This document consists of electrical plans for the design of the Establish Radiation Oncology Program at the Southeast Louisiana Veterans Health Care System (SLVHCS) in New Orleans, Louisiana. The plans detail the electrical requirements for the project, including power distribution, lighting, telecommunications, and other electrical systems across multiple floors of the building. Key details include the location and sizing of electrical panels, conduits, and other electrical infrastructure. The plans are part of a larger construction project solicitation for the Department of Veterans Affairs to establish a radiation oncology program at the SLVHCS facility. The solicitation number is 36C77624R0107_1, and the agency leading the project is the VA Technology Acquisition Center Austin.
View the file
Other files
Show all 37
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ATTACHMENT M - ELECTRICAL PLANS
629-335 Establish Radiology Oncology Program at SLVHCS
BUILDING 2
ELECTRICAL
GROUNDING PLAN
PART F AND G
2EP100-FG
WP_08
February 29, 2012 SMAC AV
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
TE
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F
IN
C H
O
N E
FO
O
T
TH
R
EE
Q U
AR
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
(1
0'
6"
6"
0'
0'
123456
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
ES
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
DN
UP
UP
UP
02 9
02 K
8.3
9.7
10.4
7.6
8.1
7.5
XE
Y49
16.1
02 J02 J.5
13.2
XC
DD
CC
EE
GG
HH
JJ
LL
8.7
E.5
E.3
E.6
8.5
KK
FF
ED
5.9ED
ED
ED
ED
G
ED
B.2
ED
B.1
02 8
Tectonic Cop yright 2007
Tectonic Cop yright 2007
Tectonic Copyright 2007
UP
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
T ectonic Cop yright 2007
T ectonic Cop yright 2007
J
J J J J J
JJJJJ
J
J
J
J
JJ
J
J
J
T6 R22141B
R22142A
L2414
P2414
D2214
D2414
FATC
EWC
2EP408
EC1R2214
LC2414
2EP401
WP
02-1G- RF-22
R22141A-11
R22141A-2,4
R22142B-23
R22142B-21
REF
PS
R22141A-6,8 R22141A -10,12
6 8 10 12
R22141A-9,15
15 15
R22141A-13
EC1R2214-2
2 2
P2414-7 (125A-3P) 3#3&1#6G.-1 1/4"C.
P2414-1 (50A-3P) 3#8&1#10G-3/4"C.
PS
REF
MIC
R22141B -12
R22141B-32
3R22141B-1,321
R22141B-21,23
P
R22141B-2,4,6,8 2,4,6,8
ST
ST
R22142B- 17,19
REX
FEMALE
1G100A
T1
SERVICE
BAY
1G227 G8A
TELECOM
1G227C G2
EMER
ELEC
1G227B G2
NORM
ELEC
1G227A G2
MALE
1G100B
T1
VOLUNTEER
LOUNGE
1G108 S15
RECEPTION/SECY
1G116 C11
STORAGE
1G106
C55E
MULTI-PURPOSE
WORK
1G107 S3A
SIGN-IN
1G105 C11
HK
1G125 C3
ID ISSUE
WAIT
1G149
CORR70A
EVIDENCE
1G151
C55E
COPIER
1G150 S18
ST
1G121 T4
ST
1G122 T4
CORR
1G-C06 C11
CORR
1G-C03
CORR70A
CORR
1G-C02C
CORR1
WC
STORAGE
1G198 C17
SECURITY
1G227D S19
RECPT/WAIT
1G131 S4B
LOCKERS
1G129
S14 DISPATCH
1G123A S15
BREAK
1G123B S15
UNASSIGNED
1G120
C55E
T 1G102 T2A
T 1G101 T2A
CAFE
1G103 P13B
STORAGE
1G104
P13D
STAIR
2F152 G1
ATC
EWC
AFS AFS AFS AFS AFS
AFSAFSAFSAFSAFS
EQ5R2224-1
EDM
R22141A-16
2E P1
-G
EP
1- A3
2E P1
-G
2E
P1
-G
EIT2214
18 R22141A-18
2EP413
P
REFER TO DRAWING 2EP413
FOR KITCHEN LAYOUT
EC1R2214-3
FB2
2 R22141B-29
2424242424
2121212121
02-1G-VFD-31
02-1G-VFD-62
R22142B
-24,26 HD
R22142B-29,31 (20A-2P)
HD
R22142B-28,30(20A-2P)
TRAP
PRIMER
R22142A-1
1/3
1/3
02-1G1-FCU-1
R22141A-39 (20A-2P)
02-1G1-CAC-1
EIT2214-32
(30A-3P) 3#10&1#10G-3/4"C
R22142B
R22141A
MIC
02-1G-SF-31
PWRLTG
R22141A-20R22141A-2
TRAP PRIMER
R22142A-4
XA
XD
A.5
AA
AA.2
Y49
16.1
13.2
A
XC
02-1G
AHU-31
200A-3P
W/125AF
60A-3P
W/50AF
48" AFF
48" AFF 48" AFF
48" AFF
48" AFF 48" AFF
48" AFF
48" AFF
ELS2224-11
REX
REX
ELS2224-11
ELS2224-11
KEY NOTES
2 13.2KV NORMAL POWER DUCT BANK RUN BELOW SLAB. SEE DWG
0ESS101 FOR CONTINUATION.
1 BRANCH CIRCUIT WIRING SERVING PARTITION SYSTEM.
SHALL BE FOUR CITCUIT, 4#12, 2#12G & 2#10 NEUTRALS.
REFER TO MANUFACTURERS WIRING DIAGRAMS.
3 13.2KV EMERGENCY POWER DUCT BANK RUN BELOW SLAB. SEE
DWG 0ESS101 FOR CONTINUATION.
4 RUN BRANCH CIRCUITS IN ACCESSIBLE CEILING SPACE OF
FLOOR BELOW AND UP NEAREST WALL TO ABOVE ACCESSIBLE
CEILING. PROVIDE BRANCH CIRCUIT AS INDICATED ON PLAN.
1. REFER TO LEGEND AND GENERAL NOTES ON DRAWING
0ES001.
2. EXACT LOCATIONS OF FLOOR OUTLETS AND/OR POKE
THRU DEVICES SHALL BE COORDINATED WITH ARCHITECTURAL
FURNITURE PLANS AND ACTUAL FIELD DIMENSIONS
BASED ON DIRECTION FROM RESIDENT ENGINEER.
3. COORDINATE EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL DRAWINGS.
4. REFER TO MOTOR WIRING SCHEDULE ON DRAWING
0ES503 FOR MOTOR FEEDER SIZES.
5. VFD’S FURNISHED AND INSTALLED UNDER DIVISION
23 WIRED UNDER DIVISION 26.
6. REFER TO MEDICAL EQUIPMENT FLOOR PLANS FOR EQUIPMENT
LOCATIONS.
7. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATION
OF WALL MOUNTED DEVICES AND MOUNTING HEIGHTS, PRIOR TO
ROUGHIN
8. REFER TO A/V CONSULTANT DRAWINGS FOR A/V DEVICES
AND REQUIREMENTS.
9. ALL BRANCH CIRCUIT WIRING FROM PANELS SHALL BE
RUN WITHIN THE INSTERSTITIAL SPACE (WHERE APPLICABLE)
AND ABOVE CEILINGS IN AN ORGANIZED MANNER TO NETWORK
JUNCTION BOXES. REFER TO TYPICAL BRANCH CIRCUITING DETAIL
DWG 0ES517.
10. WHERE BRANCH CIRCUIT CONDUITS ARE ROUTED IN
INTERSTITIAL SPACE, CONDUITS PENETRATIONS THROUGH
SLAB SHALL BE FIRE PROOFED.
11. ALL PANELBOARDS SHALL BE MOUNTED ON UNISTRUT SUPPORT
SYSTEM PER DETAIL ON DRAWING 0ES517.
GENERAL POWER NOTES:
12.PROVIDE #10 AWG CONDUCTORS THROUGHOUT ALL
BRANCH CIRCUIT WIRING AND HOMERUN TO PANELBOARD.
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
T E
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F I N
C H
O
N E
FO
O
T
TH
R
EE
Q U
A R
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
( 1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
E S
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2EP101-G1
BLDG 2 FIRST FLOOR POWER PLAN- AREA G1
LMD ADSFebruary 29, 2012
2629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
BR+A CONSULTING ENGINEERS / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
1/8" = 1'-0"1 LEVEL 01 - Power - AREA G1
REFER TO THE FOLLOWING SKETCH FOR CHANGES
PER BULLETIN 15B:
SK-8-015B-BA-2EP101G1
THIS DRAWING HAS BEEN AFFECTED BY THE BIM
COORDINATION PROCESS. PLEASE REFER TO THE
BIM COORDINATED SHOP DRAWINGS FOR DETAILS.
CR
CR
RFI 4695
CR
PD
RFI
04695
ADO
RFI 04758: CR
removed. Install PD
RFI 05857: HD got relocated to opposite wall
RFI 5746: Outlets shown in glass moved to metal panels. One outlet to be installed at each corner.
RFI 5816: Orientation of casework changed. Additional electrical requirements added. See attached sketch.
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
UP
UP
J
JJ
J
J
J
J J J J J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
JJJJ JJ
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J J
J
J
J
J
J
J
Tectonic Copyright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
J
J
J J
J
J
J
J
J
REF
REF
P
PP2
P
WP
WP WP
PS
PP2
P
R22133A-9 (2#10,1#10G-3/4"C.)
