EMBASSY OF THE UNITED STATES
INTERNATIONAL NARCOTICS AND
LAW ENFORCEMENT
BOGOTA, COLOMBIA
NOTICE:
THIS DOCUMENT IS THE PROPERTY OF
THE U.S. GOVERNMENT. FURTHER
REPRODUCTION AND/OR DISTRIBUTION IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF THE INTERNATIONAL
NARCOTICS AND LAW ENFORCEMENT
SECTION, BOGOTA, COLOMBIA.
INFORMATION ON THIS DOCUMENT IS NOT
TO BE ALTERED EXCEPT WITH THE
WRITTEN APPROVAL OF THE OFFICE.
MANAGED BY:
I.N.L
INTERNATIONAL NARCOTICS AND LAW
ENFORCEMENT EMBASSY OF THE
UNITED STATES.
BOGOTA, COLOMBIA
SHEET No:
A & E DESIGN FIRM:
DIAZ VILLEGAS ARQUITECTOS
www.diazvillegasarquitectos.com
TELEFONO: 6262659 - 7042265
PROJECT:
LOCATION:
CONTRACT NUMBER:
COR VO.Bo.:
OF:
REVIEW:PLAN No:
CONTENIDO:
LEGEND:
REVIEWS:
PHASE:
10% 35% 60% 90% 100%
DRAWING DATE:
SIGNATURE:
PROFFESIONAL CARD:
PROFFESION:
LIFETED BY:
CONTENTS:
No. SUBMITTAL DATE
CONTRACT DATE:
SCALE:
OBSERVATIONS:
SHEET PLAN:
SHEET No:
OF:
REVIEW: PLAN No:
A&E OPERATIONAL CENTER FITOUT,
12 CITIES FOR THE COLOMBIAN
NATIONAL POLICE
SCO150-16-M-0313
OCT 03 / 2016
SN230-53938
Mechanical Engineer
Ing. Yeciht Palma
GENERAL PLANT ADJUSTMENTS PROPOSED HVAC SYSTEM
SCALE 1:25
PLANTA GENERAL PROPUESTA SISTEMA AIRE ACONDICIONADO
ESCALA 1:25
A1
MAA-101
PLANTA GENERAL PROPUESTA SISTEMA
AIRE ACONDICIONADO
MAA-101
1 : 25
087.01-BOGOTA-MAA-101.dwg
GENERAL PLANT ADJUSTMENTS PROPOSED
HVAC SYSTEM
AutoCAD SHX Text
CAFETERIA
AutoCAD SHX Text
CAFETERIA
AutoCAD SHX Text
(SALIDA DE EMERGENCIA)
AutoCAD SHX Text
EMERGENCY EXIT
AutoCAD SHX Text
CORREDOR DE PASO
AutoCAD SHX Text
PASS CORRIDOR
AutoCAD SHX Text
OFICINAS
AutoCAD SHX Text
OFFICES
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
OUTDOORS
AutoCAD SHX Text
ERVC4V
AutoCAD SHX Text
AutoCAD SHX Text
ERVC4V
AutoCAD SHX Text
AutoCAD SHX Text
ERVC4V
AutoCAD SHX Text
AutoCAD SHX Text
EMSP
AutoCAD SHX Text
AutoCAD SHX Text CONDENSING UNIT MINISPLIT Capacity: 1,5Ton/18.000Btu/H Consumed Power: 220V/1fase/60Hz/1,55kW Current: 7,0A Protection: 20A Dim: 0.77X0.55X0.29Mts Weight: 34Kg Refrigerant: R410A
AutoCAD SHX Text
UCMSP
AutoCAD SHX Text
AutoCAD SHX Text CONDENSING UNIT VRF Capacity: 10,0Ton/120.000Btu/H Consumed Power: 220V/3fase/60Hz/9,1kW Current: 39,5A Protection: 50A Dim: 1,25X1.80X0.45Mts Weight: 180Kg Refrigerant: R410A
AutoCAD SHX Text
UCVRF
AutoCAD SHX Text
AutoCAD SHX Text
ERVC4V
AutoCAD SHX Text
AutoCAD SHX Text CASSETTE VRF TYPE-INTERIOR UNIT EQUIPMENT Capacity: 24.000Btu/H Consumed Power: 220V/1fase/60Hz/33W Dim Equipment: 0.84X0.84X0.21Mts Dim Panel: 0.95X0.95X0.025Mts Weight Equipment: 20,8Kg Weight Panel: 5,6Kg
AutoCAD SHX Text CASSETTE VRF TYPE-INTERIOR UNIT EQUIPMENT Capacity: 24.000Btu/H Consumed Power: 220V/1fase/60Hz/33W Dim Equipment: 0.84X0.84X0.21Mts Dim Panel: 0.95X0.95X0.025Mts Weight Equipment: 20,8Kg Weight Panel: 5,6Kg
AutoCAD SHX Text CASSETTE VRF TYPE-INTERIOR UNIT EQUIPMENT Capacity: 36.000Btu/H Consumed Power: 220V/1fase/60Hz/144W Dim Equipment: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Weight Equipment: 23,5Kg Weight Panel: 5,6Kg
AutoCAD SHX Text EQUIPO TIPO CASSETTE VRF-UNIDAD INTERIOR Capacidad: 24.000Btu/H Potencia Consumida: 220V/1fase/60Hz/33W Dim Equipo: 0.84X0.84X0.21Mts Dim Panel: 0.95X0.95X0.025Mts Peso Equipo: 20,8Kg Peso Panel: 5,6Kg
AutoCAD SHX Text EQUIPO TIPO CASSETTE VRF-UNIDAD INTERIOR Capacidad: 24.000Btu/H Potencia Consumida: 220V/1fase/60Hz/33W Dim Equipo: 0.84X0.84X0.21Mts Dim Panel: 0.95X0.95X0.025Mts Peso Equipo: 20,8Kg Peso Panel: 5,6Kg
AutoCAD SHX Text EQUIPO TIPO CASSETTE VRF-UNIDAD INTERIOR Capacidad: 36.000Btu/H Potencia Consumida: 220V/1fase/60Hz/144W Dim Equipo: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Peso Equipo: 23,5Kg Peso Panel: 5,6Kg
AutoCAD SHX Text MINISPLIT TYPE-INTERIOR UNIT EQUIPMENT Capacity: 18.000Btu/H Consumed Power: 220V/1fase/60Hz/30W Dim Equipment: 1.03X0.33X0.25Mts Weight Equipment: 14Kg
AutoCAD SHX Text EQUIPO TIPO MINISPLIT-UNIDAD INTERIOR Capacidad: 18.000Btu/H Potencia Consumida: 220V/1fase/60Hz/30W Dim Equipo: 1.03X0.33X0.25Mts Peso Equipo: 14Kg
AutoCAD SHX Text CASSETTE VRF TYPE-INTERIOR UNIT EQUIPMENT Capacity: 36.000Btu/H Consumed Power: 220V/1fase/60Hz/144W Dim Equipment: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Weight Equipment: 23,5Kg Weight Panel: 5,6Kg
AutoCAD SHX Text EQUIPO TIPO CASSETTE VRF-UNIDAD INTERIOR Capacidad: 36.000Btu/H Potencia Consumida: 220V/1fase/60Hz/144W Dim Equipo: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Peso Equipo: 23,5Kg Peso Panel: 5,6Kg
AutoCAD SHX Text MINISPLIT-UNIDAD CONDENSADORA Capacidad: 18.000Btu/H Potencia Consumida: 220V/1fase/60Hz/1,55KW Consumo de Corriente: 7,0A Proteccion Electrica: 20A Dim Equipo: 0.77X0.55X0.29Mts Peso Equipo: 34Kg Refrigerante: R410a
AutoCAD SHX Text UNIDAD CONDENSADORA REFRIGERANTE VARIABLE Capacidad: 10,O TR/120.000Btu/H Potencia Consumida: 220V/3fase/60Hz/9,1KW Consumo de Corriente: 39,5A Proteccion Electrica: 50A Dim Equipo: 1.25X1.80X0.45Mts Peso Equipo: 180Kg Refrigerante: R410a
