About this file

This document is a technical specification table for two air-cooled heat pumps (HP-1 and HP-2) serving AHU-1 and AHU-2. The heat pumps are specified with key technical details including refrigerant type (R-32/R-454B), cooling and heating capacities, electrical requirements, and physical dimensions. Each unit has a total cooling capacity of 48 MBH, total heat capacity of 125 MBH, and operates at ambient temperatures ranging from 14.3°F to 66°F. The electrical specifications include 230V, 1-phase, 60 Hz power with a minimum circuit ampacity of 33.5 and maximum overcurrent protection of 50. Additional installation requirements include a low ambient kit, crankcase heater, compressor vibration isolation, and mounting on a 6-inch concrete or composite maintenance pad with a 12-inch heat pump stand.

View the file

Other files for this federal contract opportunity

Other files attached to PEVI HVAC Replacement, newest first.
File Type Posted
Questions___Answers_0002.pdf PDF
Sol_140P6425Q0103_Amd_0002.pdf PDF
Sol_140P6425Q0103_Amd_0001.pdf PDF
Electric_Baseboard_Heat_Specs_0001.pdf PDF
Mini_Split_Outdoor_Unit_Specs_0001.pdf PDF
Heat_Pump_Air_Handler_Schedule__Specs_0001.pdf PDF
Mini_Split_Indoor_Unit__Specs_0001.pdf PDF
Suggested_Product_-_Electric_Baseboard_Heater.pdf PDF
SCA_WD_-_Ottawa_County__OH.pdf PDF
Combined_Synopsis.pdf PDF
Suggested_Product_-_Fan_Coil.pdf PDF
Price_Schedule.xlsx XLSX spreadsheet
Statement_of_Work.pdf PDF
Suggested_Product_-_Mini_Split.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VOLTS PHASE FREQUENCY

MINIMUM CIRCUIT

AMPACITY

MAXIMUM OVERCURRENT

PROTECTION

L

(IN.)

W

(IN.)

H

(IN.)

OPERATING

WEIGHT (LB)

HP-1 AHU-1 48 125 66 R-32/R-454B 14.3 7.5 230 1 60 33.5 50 1 2

HP-2 AHU-2 48 125 66 R-32/R-454B 14.3 7.5 230 1 60 33.5 50 1 2

1. PROVIDE WITH LOW AMBIENT KIT, CRANKCASE HEATER, COMPRESSOR VIBRATION ISOLATION. PROVIDE

2. INSTALL ON 6" CONCRETE OR COMPOSITE MAINTENANCE PAD AND 12" HEAT PUMP STAND.

ELECTRICAL DATA

MINIMUM

HSPF2 RMKS

REFRIGERANT

TYPE

MINIMUM

SEER2

AIR COOLED HEAT PUMP

MANUFACTUER AND MODEL

NUMBER OR EQUAL

PHYSICAL SIZETOTAL HEAT

CAPACITY

(MBH)

HEATING

AMBIENT

TEMP. (°F)MARK SERVES

TOTAL COOLING

CAPACITY (MBH)

COOLING

AMBIENT

TEMP. (°F)