R22143A-27,29 27 WP 29 WP 27 WP 29
WP 28WP 27WP 29WP 27
R22143A-6
R22143A-2,4
R22143A-1,3
R22143A-5,7
R22143A-9,11
R22143A-13,15
R22143A-10,12
R22143A-14,16
12 10
R22143A-17,19
17 19
R22143A-21
R22143B-1,3,5,7
R22143B-2,4,6,8
R22143B- 22,24,26,28
R22143B-9,11
R22143B-10,12
10 12
R22143B-29 29
R22143B-30
R22141A-6,8 R22141A -10,12
R22141A-9,15
R22141B-5,7,9,11 R22141B-25,27
R22141B-20,22
R22141B-24
R22141B-28,30
R22142A-18,20,22,24
R22142A-17,19,21,23
R22142A-2
R22142A-6,8
R22142A-10,12
R22142A-5,7
R22142A-14,16
R22142A-13,15
R22142A-25,27
R22142A-26,28
26R22142A-29
R22142B-1,3 1
R22142B -9,11
R22142B-2,4
R22142B-6,8
EC1R2214-
9,11,13,15
R22142B-18,20
20 18 20 22
R22142B-13,15
R22142B-22
19 19
9 9 9 9
PS
MIC
MIC
R22141B-1616
PS
R22141B-18
R22141B-14
FB2
R22141B-17,19
PS
REF
MIC
R22141B-13,15
R22141B -12
R22141B-32
R22141B-1,3
R22141B-21,23
P
R22141B-2,4,6,8 2,4,6,8
FB2 FB2
7 9 115 15
7 9 11 15
7 11
9 13
26 28 28 28 28 R22143A- 26,28
14 11
R22142A-9,11
9 7 5
ST
ST
26 28
ST ST
R22142B-5,7
R22142B- 17,19
R22143A-30
R22143A-25
ADO
0ES501
0ES505
TYPICAL
0ES501
0ES501
TYPICAL
CORR
1F-C01A
CORR86A
CORR
1F-C01B
CORR86A
CORR
1FC03
CORR30A
COMP
ADP STOR
1G167 C4
UNASSIGNED
1G197 G8
STAFF
LOUNGE
1G118 S15
EC
1G195 G2
CONF/
TRAINING
1G138 S9A
PAGERS
CELLS
1G184 C4
LAPTOPS
1G191 S2
PROF
STAFF
1G182 S4
WORK
AREA
1G174 S17
PROGRAM
1G176 S4B
PROGRAM
1G183 S4
HELP
1G188A S4
HELP
1G190 S4
HELP
1G188B
S4
PC TECH
1G185D S4B
PC TECH
1G166A S4B
PC TECH
1G165 S4B
PC TECH
1G185E S4B
PC TECH
1G185B S4B
PC TECH
1G185H S4B
PC TECH
1G185I S4B
PC TECH
1G185C S4B
PC TECH
1G185G S4B
PC TECH
1G166B S4B
CONFERENCE
1G196 S9A
OFFICE
ASST CH
1G169 S3A
REF LIB
1G186 S9
OFFICE
SEC CH
1G171 S3A
OFFICE
SEC CH
1G172 S3A
PROF
STAFF
1G178G S4B
PROF
STAFF
1G178A S4B
PROF
STAFF
1G175 S4
OFFICE
CIO
1G168 S3A
OFFICE
BUDGET
1G170 S3A
COPY
ROOM
1G173 S18
SECY
1G177 S4B
PROF
STAFF
1G178F S4B
ST
1G181 T4
PROF
STAFF
1G178E S4B
PROF
STAFF
1G178D S4B
PROF
STAFF
1G178H S4B
PROF
STAFF
1G178C S4B
PROF
STAFF
1G178B S4B
WS,VAVS
ORGANIZATION
1G115 C11
OFFICER
1G110
S3A OFFICER
1G109 S3A
CHIEF OF
SERVICE
1G111 S7
CONFERENCE
1G113 S9A
VOLUNTEER
LOUNGE
1G108 S15
RECEPTION/SECY
1G116 C11
MULTI-PURPOSE
WORK
1G107 S3A
ST
1G180 T4
CUSTOMER
SERVICE
1G189 S9B
SECY/
WAITING
1G162 S4B
ID ISSUE
WAIT
1G149
CORR70A
ID/REG
ISSUE
1G148 S2
PHYSICAL
SECUR
OFFICER
1G157 S3A
EVIDENCE
1G151
C55E
MALE
LOCKER
1G141A S14
DETECTIVE
1G156 S3A
DETECTIVE
1G159 S3
TRAINING
OFFICER
1G158 S3A
ASST
CHIEF
1G154 S3A
CLER
1G161G S4B
ID/KEY
STORAGE
1G147 C55E
ARMORY
1G145
C55E
ARMORY
STORAGE
1G146 C55E
ASST
CHIEF
1G153 S3A
LT/SGT
SUPER
1G155 S3A
COPIER
1G150 S18
HOLDING
1G160
C55E
SECURITY
COMMAND
CENTER
1G139 S2
FEMALE
LOCKER
1G140A S14
CLER
1G161K S4B
CLER
1G161H S4B
CLER
1G161A S4B
CLER
1G161D S4B
CLER
1G161B S4B
CLER
1G161C S4B
CLER
1G161E S4B
CLER
1G161I S4B
CLER
1G161J S4B
CLER
1G161F S4B
HC T/S
1G141C T5A
HC T/S
1G140B T5A
T/S 1G141B T5A
ST
1G122 T4
CORR
1G-C06 C11
CORR
1F-C06
CORR70A
CORR
1G-C02A
CORR70A
CORR
1G-C04
CORR75
CORR
1G-C03
CORR70A
CORR
1G-02B
CORR70A
CORR
1G-C08 S4B
CORR
1G-C09 S4B
PC TECH
1G185F S4B
PC TECH
1G185A S4B
OFFICE
1G135 S2
CLERICAL
1G132 S4
RECPT/WAIT
1G131 S4B
LOCKERS
1G129 S14
CHIEF
1G133 S7
AO
OFFICE
1G134 S2
COPY
1G130 S18
STRETCHER
STOR
1G128 C4
CORR
1G-C15 S4
CORR
1G-C16 S4
STOR
1G113B C55E
STOR
1G113A C55E
CLERICAL
1G114 S4
CORR
1G-C18
CORR75
UNASSIGNED
1G161L
NONE
R22143A-31 2#10&1#10G- 3/4"C
R22141A-16
2EP101-F2
2EP101-G2
2E P1
-F
2E
P1
-F
2E P1
-G
2E
P1
-G
EIT2214
R22143B-31
UP
2EP409
WP
WP
R22143A R22143B
EC1R2214-1
2#10,1#10G-3/4"C.
4 4
P
P
FB2
IG
PP2
P
P
R22143B-13,15,17,19
13,15,17,19
P
21,23,25,27
P
R22143B- 21,23,25,27
P
P
P
P
1R22143B- 14,16,18,20
14,16,18,20
14,16,18,20 14,16,18,20
14,16,18,20
P
IG
PP
R22142A- 31,33,35,37
PP2
REFER TO
DRAWING ESS101
FOR CONTINUATION
WP
WP
WP
R22143A-23
EIT2214-32
(20A-3P)
1/3 R22143A-33
02-1G2-FCU-1
MIC
02 E 02 D 02 C
02 H 02 F.9
A.5
Y49
16.1
02 J
13.2
02 FEJ 4 02
C.5
R22133A-32
20A-1P(GFCI)
CONNECTION TO
HEAT TRACE
EC1R2214-21
EC1R2214-19
EC1R2214-17
2EP401
48" AFF
48" AFF
48"
AFF
48" AFF
48"
AFF
R22131A-32
REX
DH
ELS2223-12
REX
REX
ELS2224-11
ELS2224-11
REX
ELS2224-13
REX
ELS2224-13
DH ELS2224-13
R22143A-23
KEY NOTES
2 13.2KV NORMAL POWER DUCT BANK RUN BELOW SLAB. SEE DWG
0ESS101 FOR CONTINUATION.
1 BRANCH CIRCUIT WIRING SERVING PARTITION SYSTEM.
SHALL BE FOUR CITCUIT, 4#12, 2#12G & 2#10 NEUTRALS.
REFER TO MANUFACTURERS WIRING DIAGRAMS.
3 13.2KV EMERGENCY POWER DUCT BANK RUN BELOW SLAB. SEE
DWG 0ESS101 FOR CONTINUATION.
4 RUN BRANCH CIRCUITS IN ACCESSIBLE CEILING SPACE OF FLOOR
BELOW AND UP NEAREST WALL TO ABOVE ACCESSIBLE CEILING.
PROVIDE BRANCH CIRCUIT AS INDICATED ON PLAN.
1. REFER TO LEGEND AND GENERAL NOTES ON DRAWING
0ES001.
2. EXACT LOCATIONS OF FLOOR OUTLETS AND/OR POKE
THRU DEVICES SHALL BE COORDINATED WITH ARCHITECTURAL
FURNITURE PLANS AND ACTUAL FIELD DIMENSIONS
BASED ON DIRECTION FROM RESIDENT ENGINEER.
3. COORDINATE EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL DRAWINGS.
4. REFER TO MOTOR WIRING SCHEDULE ON DRAWING
0ES503 FOR MOTOR FEEDER SIZES.