AutoCAD SHX Text
TUBERIA DE DRENAJE PVC RDE 21 1"
AutoCAD SHX Text
DRAINPIPE PVC RDE 21 1"
AutoCAD SHX Text TUBERIA DE REFRIGERACION COBRE TIPO K 38"x "58"
AutoCAD SHX Text 38"x " COPPER TYPE K 58" COPPER TYPE K REFRIGERATION PIPING
AutoCAD SHX Text
TUBERIA DE DRENAJE PVC RDE 21 1"
AutoCAD SHX Text
DRAINPIPE PVC RDE 21 1"
AutoCAD SHX Text TUBERIA DE REFRIGERACION COBRE TIPO K 38"x "58"
AutoCAD SHX Text 38"x " COPPER TYPE K 58" COPPER TYPE K REFRIGERATION PIPING
AutoCAD SHX Text
TUBERIA DE POTENCIA EMT 3/4"
AutoCAD SHX Text
POWER LINE EMT 3/4"
AutoCAD SHX Text
TUBERIA DE CONTROL EMT 3/4"
AutoCAD SHX Text
PIPE CONTROL EMT 3/4"
AutoCAD SHX Text
TUBERIA DE CONTROL EMT 3/4"
AutoCAD SHX Text
PIPE CONTROL EMT 3/4"
AutoCAD SHX Text
TUBERIA DE POTENCIA EMT 3/4"
AutoCAD SHX Text
POWER LINE EMT 3/4"
AutoCAD SHX Text TUBERIA DE REFRIGERACION COBRE TIPO K 14"x "12"
AutoCAD SHX Text 14"x " COPPER TYPE K 12" COPPER TYPE K REFRIGERATION PIPING
AutoCAD SHX Text TUBERIA DE REFRIGERACION COBRE TIPO K 12"x1 "18"
AutoCAD SHX Text 12"x1 " COPPER TYPE K 18" COPPER TYPE K REFRIGERATION PIPING
AutoCAD SHX Text TUBERIA DE REFRIGERACION COBRE TIPO K 38"x "58"
AutoCAD SHX Text 38"x " COPPER TYPE K 58" COPPER TYPE K REFRIGERATION PIPING
AutoCAD SHX Text TUBERIA DE REFRIGERACION COBRE TIPO K 38"x "34"
AutoCAD SHX Text 38"x " COPPER TYPE K 34" COPPER TYPE K REFRIGERATION PIPING
D
C
B
A
EMBASSY OF THE UNITED STATES
INTERNATIONAL NARCOTICS AND
LAW ENFORCEMENT
BOGOTA, COLOMBIA
NOTICE:
THIS DOCUMENT IS THE PROPERTY OF
THE U.S. GOVERNMENT. FURTHER
REPRODUCTION AND/OR DISTRIBUTION IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF THE INTERNATIONAL
NARCOTICS AND LAW ENFORCEMENT
SECTION, BOGOTA, COLOMBIA.
INFORMATION ON THIS DOCUMENT IS NOT
TO BE ALTERED EXCEPT WITH THE
WRITTEN APPROVAL OF THE OFFICE.
MANAGED BY:
I.N.L
INTERNATIONAL NARCOTICS AND LAW
ENFORCEMENT EMBASSY OF THE
UNITED STATES.
BOGOTA, COLOMBIA
SHEET No:
A & E DESIGN FIRM:
DIAZ VILLEGAS ARQUITECTOS
www.diazvillegasarquitectos.com
TELEFONO: 6262659 - 7042265
PROJECT:
LOCATION:
CONTRACT NUMBER:
COR VO.Bo.:
OF:
REVIEW:PLAN No:
CONTENIDO:
LEGEND:
REVIEWS:
PHASE:
10% 35% 60% 90% 100%
DRAWING DATE:
SIGNATURE:
PROFFESIONAL CARD:
PROFFESION:
LIFETED BY:
CONTENTS:
No. SUBMITTAL DATE
CONTRACT DATE:
SCALE:
OBSERVATIONS:
SHEET PLAN:
SHEET No:
OF:
REVIEW: PLAN No:
A&E OPERATIONAL CENTER FITOUT,
12 CITIES FOR THE COLOMBIAN
NATIONAL POLICE
SCO150-16-M-0313
OCT 03 / 2016
SN230-53938
Mechanical Engineer
Ing. Yeciht Palma
SECTIONS ADJUSTMENTS PROPOSED HVAC SYSTEM
SCALE 1:25
CORTE PROPUESTA ADECUACIONES SISTEMA DE AIRE ACONDICIONADO
ESCALA 1:25
B1
MAA-201
CORTE PROPUESTAS ADECUACIONES
SISTEMA DE AIRE ACONDICIONADO
MAA-201
1 : 25
087.01-BOGOTA-MAA-201.dwg
SECTIONS ADJUSTMENTS PROPOSED
HVAC SYSTEM
AutoCAD SHX Text F
AutoCAD SHX Text I
AutoCAD SHX Text F
AutoCAD SHX Text
CORREDOR DE PASO
AutoCAD SHX Text
PASS CORRIDOR
AutoCAD SHX Text
EXTERIOR
AutoCAD SHX Text
OUTDOORS
AutoCAD SHX Text
SALA DE REUNIONES
AutoCAD SHX Text
MEETING ROOM
AutoCAD SHX Text
AutoCAD SHX Text G
AutoCAD SHX Text R
AutoCAD SHX Text I
AutoCAD SHX Text R
AutoCAD SHX Text W
AutoCAD SHX Text W
AutoCAD SHX Text X
AutoCAD SHX Text X
AutoCAD SHX Text CASSETTE VRF TYPE-INTERIOR UNIT EQUIPMENT Capacity: 36.000Btu/H Consumed Power: 220V/1fase/60Hz/144W Dim Equipment: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Weight Equipment: 23,5Kg Weight Panel: 5,6Kg
AutoCAD SHX Text EQUIPO TIPO CASSETTE VRF-UNIDAD INTERIOR Capacidad: 36.000Btu/H Potencia Consumida: 220V/1fase/60Hz/144W Dim Equipo: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Peso Equipo: 23,5Kg Peso Panel: 5,6Kg
AutoCAD SHX Text CASSETTE VRF TYPE-INTERIOR UNIT EQUIPMENT Capacity: 36.000Btu/H Consumed Power: 220V/1fase/60Hz/144W Dim Equipment: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Weight Equipment: 23,5Kg Weight Panel: 5,6Kg
AutoCAD SHX Text EQUIPO TIPO CASSETTE VRF-UNIDAD INTERIOR Capacidad: 36.000Btu/H Potencia Consumida: 220V/1fase/60Hz/144W Dim Equipo: 0.84X0.84X0.25Mts Dim Panel: 0.95X0.95X0.025Mts Peso Equipo: 23,5Kg Peso Panel: 5,6Kg
AutoCAD SHX Text CONDENSING UNIT VRF Capacity: 10,0Ton/120.000Btu/H Consumed Power: 220V/3fase/60Hz/9,1kW Current: 46,3A Protection: 50A Dim: 1,10X1.65X0.38Mts Weight: 157Kg Refrigerant: R410A
UNIDAD CONDENSADORA REFRIGERANTE VARIABLE Capacidad: 10,O TR/120.000Btu/H Potencia Consumida: 220V/3fase/60Hz/9,1KW Consumo de Corriente: 46,3A Proteccion Electrica: 50A Dim Equipo: 1.10X1.65X0.38Mts Peso Equipo: 157Kg Refrigerante: R410a
A&E OPERATIONAL CENTER FITOUT,
12 CITIES FOR THE COLOMBIAN
NATIONAL POLICE
XXX
X
XXX
X
1 2 3 4 5 6
E
D
C
B
A
EMBASSY OF THE UNITED STATES
INTERNATIONAL NARCOTICS AND
LAW ENFORCEMENT
BOGOTA, COLOMBIA
NOTICE:
THIS DOCUMENT IS THE PROPERTY OF
THE U.S. GOVERNMENT. FURTHER
REPRODUCTION AND/OR DISTRIBUTION IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF THE INTERNATIONAL
NARCOTICS AND LAW ENFORCEMENT
SECTION, BOGOTA, COLOMBIA.
