7 t-----1-.;..i._J;;:
19';-----U
ELEVATOR
OFFICE
( 300)
CORRIDOR
( H5 )
FLOOR PLAN
SCALE: 1 / 4" = 1'-0"
CORRIDOR
( H7)
FLOOR PLAN
SCALE: 1 / 4" = 1'-0"
CORRIDOR
( H6 )
3rd FLOOR
OFFICE
( 400) r�
CORRIDOR
( HB )
4th FLOOR
. :.i
EXISTING PANEL 'D'
IJESTINGH□USE 22kA1C
PANEL 'D' (SURFACE MOUNT> BUS, lOOA
120 / 208V 3-PHASE 4-IJIRE
BRKR.
DESCRIPTION
BRKR, BRKR,
ND, SIZE SIZE
15 Existing BreQker 20A 20A
17 Existing BreQker 20A 20A
...- 19 ST□VET□P - R□□M 400 20A 20A
21 MICR□IJAVE - R□□M 400 20A 20A
"'-23 MICR□IJAVE - ROOM 400 20A 20A
PARTIAL PANEL
SCALE: NONE
DESCRIPTION
BRKR,
ND,
Existing BreQker 16
Existing BreQker 18
Existing SpQce 20
Existing SpQce 22
Existing SpQce 24
SCHEDULE
KEYED NOTES (CONTINUED)
16. REFRIGERATOR - BY OTHERS.
17. EXISTING ELECTRICAL PANEL "D". PROVIDE BREAKERS AND
EXTEND CONDUIT AND WIRING AS DESCRIBED ON THIS PLAN AND
IN THE STATEMENT OF WORK. PROVIDE NEW PANEL SCHEDULE -
ADHERED TO INSIDE FACE OF PANEL DOOR .
18. PROVIDE 120V, 20A DEDICATED DUPLEX OUTLET ABOVE COUNTER
BACKSPLASH. RUN CONDUIT AND CONDUCTORS BACK TO PANEL
"D". PROVIDE J-BOXES AS REQUIRED.
19. EXISTING WINDOW - PROTECT.
20. PROVIDE 120V, 20A DEDICATED DUPLEX OUTLET BELOW COUNTER
FOR NEW ELECTRIC STOVETOP UNIT TO PLUG INTO. CUT BACK
PANEL OF BASE CABINET AS REQUIRED TO RECEIVE OUTLET. RUN
CONDUIT AND CONDUCTORS BACK TO PANEL "D" AS DESCRIBED IN
THE STATEMENT OF WORK. PROVIDE J-BOXES AS REQUIRED.
21. RUN MC CABLE FROM J-BOX, THROUGH CEILING SPACE, AND
BACK TO EACH NEW POWER OUTLET AT KITCHENETTE.
22. PROVIDE J-BOX ABOVE 4 TH FLOOR CEILING. RUN EMT FROM
J-BOX TO 4TH FLOOR UTILITY CHASE. CONTINUE EMT DOWN
CHASE AND PENETRATE FLOOR TO THE 3RD FLOOR UTILITY CHASE,
AND INTO THE 3RD FLOOR CEILING. CONTINUE EMT TO PANEL "D".
23. RUN POWER FROM RANGE HOOD TO ABOVE CEILING AND OVER TO
ABOVE EXISTING REFRIGERATOR POWER OUTLET. PROVIDE J-BOX
ABOVE CEILING. PROVIDE A DROP FROM THE J-BOX TO THE
EXISTING OUTLET. CONNECT RANGE HOOD CONNECTORS TO THE
EXISTING OUTLET.
24. THE THREE NEW BREAKERS FOR THE OUTLETS SHALL BE AT
NO. 19, NO. 21 AND NO. 23
GENERAL PLAN NOTES:
1. CABINET, PLUMBING AND ELECTRICAL WORK WILL REQUIRE
EXTENSIVE CUTTING INTO EXISTING GYPSUM WALLBOARD IN
THE VICINITY OF THE WORK. REPLACE AND PATCH WALL
SURFACES FOLLOWING WORK, AND PAINT TO MATCH
ADJACENT WALLS.
