450 1665 1305 1450 1665 1305 1450 1665 1500 1500 1665
36,000 1100 1100 1250 1350 1350 1350 - - - - - -
42,000 1140 1270 1460 1350 1350 1460 1525 1525 1525 - - -
48,000 1305 1450 1665 1350 1450 1665 1525 1525 1665 1750 1750 1750
60,000 1630 1810 2085 1630 1810 2085 1630 1810 2085 1750 1810 2085
NOTE: Lo, NOM, and HI refer to AC, HP CFM ADJUST selection.
- Airflow not recommended for heater/system size.
MINIMUM CFM FOR ELECTRIC HEATER APPLICATION
FAN COIL UNIT
HEAT PUMP UNIT
SIZE
CFM
HEATER SIZE kW
5 8, 9, 10 15 18, 20 24, 30
Heater Only 625 625 725 875 —
018 625 625 — — —
024 650 725 875 — —
030 800 875 875 1040 —
036 970 970 970 1040 —
Heater Only 675 700 1050 1050 —
024 675 875 — — —
030 800 875 1100 — —
036 975 975 1100 1225 —
042 1125 1125 1125 1225 —
Heater Only 675 700 1050 1050 1400
018 800 875 1100 — —
036 975 975 1100 1225 —
042 1125 1125 1125 1225 —
048 1305 1305 1305 1305 1400
Heater Only 1050 1050 1050 1050 1750
018 1100 1100 1350 1350 —
042 1125 1125 1350 1350 —
048 1300 1300 1350 1465 1750
060 1625 1625 1625 1750 1750
NOTES:
1. Heater Only-Air conditioner with electric heater application.
2. These airflows are minimum acceptable airflows as UL listed. Actual airflow delivered will be per airflow delivery chart for Electric Heating Modes.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.1 0.2 0.3 0.4 0.5 0.6
RETURN STATIC PRESSURE, IN.W.C.
S U
P P
LY
S
T A
T
IC
P R
E S
S U
R E
, I N
.W .C
TOO HIGH
RETURN STATIC
PRESSURE
(DIFFICULT TO MAKE
TRAP)
ACCEPTABLE RANGE
A02296
ACCEPTABLE DUCT CONDITIONS
For satisfactory operation (specifically making dry secondary trap), subject fan coils must be installed with duct systems which fall within the “Acceptable Range” illustrated above.
The airflow performance charts for the FV4C fan coil depict nominal airflow delivery for heating and cooling mode operation versus duct system static pressure drop. Cooling mode operation is shown as solid vertical lines for all 4 system size selections.
Heating mode operation for the 4 system size selections are shown as dashed vertical lines.
The dotted curved lines are static pressure drop characteristics for several fixed−duct systems. These lines can be used to predict the system static pressure drop at any airflow given the actual drop at 1 known point.
For example, a duct system is designed for 0.15 in. water column
(in. w.c.) drop at 1200 CFM. The FV4CNF005 operating at nominal cooling airflow would deliver 1050 CFM with a duct system drop of 0.11 in. w.c.. (See point 1.) On the same duct system, the FV4CNF005 operating at nominal heating airflow would deliver 945 CFM with a duct system drop of 0.09 in. w.c.
(See point 2.)
This example is but one of many possible duct system designs. The FV4CNF005 will deliver the above airflows against much higher static pressures.
AIRFLOW PERFORMANCE
E X
T E
R N
A L
S T
A T
IC
P
R E
S S
U R
E in . w
.c
SCFM
1050 1200
.15
NOM.
CLG
NOM.
HTG
DUCT
SYSTEMS
A09339
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
500 600 700 800 900 1000 1100 1200 1300
E X
T E
R N
A L
S
TA
T
IC
P R
E S
S U
R E in
. w .c
SCFM
AIRFLOW PERFORMANCE
030024018 036
Hi Cooling
A09340
FV4CNF002
——— Nominal Cooling and Heat Pump Efficiency airflow for each size selection. Airflow can be adjusted +15% to -10%.
---- Nominal Heat Pump Comfort airflow for each size selection. Airflow can be adjusted +15% to -10%.
· - · - Maximum cooling airflow for largest size selection. Adjusted +15% from nominal.