5. VFD’S FURNISHED AND INSTALLED UNDER DIVISION
23 WIRED UNDER DIVISION 26.
6. REFER TO MEDICAL EQUIPMENT FLOOR PLANS FOR EQUIPMENT
LOCATIONS.
7. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATION
OF WALL MOUNTED DEVICES AND MOUNTING HEIGHTS, PRIOR TO
ROUGHIN
8. REFER TO A/V CONSULTANT DRAWINGS FOR A/V DEVICES
AND REQUIREMENTS.
9. ALL BRANCH CIRCUIT WIRING FROM PANELS SHALL BE
RUN WITHIN THE INSTERSTITIAL SPACE (WHERE APPLICABLE)
AND ABOVE CEILINGS IN AN ORGANIZED MANNER TO NETWORK
JUNCTION BOXES. REFER TO TYPICAL BRANCH CIRCUITING DETAIL
DWG 0ES517.
10. WHERE BRANCH CIRCUIT CONDUITS ARE ROUTED IN
INTERSTITIAL SPACE, CONDUITS PENETRATIONS THROUGH
SLAB SHALL BE FIRE PROOFED.
11. ALL PANELBOARDS SHALL BE MOUNTED ON UNISTRUT SUPPORT
SYSTEM PER DETAIL ON DRAWING 0ES517.
GENERAL POWER NOTES:
12.PROVIDE #10 AWG CONDUCTORS THROUGHOUT ALL
BRANCH CIRCUIT WIRING AND HOMERUN TO PANELBOARD.
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
T E
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F I N
C H
O
N E
FO
O
T
TH
R
EE
Q U
A R
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
( 1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
E S
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2EP101-G2
BLDG 2 FIRST FLOOR POWER PLAN- AREA G2
LMD ADSFebruary 29, 2012
2629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
BR+A CONSULTING ENGINEERS / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
1/8" = 1'-0"1 LEVEL 01 - Power - AREA G2
THIS DRAWING
HAS BEEN
AFFECTED BY
THE BIM
COORDINATION
PROCESS.
PLEASE REFER
TO THE BIM
COORDINATED
SHOP DRAWINGS
FOR DETAILS.
RFI 03478:
Added FB5
RFI 03478:
Added FB1
CR
RFI
04695
CR
CR
RFI 04695
CR
RFI 04695
RFI 05046: outlets in glazing relocated to walls. See attached sketch
RFI 04999: Locate Receptacles below window.
RFI 05011: Added Power, data, and telecom.
REFER TO THE FOLLOWING SKETCH FOR
CHANGES PER BULLETIN 15B:
SK-8-015B-BA-2EP101G2
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 05385:
Receptacle install.
RFI 08111: Revises quantity and location of receptacles in floor boxes.
Tectonic Cop yright 2007
Tectonic Cop yright 2007
Tectonic Cop yright 2007
Tectonic Cop yright 2007 ctonic Coright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007 ctonic Coright 2007ctonic Coright 2007 ctonic Coright 2007ctonic Coright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007 ctonic Coright 2007ctonic Coright 2007 ctonic Coright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007 ctonic Coright 2007
Tectonic Cop yright 2007
Tectonic Cop yright 2007 ctonic Coright 2007 ctonic Coright 2007 ctonic Coright 2007 ctonic Coright 2007
Tectonic Cop yright 2007
Tectonic Cop yright 2007 ctonic Coright 2007 ctonic Coright 2007 ctonic Coright 2007
RFI 08285:
Relocate outlets
UP DN
DN
DN
J
J
T ectonic Cop yright 2007
Tectonic Cop yright 2007
J
2E P1
-G
2E P1
-A
NORMAL PRIMARY FEEDERS UP THRU
BRICK ENCLOSED SHAFT
(CONTINUES TO PENTHOUSE)
EMERGENCY PRIMARY FEEDERS UP
THRU BRICK ENCLOSED SHAFT
(CONTINUES TO PENTHOUSE)
DOWN TO R22141A-19
2#10, 1#10G-3/4"C.19
20 20
DOWN TO R22143A-20
2#10, 1#10G-3/4"C.
02 E 02 D 02 C
XA
XD02 H 02
F.9 A.5
AA
AA.2
Y49
16.1
13.2
A
XC
02 F 02 C.5
DOWN TO R22141B-10
2#10, 1#10G-3/4"C.
1. REFER TO LEGEND AND GENERAL NOTES ON DRAWING
0ES001.
2. EXACT LOCATIONS OF FLOOR OUTLETS AND/OR POKE
THRU DEVICES SHALL BE COORDINATED WITH ARCHITECTURAL
FURNITURE PLANS AND ACTUAL FIELD DIMENSIONS
BASED ON DIRECTION FROM RESIDENT ENGINEER.
3. COORDINATE EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL DRAWINGS.
4. REFER TO MOTOR WIRING SCHEDULE ON DRAWING
0ES503 FOR MOTOR FEEDER SIZES.
5. VFD’S FURNISHED AND INSTALLED UNDER DIVISION
23 WIRED UNDER DIVISION 26.
6. REFER TO MEDICAL EQUIPMENT FLOOR PLANS FOR EQUIPMENT
LOCATIONS.
7. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATION
OF WALL MOUNTED DEVICES AND MOUNTING HEIGHTS, PRIOR TO
ROUGHIN
8. REFER TO A/V CONSULTANT DRAWINGS FOR A/V DEVICES
AND REQUIREMENTS.
9. ALL BRANCH CIRCUIT WIRING FROM PANELS SHALL BE
RUN WITHIN THE INSTERSTITIAL SPACE (WHERE APPLICABLE)
AND ABOVE CEILINGS IN AN ORGANIZED MANNER TO NETWORK
JUNCTION BOXES. REFER TO TYPICAL BRANCH CIRCUITING DETAIL
DWG 0ES517.
10. WHERE BRANCH CIRCUIT CONDUITS ARE ROUTED IN
INTERSTITIAL SPACE, CONDUITS PENETRATIONS THROUGH
SLAB SHALL BE FIRE PROOFED.
11. ALL PANELBOARDS SHALL BE MOUNTED ON UNISTRUT SUPPORT
SYSTEM PER DETAIL ON DRAWING 0ES517.
GENERAL POWER NOTES:
12.PROVIDE #10 AWG CONDUCTORS THROUGHOUT ALL
BRANCH CIRCUIT WIRING AND HOMERUN TO PANELBOARD.
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
T E
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F I N
C H
O
N E
FO
O
T
TH
R
EE
Q U
A R
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
( 1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
E S
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2EP101i-G
BLDG 2 FIRST FLOOR INTERSTITIAL POWER
PLAN G
LMD ADSFebruary 29, 2012
2629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
BR+A CONSULTING ENGINEERS / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
1/8" = 1'-0"1
LEVEL 01 INTERSTITIAL POWER PLAN
AREA G
THIS DRAWING HAS BEEN AFFECTED BY THE BIM
COORDINATION PROCESS. PLEASE REFER TO THE BIM
COORDINATED SHOP DRAWINGS FOR DETAILS.
UP
J
J
J
J
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
J
J
J
J
J
J
J
J
J J J J J
JJJJ
J
J
J
J
J
7.5
J
J J
J
T2 ELS2224EC1R22241
EC1L2424
L2424
R22241B
P2424
T6
T6 EC1D2224
D2224 FACP2-1
R22241A
R22242
2EP408
ST
ST
US
LC24242EP401
02-2G-SF-33
02-2G-RF-24
PWR LTG
PL
PL
B
TREADMILL
PS
REX
UNASSIGNED
2G230
CORR
2G-C02
CORR
2G-C06C
CLEAN
2G116
SOILED
HOLD
2G115
ECHO
2G136 SERVICE
BAY
2G227
DRESS
2G114
CARD
RECEPT
2G101C NUC MED
RECEPTION
2G101A
TELECOM
2G229A
EMER
ELEC
2G227B
NORM
ELEC
2G227A
STORAGE
ECHO
2G137
PAT HOLD
2G113
PAT HOLD
2G112
PHYSICIST
2G105
RECEPTION
2G101B
STRET/WC
2G107
DRESS
2G111
MALE
2G100B
MRI
WAITING
2G110
2G
9B
SECURITY
2G229B
HK
2G106
COPY/WORK
2G103
STAIR
2F152
2G227
2G107
2G116
2G115
2G
7A
2G
7B
2G
9A
2G137
2G105
2G-C06C
2G
2G111
2G114
2G -C
2G103
FEMALE
2G100A
2G210.2 2G210.1
ATC
R22242-10,12 R22242-6,8 R22242-2,4
42861210
2 2
1EC1R22241-2
R22241A-1
P2424-1 (20A-3P) 3#10&1#10G-3/4"C.
P2424-7 (60A-3P) 3#6 &1#8G-1"C.