INFORMATION ON THIS DOCUMENT IS NOT
TO BE ALTERED EXCEPT WITH THE
WRITTEN APPROVAL OF THE OFFICE.
MANAGED BY:
I.N.L
INTERNATIONAL NARCOTICS AND LAW
ENFORCEMENT EMBASSY OF THE
UNITED STATES.
BOGOTA, COLOMBIA
SHEET No:
A & E DESIGN FIRM:
DIAZ VILLEGAS ARQUITECTOS
www.diazvillegasarquitectos.com
TELEFONO: 6262659 - 7042265
PROJECT:
LOCATION:
CONTRACT NUMBER:
COR VO.Bo.:
OF:
REVIEW:PLAN No:
CONTENIDO:
LEGEND:
REVIEWS:
PHASE:
10% 35% 60% 90% 100%
DRAWING DATE:
SIGNATURE:
PROFFESIONAL CARD:
PROFFESION:
LIFETED BY:
CONTENTS:
No. SUBMITTAL DATE
CONTRACT DATE:
SCALE:
OBSERVATIONS:
SHEET PLAN:
SHEET No:
OF:
REVIEW: PLAN No:
A&E OPERATIONAL CENTER FITOUT,
12 CITIES FOR THE COLOMBIAN
NATIONAL POLICE
SCO150-16-M-0313
OCT 03 / 2016
SN230-53938
Mechanical Engineer
Ing. Yeciht Palma
PATTERNS HVAC SYSTEM
SCALE Unsacaled
DIAGRAMAS SISTEMA DE AIRE ACONDICIONADO
ESCALA SIN ESCALA
MAA-203
DIAGRAMAS SISTEMA DE AIRE
ACONDICIONADO
MAA-203
1 : 25
087.01-BOGOTA-MAA-203.dwg
PATTERNS HVAC SYSTEM
AutoCAD SHX Text Reference / Referencia / Referencia
AutoCAD SHX Text
A&E OPERATIONAL CENTER FITOUT - CATAM
AutoCAD SHX Text Unit / Equipo/ Equipo
AutoCAD SHX Text Cantidad
AutoCAD SHX Text Capacidad
AutoCAD SHX Text Consumo
AutoCAD SHX Text (Kw)
AutoCAD SHX Text (Btu/h)
AutoCAD SHX Text Consumo
AutoCAD SHX Text (Amps)
AutoCAD SHX Text Caracteristicas Electricas
AutoCAD SHX Text Refrigerante
AutoCAD SHX Text Ubicacion
AutoCAD SHX Text Evaporadora
AutoCAD SHX Text Total
AutoCAD SHX Text 120.000
AutoCAD SHX Text 0,354
AutoCAD SHX Text 1,44
AutoCAD SHX Text 220V -3F -60Hz
AutoCAD SHX Text R-410a
AutoCAD SHX Text AA Plate Equipment - Placa Equipos AA - Placa Equipos AA
AutoCAD SHX Text
AutoCAD SHX Text 120.000
AutoCAD SHX Text 9,1
AutoCAD SHX Text 39,50
AutoCAD SHX Text
UCA VRF 01
AutoCAD SHX Text Breaker
AutoCAD SHX Text 2 x 60
AutoCAD SHX Text Condensadora
AutoCAD SHX Text ERVC4V @ 24 KBtu/h
AutoCAD SHX Text
AutoCAD SHX Text 220V -2F -60Hz
AutoCAD SHX Text R-410a
AutoCAD SHX Text Operators - Operarios - Operarios
AutoCAD SHX Text 24.000
AutoCAD SHX Text 0,033
AutoCAD SHX Text 0,15
AutoCAD SHX Text 220V -2F -60Hz
AutoCAD SHX Text R-410a
AutoCAD SHX Text
AutoCAD SHX Text 18.000
AutoCAD SHX Text 1,55
AutoCAD SHX Text 7,0
AutoCAD SHX Text Breaker
AutoCAD SHX Text 2 x 20
AutoCAD SHX Text
MSP 01
AutoCAD SHX Text Minisplit / Minisplit / Minisplit
AutoCAD SHX Text Racks-UPS / Racks-UPS / Racks-UPS
AutoCAD SHX Text Breaker
AutoCAD SHX Text 2 x 10
AutoCAD SHX Text ERVC4V @ 36 KBtu/h
AutoCAD SHX Text
AutoCAD SHX Text 220V -2F -60Hz
AutoCAD SHX Text R-410a
AutoCAD SHX Text Meeting Room - Sala de Reuniones - Sala de Reuniones
AutoCAD SHX Text 36.000
AutoCAD SHX Text 0,144
AutoCAD SHX Text 0,57
AutoCAD SHX Text Indoor Unit
AutoCAD SHX Text Quantity
AutoCAD SHX Text Capacity
AutoCAD SHX Text Power Supply
AutoCAD SHX Text Running Current
AutoCAD SHX Text Power Supply
AutoCAD SHX Text Refrigerant
AutoCAD SHX Text Location
AutoCAD SHX Text Condensing Unit
AutoCAD SHX Text 220V / 3PH / 60 Hz
AutoCAD SHX Text UCAVRF-01 8TR @ R410a Equipment Pad Placa Equipos
AutoCAD SHX Text 3 x 50 Amp
AutoCAD SHX Text 3 x # 6 THW
AutoCAD SHX Text 1 x # 8 THW
AutoCAD SHX Text Interruptor 3 x 60 Amp
AutoCAD SHX Text 2x#12 THW
AutoCAD SHX Text 1x#12 THW
AutoCAD SHX Text
PCC
AutoCAD SHX Text 3x#18 Apantallado
AutoCAD SHX Text Centralized Control Panel
AutoCAD SHX Text 2 x 10 Amp
AutoCAD SHX Text 2 x # 12 THW
AutoCAD SHX Text 1 x # 12 THW
AutoCAD SHX Text ERVC4V-01 24 KBtu/h Operators Operadores
AutoCAD SHX Text ELECTRIC SINGLE LINE DIAGRAM DIAGRAMA UNIFILAR A&E - OPERATIONAL CENTER FITOUT - CATAM ELECTRIC PANELBOARD TA-01 TABLERO ELECTRICO TA-01TABLERO ELECTRICO TA-01
