Air_Cooled_Heat_Pump_Specs_0001.pdf
PDF 26 KB Posted
- Attached to
- PEVI HVAC Replacement Federal contract opportunity
- Solicitation number
- 140P6425Q0103
About this file
This document is a technical specification table for two air-cooled heat pumps (HP-1 and HP-2) serving AHU-1 and AHU-2. The heat pumps are specified with key technical details including refrigerant type (R-32/R-454B), cooling and heating capacities, electrical requirements, and physical dimensions. Each unit has a total cooling capacity of 48 MBH, total heat capacity of 125 MBH, and operates at ambient temperatures ranging from 14.3°F to 66°F. The electrical specifications include 230V, 1-phase, 60 Hz power with a minimum circuit ampacity of 33.5 and maximum overcurrent protection of 50. Additional installation requirements include a low ambient kit, crankcase heater, compressor vibration isolation, and mounting on a 6-inch concrete or composite maintenance pad with a 12-inch heat pump stand.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions___Answers_0002.pdf | ||
| Sol_140P6425Q0103_Amd_0002.pdf | ||
| Sol_140P6425Q0103_Amd_0001.pdf | ||
| Electric_Baseboard_Heat_Specs_0001.pdf | ||
| Mini_Split_Outdoor_Unit_Specs_0001.pdf | ||
| Heat_Pump_Air_Handler_Schedule__Specs_0001.pdf | ||
| Mini_Split_Indoor_Unit__Specs_0001.pdf | ||
| Suggested_Product_-_Electric_Baseboard_Heater.pdf | ||
| SCA_WD_-_Ottawa_County__OH.pdf | ||
| Combined_Synopsis.pdf | ||
| Suggested_Product_-_Fan_Coil.pdf | ||
| Price_Schedule.xlsx | XLSX spreadsheet | |
| Statement_of_Work.pdf | ||
| Suggested_Product_-_Mini_Split.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VOLTS PHASE FREQUENCY
MINIMUM CIRCUIT
AMPACITY
MAXIMUM OVERCURRENT
PROTECTION
L
(IN.)
W
(IN.)
H
(IN.)
OPERATING
WEIGHT (LB)
HP-1 AHU-1 48 125 66 R-32/R-454B 14.3 7.5 230 1 60 33.5 50 1 2
HP-2 AHU-2 48 125 66 R-32/R-454B 14.3 7.5 230 1 60 33.5 50 1 2
1. PROVIDE WITH LOW AMBIENT KIT, CRANKCASE HEATER, COMPRESSOR VIBRATION ISOLATION. PROVIDE
2. INSTALL ON 6" CONCRETE OR COMPOSITE MAINTENANCE PAD AND 12" HEAT PUMP STAND.
ELECTRICAL DATA
MINIMUM
HSPF2 RMKS
REFRIGERANT
TYPE
MINIMUM
SEER2
AIR COOLED HEAT PUMP
MANUFACTUER AND MODEL
NUMBER OR EQUAL
PHYSICAL SIZETOTAL HEAT
CAPACITY
(MBH)
HEATING
AMBIENT
TEMP. (°F)MARK SERVES
TOTAL COOLING
CAPACITY (MBH)
COOLING
AMBIENT
TEMP. (°F)