R22241A-3
R22242-5,7
EC1R22241-1
R22241A-8,10
R22241A-9,11
R22241A-26
R22241A-25,27
R22241A -22,24
25 12
12 12
R22241B-2
R22241B -20,22 (20A-2P)
R22241B-29
R22241B-1,3 (20A-2P)
R22241B-8
R22241A-28
28 28
EQ5R2224-2
11 EDM
3 3 3 3 3
AFS
AFS AFS AFS AFS
AFSAFSAFSAFS
AFS
2E P1
-G
EP
2- A3
2E P1
-G
2E
P1
-G
EIT2224
R22241A-29
29 29 29 29
R22242-9,11
1 11
29 29
3 EWC
R22241A-2,4
T3-1
R22241B-33 R22241B-35
R22242-3
PS
HD
R22242-13,15 (20A-2P)
R22242-14,16 (20A-2P)
HD
02-2G-VFD-33
02-2G-VFD-64
R22242-24TRAP
PRIMER
R22242-26
TRAP
PRIMER
1/3 1/3
02-2G1-FCU-1
R22242-25 (20A-2P)
02-2G1-CAC-1
EIT2224-32
(30A-3P) 3#10&1#10G-3/4"C
D2424
XA
XD
A.5
AA
AA.2
Y49
16.1
13.2
A
02-2G
AHU-33
BUSDUCT
NB241
BUSDUCT
EB214
30A-3P
W/20AF
60A-3P
W/60AF
48" AFF
EQ5R2224
ELS2424
EWC
MON
MON
ELS2224-15
REX
ELS2224-15
DH
ELS2224-15
1. REFER TO LEGEND AND GENERAL NOTES ON DRAWING
0ES001.
2. EXACT LOCATIONS OF FLOOR OUTLETS AND/OR POKE
THRU DEVICES SHALL BE COORDINATED WITH ARCHITECTURAL
FURNITURE PLANS AND ACTUAL FIELD DIMENSIONS
BASED ON DIRECTION FROM RESIDENT ENGINEER.
3. COORDINATE EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL DRAWINGS.
4. REFER TO MOTOR WIRING SCHEDULE ON DRAWING
0ES503 FOR MOTOR FEEDER SIZES.
5. VFD’S FURNISHED AND INSTALLED UNDER DIVISION
23 WIRED UNDER DIVISION 26.
6. REFER TO MEDICAL EQUIPMENT FLOOR PLANS FOR EQUIPMENT
LOCATIONS.
7. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATION
OF WALL MOUNTED DEVICES AND MOUNTING HEIGHTS, PRIOR TO
ROUGHIN
8. REFER TO A/V CONSULTANT DRAWINGS FOR A/V DEVICES
AND REQUIREMENTS.
9. ALL BRANCH CIRCUIT WIRING FROM PANELS SHALL BE
RUN WITHIN THE INSTERSTITIAL SPACE (WHERE APPLICABLE)
AND ABOVE CEILINGS IN AN ORGANIZED MANNER TO NETWORK
JUNCTION BOXES. REFER TO TYPICAL BRANCH CIRCUITING DETAIL
DWG 0ES517.
10. WHERE BRANCH CIRCUIT CONDUITS ARE ROUTED IN
INTERSTITIAL SPACE, CONDUITS PENETRATIONS THROUGH
SLAB SHALL BE FIRE PROOFED.
11. ALL PANELBOARDS SHALL BE MOUNTED ON UNISTRUT SUPPORT
SYSTEM PER DETAIL ON DRAWING 0ES517.
GENERAL POWER NOTES:
12.PROVIDE #10 AWG CONDUCTORS THROUGHOUT ALL
BRANCH CIRCUIT WIRING AND HOMERUN TO PANELBOARD.
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
T E
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F I N
C H
O
N E
FO
O
T
TH
R
EE
Q U
A R
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
( 1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
E S
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2EP102-G1
BLDG 2 SECOND FLOOR POWER PLAN- AREA
G1
LMD ADSFebruary 29, 2012
2629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
BR+A CONSULTING ENGINEERS / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
1/8" = 1'-0"1 LEVEL 02 - Power - AREA G1
THIS DRAWING HAS BEEN AFFECTED BY THE BIM
COORDINATION PROCESS. PLEASE REFER TO THE
BIM COORDINATED SHOP DRAWINGS FOR DETAILS.
RFI 04695:
No CR
CR
RFI 04695
CR
CR
PD
CR
RFI 04695
RFI 04440: Provide task lights and switches per attached drawing.
ADO
RFI 05857: HD's got relocated
RFI 06482: locate panel on shaft wall and outlet between door and shaft wall
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
MIN. DOOR SIZE
MIN. DOOR SIZE
TABLE
UP
DN
UP
J
7.5
J
J
J
J
J
J
J
J
J
J
J
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
J
J
J
J
J
J J
J
J
JJ
J
J J
J
J
J
J
J
J
J
J
J
J
J
J
JJ
J
J
J
J
J
J
J
JJ
J
J
J
J
J
J
J
J
J
J
J
J
JJ
ss
J
J
7.5
J
J
J
J
J
J
J
J
J
J
TREADMILL
B
B
TREADMILL
PS
PS
PS
ST
ST
ST
ST ST
2EP409
ST
ST
ST
B
TREADMILL
B
TREADMILL
B
B
B
MON
TREADMILL
PET/CT
MACHINE
PANEL
CEILING
MOUNTED
INJECTOR
REF
NUCLEAR MED DISCONNECT
NUCLEAR MED CIRCUIT
BREAKER
US
US
US
MRI MDP
PANEL
SEE RISER
MRI MDP
PANEL
SEE RISER
REF
02-2G-SF-32
02-2G-RF-23
P2424-8 (100A-3P) 3#4&1#6G-1 1/4"C.
LTG
PWR
R22233B-5,7 11
EC2R22232A-18
R22243A -1,3
R22233B-25
R22233B-16,18
R22233B-27 2#10 & 1#10G-3/4"C.
9 10 13 1412 15 16
R22231B-19
R22231B-20 R22231B-21 R22231B-22
19 20 21 22
PYXIS
WARMING CABINET
MIC
CC
CC
PL
US US
US USB B
PS
ST
PL
PL
TREADMILL
TREADMILL
CC
PS
CC
B
TREADMILL
ADO
PS
CORR
2F-C06
CORR
2F-C05
CORR
2G-C02
CORR
2G-C03
CORR
2G-C05A
CORR
2G-C07
CORR
2G-C06B
CORR
2G-C10
CORR
2G-C08A
CORR
2G-C09
CORR
2G-C11
CORR
2G-C04
CORR
2G-C06A
CORR
2G-C05B
CORR
2G-C08B
CC
2G119B
REF:2E139
SCR
2G117
CLEAN
2G116
REF:1D159
SOILED
HOLD
2G115
REF:2G166
MRI
2G129
REF:2G128
MRI
2G128
CONTROL
2G131
SCR
2G127
GAS/CRY
ROOM
2G125
DRESS
2G194
REF:2E117
DRESS
2G185
REF:2E117
DRESS
2G191
REF:2E117
DRESS
2G195
REF:2E117
STRESS
2G193
REF:2G196
STRESS
2G186
REF:2G196
STRESS
2G196
STRESS
2G199
STRESS
2G190
ECHO
2G141
REF:2G136
ECHO
2G140
REF:2G136
STRESS
ECHO
2G139
PERIPHERAL
VASCULAR
2G182
VASC
TREAD
2G181
STRESS
ECHO
2G138
REF:2G139
ECHO
2G136
EKG/
HOLTER
VIEW/WORK
2G192
DOSE
ADMIN
NM
2G159
TILT
TABLE
2G180
CARD
EQUIP
2G183
T
2G143
T/D
2G168
T
2G202
NUCLEAR
MED
2G164
NUCLEAR
MED
2G151
DRESS
2G160
REF:2E117
PET-CT
2G167
THYROID
UPTAKE
2G170
SCR
2G167B
REF:2E109
HOT
LAB
2G158
CONTROL
2G167A
REF:2E107
NUCLEAR
MED
2G149
REF:2G164
NUCLEAR
MED
2G150
REF:2G164
SUB-WAITING
2G201
RAD
CONF
2G178
SERVICE
BAY
2G227
INTERVIEW
NM
2G189
DRESS
2G120
REF:2E117
DRESS
2G114
REF:2E117
DRESS
2G121
REF:2E117
STAFF
WORK
2G119A
TELECOM
2G229A
PET
READ
2G175
CC
2G156
REF:2E139
STORAGE
ECHO
2G137
SUB-WAIT
CARDIO
2G123
CONTROL
2G130
REF:2G131
PAT
HOLD
2G113
REF:2G112
PAT
HOLD
2G112
T
2G118
LINEN
2G124
EQUIP
STORAGE
2G122
HK
2G126
REF:1D217
REF
STOR
2G154
REF:2G153
DRESS
2G198
REF:2E117
HK
2G169
REF:1D217
T
2G157
DRESS
2G155
REF:2E117
DRESS
2G150A
REF:2E117
DRESS
2G152
REF:2E117
LINEN
2G163
AMBULETTE
2G145
REF:2G144
AMBULETTE
2G144
DRESS
2G111
REF:2E117
LINEN
2G148A
CONTROL
RM
2G153
CC
2G184
REF:2E139
EC
2G177
LOUNGE
2G176
REF:1D162
DRESS
2G200
REF:2E117
MRI
WAITING
2G110
T
2G165
SERVICE
BAY
2G228
T
2G142
2G183.1
2G
STRESS
2G197
REF:2G196
ECHO
READING
2G187
CARD
EQUIP
2G188
HK
2G106
REF:1D217
SOILED
HOLD
2G166
2G -C
B
2G
2G227
2G
2G
-C
2G107
2G
2G1202G121
2G
2G1302G131
2G116
2G115
2G
2G
2G-C05A.1
2G -C
B
2G-C05A.2
2G
2G169
2G
2G
2G
0A
2G
2G159
2G158
2G167A.1
2G
7A .2
2G
7B
2G180
2G190
2G197
2G193
2G186
2G
2G192
2G
2G
2G187
2G188
2G189
2G
2G157
2G118
2F-C06
2G-C09
2G-C06A
2G
9A
2G
2G
7.