· · · · · · Fixed Duct Systems (See description under Acceptable Duct Conditions.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
600 700 800 900 1000 1100 1200 1300 1400 1500
E X
T E
R N
A L
S
TA
T
IC
P R
E S
S U
R E in
. w .c
SCFM
AIRFLOW PERFORMANCE
030 042024 036
Hi Cooling
A09341
FV4CN(B,F)003
——— Nominal Cooling and Heat Pump Efficiency airflow for each size selection. Airflow can be adjusted +15% to -10%.
---- Nominal Heat Pump Comfort airflow for each size selection. Airflow can be adjusted +15% to -10%.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
700 800 900 1000 1100 1200 1300 1400 1500 1600 1700
E X
T E
R N
A L
S
TA
T
IC
P R
E S
S U
R E in
. w .c
SCFM
AIRFLOW PERFORMANCE
042030 036 048
Hi Cooling
A09342
FV4CN(B,F)005
——— Nominal Cooling and Heat Pump Efficiency airflow for each size selection. Airflow can be adjusted +15% to -10%.
---- Nominal Heat Pump Comfort airflow for each size selection. Airflow can be adjusted +15% to -10%.
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
900 1000 12001100 1300 1400 1500 1600 1700 1800 1900 2000 2100
E X
T E
R N
A L
S
TA
T
IC
P R
E S
S U
R E in
. w .c
SCFM
AIRFLOW PERFORMANCE
036 042 048 060
Hi Cooling
A09343
FV4CNB006
——— Nominal Cooling and Heat Pump Efficiency airflow for each size selection. Airflow can be adjusted +15% to -10%.
---- Nominal Heat Pump Comfort airflow for each size selection. Airflow can be adjusted +15% to -10%.
COOLING CAPACITIES (MBtuh)
UNIT
SIZE
EVAP
COIL
AIR
Cfm
BF
SATURATED TEMPERATURE LEAVING EVAPORATOR (�F / �C)
35 / 2 40 / 4 45 / 7 50 / 10 55 /13
Evaporator Air — Entering Wet-Bulb Temperature
72�F 22�C
67�F 19�C
62�F 17�C
72�F 22�C
67�F 19�C
62�F 17�C
72�F 22�C
67�F 19�C
62�F 17�C
72�F 22�C
67�F 19�C
62�F 17�C
72�F 22�C
67�F 19�C
62�F 17�C
0.04
40 32 26 36 28 22 32 24 18 27 19 14 21 13 11
18 18 19 16 16 17 14 14 15 12 12 13 10 10 11
0.07
50 40 32 45 36 27 39 30 22 33 24 18 26 17 14
21 22 23 19 20 21 16 17 18 14 15 16 12 13 14
0.10
58 49 38 53 42 32 46 35 27 39 28 22 31 20 18
24 26 28 22 24 25 19 21 22 17 19 19 15 16 18
0.11
62 51 41 56 45 35 50 38 29 42 30 24 33 22 20
26 28 31 23 26 28 21 23 25 18 20 21 16 18 20
0.13
67 55 45 61 49 39 54 42 33 46 34 28 37 25 24
29 33 36 27 30 33 24 27 30 22 24 26 19 21 24
0.20
59 48 38 53 42 32 46 35 24 39 27 20 30 18 16
28 29 31 25 27 28 22 23 24 19 20 20 16 16 16
0.22
68 56 45 61 49 37 54 41 29 45 32 25 35 22 20
32 34 37 29 31 33 26 28 28 23 24 25 19 20 20
0.25
75 62 49 68 54 42 60 45 34 50 36 29 40 25 23
35 39 42 32 36 38 29 32 33 26 28 29 22 23 23
0.27
80 67 54 73 59 46 64 49 38 54 39 32 43 28 27
38 43 47 35 39 43 32 36 37 28 32 32 24 26 27
0.04
61 49 39 55 43 33 48 37 27 41 29 20 33 21 17
27 27 28 24 25 25 21 22 22 18 18 18 15 15 15
0.06
74 60 48 67 53 40 59 45 33 50 35 25 39 24 21
32 34 35 29 30 31 25 26 27 22 23 23 18 18 19
0.07
89 72 57 79 63 48 69 52 38 58 41 31 44 29 25
37 39 41 33 35 36 29 31 32 25 26 27 20 22 22
0.10
103 84 66 92 73 56 81 61 46 67 48 39 52 34 31
43 46 49 38 41 44 34 37 39 29 32 33 25 27 27
0.11
110 89 71 99 78 60 86 65 49 72 51 42 56 37 35
45 50 53 41 45 48 36 39 42 31 34 36 27 29 30
0.01
77 62 50 69 55 43 61 47 35 52 38 27 41 27 22
34 36 37 31 32 33 27 28 29 23 25 24 20 20 20
0.02
100 82 65 90 71 55 79 60 45 66 47 37 49 32 27
42 45 47 37 40 42 33 35 37 29 31 32 23 25 24
0.04
117 96 77 106 84 65 93 71 53 78 56 46 60 40 34
48 53 57 44 48 52 39 43 46 34 38 39 29 31 31
0.05
126 103 83 114 91 71 99 76 59 84 60 50 65 44 39
52 58 63 48 53 57 43 47 51 37 42 43 33 35 35
0.06
132 108 87 119 95 75 105 80 63 88 63 54 70 47 42
55 62 68 50 57 61 45 51 54 40 45 46 35 39 38
BF - Bypass Factor
- Sensible Heat Capacity (1000 Btuh)
- Gross Cooling Capacity (1000 Btuh)
NOTES:
1. Contact manufacturer for cooling capacities at conditions other than shown in table.
2. Formulas:
Leaving db = entering db −sensible heat cap.
1.09 x CFM Leaving wb = wb corresponding to enthalpy of air leaving coil (hlwb) hlwb = hewb −total capacity (Btuh)
4.5 x CFM where hewb = enthalpy of air entering coil. Direct interpola-tion is permissible. Do not extrapolate.
3. SHC is based on 80�F db temperature of air entering coil.
Below 80�F db, subtract (Correction Factor x CFM) from
SHC. Above 80�F db, add (Correction Factor x CFM) to
SHC.
4. Bypass Factor = 0 indicates no psychometric solution. Use bypass factor of next lower EWB for approximation.
SHC CORRECTION FACTOR
BYPASS
FACTOR
ENTERING AIR DRY-BULB TEMPERATURE �F (�C)
79 (26) 78 (26) 77 (25) 76 (24) 75 (24) Under 75 (24)
81 (27) 82 (28) 83 (28) 84 (29) 85 (29) Over 85
Correction Factor
0.10 .098 1.96 2.94 3.92 4.91 Use formula shown below
0.20 0.87 1.74 2.62 3.49 4.36
0.30 0.76 1.53 2.29 3.05 3.82
Interpolation is permissible.
Correction Factor = 1.09 x (1 - BF) x (db - 80)
ESTIMATED SOUND POWER LEVEL (dBA)*
UNIT
SIZE
CONDITIONS OCTAVE BAND CENTER FREQUENCY
CFM ESP 63 125 250 500 1000 2000 4000
FV-002
400 0.25 63.0 59.0 55.0 52.0 50.0 48.0 44.0
600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7
800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0
1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0
1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8
1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4
FV-003
400 0.25 63.0 59.0 55.0 52.0 50.0 48.0 44.0
600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7
800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0
1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0
1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8
1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4
636 0.25 65.0 61.0 57.0 54.0 52.0 50.0 46.0
FV-005
400 0.25 63.0 59.0 55.0 52.0 50.0 48.0 44.0
600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7
800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0
1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0
1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8
1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4
1600 0.25 69.0 65.0 61.0 58.0 56.0 54.0 50.0
FV-006
600 0.25 64.7 60.7 56.7 53.7 51.7 49.7 45.7
800 0.25 66.0 62.0 58.0 55.0 53.0 51.0 47.0
1000 0.25 67.0 63.0 59.0 56.0 54.0 52.0 48.0
1200 0.25 67.8 63.8 59.8 56.8 54.8 52.8 48.8
1400 0.25 68.4 64.4 60.4 57.4 55.4 53.4 49.4
1600 0.25 69.0 65.0 61.0 58.0 56.0 54.0 50.0
1800 0.25 69.5 65.5 61.5 58.5 56.5 54.5 50.5
2000 0.25 70.0 66.0 62.0 59.0 57.0 55.0 51.0
2150 0.25 70.3 66.3 62.3 59.3 57.3 55.3 51.3
* Estimated sound power levels have been derived using the method described in the 1987 ASHRAE Systems & Applications Handbook, chapter 52, p. 52.7.