2. THE EXIS11NG CEILING IS A SUSPENDED 2x4 LAY-IN TILE
GRID CEILING - AT 7'-8" A.F.F. REMOVE TILES AND GRID
AS REQUIRED TO PERFORM WALL AND CEILING SPACE WORK.
RE-INSTALL FOLLOWING COMPLETION OF WORK. REPLACE IF
DAMAGED DURING CONSTRUCTION .
P
ELEVA Tl ON "A"
SCALE: 1 / 4" = 1'-0"
14TYP
3'-0'
ELEVATION "B"
SCALE: 1/4" = 1'-0"
14TYP
--"l--+--+---{ 3
3'-0'
ELEVATION "C"
SCALE: 1 / 4" = 1'-0"
GENERAL NOTES
1. REFER TO STATEMENT OF WORK FOR ADDITIONAL INFORMATION
REGARDING THIS WORK PLAN.
2. FLOOR PLANS ARE APPROXIMATE AND ACTUAL CONFIGURATIONS,
ELEMENTS, DIMENSIONS, ETC. MUST BE FIELD VERIFIED PRIOR TO
DESIGN.
3. PROTECT ALL EXISTING ELECTRICAL AND MECHANICAL DEVICES,
COVERS, WIRING, ETC., NOT AFFECTED BY DESIGN. REPLACE
DAMAGED ITEMS, INCLUDING ALARMS, HORNS, STROBES, EXIT LIGHTS,
GRILLES, DIFFUSERS, SWITCHES, OUTLETS, LIGHT FIXTURES, ETC. WITH
NEW TO MATCH EXISTING.
4. PROTECT ALL EXISTING SIGNAGE. REPLACE DAMAGED ITEMS WITH
NEW TO MATCH EXISTING .
5. PROTECT ALL FLOOR, WALL AND CEILING SURFACES FROM DAMAGE
DURING CONSTRUCTION. REPAIR OR REPLACE ALL DAMAGED
SURFACES AND FINISHES WITH NEW TO MATCH EXISTING.
KEYED NOTES
1. 36-INCH WIDE X 24-INCH DEEP X 34.5-INCH HIGH PLASTIC-LAM
FACED BASE CABINET W/ DRAWERS. PROVIDE ONE ADJUSTABLE
SHELF .
2. NOT USED.
3. 36-INCH WIDE X 24-INCH DEEP X 34.5-INCH HIGH PLASTIC-LAM
FACED SINK BASE CABINET. PROVIDE ONE ADJUSTABLE SHELF AT
SINK BASE CABINET AT STOVETOP.
4. 36-INCH WIDE X 12-INCH DEEP X 24-INCH HIGH PLASTIC-LAM
FACED UPPER CABINET. PROVIDE ONE ADJUSTABLE SHELF.
5. 18-INCH WIDE X 12-INCH DEEP X 18-INCH HIGH PLASTIC-LAM
FACED UPPER CABINET. CUT HOLES IN OVERHEAD CABINET AS
REQUIRED TO ACCEPT RANGE HOOD DUCT.
6. 36-INCH WIDE X 12-INCH DEEP X 12-INCH HIGH PLASTIC-LAM
FACED UPPER CABINET.
7. 18-INCH WIDE X 12-INCH DEEP X 24-INCH HIGH PLASTIC-LAM
FACED UPPER CABINET. PROVIDE ONE ADJUSTABLE SHELF.
8. PROVIDE BLOCKING IN EXISTING STUD WALL AS REQUIRED FOR
MOUNTING OF ALL CABINETS. REPAIR GYPSUM WALLBOARD AND
PAINT TO MATCH EXISTING.
9. 1-1/2-INCH THICK X 25.5-INCH DEEP PLASTIC-LAM FACED
COUNTERTOP WITH 4-INCH HIGH BACKSPLASH. CUT TO FIT AS
REQUIRED. REMOVE EXISTING WOOD TRIM ALONG WALL AND
WINDOW, IN ORDER TO FIT COUNTERTOP TO WALL. DO NOT RUN
BACKSPLASH ALONG PORTION OF WINDOW.