2G167
2G164
2G151.2
2G150
2G149
2G136
2G137
2G105
2G
2G
2G143
2G -C
2G -C
2G
2G196
2G199
2G
2G182
2G181
2G183.2
2G178.1
2G
2G
2G111
2F175
2G176
2G175
2G114
2G -C
2G
2G
2G
2G128 2G129
2G142
2G210.2
2G
7.
CORR
2F-C05
EC
2G183A
2G183A
LINEN
2G148B
LINEN
2G148C
2G128.2 2G129.2
2G
2G
1.
R22234-12
R22241A-9,11
R22241A-26
R22241A-25,27
R22241A -22,24
12 12
EC1R22241
-10,12
21EC1R22241
-18,20
R22241A-21
R22241A-16,18
18 18
EC1R22241-21
EC1R22241
-13,15
R22241A-20
E
EC1R22241
-17,19
R22241A-23
EC1R22241-14,16
R22241B -25,27
1 2 1 2
EC1R22241-11
R22242 -17,19
R22241A-38
2 2
R22241B-2
R22241B -20,22 (20A-2P)
R22241B -24
R22241B-29
R22242 -18,20
EC1R22241-6,8R22241B
-7,9
R22241B-1,3 (20A-2P)
R22241B-8
R22241B -10,12
10 10
REF
EC1R22241
-3,5
R22241B-4,6 (20A-2P)
R22241B-5
8 8
R22241B -11,13
R22241B-14
EC1R22241-7
R22241B -15,17
R22241B-16
R22241B-18
R22241B-19
R22241B-21
R22241B-23
R22243A -28,30
R22241A-28
R22243B-1
R22244-14
R22243A-25,27 (20A-2P)
R22243A-24,26
EC1R22241B-11,13
2424 23
EC1R22242A
-24,26
R22243A-16,18 (20A-2P)
R22243A-17,19 (20A-2P)
R22243A -21,23
EC1R22242B-6
R22243A -20,22
R22243B-2
5 9
R22243B -7,9
EC1R22242A
-23,25
R22243B-17,19 (20A-2P)
R22243B -13,15
R22243B-11
EC1R22242A
-20,22
EC1R22242A-21
R22243B-21
EC1R22242A-16,18EC1R22242A-17,19
R22243A-14
EC1R22242B-9
R22243A -10,12
161616
R22243B -16,183
R22243B -3,5
R22243B-14
R22243B-4
FB2 FB2
101313
R22243A -13,15
EC1R22242A
-10,12
EC1R22242A-9
REF
EC1R22242A-8
EC1R22242A-14
R22243A-5
EC1R22242A-6
EC1R22242A-4
R22243A -7,9
FH E
EC1R22242A-2
(30A-1P)
EC1R22242A-1
EC1R22242A-3
R22243A -2,4
EC1R22242A
-5,7
R22243A-11
R22243A-6,8
EQ1R2223-4
EC1R22242A-151
EDM
11 EDM
R22243B-6,8
R22243B-10,12 (20A-2P)
R22243B-24,26 (20A-2P)
R22243B- 23,25
R22243B-20,22 (20A-2P)
R22244-5,7
2 4
R22244-2,4
R22244-6
R22244-99
10 5 5
R22244-8,10EC1R22242B-5,7
1313 11
EDM
EC1R22242A-11,13
3 3
R22244-1,3
R22233B-9,11
2EP102-F2
2EP102-G2
E
P -F
E
P -F
E
P -G
E
P -G
EIT2224
EC2R22232B-2,4
R22234-14,16
R22244-12
17 13 12
R22241A-30
EC1R22242B-8,10
35 37
R22241A -35,37
R22244-13
R22244-21
ELS2223-13
2#10&1#10G-3/4"C
MGAP
MGAP
MGAP
ELS2224-10
2#10&1#10G-3/4"C
MGAP MGAP
MGAP
ELS2224-4
MGAP
MGAP
ELS2224-8
2#10&1#10G-3/4"C
MGAP
ELS2224-8
PS
EC1R22242B-4
TREADMILL
R22244-11
ATC
02-2F-VFD-53
02-2G-VFD-32
ATC
EQ5R2224-4
02-2G-VFD-63
P2424-2 (20A-3P) 3#10&1#10G-3/4"C.
MIXER PUMPS
CONTROL
PANEL
EQ5P24342-1
(125A-3P) 3#3&1#6G-1 1/4"C.
LIFT STATION
CONTROL
PANEL
EQ5P24342-7
(50A-3P) 3#8&1#10G-1 1/4"C.
EC1R22242A-28
2#10&1#10G-3/4"C.
1/3 1/3
02-2G2-FCU-1
R22243B-30 (20A-2P)
1/3
02-2G2-FCU-2
R22243B-28
2EP419
2EP418
2EP418
EC1R22242A
EC1R22242B
R222433B
R222433A
R22244
R22245
AA2
NUCLEAR MED CIRCUIT
BREAKER
NUCLEAR MED DISCONNECT
02 E 02 D C
02 H F.9
A.5
Y49
16.1
02 J
13.2
02 FEJ 4
C.5
02-2G
AHU-32
30A-3P
W/30AF
100A-3P
W/100AF
MGAP8
MGAP
ELS2224-12
48" AFF
48" AFF
48" AFF
48" AFF
48" AFF
02-2G2-CAC-3
R22244-15 (20A-3P)
02-2G2-CAC-2
R22241B-24 (30A-3P) 3#10&1#10G-3/4"C
02-2G2-CAC-1
R22241A-13 (20A-3P)
XD2424
R2241A-36
B
R22241B-30,32 (20A-2P)
TREADMILL
B R22241B-34,36 (20A-2P)
25 19
MON
MON
DH ELS2223-16
REX
ELS2224-15
DH
ELS2224-15
DH
ELS2224-16
DH
ELS2224-16
REX
ELS2224
-16
DH
ELS2224-16
DH
ELS2224-16 DH
ELS2224-16
R22241A-6
REX
ELS2224-15
L6-30R
FOR SCANNER
SEE RISER
L6-30R
FOR SCANNER
SEE RISER
MP
SEE RISER
L6-30R
FOR SCANNER
SEE RISER
KEY NOTES:
ALL MATERIALS WITHIN MRI ROOM
SHALL BE NON-FERROUS TYPE:
LIGHTING, CONDUIT, DEVICES, ETC.
2 ALL BRANCH CIRCUITS AND OTHER
SYSTEM WIRING SHALL PASS
THROUGH APPROPRIATE CURRENT
RATED THRU RF FILTER.
3 120 VOLT POWER TO FERROMAGNETIC
DETECTOR SYSTEM POWER SUPPLY
MOUNTED ABOVE DOOR. PROVIDE
SINGLE POLE TOGGLE SWITCH AND
COORDINATE LOCATION WITH
EQUIPMENT SUPPLIER.
1. REFER TO LEGEND AND GENERAL NOTES ON DRAWING
0ES001.
2. EXACT LOCATIONS OF FLOOR OUTLETS AND/OR POKE
THRU DEVICES SHALL BE COORDINATED WITH ARCHITECTURAL
FURNITURE PLANS AND ACTUAL FIELD DIMENSIONS
BASED ON DIRECTION FROM RESIDENT ENGINEER.
3. COORDINATE EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL DRAWINGS.
4. REFER TO MOTOR WIRING SCHEDULE ON DRAWING
0ES503 FOR MOTOR FEEDER SIZES.
5. VFD’S FURNISHED AND INSTALLED UNDER DIVISION
23 WIRED UNDER DIVISION 26.
6. REFER TO MEDICAL EQUIPMENT FLOOR PLANS FOR EQUIPMENT
LOCATIONS.
7. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATION
OF WALL MOUNTED DEVICES AND MOUNTING HEIGHTS, PRIOR TO
ROUGHIN
8. REFER TO A/V CONSULTANT DRAWINGS FOR A/V DEVICES
AND REQUIREMENTS.
9. ALL BRANCH CIRCUIT WIRING FROM PANELS SHALL BE
RUN WITHIN THE INSTERSTITIAL SPACE (WHERE APPLICABLE)
AND ABOVE CEILINGS IN AN ORGANIZED MANNER TO NETWORK
JUNCTION BOXES. REFER TO TYPICAL BRANCH CIRCUITING DETAIL
DWG 0ES517.
10. WHERE BRANCH CIRCUIT CONDUITS ARE ROUTED IN
INTERSTITIAL SPACE, CONDUITS PENETRATIONS THROUGH
SLAB SHALL BE FIRE PROOFED.
11. ALL PANELBOARDS SHALL BE MOUNTED ON UNISTRUT SUPPORT
SYSTEM PER DETAIL ON DRAWING 0ES517.
GENERAL POWER NOTES:
12.PROVIDE #10 AWG CONDUCTORS THROUGHOUT ALL
BRANCH CIRCUIT WIRING AND HOMERUN TO PANELBOARD.