CFM - Cubic Ft Per Minute
ESP - External Static Pressure (in. w.c.)
RPM - Revolutions Per Minute
AIRFLOW PERFORMANCE CORRECTION FACTORS
HEATER kW ELEMENTS
STATIC PRESSURE
CORRECTION (in. wc)
Sizes 002–005 Size 006
0 0 +.02 +.03
5 1 +.01 +.02
8, 10 2 0 0
9, 15 3 –.02 –.03
20 4 –.04 –.06
18, 24, 30 6 –.06 –.10 The FV4C airflow performance table was developed using fan coils with 10-kW electric heaters (2 elements) in the units. For fan coils with heaters made up of a different number of elements, the external available static at a given CFM from the table may be corrected by adding or subtracting pressure. Use table for this correction.
FACTORY−INSTALLED FILTER STATIC PRESSURE DROP (in. wc)
UNIT
SIZE
CFM
400 600 800 1000 1200 1400 1600 1800 2000
002 0.020 0.044 0.048 0.072 0.100 — — — —
003 — 0.020 0.035 0.051 0.070 0.092 — — —
005 — — 0.035 0.051 0.070 0.092 0.120 — —
006 — — — 0.038 0.053 0.070 0.086 0.105 0.133
AIR DELIVERY PERFORMANCE CORRECTION COMPONENT PRESSURE DROP (IN. WC)
AT INDICATED AIRFLOW (DRY TO WET COIL)
UNIT
SIZE
CFM
600 700 800 900 1000 1100 1200 1300 1400 1500 1600
002 0.012 0.016 0.022 0.028 0.034 0.040 0.049 — — — —
003 — 0.026 0.034 0.042 0.052 0.063 0.075 0.083 0.091 0.098 0.110
005 — 0.006 0.008 0.010 0.012 0.015 0.017 0.020 0.023 0.027 0.030
CFM
1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100
006 0.013 0.016 0.018 0.020 0.023 0.027 0.030 0.034 0.039 0.044 0.048
UNITS WITHOUT ELECTRICAL HEAT
UNIT SIZE VOLTS-PHASE FLA
MIN
CKT
AMPS
BRANCH CIRCUIT
Min Wire Size Awg*
Fuse/Ckt Bkr Amps
002 208/230-1 4.3 5.4 14 15
003 208/230-1 4.3 5.4 14 15
005 208/230-1 4.3 5.4 14 15
006 208/230-1 6.8 8.5 14 15
* Use copper wire only to connect unit. If other than uncoated (non-plated) 75°C copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than
10 AWG) is used consult applicable tables of the National Electric Code (ANSI/NFPA 70).
NOTE: If branch circuit wire length exceeds 100 ft, consult NEC 210-19a to determine maximum wire length. Use 2% voltage drop.
FLA — Full Load Amps
ELECTRIC HEATERS
HEATER
PART NO.
kW @ 240V
VOLTS/
PHASE
STAGES (kW
OPERATING)
INTERNAL
CIRCUIT
PROTECTION
FAN COIL
SIZE USED
WITH
HEATING
CAP. @
230V‡
INTELLIGENT
HEAT
CAPABLE†† (kW
OPERATING)
KFCEH0501N05 5 230/1 5 None All 15,700 —
KFCEH0801N08 8 230/1 8 None All 25,100 —
KFCEH0901N10 10 230/1 10 None All 31,400 —
KFCEH3001F15 15 230/1 5, 15 Fuses** All 47,100 5, 10, 15
KFCEH3201F20 20 230/1 5, 20 Fuses** All 62,800 5, 10, 15, 20
KFCEH2901N09 9 230/1* 3, 9 None All 28,300 3, 6, 9
KFCEH1601315 15 230/3 5, 15 None All 47,100 —
KFCEH2001318 18 230/3 6, 12, 18 None All 56,500 —
KFCEH3401F24 24 230/3† 8, 16, 24 Fuses 005, 006 78,500 8, 16, 24
KFCEH3501F30 30 230/3† 10, 20, 30 Fuses 005, 006 94,200 10, 20, 30
KFCEH2401C05 5 230/1 5 Ckt Bkr All 15,700 —
KFCEH2501C08 8 230/1 8 Ckt Bkr All 25,100 —
KFCEH2601C10 10 230/1 10 Ckt Bkr All 31,400 —
KFCEH3101C15 15 230/1 5, 15 Ckt Bkr All 47,100 5, 10, 15
KFCEH3301C20 20 230/1 5, 20 Ckt Bkr All 62,800 5, 10, 15, 20
* Field convertible to 3 phase.