10. TWO-COMPARTMENT STAINLESS STEEL SINK WITH GOOSENECK
TYPE FAUCET. CONNECT TO EXISTING HOT AND COLD WATER
SUPPLY LINES (WITH BRAIDED-TYPE FLEX PIPING), EXISTING SEWER
DRAIN AND VENT. THERE IS AN EXISTING TOILET AND LAVATORY
IN THE BATHROOM ADJACENT TO THE NEW SINK. PROVIDE STOP
ISOLATION VALVES AT THE SUPPLY LINES. PATCH GYPSUM
WALLBOARD AND PAINT TO MATCH EXISTING FOLLOWING PLUMBING
WORK.
11. TWO-BURNER ELECTRIC STOVETOP UNIT WITH POWER CORD. CUT
OUT COUNTERTOP AND RECESS IN CABINET.
12. NEW ELECTRIC RANGE HOOD UNDER OVERHEAD CABINET. PROVIDE
DEDICATED POWER FOR FAN AND RUN BACK TO PANEL "D" ON
THIRD FLOOR. PROVIDE EXHAUST DUCT (HARD) FROM THE HOOD
OUTLET TO THE EXISTING EXHAUST GRILLE ABOVE THE WINDOW.
PROVIDE A TRANSITION (HARD) WITHIN THE OVERHEAD CABINET,
FROM THE RECTANGULAR OUTLET TO A ROUND DUCT. TURN THE
DUCT TO RUN HORIZONTAL ALONG THE TOP OF THE CABINET AND
ALONG THE HEADER OF THE WINDOW; AND THEN TURN THE DUCT
TO PENETRATE INTO THE EXHAUST GRILLE. PAINT THE EXPOSED
PORTION OF THE DUCT TO MATCH THE WALL. PATCH ANY STUDS
OR GYPSUM BOARD DAMAGED BY INSTALLATION. REFER TO KEYED
NOTE NO. 23 FOR POWER REQUIREMENTS.
13. REMOVE PORTION OF EXISTING CARPET TILES AND MASTIC BELOW
DOWN TO SUBSTRATE - AT AREA AROUND NEW CABINETS. CUT
CARPET TILES TO PROVIDE A CLEAN EDGE AND LINE. CLEAN
FLOOR OF ALL DIRT AND DEBRIS. PATCH FLOOR WITH LEVELER AS
REQUIRED TO RECEIVE NEW SHEET VINYL FLOORING. PROVIDE NEW
SHEET VINYL FLOORING. PROVIDE NEW TRANSITION STRIP WHERE
NEW SHEET VINYL MEETS EXISTING CARPET.
14. REMOVE EXISTING RESILIENT WALL BASE AT AREA RECEIVING NEW
BASE CABINETS. PATCH EXISTING GYPSUM BOARD WALL AT BASE
AS REQUIRED TO RECEIVE NEW RESILIENT WALL BASE. PROVIDE
NEW 4-INCH HIGH RESILIENT WALL BASE ALONG WALLS AND BASE
CABINET TOE-KICKS.
15. EXISTING VENTED LOUVER IN FURRED STUD WALL - PROTECT.
(Y) (\J 0 [
(\J � 1-ll i::q� w a, I.,_ C
Qi I i= +'.-, d d � " "
>. o_ o_ -" i::q i::q u
C, t-"' u'"' u t-
C, u w
I u ' > 11 w• "'
'Sj" "' w C, .--, w
E u d "" z
C:
C'l V) <[ ll::'. ):
w ' w
P'.1 z I-< • Li..
L'.J w .
z ci <[ w w r=1 _Jud I-< I-< u
('\J (J'I
:r:
u ll::'.
I-<
Li..
ll::'.
_J 'Sj" w L..
I' I- I
If) I- :r:
� w 'Sj" � ....., .. Z O I _,WW ru -'S/"�
�I..--1�0Z o_ zU l<i:C\J <I:
I- L'.J z ....., I o_>->-<z 1�
□ u Y'. >-a ti L'.J o2
� l�w� (Y) ll::'.□ �_JI_J Iw � � ...... (/) i::q (/) P'.1 n. e;: ::::J z ::,: I i::q <I:
::::J � _J z � o_
<[ I 1-u w ll::'.
0..
Sheet reference nuMber
A-1 ll::'.
_J L..
Sheet--=- of--=-
FA462023R0002
SOW Attachment G - Government Provided Work Plan