About this file

This document is a Heat Pump Air Handler Schedule detailing specifications for two air handling units (AHU-1 and AHU-2). Both units have identical configurations with a 1400/1260 CFM airflow, 0.5 HP fan motor, and an external static pressure of -0.02 inches of water gauge. They feature 1" MERV 8 or MERV 13 filters, single-phase 230V electrical systems, and operate with entering air temperatures of 80°F dry bulb and 67°F wet bulb. Each unit has specific physical dimensions (approximately 21.5" x 23.5" for AHU-1 and 21.5" x 21" for AHU-2) and an operating weight of around 1-2 pounds. The schedule includes additional technical details such as cooling and heating coil data, electric data, and supplemental electric heat information, with notes indicating electrically commutated motors and throwaway filter types.

View the file

Other files for this federal contract opportunity

Other files attached to PEVI HVAC Replacement, newest first.
File Type Posted
Sol_140P6425Q0103_Amd_0002.pdf PDF
Questions___Answers_0002.pdf PDF
Mini_Split_Outdoor_Unit_Specs_0001.pdf PDF
Mini_Split_Indoor_Unit__Specs_0001.pdf PDF
Sol_140P6425Q0103_Amd_0001.pdf PDF
Electric_Baseboard_Heat_Specs_0001.pdf PDF
Air_Cooled_Heat_Pump_Specs_0001.pdf PDF
Combined_Synopsis.pdf PDF
Suggested_Product_-_Fan_Coil.pdf PDF
Price_Schedule.xlsx XLSX spreadsheet
Statement_of_Work.pdf PDF
Suggested_Product_-_Mini_Split.pdf PDF
Suggested_Product_-_Electric_Baseboard_Heater.pdf PDF
SCA_WD_-_Ottawa_County__OH.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E.A.T.

DB °F

E.A.T.

WB °F

TOTAL

(MBH)

SENSIBLE

(MBH)

E.A.T.

DB °F

E.A.T.

WB °F

TOTAL

(MBH) VOLTS PHASE FREQUENCY VOLTS KW STAGES MCA MOCP

L

(IN.)

W

(IN.)

H

(IN.)

OPERATING

WEIGHT (LB)

AHU-1 iQMIS

000003 1400/1260 -0.02 .5 HP 80 67 70 60 1" MERV 8

OR MERV 13 230 single 60 230/1 15 2 10 60 21 1/2 23 1/2 57 1/4 1 2

AHU-2 iQMIS

000016 1400/1260 -0.02 .5HP 80 67 70 60 1" MERV 8

OR MERV 13 230 single 60 230/1 15 2 10 60 21 1/2 21 45 1/4 1 2

MANUFACTUER AND MODEL

NUMBER OR EQUAL RMKS.

HEAT PUMP AIR HANDLER SCHEDULE

FILTER

DEPTH &

MERV

1. ELECTRICALLY COMUTATED MOTOR.

2. THROW AWAY FILTER.

E.A.T.: ENTERING AIR TEMPERATURE; DB: DRY BULB; WB: WET BULB; MOCP: MAXIMUM OVERCURRENT PROTECTION; MCA: MINIMUM CIRCUIT AMPACITY; KW: KILOWATTS

SERVESMARK

AIRFOW

(CFM)

MINIMUM

EXTERNAL STATIC

PRESSURE (IN. W.G.)

FAN

MOTOR

(HP)

ELECTRIC DATA SUPPLEMENTAL ELECTRIC HEATCOIL DATA COOLING COIL DATA HEATING PHYSICAL SIZE