† These heaters field convertible to single phase.
‡ Blower motor heat not included.
** Single point wiring kit required for these heaters in Canada.
†† Heaters designated with kW Operating Values are Intelligent Heat capable when used with compatible thermostat.
ELECTRIC HEATER INTERNAL PROTECTION
HEATER kW FUSES QTY/SIZE CKT BKR QTY/SIZE*
5 — 1/60
8 — 1/60
9 — —
10 — 1/60
15 2/30, 2/60 2/60
15 — —
18 — —
20 4/60 2/60
24 6/60 —
30 6/60 —
* All circuit breakers are 2 pole.
A C
C E
SS
O
R Y
E L
E C
T R
IC
H
E A
T E
R E
L E
C T
R
IC
A L
D A
TA
H E
A T
E R
P A
R T
N O k W
P H A S E
IN
T
E R
N A
L C
IR
C
U
IT
P R
O T
E C
T
IO
N
H E
A T
E R
A M
P S
/2
V
B R
A N
C H
C
IR
C U
IT
M in
A m p a c it y
/2
V
M in
W ir e S iz e
A
W G
/2
V
M in
G n d W ir e
S iz e
/2
V
M a x F u s e
/C k t
B k r
A m p s
/2
V
M a x W ir e
L e n g th
/2
V ft
S in g le
C ir c u it
D u a l C ir c u it S in g le C ir c u it
D u a l C ir c u it S in g le C ir c u it
D u a l C ir c u it S in g le C ir c u it
D u a l C ir c u it S in g le C ir c u it
D u a l C ir c u it S in g le C ir c u it
D u a l C ir c u it v v
L ,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
K F
C E
H N
.8
N o n e
.1 /2
.0
.2 /3
.5
/8
/1
/3
/8
K F
C E
H C
.8
C k t
B k r
.1 /2
.0
.2 /3
.5
/8
/1
/3
/8
K F
C E
H N
.0
N o n e
.9 /3
.0
.7 /4
.5
/8
/1
/5
/6
K F
C E
H C
.0
C k t
B k r
.9 /3
.0
.7 /4
.5
/8
/1
/5
/6
K F
C E
H N
.8
N o n e
.8 /3
.0
.5 /5
.5
/6
/1
/6
/8
K F
C E
H N
.8
N o n e
.8 /2
.8
.0 /3
.5
/8
/1
/3
/8
K F
C E
H N
.5
N o n e
.2
/4
.0
.8
/5
.5
/6
/1
/6
/8
K F
C E
H C
.5
C k t
B k r
.2 /4
.0
.8 /5
.5
/6
/1
/6
/8
K F
C E
H F
.3
F u s e
.2 /5
.9
.2 /4
.0
.1 /2
.0
.3 /8
.4
.8 /5
.5
.7 /2
.0
/4
/6
/1
/8
/1
/1
/9
/6
/2
/8
/8
/7
K F
C E
H C
.3
C k t
B k r
.2
/4
.0
.1
/2
.0
.8 /5
.5
.7 /2
.0
/6
/1
/1
/1
/6
/2
/8
/7
K F
C E
H
.3
N o n e
.3 /3
.6
.7 /5
.8
/6
/1
/6
/9
K F
C E
H
.5
N o n e
.6 /4
.5
.5 /6
.4
/6
/8
/7
/7
K F
C E
H F
.0
F u s e
.3 /7
.9
.2 /4
.0
.2 /4
.0
.9 /1
.4
.8
/5
.5
.3
/5
.0
/2
/6
/8
/6
/1
/1
/1
/6
/5
/1
/8
/5
K F
C E
H C
.0
C k t
B k r
.2
/4
.0
.2
/4
.0
.8 /5
.5
.3 /5
.0
/6
/8
/1
/1
/6
/5
/8
/5
K F
C E
H F
.0
F u s e
.1 /5
.4
.2 /7
.8
/4
/8
/8
/9
.0
F u s e
.7 /9
.5
.9
/1
.9
/1
/6
/1
/1
K F
C E
H F
.5
F u s e
.6 /6
.2
.8 /9
.0
/3
/8
/1
/9
.5
F u s e
.0
/1
.0
.8
/1
.5
/0
/6
/1
/1
FI
E
L D
M U
LT
IP
O
IN
T W
IR
IN
G O
F
A N
D
0− kW
S
IN
G L
E P
H A
SE
H E
A T
E R
P A
R T
N O k W
P H A S E
H E
A T
E R
A M
P S
/2
V
M
IN
A M
P A
C
IT
Y /2
V
M
IN
W
IR
E S
IZ
E
A
W G
/2
V
M
IN
G N
D W
IR
E
S
IZ
E /2
V
M A
X F
U S
E /C
K T
B K
R A
M P
S /2