AutoCAD SHX Text ERVC4V-02 24 KBtu/h Operators Operadores
AutoCAD SHX Text ERVC4V-03 36 KBtu/h Meeting Room Sala de Reuniones
AutoCAD SHX Text ERVC4V-04 36 KBtu/h Meeting Room Sala de Reuniones
AutoCAD SHX Text EMSP-01 18 KBtu/h Racks-UPS room Cto Racks -UPS
AutoCAD SHX Text 2 x 20 Amp
AutoCAD SHX Text 2 x # 12 THW
AutoCAD SHX Text 1 x # 12 THW
AutoCAD SHX Text UCMSP-01 18 KBtu/h Equipment Pad Placa Equipos AA
AutoCAD SHX Text 2x#12 THW
AutoCAD SHX Text 1x#12 THW
AutoCAD SHX Text 2x#12 THW
AutoCAD SHX Text 1x#12 THW
AutoCAD SHX Text 2x#12 THW
AutoCAD SHX Text 1x#12 THW
AutoCAD SHX Text Electric Switch 3 x 60 Amp
AutoCAD SHX Text Panel de Control Centralizado
AutoCAD SHX Text 1 x 5 Amp
AutoCAD SHX Text 1 x # 12 THW
AutoCAD SHX Text 1 x # 12 THW
AutoCAD SHX Text 1 x # 12 THW
AutoCAD SHX Text
2.120 CFM
AutoCAD SHX Text
OPERATIONAL CENTER FITOUT CATAM 21°C DB, RH 50%
AutoCAD SHX Text
130 CFM EXFILTRACION POR PUERTAS
AutoCAD SHX Text
EVAPORADORAS DE AIRE ACONDICIONADO REFRIGERANTE VARIABLE
AutoCAD SHX Text
AIRE EXTERIOR 19°C DB, 82 °WB
AutoCAD SHX Text
2.120 CFM AIR CONDITIONING SUPPLY EQUIPMENT
AutoCAD SHX Text
2.120 CFM RETURN AIR CONDITIONING EQUIPMENT
AutoCAD SHX Text
ECRV4V 01-04
AutoCAD SHX Text
FLOW AIR DIAGRAM DIAGRAMA DE FLUJO DE AIRE OPERATIONAL CENTER FITOUT - CATAM
AutoCAD SHX Text
INFILTRACCION POR PUERTAS 130 CFM 19°C DB, 82 °WB
AutoCAD SHX Text
OUTDOOR AIR 19°C DB, 82 °WB
AutoCAD SHX Text
INFILTRATION BY DOORS 130 CFM 19°C DB, 82 °WB
AutoCAD SHX Text
130 CFM EXFILTRATION POR DOORS
AutoCAD SHX Text
2.120 CFM RETORNO DE EQUIPOS A.A.
AutoCAD SHX Text
2.120 CFM SUMINISTRO DE EQUIPOS A.A.
AutoCAD SHX Text
INDOOR UNITS VARIABLE REFRIGERANT
AutoCAD SHX Text Communication Line
AutoCAD SHX Text
UCAVRF 01
AutoCAD SHX Text 220V -3F -60Hz
AutoCAD SHX Text Power Line
AutoCAD SHX Text Breaker
AutoCAD SHX Text 2 x 10
AutoCAD SHX Text 220V -2F -60Hz
AutoCAD SHX Text
ERVC4V 01
AutoCAD SHX Text Breaker
AutoCAD SHX Text 3 x 50
AutoCAD SHX Text
ERVC4V 02
AutoCAD SHX Text
ERVC4V 03
AutoCAD SHX Text
ERVC4V 04
AutoCAD SHX Text Tuberia EMT "34"
AutoCAD SHX Text Línea Eléctrica EMT "34"
AutoCAD SHX Text Tuberia EMT 1- "14"
AutoCAD SHX Text Electric Line EMT "34"
AutoCAD SHX Text Electric Line EMT "34"
AutoCAD SHX Text Electric Line EMT 1- "14"
AutoCAD SHX Text Panel de Control Centralizado
AutoCAD SHX Text Centralized Control Panel
AutoCAD SHX Text 120V -1F -60Hz
AutoCAD SHX Text Breaker
AutoCAD SHX Text 1 x 5
AutoCAD SHX Text Tuberia EMT "34"
AutoCAD SHX Text Electric Line EMT "34"
AutoCAD SHX Text ( Liq 1/2" Gas 1-1/8")
AutoCAD SHX Text 7,4 mts
AutoCAD SHX Text Unidad Condensadora de Refrigerante Variable UCAVRF 01
AutoCAD SHX Text 120 KBtu/h Refrigerante 410a @ 220V-3F-60Hz
AutoCAD SHX Text Longitud 4,9 mts
AutoCAD SHX Text Longitud 1,4 mts
AutoCAD SHX Text Tuberia de cobre tipo K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text Longitud 5,4 mts
AutoCAD SHX Text Longitud 0,9 mts
AutoCAD SHX Text Evaporadora de Refrigerante Variable tipo Cassette de 4 vias de 24 KBtu/h - ERVC 01
AutoCAD SHX Text Tuberia de cobre tipo K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text Evaporadora de Refrigerante Variable tipo Cassette de 4 vias de 24 KBtu/h - ERVC 02
AutoCAD SHX Text Evaporadora de Refrigerante Variable tipo Cassette de 4 vias de 36 KBtu/h - ERVC 03
AutoCAD SHX Text Evaporadora de Refrigerante Variable tipo Cassette de 4 vias de 36 KBtu/h - ERVC 04
AutoCAD SHX Text Tuberia de cobre tipo K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text Tuberia de cobre tipo K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text ( Liq 3/8" Gas 3/4")
AutoCAD SHX Text 3,9 mts
AutoCAD SHX Text ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text 6,3 mts
AutoCAD SHX Text Length 4,9 mts
AutoCAD SHX Text Length 1,4 mts
AutoCAD SHX Text Length 5,4 mts
AutoCAD SHX Text Length 0,9 mts
AutoCAD SHX Text Cooper Tubing type K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text Cooper Tubing type K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text Cooper Tubing type K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text Cooper Tubing type K ( Liq 3/8" Gas 5/8")
AutoCAD SHX Text Unit Ceiling 4 way Cassette 24 KBtu/h - ERVC 01
AutoCAD SHX Text Unit Ceiling 4 way Cassette 24 KBtu/h - ERVC 02
AutoCAD SHX Text Unit Ceiling 4 way Cassette 36 KBtu/h - ERVC 03
AutoCAD SHX Text Unit Ceiling 4 way Cassette 36 KBtu/h - ERVC 04
AutoCAD SHX Text Variable Refrigerant Condensing Unit CAVRF 01
AutoCAD SHX Text 120 KBtu/h Refrigerant 410a @ 220V-3F-60Hz
AutoCAD SHX Text
EQUIPMENT DESIGNATION
AutoCAD SHX Text
EQUIPMENT NUMBER
AutoCAD SHX Text
EQUIPMENT DESIGNATION
AutoCAD SHX Text Unidad Evaporadora de Refrigerante Variable tipo Cassette
AutoCAD SHX Text
ERVC
AutoCAD SHX Text Unidad Condensadora tipo Refrigerante Variable
AutoCAD SHX Text
UCAVRF
AutoCAD SHX Text Unidad Evaporadora de Minisplit tipo Pared
AutoCAD SHX Text
EMSP
AutoCAD SHX Text Unidad Condensadora Minisplit de Pared
AutoCAD SHX Text
UCMSP
AutoCAD SHX Text TUBERIA ELECTRICA EMT PARA POTENCIA ELECTRICA DIMENSIONES DADAS EN EL ARBOL ELECTRICO
AutoCAD SHX Text DIMENSIONES DADAS EN EL ARBOL DE REFRIGERACION AISLADA Y ENCHAQUETADA EN LA TUBERIA INSTALADA AL EXTERIOR
AutoCAD SHX Text
TUBERIA DE REFRIGERACION DE COBRE TIPO K
AutoCAD SHX Text
DIMENSIONES DADAS EN EL ARBOL ELECTRICO
AutoCAD SHX Text
TUBERIA ELECTRICA EMT PARA CONTROL
AutoCAD SHX Text BRANCH o REFJOINT DE DISTRIBUCION DE REFRIGERACION
AutoCAD SHX Text
EMT BOX ELECTRIC
AutoCAD SHX Text Unit Ceiling Cassette Variable Refrigerant
AutoCAD SHX Text Variable Refrigerant Condensing Unit
AutoCAD SHX Text Minisplit Indoor Unit Wall Mounted
AutoCAD SHX Text Minisplit Condensing Unit
AutoCAD SHX Text
CAJA ELECTRICA EMT
AutoCAD SHX Text BRANCH o REFJOINT
AutoCAD SHX Text
DIMENSIONS GIVEN IN THE ELECTRIC TREE
AutoCAD SHX Text
EMT ELECTRIC LINE FOR CONTROL
AutoCAD SHX Text
EMT ELECTRIC LINE FOR POWER LINE DIMENSIONS GIVEN IN THE ELECTRIC TREE
AutoCAD SHX Text COPPER PIPE COOLING TYPE K DIMENSIONS GIVEN IN THE TREE OF REFRIGERATION ISOLATED AND IN THE PIPELINE INSTALLED JACKETED ABROAD
AutoCAD SHX Text
DESIGNACION DEL EQUIPO
AutoCAD SHX Text
NUMERO DE EQUIPO
DESIGNACION DE LOS EQUIPOS
D
C
B
A
EMBASSY OF THE UNITED STATES
INTERNATIONAL NARCOTICS AND
LAW ENFORCEMENT
BOGOTA, COLOMBIA
NOTICE:
THIS DOCUMENT IS THE PROPERTY OF
THE U.S. GOVERNMENT. FURTHER
REPRODUCTION AND/OR DISTRIBUTION IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF THE INTERNATIONAL
NARCOTICS AND LAW ENFORCEMENT
SECTION, BOGOTA, COLOMBIA.
