SOW Pinecastle B149-L HVAC Pics.pdf
PDF 1 MB Posted
- Attached to
- Pinecastle HVAC replacement
- Solicitation number
- N6945020R0120
About this file
This document outlines requirements for replacing HVAC systems at Building L/149 at Pinecastle Bombing Range. The contractor shall replace five HVAC units, including replacing a 5-ton packaged heat pump unit with backup electric heat that provides air conditioning for the operations control center, replacing an existing 3.5-ton packaged heat pump unit with a 3.5-ton straight cooling air conditioning unit that provides air conditioning for the IT server room, and installing a new 3-ton split CRAC unit with humidifier/electric reheat package for the IT server room. The contractor must route refrigerant lines and electrical circuits, relocate electrical devices, and install outdoor units according to specifications provided. Work must be completed per Statement of Work requirements for the Navy's Pinecastle HVAC replacement contract under Solicitation Number N6945020R0120.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| AMD 02 RFP N6945020R0120.pdf | ||
| AMD 01 RFP N6945020R0120.pdf | ||
| PRE-PROPOSAL INQUIRY FORM.xlsx | XLSX spreadsheet | |
| Price Proposal spreadsheet.xls | XLS spreadsheet | |
| Pinecastle B149 HVAC Repl SOW .docx | DOCX document | |
| SOW Pinecastle B149 HVAC Repl Sketch.pdf | ||
| RFP N6945020R0120.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Pinecastle Bombing Range A/C Units Building L/149
PMB / Building (L/149) Pinecastle
Replace 5 Ton Packaged Heatpump With Back-Up Electric Heat (Unit #1)
This Unit Provides Conditioned Air For The Operations Control Center
Existing 5 Ton Package Unit Shall Be Replaced. Unit
Replacement Shall Include Replacing All Interior
Lined Ductwork On The Exterior Of Bldg. L/149
Electrical Panel (Labeled Panel 16)
Feeds Both Existing HVAC Units
Electrical Panel 16 Has A 200 Amp Main Breaker
Panel 16 Index Card
Replace existing 3.5 Ton Packaged Heatpump (Unit # 2) with a 3.5 Straight Cool A/C Unit
Unit Replacement Shall Include Replacing All Interior Lined Ductwork On The Exterior Of Bldg. L/149
(This Unit Provides Conditioned Air To The IT Server Room)
Contractor Shall Provide And Install An Additional Unit For The IT Server Room. The New Unit Shall Be
A 3-Ton Split CRAC Unit With A Humidifier/Electric Reheat Package.
New Indoor Modular Cabinet Shall Be Mounted (On The Northwest Wall) With A 4” Channel Spacer To
Stand The Indoor Unit Off The Wall To Allow For Routing Of Refrigerant, Condensate Drain And Electrical Circuit
Connections.
Contractor Shall Route Refrigerant & Electrical
Circuits Up The Wall To The Overhead. Items
Shown Below Electrical Devices (Cabinet On
Casters) Will Be Relocated By Occupants
Once Refrigerant Lines & Primary Electrical Circuit/Conduit Is
In The Overhead They Shall Route Toward The West Wall Of
Server Room. Electrical Circuit/Conduit Shall Extend Thru
Wall To The Exterior Of Bldg.
Refrigerant Lines Continue Around Wall
(Above Door To The Exterior) To
Southwest Corner Of Bldg.
Refrigerant Lines Continue Along Wall
(From Column To Column) To Where
They Penetrate Exterior Wall, Continue
Down Wall To The New Outdoor Unit
Location
New Outdoor Unit Location
Refrigerant Lines Down Exterior Wall
(On The Interior Or Exterior Side Of
Wall) Preferably Interior Side.
Condensate Drain Line Shall Be Routed Out The Right Side Of The Modular Cabinet Spacer Along Wall 90° At
Corner And Follow Wall To The Exterior Wall Of Building