This is an addendum to the mechanical specifications for the Stokes County Animal Shelter renovation and expansion project located at 1075 Dodgetown Road in Walnut Cove, North Carolina. The addendum establishes general mechanical notes and requirements governing the installation of all mechanical equipment, piping, ductwork, and related components for the comprehensive facility upgrade. Key specifications include compliance with all contract documents and building codes, strict adherence to manufacturer installation instructions, vibration isolation measures to prevent transmission to the building structure, and proper positioning of manual dampers, access doors, valves, air vents, and drains with adequate clearance for maintenance and operation. The document requires duct smoke detectors to be connected to the building fire alarm system or a remote annunciator in occupied areas, mandates airflow balancing to within 10 percent of design values, and establishes duct construction standards using G-60 coated galvanized steel meeting ASTM A653 and A924 standards, with options for double-wall spiral or rectangular ductwork configurations.
The addendum further specifies that all ductwork shown on plans represents free flow area without duct and insulation thickness, requires SMACNA Seal Class C sealing with a minimum of two layers of mastic applied to transverse joints with specified width and coverage, and mandates inspection by the local code official prior to installation of external duct wrap insulation. The document indicates that ductwork layouts are diagrammatic in nature, allowing contractors to resize duct to accommodate actual field conditions while maintaining designed velocity and a maximum aspect ratio of 2:1. These mechanical specifications are integral to the larger animal shelter project involving approximately 3,442 square feet of new construction, 3,860 square feet of renovation, and 800 square feet of outside kennels with complete replacement of mechanical systems as part of the overall facility modernization.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL GENERAL NOTES
1. MATERIALS, EQUIPMENT AND INSTALLATION SHALL COMPLY WITH ALL REQUIREMENTS OF THE
CONTRACT DOCUMENTS, BUILDING CODES, AND EQUIPMENT / MATERIALS INSTALLATION
INSTRUCTIONS.
2. INSTALL ALL EQUIPMENT IN STRICT ACCORDANCE WITH THE MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
3. CONTRACTOR SHALL VERIFY ALL EQUIPMENT, PIPING, AND DUCTWORK HAS BEEN INSTALLED IN A
MANNER THAT VIBRATIONS WILL NOT BE TRANSMITTED TO THE BUILDING STRUCTURE.
4. LOCATE MANUAL DAMPERS, ACCESS DOORS, VALVES, AIR VENTS, DRAINS AND THE LIKE IN
ACCESSIBLE POSITIONS WITH ADEQUATE CLEARANCE FOR ACCESS AND MAINTENANCE.
COORDINATE AND LOCATE DEVICES SO ACCESS IS NOT BLOCKED BY LIGHTS, GRILLS, DUCTWORK, PIPING, STRUCTURE, CONDUIT AND THE LIKE.
5. ANY TIME DUCT SMOKE DETECTORS ARE INSTALLED, THEY SHALL BE EITHER CONNECTED TO THE BUILDING FIRE ALARM SYSTEM (IF PRESENT) OR A REMOTE AUDIBLE/VISUAL ANNUNCIATOR IN A
NORMALLY OCCUPIED PORTION OF THE BUILDING.
6. EQUIPMENT, DUCT AND PIPING LAYOUTS ARE GENERALLY DIAGRAMMATIC.
7. BALANCE AIRFLOWS TO 10% +/- OF VALUES SHOWN.
8. DUCT
a. RESIZE DUCT TO ACCOMMODATE ACTUAL FIELD CONDITIONS. MAINTAIN DUCT VELOCITY AS
DESIGNED. MAINTAIN A MAXIMUM ASPECT RATIO OF 2:1.
b. DUCT MATERIAL SHALL BE G-60 COATED GALVANIZED STEEL OF ASTM STANDARDS A653 AND A924
GRADES.
c. DOUBLE WALL SPIRAL DUCT TO HAVE PERFORATED INNER WALL, SOLID INNER WALL FOR
FITTINGS, GALVANIZED STEEL SURFACE FINISH. HANG DOUBLE WALL DUCT WITH GRIPPLE
HANGING SYSTEMS (OR EQUIVALENT) CABLE HANGERS.
d. RECTANGULAR DUCT MAY BE USED IN LIEU OF ROUND OR VICE VERSA.
e. ALL DUCTWORK SHOWN OF THE PLANS ARE FREE FLOW AREA (DOES NOT INCLUDE DUCT AND
INSULATION THICKNESS).