V
M A
X W
IR
E
L E
N G
T H
/2
V
F
T
V
V
L ,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
L
,L
K F
C E
H
F
.0
.9 /3
.0
.9 /3
.0
.9 /3
.0
.7 /4
.5
.2 /4
.0
.2 /4
.0
/8
/8
/8
/1
/5
/4
/4
/6
/7
/7
K F
C E
H
F
.5
.2 /4
.0
.2 /4
.0
.2 /4
.0
.8 /5
.5
.3 /5
.0
.3 /5
.0
/6
/8
/8
/1
/6
/5
/5
/8
/5
/5
H e a te rs a re I n te lli g e n t H e a t c a p a b le w h e n u s e d w it h t h e F
V f a n c o il a n d C o m fo rt
Z o n e I I� o r
In fi n it y C o n tr o l�
F ie ld c o n v e rt ib le t o p h a s e s in g le o r m u lt ip le s u p p ly c ir c u it
F ie ld c o n v e rt ib le t o p h a s e
In c lu d e s b lo w e r m o to r a m p s o f la rg e s t fa n c o il u s e d w it h h e a te r.
C o p p e r w ir e m u s t b e u s e d
If o th e r th a n u n c o a te d n o n p la te d
C c o p p e r w ir e s o lid w ir e f o r
A
W G a n d s m a lle r, s tr a n d e d w ir e f o r la rg e r th a n
A W
G is u s e d c o n s u lt a p p lic a b le t a b le s o f th e N a ti o n a l E le c tr ic C o d e
A N
S I/
N F
P A
L e n g th s h o w n i s a s m e a s u re d w a y a lo n g w ir e p a th b e tw e e n u n it a n d s e rv ic e p a n e l fo r a v o lt a g e d ro p n o t to e xc e e d
N O
T E
S
S in g le c ir c u it a p p lic a ti o n o f F a n d
F h e a te rs r e q u ir e s s in g le p o in t w ir in g k it a c c e s s o ry
ACCESSORIES
ITEM ACCESSORY PART NO.* FAN COIL SIZE USED WITH
1. Disconnect Kit KFADK0201DSC Cooling controls and heaters 3- through 10-kW
2. Downflow Base Kit
KFACB0201CFB 002
KFACB0301CFB 003, 005
KFACB0401CFB 006
3. Downflow Conversion Kit
KFADC0201SLP 003
KFADC0401ACL 002, 005, 006
4. Single-Point Wiring Kit KFASP0101SPK Only with 15- and 20-kW Fused Heaters
5. Filter Kit (12 Pack)
KFAFK0212MED 002
KFAFK0312LRG 003, 005
KFAFK0412XXL 006
6.
Fan Coil Filter Cabinet (Fan Coil Filter Media)
FNCCABCC0017
(FILCCFNC0017)
FNCCABCC0021
(FILCCFNC0021)
003, 005
FNCCABCC0024
(FILCCFNC0024)
7.
Infinity� Air Purifier
(Infinity� Purifier Replacement Cartridge)
GAPABXCC1620
(GAPCCCAR1620)
GAPABXCC2020
(GAPCCCAR2020)
003, 005
GAPABXCC2420
(GAPCCCAR2420)
8. PVC Condensate Trap Kit (50 pack) KFAET0150ETK All
9. Air Cleaner 240-volt Conversion Kit KEAVC0201240 All
10. Downflow/Horizontal Conversion Gasket Kit KFAHD0101SLP All
11. ECM Motor Test KFASD0301VSP All
12. Horizontal Water Management Kit (25 pack) KFAHC0125AAA All
13. Standard Filter Rack Kit
KFAFR0101FRM NA
KFAFR0201FRM 002
KFAFR0301FRM 003, 005
KFAFR0401FRM 006
14. Door Gasket Kit ** 344994-751 All
* Factory authorized and listed, field installed.