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
TE
R
IN
C H
O
N E
FO
O
T O
N E
H A L
F
IN
C H
O
N E
FO
O
T
TH
R
EE
Q U
AR
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
E E T
(1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
X T
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
ES
O N
E
FO
O T
6"
BUILDING NUMBER
2EP102-G2
BLDG 2 SECOND FLOOR POWER PLAN- AREA
G2
LMD ADSFebruary 29, 2012
2629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
NEW ORLEANS, LOUISIANA
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
BR+A CONSULTING ENGINEERS / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of
Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
1/8" = 1'-0"
LEVEL 02 - Power - AREA G2
3 Door Hardware Revisions
30 BULL 029C - Imaging 7/23/2014
RFI 02674: Provide a receptacle in lieu of a hard wired connection for horizontal bench hood L2290.
THIS DRAWING HAS
BEEN AFFECTED
BY THE BIM
COORDINATION
PROCESS. PLEASE
REFER TO THE BIM
COORDINATED
SHOP DRAWINGS
FOR DETAILS.
RFI 03960:
Locate per arch.
sketch for room 2G181
RFI 03959:
Locate per
Arch. sketch.
RFI 03958:
Locate per arch. sketch
RFI 03957:
Relocate Recept per arch. sketch.
RFI 03956: Locate Receptacles per Arch Sketch.
CR
RFI 04695
PD
PD
RFI
04695
RFI 05018:
Not Required
RFI 05019: Locate at 48" AFF.
RFI 05644: Relocate outlet
RFI 06141:
Locate below window
RFI 06205: CAC
relocated to south wall
RFI 06205: CAC
relocated to south wall
RFI 06790 Directs to install pull boxes per the drawings with no additional access
RFI's 08012 & 08012.1 further clarify Bull 29 requirements
RFI 08455 Metal Detector J-Box
T ectonic Cop yright 2007
Tectonic Cop yright 2007
Tectonic Cop yright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
UP
J
J
J
J J
J
J
J
JJ J
J
J
J
J
J
J
JJ
JJ
JJ
J
J
J
J
J
J
J
J
J
J
EC1L2434
R22341B
T6T6
L2434
EC1D2234D2234
FATCR22341A
2EP408
R22342A
R22342BLC2434
2EP402
REF
TREADMILL
PS
MON
PL 02- 3G-SF-35
02-3G-RF-26
EQ5P24341-1
(20A-3P) 3#10&1#10G- 3/4"C
EQ5P24341-7
(50A-3P) 3#8&1#10G-3/4"C
LTGPWR
3 3
EC1R22341A
R22341A-16,18
R22341A -22
R22341A -23,25
R22342A -19,21
R22341B-6,8
R22341B-20
R22342A-14
R22342A-22
E E
R22342A-24
15 1517
R22341B- 21,23
R22341B- 17,19 R22341B-
16,18
12 14
R22341B- 12,14
R22341B- 13,15
13 13 17
R22341B-9,11
R22341B-10
A
9 A
EC1R22341A-
12,14
EC1R22341A-
16,18
EC1R22341A-
15,17
EQ5P24341
EC1R22341A
-20
EC1R22341A-22
MALE
3G100B
T1
EQUIP
STOR
3G108 C4
PULM
RECEPT
3G101 M1A
SERVICE
BAY
3G227 G8A
TELECOM
3G227A G2
EMER
ELEC
3G227D G2
NORM
ELEC
3G227C G2
FEMALE
3G100A
T1
ISOL
3G103 C33
ISOL
3G104
C33 PULM
SCREEN
3G106
C32A
PFT
3G105
C32A
EXERCISE
PHYS
3G102 C38
CYLINDER
3G108C C55B
CC
3G107 C35
SECY/WAIT
3G136 S1
SOILED
3G134 C2
RECOVERY
3G115
C20A
BLOOD
GAS
3G135 C6A
CLEAN
3G133 C6
CORR
3G-C02A
CORR70
CORR
3G-C02C
CORR70
CORR
3G-C02B
CORR70
CORR
3G-C01
CORR73
SECURITY
3G227B S19
STAIR
2F152 G1
RT
3G110E S4
RT
3G110D
S4
RT
3G110C S4
RT
3G110B S4
RT
3G110A
S4
ADO
ADO
GFCI GFCIGFCI
GFCI
ATC
AFS
AFS
AFS 21AFS
EQ5R2244-5
2E P1
-F
EP
3- A3
2E P1
-G
EP
3- A3
2E P1
-F
2E
P1
-F
2E P1
-G
2E
P1
-G
EIT2234
EC1R22341B
R22342A-20
T4-1
EQ5R2244-1
EWC
UP TO
ELS2244-7
MGAP
MGAP
MGAP
UP TO ELS2244-5
2#10&1#10G-3/4"C
R22342A-16
EWC
ST
02-3G-VFD-66
P P P P
R22341B- 25,27,29,31
1 1 1
25,27,29,31 25,27,29,31 25,27,29,31
HD
R22342A-26,28 (20A-2P)
HD
R22342A-23,25 (20A-2P)
R22342B-1
TRAP
PRIMER
1/3 1/3
02-3G1-FCU-1
R22342A-27 (20A-2P)
02-3G1-CAC-1
EIT2234-32
(30A-3P) 3#10&1#10G-3/4"C
02-3G-VFD-35
XA
XD
A.5
AA
AA.2
16.1
13.2
A
XC
8 8
02- 3G
AHU-35
BUSDUCT
NB241
BUSDUCT
EB214
60A-3P
W/50AF
30A-3P
W/20AF
48" AFF
48" AFF
EC1R22341-19
EQ5R2244-3
R22341B-24
REX
ELS2244-15
R22341B-30
DH
ELS2244-14
DH
DH
KEY NOTES
1 BRANCH CIRCUIT WIRING SERVING PARTITION SYSTEM
SHALL BE FOUR CIRCUIT, 4#12,2#12G & 2#10 NEUTRALS
REFER TO MANUFACTURERS WIRING DIAGRAMS.
1. REFER TO LEGEND AND GENERAL NOTES ON DRAWING
0ES001.
2. EXACT LOCATIONS OF FLOOR OUTLETS AND/OR POKE
THRU DEVICES SHALL BE COORDINATED WITH ARCHITECTURAL
FURNITURE PLANS AND ACTUAL FIELD DIMENSIONS
BASED ON DIRECTION FROM RESIDENT ENGINEER.
3. COORDINATE EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL DRAWINGS.
4. REFER TO MOTOR WIRING SCHEDULE ON DRAWING
0ES503 FOR MOTOR FEEDER SIZES.
5. VFD’S FURNISHED AND INSTALLED UNDER DIVISION
23 WIRED UNDER DIVISION 26.
6. REFER TO MEDICAL EQUIPMENT FLOOR PLANS FOR EQUIPMENT
LOCATIONS.
7. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATION
OF WALL MOUNTED DEVICES AND MOUNTING HEIGHTS, PRIOR TO
ROUGHIN
8. REFER TO A/V CONSULTANT DRAWINGS FOR A/V DEVICES
AND REQUIREMENTS.
9. ALL BRANCH CIRCUIT WIRING FROM PANELS SHALL BE
RUN WITHIN THE INSTERSTITIAL SPACE (WHERE APPLICABLE)
AND ABOVE CEILINGS IN AN ORGANIZED MANNER TO NETWORK
JUNCTION BOXES. REFER TO TYPICAL BRANCH CIRCUITING DETAIL
DWG 0ES517.
10. WHERE BRANCH CIRCUIT CONDUITS ARE ROUTED IN
INTERSTITIAL SPACE, CONDUITS PENETRATIONS THROUGH
SLAB SHALL BE FIRE PROOFED.
11. ALL PANELBOARDS SHALL BE MOUNTED ON UNISTRUT SUPPORT
SYSTEM PER DETAIL ON DRAWING 0ES517.
GENERAL POWER NOTES:
12.PROVIDE #10 AWG CONDUCTORS THROUGHOUT ALL
BRANCH CIRCUIT WIRING AND HOMERUN TO PANELBOARD.
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
T E
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F I N
C H
O
N E
FO
O
T
TH
R
EE
Q U
A R
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
( 1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
E S
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2EP103-G1
BLDG 2 THIRD FLOOR POWER PLAN- AREA G1
LMD ADSFebruary 29, 2012
2629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
BR+A CONSULTING ENGINEERS / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
1/8" = 1'-0"1 LEVEL 03 - Power - AREA G1
THIS DRAWING HAS BEEN AFFECTED BY THE BIM
COORDINATION PROCESS. PLEASE REFER TO THE
BIM COORDINATED SHOP DRAWINGS FOR DETAILS.
RFI 04070:
Delete duplex.
RFI 04069:
Relocate receptacles.
RFI 04068:
Locate per Arch. Elev.
PD
PD
PD
CR
CR
RFI 04695
CR
RFI
04695
RFI 04440: Provide task lights and switches per attached drawing.
RFI 05857: HD's got relocated to opposite wall.
RFI 06482: locate panel on shaft wall and outlet between door and shaft wall
Tectonic Copyright 2007
Tectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
T ectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Copyright 2007
Tectonic Cop yright 2007
T ectonic Cop yright 2007
Tectonic Copyright 2007
DN
UP
UP
UP
J
J
J
J
J J J J J J J
J
J J
JJ J
J
J J
J
J
J J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J J J J J J J
J
J J
J
JJ
J J
J
JJ
J
J
J
J
J
J JJ J
J
J
J
J J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
MIC
MON
PS
2EP409
AB
PED
R22333A-6
SS LB2
MS
REF
P
PS
PS
MON
PS
MON
PS
MON
PS
MON
PS
MON
PS
MON
PS
MON
MON
PS
MON
MC
MC
EEC
ERCP CIRCUIT BREAKER
ERCP3G166
100AF/60AT/3P
MC
EEC
MC
MC
RDM
E
2EP403
2EP403
PL
PL PL PL PL PL PL PL
ADO
ADOADO
ADO
ADO
ADO
ADO
ADO
ADO
ADO
ADO
02-3G-SF-34
02-3G-RF-25
LTGPWR
EQ5P24342-2
(80A-3P) 3#6&1#8G-1"C.
