Mini_Split_Outdoor_Unit_Specs_0001.pdf

PDF 25 KB Posted

Attached to
PEVI HVAC Replacement Federal contract opportunity
Solicitation number
140P6425Q0103
Issued by
Department of the Interior National Park Service Midwest Region

About this file

This document is a Mini-Split Outdoor Unit Schedule detailing technical specifications for an HVAC system component. The schedule provides comprehensive data for an outdoor unit (IMS-1) with specific operating characteristics: cooling range from 126°F to -22°F, using R-410A refrigerant, with a cooling capacity of 10.9 MBH at 47°F and a heating capacity of 9 MBH at 95°F. Electrical specifications include 230V single-phase power, with 15 MCA and 15 MOCP at 60 Hz. The contractor is required to install a 6" concrete or composite maintenance pad and a 12" stand, and provide the unit with a base pan, base pan heater, factory-insulated refrigerant lines, and wind baffles.

View the file

Other files for this federal contract opportunity

Other files attached to PEVI HVAC Replacement, newest first.
File Type Posted
Sol_140P6425Q0103_Amd_0002.pdf PDF
Questions___Answers_0002.pdf PDF
Air_Cooled_Heat_Pump_Specs_0001.pdf PDF
Sol_140P6425Q0103_Amd_0001.pdf PDF
Electric_Baseboard_Heat_Specs_0001.pdf PDF
Heat_Pump_Air_Handler_Schedule__Specs_0001.pdf PDF
Mini_Split_Indoor_Unit__Specs_0001.pdf PDF
Combined_Synopsis.pdf PDF
Suggested_Product_-_Fan_Coil.pdf PDF
SCA_WD_-_Ottawa_County__OH.pdf PDF
Suggested_Product_-_Electric_Baseboard_Heater.pdf PDF
Price_Schedule.xlsx XLSX spreadsheet
Statement_of_Work.pdf PDF
Suggested_Product_-_Mini_Split.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COOLING HEATING VOLT PHASE MCA MOCP HZ

IMS-1 126°F -22°F R-410A 10.9 @ 47°F 230 single 15 15 60 1 2

1.

2. PROVIDE WITH BASE PAN AND BASE PAN HEATER, FACTORY INSULATED REFRIGERANT LINES, WIND BAFFLES.

ELECTRICAL DATA MANUFACTURER AND MODEL

NO. OR EQUAL RMKS

MINI-SPLIT OUTDOOR UNIT SCHEDULE

CONTRACTOR SHALL INSTALL 6" CONCRETE OR COMPOSITE MAINTENANCE PAD, 12" STAND.

GUARANTEED OPERATING RANGE COOLING CAP.

TOTAL MBH

9 @ 95°F

REFR.

OMS-1

HEATING CAP. MIN. @

AMB. TEMP.MARK INDOOR UNIT