INFORMATION ON THIS DOCUMENT IS NOT
TO BE ALTERED EXCEPT WITH THE
WRITTEN APPROVAL OF THE OFFICE.
MANAGED BY:
I.N.L
INTERNATIONAL NARCOTICS AND LAW
ENFORCEMENT EMBASSY OF THE
UNITED STATES.
BOGOTA, COLOMBIA
SHEET No:
A & E DESIGN FIRM:
DIAZ VILLEGAS ARQUITECTOS
www.diazvillegasarquitectos.com
TELEFONO: 6262659 - 7042265
PROJECT:
LOCATION:
CONTRACT NUMBER:
COR VO.Bo.:
OF:
REVIEW:PLAN No:
CONTENIDO:
LEGEND:
REVIEWS:
PHASE:
10% 35% 60% 90% 100%
DRAWING DATE:
SIGNATURE:
PROFFESIONAL CARD:
PROFFESION:
LIFETED BY:
CONTENTS:
No. SUBMITTAL DATE
CONTRACT DATE:
SCALE:
OBSERVATIONS:
SHEET PLAN:
SHEET No:
OF:
REVIEW: PLAN No:
A&E OPERATIONAL CENTER FITOUT,
12 CITIES FOR THE COLOMBIAN
NATIONAL POLICE
SCO150-16-M-0313
OCT 03 / 2016
SN230-53938
Mechanical Engineer
Ing. Yeciht Palma
MAA-501
DETALLES TIPICOS SISTEMA DE AIRE
ACONDICIONADO
MAA-501
1 : 5 - 1 : 20
087.01-BOGOTA-MAA-501.dwg
HVAC SYSTEM TYPICAL DETAILS
AutoCAD SHX Text Chassis
AutoCAD SHX Text Grille
AutoCAD SHX Text Wiring Entry
AutoCAD SHX Text Ceiling Level
AutoCAD SHX Text Drain Line
AutoCAD SHX Text Vapor Line
AutoCAD SHX Text Liquid Line
AutoCAD SHX Text Branch Duct Knockout
AutoCAD SHX Text Branch Duct Knockout
AutoCAD SHX Text 2-3/4" OutdoorAir Knockout
AutoCAD SHX Text Branch Duct Knockout
AutoCAD SHX Text Branch Duct Knockout
AutoCAD SHX Text Branch Duct Knockout
AutoCAD SHX Text
TOP
AutoCAD SHX Text Branch Duct Knockout
AutoCAD SHX Text
VIEWS
AutoCAD SHX Text
INDOOR UNIT CEILING CASSETTE
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
VISTAS GEOMETRICAS
AutoCAD SHX Text
UNIDAD EVAPORADORA TIPO CASSETTE
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text
VIEWS
AutoCAD SHX Text
VARIABLE REFRIGERANT CONDENSING UNIT
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
VISTAS GEOMETRICAS
AutoCAD SHX Text
UNIDAD CONDENSADORA VRF
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text
LINEA DE GAS
AutoCAD SHX Text
LINEA DE LIQUIDO
AutoCAD SHX Text
CONTROL REMOTO
AutoCAD SHX Text
LINEA DRENAJE O CONDENSADO A DESAGUE MAS CERCANO
AutoCAD SHX Text
POWER LINE AND CONTROL LINE
AutoCAD SHX Text
PASSES TO ENSURE
AutoCAD SHX Text
SEALING LEAKS
AutoCAD SHX Text
EVAPORADORA
AutoCAD SHX Text
UNIDAD CONDENSADORA
AutoCAD SHX Text Typical connection detail
AutoCAD SHX Text equipment Minisplit
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text Detalle conexion tipica
AutoCAD SHX Text equipo Minisplit
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text
INDOOR UNIT
AutoCAD SHX Text
REMOTE CONTROL
AutoCAD SHX Text
DRAIN LINE TO DRAIN THE NEAREST
AutoCAD SHX Text
LINEA DE INTERCONEXION DE FUERZA Y CONTROL
AutoCAD SHX Text
SELLAR PASADAS
AutoCAD SHX Text
QUE GARANTICE ESTANQUEIDAD
AutoCAD SHX Text
GAS PIPELINE
AutoCAD SHX Text
LIQUID PIPELINE
AutoCAD SHX Text
CONDENSING UNIT
AutoCAD SHX Text Soporte para tuberia de refrigeración
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text Detalle paso de Tuberías a través
AutoCAD SHX Text de los Muros y Pisos
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text
MURO EN CONCRETO
AutoCAD SHX Text
ABRAZADERA
AutoCAD SHX Text
PIPELINE
AutoCAD SHX Text
SEAL TOP AND BOTTOM
AutoCAD SHX Text
DE MASILLA ELASTICA
AutoCAD SHX Text
SELLO EN AMBOS LADOS
AutoCAD SHX Text
1/2 A 5/8 -IN
AutoCAD SHX Text
DE ENVOLTURA FIBROSA
AutoCAD SHX Text
ALREDEDOR DE TUBO
AutoCAD SHX Text
O MAMPOSTERIA
AutoCAD SHX Text
TUBERÍA
AutoCAD SHX Text
DE NEOPRENO QUE PERMITA
AutoCAD SHX Text
MINIMO 2 CAPAS DE 5/16
AutoCAD SHX Text
DEL PISO
AutoCAD SHX Text
SEPARA LA ABRAZADERA
AutoCAD SHX Text
OF FILLER SEALANT
AutoCAD SHX Text
WRAP FIBROUS
AutoCAD SHX Text
MATERIAL
AutoCAD SHX Text
SLAB
AutoCAD SHX Text
STEEL CUSHION
AutoCAD SHX Text
CALIBER 10
AutoCAD SHX Text
WALL IN CONCRETE
AutoCAD SHX Text
OR MANSORY
AutoCAD SHX Text
1/2 A 5/8 -IN
AutoCAD SHX Text
FIBROUS WRAP
AutoCAD SHX Text
AROUND THE PIPELINE
AutoCAD SHX Text
PIPELINE
AutoCAD SHX Text
OF MASTIC SEALANT
AutoCAD SHX Text
STAMPS ON BOTH SIDES
AutoCAD SHX Text
TUBERÍA
AutoCAD SHX Text
ENVOLTURA EN
AutoCAD SHX Text
MATERIAL FIBROSO
AutoCAD SHX Text
N.P.OBRA NEGRA
AutoCAD SHX Text
COJÍN EN ACERO
AutoCAD SHX Text
CALIBRE 10
AutoCAD SHX Text
CLAMP
AutoCAD SHX Text
SELLO SUPERIOR E INFERIOR
AutoCAD SHX Text
DE MASILLA ELASTICA
AutoCAD SHX Text
OF NEOPRENE 5/16 ALLOWING
AutoCAD SHX Text
MINIMUM 2 LAYERS OF
AutoCAD SHX Text
AND THE FLOOR
AutoCAD SHX Text
THE SEPARATION BETWEEN CLAMP
AutoCAD SHX Text Detail step pipes
AutoCAD SHX Text through walls and slabs
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
2.50 M.
AutoCAD SHX Text
1.75 M.
AutoCAD SHX Text
2.20 M.
AutoCAD SHX Text
L=MAXIMUM SPACE BETWEEN SUPPORTS
AutoCAD SHX Text
ENTRE SOPORTES
AutoCAD SHX Text
%%CTUBERIA
AutoCAD SHX Text %%C hasta 3/4"
AutoCAD SHX Text %%C until 2"
AutoCAD SHX Text %%C1"
AutoCAD SHX Text %%C1-1/4"
