SOW- Replace Heating Condensate Pumps and Motors.docx
DOCX document 30 KB Posted
- Attached to
- FCC TERRE HAUTE Heating Condensate Pumps
- Solicitation number
- 15B41826Q00000005
About this file
This is a Statement of Work (SOW) for the supply and delivery of heating condensate pumps and motors for the Federal Bureau of Prisons' Federal Correctional Complex (FCC) in Terre Haute, Indiana. The contractor must provide all equipment, materials, and incidentals necessary for BOP personnel to install replacements meeting specified technical requirements.
The required equipment consists of three condensate pumps equivalent to models including Goulds Pump Model #46SV20GK4C50 (2-Stage, 15 HP, 3500 RPM) and four 25HP motors rated 460/3/60 volts at 3500 RPM. All pumps must be two-stage centrifugal designs with bronze fittings, axial flow propellers with straightening vanes, mechanical seals rated to 250°F, bleed lines for seal flushing, and horizontal mounting. An isolation valve of all-bronze construction with O-rings must be installed in the suction piping between the pump and receiver tank. The contractor shall deliver equipment cut sheets, specifications, and manufacturer warranty documentation covering pumps, motors, and valves. Deliveries are FOB destination to 4200 Bureau Road North, Terre Haute, Indiana 47802. The solicitation (15B41826Q00000005) is a 100% Small Business set-aside under NAICS code 423720, with awards based on best value considering price, past performance, and delivery time. All offerors must be registered in SAM.gov and submit SF 1449 forms with original signatures and completed quote sheets including offeror name and UEI number.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Memo to File Quote Due Date Extension.docx | DOCX document | |
| Combined Synopsis Solicitation Replace Heating Condensate Pumps and Motors.docx | DOCX document | |
| RFQ- 15B41826Q00000005.pdf | ||
| Combined Synopsis Solicitation Replace Heating Condensate Pumps and Motors.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SUPPLY and DELIVERY
SPECIFICATIONS
Replace Heating Condensate Pumps and Motors FCC Terre Haute
I. SPECIFICATIONS
A. Scope Of Work
The Federal Bureau of Prisons (FBOP), Federal Correctional Complex – Terre Haute (FCC Terre Haute) intends to award to a responsible entity for the provision and installation of all parts and material necessary for BOP personnel to replace the heating condensate pumps and motors to meet all necessary requirements.
Operation Specifications
The Contractor shall provide a supply and delivery of all equipment, materials, and incidentals required to replace heating condensate pumps and motors meeting the requirements of the specification.
The assembly will be a two-stage, centrifugal, bronze-fitted design for applications requiring low NPSH. The pump will be fitted with an axial flow propeller (sometimes called an inducer) and straightening vanes that provide the necessary NPSH for pumping high temperature water without cavitation occurring. Pumps will be furnished with bleed lines, sometimes called seal flushing lines, to help prevent the pump from vapor binding and to allow pump operation against a dead shut off for a period of time without burning seals. Standard mechanical seals will provide for temperatures up to 250°F. Higher temperature seals and special faces may be required.
The pumps will be designed for the specific operating conditions—flow rate, discharge pressure and NPSH requirements; impellers trimmed to operating conditions. It will be horizontally mounted.
The motor will be 25HP 460/3/60 HORZ at 3500 RPM quantity needed will be 4.
An isolation valve will be installed in the suction piping between the pump and receiver tank to quickly remove the pump for repair and maintenance without draining the receiver. The valve will be of all bronze construction with “O” rings in the housing allowing for thermal expansion. The flow will be indicated by the handle direction
The following condensate pumps will need to be the equivalent to the following and a quantity of three each will be required:
1. Goulds Pump Model # 46SV20GK4C50, 2 Stage, With 15 HP, 3500 RPM, 215TC Frame
2. WEG Motor Cat # 00718ET3E213JP-S, 7.5 HP, 1800 RPM, 230/460 V, 60 HZ, TEFC, 3 PH, 213JP Frame
3. Marathon Model # ZVF182TTDW1601, HP5, RPM 3500, FR 182TCVZ, 233/460v, 60Hz
4. FR213JP, 7.5HP, RPM 1745, 208/230v/460, 3PH
5. Marathon Model # PVL213TTDW14029BBM, FR 213TCVZ, HP7.5, RPM 1760, 208v/3 PH
B. FCC Terre Haute Responsibilities
FCC Terre Haute shall provide a point of contact to liaise between the Contractor and personnel on site to coordinate the delivery.
C. Equipment Salient Characteristics
1. Funding this project will allow for the replacement of the heating condensate pumps and motors by BOP Staff.
D. Warranty
1. Manufacturer shall provide a commercial warranty covering:
a. Pumps
b. Motors
c. Valves
E Deliverables/Submittals
The Contractor shall provide the following at the time of delivery:
Equipment cut sheets/specifications Warranty documentation
END OF SPECIFICATIONS
File details come from the government source that posted it. Updated .