EQ5P24342-8
(20A-3P) 3#10&1#10G- 3/4"C
R22343A- 5,7
R22343A- 14,16
12 10 12 10
R22343A- 10,12
R22343A- 18,2020
R22343A-23 R22343A- 13,15
R22343A-19
R22343B-2
R22343A- 26,28
EC1R22342A-2
1R22343B-1
R22343B-7
1 1
EC1R22342A-1
R22343A-27
R22343A-22,24
R22344-7
13 15
13R22344-
13,15
R22344-3,5
R22344-14
11 11
1111 PS
AV
AV
R22344-2,4
PD
R22343B-5
R22344-102
8 6 8
EC1R22342A-3
R22343B-4
R22341A-1,3
9 9
7 7
4 4
8 8
6 6
3 3
R22341A-2,4 R22341A-5,7 R22341A-6,8
R22341A-24
R22341A-13,15
17 17
R22341A-19,21
R22341A-16,18
R22341A -22
R22341A -23,25
R22342A -19,21
R22341B- 1,3,5,7
R22341A-20
R22342A- 1,3,5,7
3 4
R22341A- 26,28
R22342A- 10,12
13 13
R22342A- 11,13
R22341B-2,4
R22341B-6,8
R22341B-20
R22342A- 15,17
R22342A-9
R22341A-9,11
13 13
R22341B- 21,23
R22341B- 13,15
27 29
R22332B- 27,29
1717 17
PL MON
5 7
12 12
15 PL MON
6 8
10 10
PL
MON
28 30 9 9
MON
PL
21 19
5 7
7EC2R22331B-5,7
EC2R22331B-
9,11
R22332B-15
EC2R22331B-10,12
R22332A- 6,8 R22332A-19,21
R22332A-9
209 9 9
R22333A-9
PANEL FOR
XRAY MACHINE
EC2R2232A-11
21 10
E E
EC1R22341A-7,9 EC1R22341A-52
EC1R22341A-2,4
R22341A-17
EC1R22341A
-10
EC1R22341A-
11,13
EC1R22341A-
1,3
EC1R22341A
-6,8
EC1R22341A-
12,14
EC
R22343A-21
MON
MON
SCR
3F167D C15
CONTROL
3F167C C16
STAFF
LOCKERS
3G193 S14C
SCRUB
3F167B C14
STRETCHER
3F164D C17
STAFF
LOCKERS
3G192 S14C
STAFF
LOUNGE
3G194
S15PHYS
LOUNGE
3G191 S15
PRE/REC
3F144
C20A
PREP/
INDUCT
3F145
C20A
PRE/REC
3F142
C20A
PRE/REC
3F143
C20A
PRE/REC
3F141
C20A
HC ST/S
3G192C
T5
CORR
3G-C05
CORR73
SOILED
3F176 C2
GI ASSIST
3G145O S4B
PHYS
3G146C S4B
RN TECH
3G145K S4B
ADMIN
3G146A S4B
PHYS
3G145C S4B
PHYS
3G145F S4B
PHYS
3G145E S4B
PHYS
3G145D S4B
PHYS
3G145A S4B
SECY
3G146B S4B
RN TECH
3G145N S4B
RN TECH
3G145L S4B
RN TECH
3G145M S4B
GI ASSIST
3G145J S4B
GI ASSIST
3G145I S4B
EC
3G186 G2
SERVICE
BAY
3G228 G8
NURSES
STATION
3G124 M5K
STRETCHER
STORAGE
3G152 C17
DIG
DISEASE
RESIDENTS
3G185 S9
DICT/
VIEW
3G178 S17
DG CLER
3G145P S4B
PHYS
3G145B S4B
T 3G127 T3
PHYS
3G145G S4B
CC
3G128 C35
TELECOM
3G227A G2
T 3G126 T3
ISOL
3G103 C33
CC
3G107 C35
STORAGE/
COPY
3G144 S18
RES
CONF/
CLASSROOM
3G181 S12
OFFICE
CHIEF
CARDIO
3G138 S7
CHIEF
RESIDENT
3G137 S7
OFFICE
NURSE
MGR
3G139 S3
CONFERENCE
ROOM
(CL)
3G180 S9A
SECY/WAIT
3G136 S1
TEST
3G129 C30J
SOILED
3G134 C2
RECOVERY
3G116
C20A
RECOVERY
3G122
C20A
RECOVERY
3G121
C20A
RECOVERY
3G118
C20A
CLEAN
3G125 C6
RECOVERY
3G120
C20A
RECOVERY
3G117
C20A
GENERAL
ENDO
3G169
C12A
GENERAL
ENDO
3G168
C12A
CLEAN
SCOPE
STORAGE
3G160 C6B
SCOPE
STORE
3G158 C6B
STRETCHER
STORAGE
3G171 C17
T 3G165 T3
T 3G175 T3
CLEAN
3G162 C6
SOILED
3G161 C2
COPY/
WORK
3G179 S18
PROCEDURE
BRONCH
3G153 C12H
GENERAL
ENDO
3G156
C12A
GENERAL
ENDO
3G155
C12A
CONTROL
3G153A C12H
DG
PRIVATE
INTERVIEW
3G141 S3
DG CHIEF
OFFICE
3G140 S7
DG NURSE
MANAGER
3G143 S3
RECOVERY
3G115
C20A
RECOVERY
3G119
C20A
LINEN
STOR
3G157
CORR79
EQUIP
CLEAN-UP
3G159 C6C
STRETCHER
STORAGE
3G170 C17
STRETCHER
STORAGE
3G154 C17
HK
3G190 C3
BLOOD
GAS
3G135 C6A
CLEAN
3G133 C6
FULL
CYLINDER
3G151 C55B
RECOVERY
3G123
C20A
PHYS
3G145H S4B
ST
3G176 T4
ST
3G177 T4
EMPTY
CYLINDER
3G150 C4A
CORR
3G-C02A
CORR70
CORR
3G-C02C
CORR70
CORR
3G-C02B
CORR70
CORR
3G-C03B
CORR74
CORR
3G-C11
CORR78
CORR
3G-C12
CORR73
CORR
3G-C07A
CORR70
CORR
3G-C07B
CORR77
CORR
3G-C08A
CORR79
CORR
3G-C09
CORR79
CORR
3G-C10
CORR79
CORR
3G-C08B
CORR72
CORR
3G-C03A
CORR74
CORR
3G-C04
CORR72
CORR
3G-C06
CORR79
CORR
3G-C13 S4B
TRAINING/
WORK
3G187 S9
MED PREP
3G163
C15E
EUS/COMPLEX
3G167 C12J
ERCP
3G166 C12J
DG SECY/
FILES
3G142 S4B
PHYS
WORK
3G164 C12J
HC ST/S
3G193C
T5
LINEN
STOR
3G157A
CORR79
R22143A-31 REX
R22344-6,8ADO
26 26
EC
7 23
REF
R22344-19,21
EC1R22342B-11
R22344-23
R22344-18,20
EC1R22342B-9
EC1R22342B-6
R22343B-25EC1R22342B-7
ADO
ADO
ADO
J
ADO
GFCI
GFCI
EC1R22341A
-21,23
REX
ATC
PTF
FB1
FB2
EC2P2236-5 5
ICIC
EC1P2236-6
EC1P2236-5,7
EC1P2236-12EC2P2236-4,6
EC1P2236-9
PD
EC1R22342B-8,10
EC1R223432B-2,42
12 14
EC1R22342B-12,14
18 18 4 20
2 5 5 5 3 3
EC1R22342B-3,5
EC1R22342B-16
R22344-16
1717 29 15 29 27 27
15 15 15 13 13
EC1R22342B-13,15
R22343B-27,29
EC1R22342B-17,19
6 6 6
R2234A-6,8
R22343A-1,3
R22343A -2,4
REF
MIC
EDM
28EC1R2234B
-26,28
EC1R22342A-31
EC1R22342B-21,23,25
R22343B-21
R22344-22,24
R22343B-19
11 24 13 11
22 24 22
EC1R22342A-22,24 R22343B-11,13
R22343B-15
EC1R22342A-20
R22343B-9
EC1R22342A-25,27,29
EC1R22342A-23
EC1R22342A-14
141416
R22343B-16
EC1R22342A
-17,19
191212
R22343B-12,14
EC1R22342A-15
EC1R22342A-16,18
2EP103-F2
2EP103-G2
2E P1
-F
2E
P1
-F
2E P1
-G
2E
P1
-G
EIT2234
20EC1R22341A-32
R22341B-32
17R22343A-17
R22343B-17
R22343A -25
REX
EQ5R2244-11
MGAP
MGAP
MGAP
UP TO ELS2244-1
2#10&1#10G-3/4"C
MGAP
MGAP
UP TO ELS2244-5
2#10&1#10G-3/4"C
MGAP
5MGAP
MGAP
UP TO ELS2244-3
2#10&1#10-3/4"C
MGAP
PS
PS
PS
PS
EC2R2232A-5
EC16
EC1R22342A-6
ST
R22343A-9,11
JEC 14
EC 3 J
GFI
EC1P2231
EC2P2231
EC1R22343B-2,4
EC 9
R22344
1 1
EC1R22343B-1
EC1R22343B-75
ADO
02-3G-VFD-65
02-3G-VFD-34
1 FB1 1 FB1
R22344-1
UPDN
R22344-9,11
FB2
IG
PTF
1,3,5,7
R22342A-
2,4,6,8PTF
PTF
2,4,6,8
IG
P
P
1,3,5,7
1,3,5,7
1/3
R22343B-18
02-3G2-FCU-1
EC1R22342B
EC1R22342A
R22343B R22343A
R22343B-22
G
G
EQ5P24342
02 E 02 D 02 C
02 H 02 F.9
A.5
16.1
02 J
13.2
02 F 02 C.5
MON
PL
11 23
02-3G
AHU-34
30A-3P
W/20AF
100A-3P
W/80AF
48" AFF
48" AFF
48" AFF
48" AFF
48' AFF48" AFF
48" AFF
48" AFF
02-3F2-CAC-6
EQ5R2244-9
EQ5R2244-7
DH
ELS2223-12
R22331A-33
EC1R22342B-18
R22341B-24
REX
REX
ELS2244-16
REX
ELS2244-16
ELS2244-16
ELS2244-16
R22341B-30 R22341B-30R22341B-30
R22341B-30
R22341B-26 R22341B-26
R22341B-26
R22341B-26
R22341B-28 R22341B-28
R22341B-28 R22341B-28
R22341B-24
R22341B-24
ELS2244-16
RG
DH
DH
ELS2244-14
DH
DH
DH
ELS2244-14
DH
DH
PROVIDE #10 AWG CONDUCTORS THROUGHOUT ENTIRE
LENGTH OF HOMERUN AND BRANCH CIRCUIT.