AutoCAD SHX Text
1.5 M.
AutoCAD SHX Text Cooling pipe support
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AISLAMIENTO TERMICO
AutoCAD SHX Text
UNICANAL U - 10
AutoCAD SHX Text
FLEJE DE ALUMINIO
AutoCAD SHX Text
DE 0.20 DE LONG. EN APOYO LIBRE SOBRE SOPORTE
AutoCAD SHX Text
ABRAZADERA PARA UNICANAL SEGUN DIAMETRO DE TUBERIA
AutoCAD SHX Text
CORAZA PROTECTORA DE LAMINA GALVANIZADA CAL # 26
AutoCAD SHX Text
MOVIMIENTO DE LA TUBERIA EN SENTIDO LONGITUDINAL
AutoCAD SHX Text
LA ABRAZADERA DEBERA PERMITIR EL LIBRE
AutoCAD SHX Text N O T A :
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
%%CPIPELINE
AutoCAD SHX Text
L=ESPACIO MAXIMO
AutoCAD SHX Text %%C until 3/4"
AutoCAD SHX Text %%C hasta 2"
AutoCAD SHX Text
AutoCAD SHX Text
THERMAL ISOLATION
AutoCAD SHX Text
CHANNEL RIEL U - 10
AutoCAD SHX Text
ALUMINUM STRIP
AutoCAD SHX Text
DE 0.20 DE LENGTH. WITH FREE ON SUPPORT
AutoCAD SHX Text
CHANEL BY RAIL CLAMP DIAMETER PIPE
AutoCAD SHX Text
PROTECTIVE ARMOUR PLATE GALVANIZED CAL # 26
AutoCAD SHX Text
MOVEMENT OF THE PIPE LENGTHWAYS
AutoCAD SHX Text
CLAMP SHALL PERMIT THE FREE
AutoCAD SHX Text N O T E :
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
PLACA
AutoCAD SHX Text
ANGULO DE 1' * 1' * 1/8'
AutoCAD SHX Text
ANGULO DE 1 1/2' * 1 1/2' * 1/8'
AutoCAD SHX Text
SOPORTE INDIVUDUAL POR TUBO
AutoCAD SHX Text Support coling pipe
AutoCAD SHX Text installed outside
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text Soporte tubería
AutoCAD SHX Text de Refrigeración al Exterior
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text
INDIVIDUAL SUPPORT FOR PIPELINE
AutoCAD SHX Text
L PROFILE IRONSTEEL 1' * 1' * 1/8'
AutoCAD SHX Text
L PROFLE IRONSTEEL 1 1/2' * 1 1/2' * 1/8'
AutoCAD SHX Text Typical plate equipment
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
MALLA ELECTROSOLDADA
AutoCAD SHX Text A
AutoCAD SHX Text A
AutoCAD SHX Text
DEL EQUIPO
AutoCAD SHX Text
VARIA SEGÚN DIMENSIONES
AutoCAD SHX Text
ICOPOR DE ALTA
AutoCAD SHX Text DENSIDAD ESPESOR 50 mm
AutoCAD SHX Text
SECCIÓN A-A
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text Detail slab support
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text D: 1"
AutoCAD SHX Text D: 1"
AutoCAD SHX Text D: 1"
AutoCAD SHX Text D: 1-1/4"
AutoCAD SHX Text D: 1-1/4"
AutoCAD SHX Text D: 1-1/4"
AutoCAD SHX Text D: 1-1/4"
AutoCAD SHX Text Detail drainage network
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
PIPELINE
AutoCAD SHX Text
DESAGUE
AutoCAD SHX Text
SOPORTE
AutoCAD SHX Text
SOPORTE
AutoCAD SHX Text
SOPORTE
AutoCAD SHX Text Support and installation detail
AutoCAD SHX Text Ceiling 4 way Cassette
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
MANGUERA FLEXIBLE
AutoCAD SHX Text
30 CMS.
AutoCAD SHX Text
70 CMS
AutoCAD SHX Text
MAX.
AutoCAD SHX Text
DESNIVEL 1 / 100
AutoCAD SHX Text 1 a 1,5 MTS.
AutoCAD SHX Text
MAX. 70 CMS
AutoCAD SHX Text 1 a 1,5 MTS.
AutoCAD SHX Text
DESNIVEL 1 / 100
AutoCAD SHX Text Connection detail
AutoCAD SHX Text drain indoor units
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text
LINEA DE GAS
AutoCAD SHX Text
LINEA DE LIQUIDO
AutoCAD SHX Text
CONTROL REMOTO
AutoCAD SHX Text
LINEA DRENAJE O CONDENSADO A DESAGUE MAS CERCANO
AutoCAD SHX Text
POWER LINE AND CONTROL LINE
AutoCAD SHX Text
PASSES TO ENSURE
AutoCAD SHX Text
SEALING LEAKS
AutoCAD SHX Text
EVAPORADORA
AutoCAD SHX Text
UNIDAD CONDENSADORA
AutoCAD SHX Text Typical connection detail
AutoCAD SHX Text Detalle conexion de drenajes de
AutoCAD SHX Text unidades evaporadoras
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text Detalle conexion de drenaje de
AutoCAD SHX Text unidad evaporadora
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text Connection detail
AutoCAD SHX Text drain indoor unit
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text Detalle red de desagüe
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text Detalle soporte e instalación
AutoCAD SHX Text cassette 4 vias en cielo falso
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text Base Típica para Equipos
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text Support and installation detail
AutoCAD SHX Text Ceiling 4 way Cassette
AutoCAD SHX Text Unscaled
AutoCAD SHX Text
AutoCAD SHX Text Detalle soporte e instalación
AutoCAD SHX Text cassette 4 vias en cielo falso
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text Detalle soporte en losa
AutoCAD SHX Text Sin Escala
AutoCAD SHX Text
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
SUPPORT
AutoCAD SHX Text
TUBERIA
AutoCAD SHX Text
DRAIN
AutoCAD SHX Text
INDOOR UNIT
AutoCAD SHX Text
REMOTE CONTROL
AutoCAD SHX Text
DRAIN LINE TO DRAIN THE NEAREST
AutoCAD SHX Text
LINEA DE INTERCONEXION DE FUERZA Y CONTROL
AutoCAD SHX Text
SELLAR PASADAS
AutoCAD SHX Text
QUE GARANTICE ESTANQUEIDAD
AutoCAD SHX Text
GAS PIPELINE
AutoCAD SHX Text
LIQUID PIPELINE
AutoCAD SHX Text
CONDENSING UNIT
WELDED MESH
1 2 3 4 5 6
E
D
C
B
A
EMBASSY OF THE UNITED STATES
INTERNATIONAL NARCOTICS AND
LAW ENFORCEMENT
BOGOTA, COLOMBIA
NOTICE:
THIS DOCUMENT IS THE PROPERTY OF
THE U.S. GOVERNMENT. FURTHER
REPRODUCTION AND/OR DISTRIBUTION IS
PROHIBITED WITHOUT THE WRITTEN
PERMISSION OF THE INTERNATIONAL
NARCOTICS AND LAW ENFORCEMENT
SECTION, BOGOTA, COLOMBIA.
INFORMATION ON THIS DOCUMENT IS NOT
TO BE ALTERED EXCEPT WITH THE
WRITTEN APPROVAL OF THE OFFICE.
MANAGED BY:
I.N.L
INTERNATIONAL NARCOTICS AND LAW
ENFORCEMENT EMBASSY OF THE
UNITED STATES.
