Mini_Split_Outdoor_Unit_Specs_0001.pdf
PDF 25 KB Posted
- Attached to
- PEVI HVAC Replacement
- Solicitation number
- 140P6425Q0103
About this file
This document is a Mini-Split Outdoor Unit Schedule detailing technical specifications for an HVAC system component. The schedule provides comprehensive data for an outdoor unit (IMS-1) with specific operating characteristics: cooling range from 126°F to -22°F, using R-410A refrigerant, with a cooling capacity of 10.9 MBH at 47°F and a heating capacity of 9 MBH at 95°F. Electrical specifications include 230V single-phase power, with 15 MCA and 15 MOCP at 60 Hz. The contractor is required to install a 6" concrete or composite maintenance pad and a 12" stand, and provide the unit with a base pan, base pan heater, factory-insulated refrigerant lines, and wind baffles.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COOLING HEATING VOLT PHASE MCA MOCP HZ
IMS-1 126°F -22°F R-410A 10.9 @ 47°F 230 single 15 15 60 1 2
1.
2. PROVIDE WITH BASE PAN AND BASE PAN HEATER, FACTORY INSULATED REFRIGERANT LINES, WIND BAFFLES.
ELECTRICAL DATA MANUFACTURER AND MODEL
NO. OR EQUAL RMKS
MINI-SPLIT OUTDOOR UNIT SCHEDULE
CONTRACTOR SHALL INSTALL 6" CONCRETE OR COMPOSITE MAINTENANCE PAD, 12" STAND.
GUARANTEED OPERATING RANGE COOLING CAP.
TOTAL MBH
9 @ 95°F
REFR.
OMS-1
HEATING CAP. MIN. @
AMB. TEMP.MARK INDOOR UNIT
Sheet1