This document is a detailed specification sheet for electric baseboard heaters, providing comprehensive physical and electrical data for 16 different heating units across various rooms in a building. The heaters are constructed with 80% Nickel and 20% Chromium, with consistent specifications including 1 kW power, 240/208V voltage, 60 Hz frequency, and similar dimensional measurements (2.875" width, 6.75" height). Each unit is designed for a specific room location such as laundry, living areas, bedrooms, bathrooms, sun rooms, and dining areas, with weights ranging from 10 to 23 pounds. The specification includes three key technical remarks: the heaters must have an automatic overheat shutoff with temperature reactivation, be fabricated from minimum .024-inch steel with .035-inch steel control boxes, and feature heating elements encased in steel sheaths with aluminum fins.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P6425Q0103_Amd_0002.pdf | ||
| Questions___Answers_0002.pdf | ||
| Mini_Split_Outdoor_Unit_Specs_0001.pdf | ||
| Air_Cooled_Heat_Pump_Specs_0001.pdf | ||
| Sol_140P6425Q0103_Amd_0001.pdf | ||
| Heat_Pump_Air_Handler_Schedule__Specs_0001.pdf | ||
| Mini_Split_Indoor_Unit__Specs_0001.pdf | ||
| Combined_Synopsis.pdf | ||
| Suggested_Product_-_Fan_Coil.pdf | ||
| SCA_WD_-_Ottawa_County__OH.pdf | ||
| Suggested_Product_-_Electric_Baseboard_Heater.pdf | ||
| Price_Schedule.xlsx | XLSX spreadsheet | |
| Statement_of_Work.pdf | ||
| Suggested_Product_-_Mini_Split.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
KW VOLTS PHASE HERTZ L (IN.) W (IN.) H (IN.) WEIGHT (LB)
BBH-1 Laundry 80% Ni 20% Cr 1 200/1504 240/208 1 60 96 2.875 6.75 18.5 1 2 3
BBH-2 Living 80% Ni 20% Cr 1 1250/940 240/208 1 60 120 2.875 6.75 23 1 2 3
BBH-3 Living 80% Ni 20% Cr 1 1000/752 240/208 1 60 48 2.875 6.75 10 1 2 3
BBH-4 Living 80% Ni 20% Cr 1 1000/752 240/208 1 60 48 2.875 6.75 10 1 2 3
BBH-5 Bedroom 1 80% Ni 20% Cr 1 1500/1128 240/208 1 60 72 2.875 6.75 14 1 2 3
BBH-6 Bedroom1 80% Ni 20% Cr 1 1500/1128 240/208 1 60 72 2.875 6.75 14 1 2 3
BBH-7 Bedroom2 80% Ni 20% Cr 1 200/1504 240/208 1 60 96 2.875 6.75 18.5 1 2 3
BBH-8 Bedroom2 80% Ni 20% Cr 1 200/1504 240/208 1 60 96 2.875 6.75 18.5 1 2 3
BBH-9 Barhroom 80% Ni 20% Cr 1 1250/940 240/208 1 60 60 2.875 6.75 11.5 1 2 3
BBH-10 Bedroom3 80% Ni 20% Cr 1 1250/940 240/208 1 60 60 2.875 6.75 11.5 1 2 3
BBH-11 Bedroom3 80% Ni 20% Cr 1 1500/1128 240/208 1 60 72 2.875 6.75 14 1 2 3
BBH-12 Bathroom 80% Ni 20% Cr 1 1250/940 240/208 1 60 60 2.875 6.75 11.5 1 2 3
BBH-13 SunRoom 80% Ni 20% Cr 1 1500/1128 240/208 1 60 72 2.875 6.75 14 1 2 3
BBH-14 SunRoom 80% Ni 20% Cr 1 1250/940 240/208 1 60 60 2.875 6.75 11.5 1 2 3
BBH-15 SunRoom 80% Ni 20% Cr 1 1000/752 240/208 1 60 48 2.875 6.75 10 1 2 3
BBH-16 Dining 80% Ni 20% Cr 1 1000/752 240/208 1 60 48 2.875 6.75 10 1 2 3
RMKS.
ELECTRIC BASEBOARD HEAT
PHYSICAL DATA
1. PROVIDE WITH OVERHEAT AUTOMATIC SHUTOFF WITH REACTIVATION UPON RETURN TO NORMAL TEMPERATURE.
2. THE HEATERS SHALL BE FABRICATED OF MINIMUM .024 INCH STEEL WITH MINIMUM .035 INCH STEEL CONTROL BOXES. JUNCTION BOX ENCLOSURE TO HAVE PROVISIONS FOR INCOMING AND OUTGOING CABLE WITH CABLE CLAMP FOR RESTRAINING WITHOUT ADDITIONAL HARDWARE. GROUND WIRE PIGTAIL PROVIDED IN EACH JUNCTION BOX FOR
GROUNDING.
3. HEATING ELEMENT SHALL BE ENCASED IN STEEL SHEATH. HEATING ELEMENT SHALL HAVE ALUMINUM FINS.
MARK ROOM ELEMENT
NO. OF
ELEMENTS
ELECTRIC DATA MANUFACTURER AND MODEL
NO. OR EQUAL
Sheet1