BOGOTA, COLOMBIA
SHEET No:
A & E DESIGN FIRM:
DIAZ VILLEGAS ARQUITECTOS
www.diazvillegasarquitectos.com
TELEFONO: 6262659 - 7042265
PROJECT:
LOCATION:
CONTRACT NUMBER:
COR VO.Bo.:
OF:
REVIEW:PLAN No:
CONTENIDO:
LEGEND:
REVIEWS:
PHASE:
10% 35% 60% 90% 100%
DRAWING DATE:
SIGNATURE:
PROFFESIONAL CARD:
PROFFESION:
LIFETED BY:
CONTENTS:
No. SUBMITTAL DATE
CONTRACT DATE:
SCALE:
OBSERVATIONS:
SHEET PLAN:
SHEET No:
OF:
REVIEW: PLAN No:
A&E OPERATIONAL CENTER FITOUT,
12 CITIES FOR THE COLOMBIAN
NATIONAL POLICE
SCO150-16-M-0313
OCT 03 / 2016
SN230-53938
Mechanical Engineer
Ing. Yeciht Palma
MAA-601
NOTAS DE DISEÑO SISTEMA DE AIRE
ACONDICIONADO
MAA-601
SIN
087.01-BOGOTA-MAA-601.dwg
HVAC DESIGN NOTES
AutoCAD SHX Text GENERAL NOTES: 1. ALL WORK SHALL CONFORM WITH APPLICABLE CODES AND STANDARDS: COMPLY WITH THE LATEST EFFECTIVE PUBLICATIONS OF THE FOLLOWING CODES AND STANDARDS. MINIMUM REQUIREMENTS ALL WORK SHALL CONFORM WITH APPLICABLE CODES AND STANDARDS: COMPLY WITH THE LATEST EFFECTIVE PUBLICATIONS OF THE FOLLOWING CODES AND STANDARDS. MINIMUM REQUIREMENTS OF THESE PUBLICATIONS SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY FOR PROVIDING ANY WORK INCLUDED HEREIN WHICH EXCEEDS THESE MINIMUM REQUIREMENTS: INTERNATIONAL BUILDING CODE 2003(IBC). INTERNATIONAL MECHANICAL CODE 2003(IMC). NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), 2002. UNDERWRITERS LABORATORIES, INC. (UL). AMCA STANDARDS. NATIONAL ELECTRICAL CODE (NEC), 2005. AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME). SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA). OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA). LOCAL APPLICABLE CODES AND REQUIREMENTS. 2. EXAMINE ALL DRAWINGS CAREFULLY AND VERIFY EXISTING CONDITION IN FIELD PRIOR TO SUBMITTING A BID OR BEFORE COMMENCING ANY WORK. CONTRACTORS WILL BE REQUIRED TO FURNISH, EXAMINE ALL DRAWINGS CAREFULLY AND VERIFY EXISTING CONDITION IN FIELD PRIOR TO SUBMITTING A BID OR BEFORE COMMENCING ANY WORK. CONTRACTORS WILL BE REQUIRED TO FURNISH, INSTALL AND/OR CONNECT WITH APPROPRIATE SERVICES ALL AIR CONDITIONING ITEMS SHOWN ON ANY OF THE ARCHITECTURAL, PLUMBING, ELECTRICAL AND SPRINKLER DRAWINGS WITHOUT ADDITIONAL EXPENSE TO THE OWNER IF DISCREPANCIES, CONFLICTS, INTERFERENCE OR OMISSIONS OCCUR BETWEEN DRAWINGS, NOTIFY IN WRITING TO THE ARCHITECT/ ENGINEER IN AMPLE TIME TO PERMIT REVISIONS BEFORE THE BIDS ARE SUBMITTED. 3. THE DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARY SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS, UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE THE DRAWINGS ARE TO BE CONSIDERED DIAGRAMMATIC, NOT NECESSARY SHOWING IN DETAIL OR TO SCALE ALL OF THE MINOR ITEMS, UNLESS SPECIFIC DIMENSIONS ARE SHOWN, THE STRUCTURAL, ARCHITECTURAL AND SITE CONDITIONS SHALL GOVERN THE EXACT LOCATIONS, CONTRACTOR SHALL FOLLOW DRAWINGS IN LAYING OUT WORK, CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED AND MAINTAIN MAXIMUM HEAD ROOM, AND SPACE CONDITIONS AT ALL POINTS. WHERE HEAD ROOM, OR SPACE CONDITIONS APPEAR INADEQUATE, ARCHITECT OR ENGINEER SHALL BE NOTIFIED ON WRITING BEFORE PROCEEDING WITH INSTALLATION, THIS CONTRACTOR SHALL, WITHOUT EXTRA CHARGE, MAKE FIELD MODIFICATION IN LAYOUT AS NEEDED TO PREVENT CONFLICT WORK OF VARIOUS TRADES FOR PROPER EXECUTION OF THE WORK. 4. CONTRACTOR SHALL SUBMIT TO ENGINEERS SHOP DRAWINGS OF ALL MATERIALS AND EQUIPMENT FOR APPROVAL PRIOR TO FABRICATION AND/OR PURCHASING. CONTRACTOR SHALL SUBMIT TO ENGINEERS SHOP DRAWINGS OF ALL MATERIALS AND EQUIPMENT FOR APPROVAL PRIOR TO FABRICATION AND/OR PURCHASING. 5. INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER. THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS WHICH, IN HIS INSTALL MATERIALS AND EQUIPMENT IN A NEAT AND FIRST CLASS WORKMANLIKE MANNER. THE OWNER RESERVES THE RIGHT TO DIRECT REMOVAL AND REPLACEMENT OF ITEMS WHICH, IN HIS OPINION, DO NOT PRESENT A NEAT AND WORKMANLIKE APPEARANCE, REMOVAL AND REPLACEMENT IS TO BE DONE IMMEDIATELY WHEN DIRECTED BY THE OWNER IN WRITING, AT THE SOLE EXPENSE OF CONTRACTOR. 6. START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABLE OF THE WORK OF OTHER TRADES OR OTHER CONTRACTORS START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM OF ALL CLAIMS OR QUESTIONS AS TO SUITABLE OF THE WORK OF OTHER TRADES OR OTHER CONTRACTORS TO RECEIVE HIS WORK. THIS CONTRACTOR SHALL REMOVE AND REPLACE, AT HIS EXPENSE, ALL AIR CONDITIONING WORK WHICH MAY HAVE TO BE REMOVED BECAUSE OF INTERFERENCE WITH OTHER TRADES. 7. START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM TO COMPLY WITH ALL THE SPECIFICATIONS AND NOTES INCLUDED ON THE SET OF CONTRACT DRAWINGS, AS START OF WORK BY CONTRACTOR SHALL BE CONSIDERED AS ACCEPTANCE BY HIM TO COMPLY WITH ALL THE SPECIFICATIONS AND NOTES INCLUDED ON THE SET OF CONTRACT DRAWINGS, AS WELL AS THE INSTRUCTIONS SUPPLY IN WRITING BY THE ENGINEER OFFICE THROUGH RFI'S OR SIMILARS. 8. ALL MATERIALS SHALL BE NEW, FREE FROM DEFECTS, INDELIBLY MARKED WITH NAME OF MANUFACTURER, WEIGHT AND/OR CLASS. ALL MATERIALS SHALL BE NEW, FREE FROM DEFECTS, INDELIBLY MARKED WITH NAME OF MANUFACTURER, WEIGHT AND/OR CLASS. 9. THE WORD "AIR CONDITIONING" MEANS HEATING, VENTILATION, AIR CONDITIONING, DUCT WORK, PIPING REFRIGERANT LINES, CONTROLS, SMOKE AND FIRE/SMOKE DAMPERS ETC. THE WORD "AIR CONDITIONING" MEANS HEATING, VENTILATION, AIR CONDITIONING, DUCT WORK, PIPING REFRIGERANT LINES, CONTROLS, SMOKE AND FIRE/SMOKE DAMPERS ETC. 10. PROVIDE MEANS "FURNISH AND INSTALL". PROVIDE MEANS "FURNISH AND INSTALL". 11. DO A COMPLETE JOB, EVERYTHING CONNECTED, READY FOR USE. DO A COMPLETE JOB, EVERYTHING CONNECTED, READY FOR USE. 12. AT COMPLETION OF JOB THE HVAC CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF DRAWINGS SHOWING THE AIR CONDITIONING SYSTEM AS INSTALLED IN THE FIELD. AT COMPLETION OF JOB THE HVAC CONTRACTOR SHALL GIVE THE OWNER AN AS-BUILT SET OF DRAWINGS SHOWING THE AIR CONDITIONING SYSTEM AS INSTALLED IN THE FIELD. 13. MOUNT ALL EQUIPMENT FOR WIND LOADS, SISMIC LOADS AND MOUNTING HEIGHTS AS REQUIRED BY IBC & LOCAL CODES. MOUNT ALL EQUIPMENT FOR WIND LOADS, SISMIC LOADS AND MOUNTING HEIGHTS AS REQUIRED BY IBC & LOCAL CODES. 14. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. ALL DUCT SIZES ARE CLEAR INSIDE DIMENSIONS. 15. THE HVAC CONTRACTOR SHALL WARRANT ALL WORKMANSHIP AND MATERIALS FOR ONE YEAR FROM THE DATE OF FINAL WORK ACCEPTANCE BY OWNER, ANY BREAKDOWN OCCURRING IN FIRST THE HVAC CONTRACTOR SHALL WARRANT ALL WORKMANSHIP AND MATERIALS FOR ONE YEAR FROM THE DATE OF FINAL WORK ACCEPTANCE BY OWNER, ANY BREAKDOWN OCCURRING IN FIRST YEAR SHALL BE REPAIRED AT NO EXPENSE TO THE OWNER. THE COMPRESSOR(S) SHALL HAVE A FIVE YEAR GUARANTEE. 16. ALL SHEET METAL DUCTWORK TO BE CONSTRUCTED IN ACCORDANCE WITH SMACNA'S STANDARDS. ALL DUCTWORK TO BE MINIMUM 24 GA, GALVANIZED STEEL. ALL JOINTS AND SEAMS OF ALL SHEET METAL DUCTWORK TO BE CONSTRUCTED IN ACCORDANCE WITH SMACNA'S STANDARDS. ALL DUCTWORK TO BE MINIMUM 24 GA, GALVANIZED STEEL. ALL JOINTS AND SEAMS OF INTERIOR DUCTS TO BE SEALED WITH NON HARDENING, WATER BASED RESISTANT WHEN FULLY CURED, FIRE RESISTIVE COMPATIBLE WITH MATING MATERIALS; LIQUID USED ALONE OR WITH TAPE OR HEAVY MASTIC. SEALANT SHALL BE UNITED MCGILL SEALANT TO MAKE JOINTS AIRTIGHT. ALL DUCTWORK SHALL BE SEALED IN ACCORDANCE WITH SMACNA'S STANDARDS. REFER TO SPECIFICATIONS SECTION 15.32.