f. SEALING: SMACNA SEAL CLASS C: A MINIMUM OF TWO LAYERS OF MASTIC SHALL BE APPLIED TO
TRAVERSE JOINTS. WIDTH SHALL EXTEND ½” ON EACH SIDE OF THE SEAM. MASTIC SHALL BE
THICK ENOUGH SO THAT NO METAL IS VISIBLE THROUGH THE MASTIC. NOT APPLICABLE TO
EXPOSED DUCT IN CONDITIONED SPACES. SEAL ALL TRANSVERSE JOINTS, LONGITUDINAL SEAMS, DUCT WALL PENETRATIONS OF AIR HANDLERS AND FILTER BOXES. DUCT SEALING MUST BE
INSPECTED BY THE LOCAL CODE OFFICIAL PRIOR TO INSTALLING EXTERNAL DUCT WRAP
INSULATION.
g. DUCT PRESSURE CLASS IS <2” UNLESS NOTED OTHERWISE.
h. INSULATION:
i. INDOORS: SUPPLY, RETURN, AND OUTSIDE AIR DUCT INSULATION: R6 DUCT LINER.
ii. OUTSIDE: INSULATE EXTERIOR OF DUCT WITH A RIGID DUCT BOARD AND COAT WITH MASTIC
FOR WATER-PROOFING. INSTALL INSULATION TO ALLOW WATER TO DRAIN OFF TOP OF DUCT.
PONDING OF WATER ON DUCT IS NOT ACCEPTABLE.
i. DUCTWORK AND PIPING SHALL BE STORED IN COVERED AREAS SO THAT IT IS NOT EXPOSED TO THE ELEMENTS. THE ENDS OF THE DUCT MUST BE WRAPPED TO PREVENT DEBRIS FOR ENTERING
THE DUCT.
j. INSTALL DUCT PER CURRENT SMACNA STANDARDS AND NC MECH CODE. DUCT SHALL BE
GALVANIZED.
k. RADIUS ELS SHALL BE SMOOTH RADIUS TYPE WITH TWO SPLITTER VANES. SQUARE MITERED ELS
SHALL HAVE SMACNA TYPE 1 SINGLE THICKNESS TURNING VANES WITH MINIMUM ¾” TRAILING
EDGES.
l. ALL BRANCH DUCTS SHALL BE 45 DEGREE ENTRY TYPE.
m. PROVIDE BALANCING DAMPERS AT ALL BRANCH RUNOUTS TO GRILLES. BALANCING DAMPERS
MUST BE ACCESSIBLE.
n. FLEX DUCT SHALL BE UL 181 LISTED.
9. ALL ROOF OPENINGS SHALL BE PROVIDED BY THE GC AND CLOSELY COORDINATED WITH THE
STRUCTURAL ENGINEER.
10.ALL MISCELLANEOUS STEEL SUPPORTS PROVIDED FOR EQUIPMENT, PIPING, AND ACCESSORIES
SHALL BE FULLY COATED WITH APPROVED SHOP PRIMER PAINT.
11.PROVIDE SECONDARY DRAIN PANS WITH CONDENSATE OVERFLOW CUT-OFF SWITCH FOR EACH
FAN COIL.
12.THE MECHANICAL CONTRACTOR SHALL COORDINATE UNIT ELECTRICAL DATA WITH ELECTRICAL
CONTRACTOR ON ALL EQUIPMENT DEVIATIONS FROM THE DESIGN DRAWINGS.
13.ALTERNATE EQUIPMENT MANUFACTURERS.
a. HVAC EQUIPMENT: CARRIER, DAIKIN, AMERICAN STANDARD TRANE, AND VALENT.
b. DIFFUSERS AND GRILLES: PRICE, NAILOR AND METAL AIRE.
c. FANS: GREENHECK, COOK AND PENN
d. MINI-SPLITS: MITISUBISHI AND DAIKIN
14.PIPING
a. CONDENSATE: SCHEDULE 40 PVC.
b. GAS: LABEL PIPE IN ACCORDANCE WITH CODE. GAS PIPING SHALL BE SCHEDULE 40 STEEL, ASTM A-106, WITH MALLEABLE THREADED FITTINGS FOR 2” AND SMALLER AND WITH WELDED FITTINGS
FOR 2.5” AND LARGER. GAS PIPING EXPOSED ON THE ROOF SHALL BE PRIMED AND PAINTED.
SUPPORT ½” PIPING AT 6 FOOT INTERVALS, ¾” AND 1” PIPING AT 8 FOOT INTERVALS AND 1 ¼” AND
LARGER AT 10 FOOT INTERVALS. VIEGA MEGA PRESS FITTINGS ARE ACCEPTABLE.
c. FIRE CAULK ALL PIPING PENETRATIONS TO MATCH FIRE RATINGS (IF NEEDED).
MECHANICAL DRAWINGS INDEX
M1.1 MECHANICAL NOTES AND SCHEDULES.
M1.2 MECHANICAL SCHEDULES AND DETAILS.
M2.1 MECHANICAL PLAN.
M2.2 MECHANICAL PLAN - PKU-1 RETURN DUCT.