PROVIDE #10 AWG CONDUCTORS ON HOMERUN FROM PANEL TO
JUNCTION BOX. PROVIDE #12AWG THOUGHOUT FOR BRANCH
CIRCUIT WIRING.
BRANCH CIRCUIT WIRING SERVING PARTITION SYSTEM SHALL BE
FOUR CIRCUIT 4#12, 2#12G & 2#10 NEUTRALS. REFER TO
MANUFACTURER'S WIRING DIAGRAM.
RUN BRANCH CIRCUITS IN ACCESSIBLE CEILING SPACE OF FLOOR
BELOW AND UP NEAREST WALL TO ABOVE ACCESSIBLE CEILING.
PROVIDE BRANCH CIRCUIT AS INDICATED ON PLAN.
KEY NOTES:
1. REFER TO LEGEND AND GENERAL NOTES ON DRAWING
0ES001.
2. EXACT LOCATIONS OF FLOOR OUTLETS AND/OR POKE
THRU DEVICES SHALL BE COORDINATED WITH ARCHITECTURAL
FURNITURE PLANS AND ACTUAL FIELD DIMENSIONS
BASED ON DIRECTION FROM RESIDENT ENGINEER.
3. COORDINATE EXACT LOCATION OF ALL MECHANICAL
EQUIPMENT WITH MECHANICAL DRAWINGS.
4. REFER TO MOTOR WIRING SCHEDULE ON DRAWING
0ES503 FOR MOTOR FEEDER SIZES.
5. VFD’S FURNISHED AND INSTALLED UNDER DIVISION
23 WIRED UNDER DIVISION 26.
6. REFER TO MEDICAL EQUIPMENT FLOOR PLANS FOR EQUIPMENT
LOCATIONS.
7. REFER TO ARCHITECTURAL ELEVATIONS FOR COORDINATION
OF WALL MOUNTED DEVICES AND MOUNTING HEIGHTS, PRIOR TO
ROUGHIN
8. REFER TO A/V CONSULTANT DRAWINGS FOR A/V DEVICES
AND REQUIREMENTS.
9. ALL BRANCH CIRCUIT WIRING FROM PANELS SHALL BE
RUN WITHIN THE INSTERSTITIAL SPACE (WHERE APPLICABLE)
AND ABOVE CEILINGS IN AN ORGANIZED MANNER TO NETWORK
JUNCTION BOXES. REFER TO TYPICAL BRANCH CIRCUITING DETAIL
DWG 0ES517.
10. WHERE BRANCH CIRCUIT CONDUITS ARE ROUTED IN
INTERSTITIAL SPACE, CONDUITS PENETRATIONS THROUGH
SLAB SHALL BE FIRE PROOFED.
11. ALL PANELBOARDS SHALL BE MOUNTED ON UNISTRUT SUPPORT
SYSTEM PER DETAIL ON DRAWING 0ES517.
GENERAL POWER NOTES:
12.PROVIDE #10 AWG CONDUCTORS THROUGHOUT ALL
BRANCH CIRCUIT WIRING AND HOMERUN TO PANELBOARD.
Q D2 D1
E2 E1
F2 F1
G2 G1
A2
A4
A5
A1
A6
B1
C1 C2
B2
H
J1 J2
L
K
M1 M2 M3
N1 N2
A7
D3
E3
F3
R1
R4
R2 R3
A3
08 P
PLAN
NORTH
DATE
LOCATION
CHECKED DRAWN
PROJECT TITLE PROJECT NUMBER
DOCUMENT SET PACKAGE
DRAWING NUMBERAPPROVED: PROJECT DIRECTOR
DRAWING TITLEARCHITECT/ENGINEERS:CONSULTANTS:
REVISIONS: DATE
B
A
D
C
E
VA FORM 08-6231
O N
E
EI
G H
T
IN
C H
O
N E
FO
O
T O
N E
Q U
AR
T E
R
IN
C H
O
N E
FO
O
T O
N E
H
AL
F I N
C H
O
N E
FO
O
T
TH
R
EE
Q U
A R
TE
R S
IN
C
H
O N
E
FO
O T
TH
R
EE
IN
C H
ES
O N
E
FO
O T
O N
E
IN
C H
F
O R
TY
F
EE
T
( 1
0'
6"
6"
0'
0'
123456
F
B
A
D
C
E
F
O N
E
SI
XT
EE
N
TH
IN
C
H
O N
E
FO
O T
O N
E
AN
D O
N E
H
AL
F
IN
C H
E S
O N
E
FO
O T
6"
BUILDING NUMBER
NEW ORLEANS, LOUISIANA
2EP103-G2
BLDG 2 THIRD FLOOR POWER PLAN- AREA G2
LMD ADSFebruary 29, 2012
2629-HS2-401SLVHCS REPLACEMENT MEDICAL
CENTER PROJECT
SCHRENK & PETERSON CONSULTING ENGINEERS / CIVIL
KORDA/NEMETH ENGINEERING / STRUCTURAL
BR+A CONSULTING ENGINEERS / MECH, ELECT, PLUMBING, LOW VOLTAGE
ARCHITECTURAL ENGINEERING / PLUMBING
SCALES ASSOCIATES / FIRE PROTECTION
BR+A CONSULTING ENGINEERS / LOW VOLTAGE
DESMAN ASSOCIATES / PARKING
CODE CONSULTANTS, INC. / CODE CONSULTANT
THE SEXTANT GROUP / AV & ACOUSTICAL
HAMMER DESIGN ASSOCIATES / FOOD SERVICE
PYBURN & ODOM / ABATEMENT
TATA & HOWARD / TANK CONSULTANT
I.S.C. GROUP, INC./ IRRIGATION
DAN EUSER WATER ARCHITECTURE, INC./ WATER FEATURE
Department of Veterans Affairs
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
WP_08
CONSTRUCTION DOCUMENTS 1
FULLY SPRINKLERED
1/8" = 1'-0"1 LEVEL 03 - Power - AREA G2
THIS DRAWING HAS
BEEN AFFECTED BY
THE BIM
COORDINATION
PROCESS. PLEASE
REFER TO THE BIM
COORDINATED SHOP
DRAWINGS FOR
DETAILS.
RFI 04079:
18" AFF.
PD
PD
PD
PD
RFI 04695
PD
PD
PD
PD
CR
CR
PD
PD
PDPD
PDPD
PDPD
CR
PD
PD
CR
REX
PD
PD
PD
PD
PD
PD
PD PD
PD
PDPD
PD
PD
PD
PD
PD
PD
PD
RFI 04695: All
CR'S AND PD'S
ADDED TO THIS
PAGE
ADO
PD
PD
RFI 04767:
Located PD's
ADO
RFI 06066: Added receptacle for
CAB3107
RFI 06066.2: Install above cabinet
RFI 06066: Added receptacle for
CAB3107
RFI 06066.2: Install above cabinet
RFI 06066: Added receptacle for
CAB3107
RFI 06066.2: Install above cabinet
RFI 06066: Added receptacles for CAB3107's RFI 06066.2: Install above cabinet
RFI 06066: Added receptacle for CAB3107 RFI 06066.2: Install above cabinet
RFI 06066: Added receptacle for CAB3107 RFI 06066.2: Install above cabinet
RFI 06066.1: Added receptacle, center of wall for CAB3107
RFI 06280:
Receptacle locations
RFI 06280:
Receptacle locations
RFI 06280:
Receptacle locations
RFI 06280:
Receptacle locations
RFI 06280:
Receptacle locations
RFI 06280:
Receptacle locations
RFI 07965: Provide j-box with blank plate above ceiling at motorized screen. No projector to be provided.