** This kit is for replacement of factory installed gaskets if they are damaged or removed from the fan coil.
Accessory Kits Description Suggested and Required Use
1. Disconnect Kit
The kit is used to disconnect electrical power to the fan coil so service or maintenance may be performed safely.
SUGGESTED USE: Units for 3− through 10−kW electric resistance heaters and cooling controls.
2. Downflow Base Kit This kit is designed to provide a 1−in. (25MM) minimum clearance between unit discharge plenum, ductwork, and combustible mater-ials. It also provides a gap−free seal with the floor.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
3. Downflow Conversion Kit Fan coils are shipped from the factory for upflow or horizontal−left applications. Downflow conversion kits provide proper condensate water drainage and support for the coil when used in downflow applications. Separate kits are available for slope coils and A−coils.
REQUIRED USE: This kit must be used whenever fan coils are used in downflow applications.
4. Single Point Wiring Kit The single point wiring kit acts as a jumper between L1 and L3 lugs, and between the L2 and L4 lugs. This allows the installer to run 2 heavy−gauge, high−voltage wires into the fan coil rather than 4 light−gauge, high−voltage wires.
SUGGESTED USE: Fan coils with 15− and 20−kW fused heaters only.
5. Filter Kit (12 pack) The kit consists of 12 fan coil framed filters. These filters collect large dust particles from the return air entering the fan coil and prevents them from collecting on the coil. This process helps to keep the coil clean, which increases heat transfer and, in turn, the efficiency of the system.
SUGGESTED USE: To replace filters in fan coils.
REQUIRED USE: All units unless a filter grille is used.
6. Fan Coil Filter Cabinet This cabinet is mounted to the fan coil on the return air end and designed to slip over the outer fan coil casing. The cabinets are insulated using the same insulation as production fan coils. They are designed for the removal of particulates from indoor air using FILCCFNC00(14, 17, 21, 24) media filter cartridges. These fan coil media filter cartridge kits are designed for the removal of particles from indoor air. The cartridge is installed in the return air duct next to the air handler or further upstream.
SUGGESTED USE: All fan coils.
ACCESSORIES (cont)
7. Infinity� Air Purifier
The Infinity Air Purifier wires directly to fan coil and requires no duct transitions with Carrier units. These purifiers both capture and kill airborne viruses, bacteria, mold spores, and allergens. It comes with an airflow sensor. Maintenance is limited to replacement of the purification cartridge, GAPCCAR (1620/2020 or 2420), and inspection/brush cleaning of the ionization array.
SUGGESTED USE: All fan coils.
8. Condensate Drain Trap Kit This kit consists of 50 PVC condensate traps. Each trap is pre−formed and ready for field installation. This deep trap helps the system make and hold proper condensate flow even during blower initiation.
SUGGESTED USE: All fan coils.
9. Air Cleaner 240−volt Conversion Kit The AIRA electronic air cleaner comes ready for 115−v operation.
REQUIRED USE: This kit is required when running 240−volt circuit to air cleaner.
10. Downflow/Horizontal Conversion Gasket Kit This kit provides the proper gasketing of units when applied in either a downflow (FE4A or FE5A) or horizontal (FE4A only) applica-tion.
REQUIRED USE: Fan coils in either downflow or horizontal applications.
11. ECM Motor Test Kit Operates variable speed blower at several speeds independent of circuit board and wiring harness.
12. Horizontal Water Management Kit This kit provides proper installation of fan coils under conditions of high static pressure and high relative humidty.
SUGGESTED USE: All fan coils.
13. Standard Filter Rack Kit This kit mounts in fan coil filter rack area and modifies the existing filter rack to support standard 1−in. filter sizes.
SUGGESTED USE: Fan coils using standard filter sizes.
14. Door Gasket Kit This kit consists of specific adhesive−backed foam strips which are applied to the unit door and frame, limiting air leakage.
Copyright 2019 Carrier Corp. � 7310 W. Morris St. � Indianapolis, IN 46231 Edition Date: 07/19 U.S. Export Classification: EAR99.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: FV4C-05PD
Replaces: FV4C-04PD
File details come from the government source that posted it. Updated .