M3.1 PKU-1/ VAV SEQUENCE OF OPERATIONS.
M3.2 DOAS-1 SEQUENCE OF OPERATIONS.
M3.3 DOAS-2 SEQUENCE OF OPERATIONS.
M3.4 EXHAUST FAN SEQUENCE OF OPERATIONS.
SUPPLY AIR GRILLE
SYMBOL DESCRIPTION
MECHANICAL SYMBOLS & LEGEND
RETURN AIR GRILLE
EXHAUST AIR GRILLE
DUCT TRANSITION
SMOOTH RADIUS ELBOW
(RADIUS = 1.5 x DUCT DEPTH)
90° ELBOW WITH TURNING VANES
FIRE DAMPER (VERTICAL)
FIRE DAMPER (HORIZONTAL)
OR RADIATION DAMPER
FLEX DUCT
VOLUME DAMPER
MANUAL DAMPER
CONNECT NEW TO EXISTING
T THERMOSTAT
XX
X
AIR DISTRIBUTION TAG
(SEE SCHEDULE)
CFM
2018 APPENDIX B
BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS
MECHANICAL DESIGN
MECHANICAL SYSTEMS, SERVICE SYSTEMS AND EQUIPMENT
MECHANICAL SUMMARY
THERMAL ZONE 4A
WINTER DRY BULB: 14°F
SUMMER DRY BULB: 93°F
INTERIOR DESIGN CONDITIONS
WINTER DRY BULB: 70°F
SUMMER DRY BULB: 74°F
RELATIVE HUMIDITY: 30-50%
BUILDING HEATING LOAD: 133 MBH
BUILDING COOLING LOAD: 16.4 TONS
MECHANICAL SPACING CONDITIONING SYSTEM
UNITARY
DESCRIPTION OF UNIT: SEE EQUIPMENT NOTES.
HEATING EFFICIENCY: SEE EQUIPMENT NOTES.
COOLING EFFICIENCY: SEE EQUIPMENT NOTES.
HEAT OUTPUT OF UNIT: SEE EQUIPMENT NOTES.
COOLING OUTPUT OF UNIT: SEE EQUIPMENT NOTES.
BOILER
SIZE CATEGORY. IF OVERSIZED, STATE REASON: N/A
CHILLER
SIZE CATEGORY. IF OVERSIZED, STATE REASON: N/A
LIST EQUIPMENT EFFICIENCIES: N/A
210 N. MAIN ST. SUITE 340
KERNERSVILLE, NC
LC# P-0504
DEC. 01, 2025
MECHANICAL NOTES AND
SCHEDULES.
M1.1
H
VA
C D
ES
IG
N F
O R
1 12-17-2025 SCHEDULE CHANGES
2 01-05-2026 SCHEDULE CHANGES
AutoCAD SHX Text
PROJECT NO.
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text C COPYRIGHT 2025 NO PART OF THIS DRAWING MAY BE REPRODUCED WITHOUT THE WRITTEN CONSENT OF FREEMAN KENNETT ARCHITECTS, PLLC
AutoCAD SHX Text
A NEW ANIMAL SHELTER FOR STOKES COUNTY, NC
AutoCAD SHX Text
1075 DODGETOWN RD WALNUT COVE, NC 27052
AutoCAD SHX Text
SEAL
AutoCAD SHX Text 026014
AutoCAD SHX Text N
AutoCAD SHX Text O
AutoCAD SHX Text R
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text C
AutoCAD SHX Text A
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text P
AutoCAD SHX Text R
AutoCAD SHX Text O
AutoCAD SHX Text F
AutoCAD SHX Text E
AutoCAD SHX Text S
AutoCAD SHX Text S
AutoCAD SHX Text I
AutoCAD SHX Text O
AutoCAD SHX Text N
AutoCAD SHX Text A
AutoCAD SHX Text L
AutoCAD SHX Text E
AutoCAD SHX Text N
AutoCAD SHX Text G
AutoCAD SHX Text I
AutoCAD SHX Text N
AutoCAD SHX Text E
AutoCAD SHX Text E
AutoCAD SHX Text R
AutoCAD SHX Text W
AutoCAD SHX Text I
AutoCAD SHX Text L
AutoCAD SHX Text L
AutoCAD SHX Text I
AutoCAD SHX Text A
AutoCAD SHX Text M
AutoCAD SHX Text G
AutoCAD SHX Text
AutoCAD SHX Text S
AutoCAD SHX Text M
AutoCAD SHX Text I
AutoCAD SHX Text T
AutoCAD SHX Text H
AutoCAD SHX Text 01/05/2026
AutoCAD SHX Text (336)999-4097
| Sheets and Views |
| Stokes Co Animal Shelter - M-M1.1 |
File details come from the government source that posted it. Updated .