AutoCAD SHX Text
17. ALL ROUND DUCTWORK SHALL BE SPIRAL LOCK SEAM. ALL ROUND DUCTWORK SHALL BE SPIRAL LOCK SEAM. 18. BRANCH TAKEOFFS MUST BE PROVIDED WITH APPROVED, ADJUSTABLE AND ACCESSIBLE AIR VOLUME DAMPERS. BRANCH TAKEOFFS MUST BE PROVIDED WITH APPROVED, ADJUSTABLE AND ACCESSIBLE AIR VOLUME DAMPERS. 19. FOR EXACT LOCATION OF CEILING DIFFUSERS REFER TO ARCHITECTURAL/INTERIOR DESIGNER REFLECTED CEILING PLAN. ALL DUCT MOUNTED OPPOSED BLADE VOLUME FOR EXACT LOCATION OF CEILING DIFFUSERS REFER TO ARCHITECTURAL/INTERIOR DESIGNER REFLECTED CEILING PLAN. ALL DUCT MOUNTED OPPOSED BLADE VOLUME DAMPERS USED FOR AIR BALANCING MUST BE AIRFOIL BLADE TYPE AS MANUFACTURED BY RUSKIN MODEL CD-50, OR APPROVED EQUAL. 20. THE CONTRACTOR MUST FURNISH AND INSTALL ALL U.L. APPROVED FIRE DAMPERS AND/OR MOTORIZED FIRE/SMOKE DAMPER COMBINATIONS WHERE SHOWN ON DRAWINGS, THE CONTRACTOR MUST FURNISH AND INSTALL ALL U.L. APPROVED FIRE DAMPERS AND/OR MOTORIZED FIRE/SMOKE DAMPER COMBINATIONS WHERE SHOWN ON DRAWINGS, AS REQUIRED BY THE BUILDING CODE, AS REQUIRED BY NFPA CODES, AND/OR AS REQUIRED BY ANY GOVERNMENT AUTHORITY HAVING JURISDICTION OVER THE PROJECT. 21. FURNISH SMOKE DETECTORS, FIRE STATS AS REQUIRED BY NFPA. 22. THIS CONTRACTOR SHALL FURNISH ALL MOTOR STARTERS AND FREQUENCY DRIVES REQUIRED FOR ALL EQUIPMENT FURNISHED UNDER THIS CONTRACT AND SHALL BE INSTALLED BY THE ELECTRICAL CONTRACTOR. 23. VIBRATION ISOLATION: ALL EQUIPMENT AS PER MANUFACTURER SPECIFICATIONS DIV 15 TO ELIMINATE ANY VIBRATION FROM BEING TRANSFERRED TO STRUCTURE. VIBRATION ISOLATION: ALL EQUIPMENT AS PER MANUFACTURER SPECIFICATIONS DIV 15 TO ELIMINATE ANY VIBRATION FROM BEING TRANSFERRED TO STRUCTURE. 24. PROVIDE COMPLETE CONTROLS FOR THE OPERATION OF THE AIR CONDITIONING SYSTEM. CONNECT TO EXISTING BUILDING MANAGEMENT SYSTEM AND FIRE ALARM, COORDINATE PROVIDE COMPLETE CONTROLS FOR THE OPERATION OF THE AIR CONDITIONING SYSTEM. CONNECT TO EXISTING BUILDING MANAGEMENT SYSTEM AND FIRE ALARM, COORDINATE WITH ELECTRICAL & CONTROLS CONTRACTOR TO PROVIDE A COMPLETE OPERATING SYSTEM. 25. EQUIPMENT BY MANUFACTURERS OTHER THAN THOSE SPECIFIED MAY BE ACCEPTABLE. HOWEVER, THE COORDINATION WITH ALL TRADES FOR INSTALLING ACCEPTABLE EQUIPMENT BY MANUFACTURERS OTHER THAN THOSE SPECIFIED MAY BE ACCEPTABLE. HOWEVER, THE COORDINATION WITH ALL TRADES FOR INSTALLING ACCEPTABLE ALTERNATIVE INCLUDING AUXILIARY EQUIPMENT (I.E. CONTROLS, STARTERS, SPACE AVAILABILITY, ETC.) SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. PROVIDE SHOP DRAWINGS FOR ALL TRADES INVOLVED IN THE ALTERNATE. SEND ALTERNATIVES TO THE ARCHITECT/ENGINEER IN AMPLE TIME TO PERMIT REVIEW. 26. ALL RFI'S OR SIMILARS TO THE ENGINEER'S OFFICE SHALL BE SUBMITTED IN WRITING THROUGH THE ARCHITECT'S OFFICE. ALL RFI'S OR SIMILARS TO THE ENGINEER'S OFFICE SHALL BE SUBMITTED IN WRITING THROUGH THE ARCHITECT'S OFFICE. 27. IF SPACE ABOVE CEILING IS USED AS RETURN AIR PLENUM. PVC OR ANY OTHER EXPOSED COMBUSTIBLE MATERIAL WILL NOT BE ALLOWED TO USE ABOVE CEILING. IF SPACE ABOVE CEILING IS USED AS RETURN AIR PLENUM. PVC OR ANY OTHER EXPOSED COMBUSTIBLE MATERIAL WILL NOT BE ALLOWED TO USE ABOVE CEILING. 28. PROVIDE SECONDARY DRAIN WITH SAFETY DEVICE TIED INTO THE SECONDARY CONDENSATE DRAIN LINE THAT SHUTS OFF THE SYSTEM IF A CLOGGED CONDENSATE LINE IS PROVIDE SECONDARY DRAIN WITH SAFETY DEVICE TIED INTO THE SECONDARY CONDENSATE DRAIN LINE THAT SHUTS OFF THE SYSTEM IF A CLOGGED CONDENSATE LINE IS DETECTED . REFER TO PLUMBING PLANS FOR CONDENSATE DISCHARGE PIPES AND RISERS. 29. IF PROPER CONDENSATE DRAIN SLOPE TO DISPOSAL POINT IS NOT POSSIBLE TO ACHIEVE, PROVIDE CONDENSATE PUMP AND ALL ELECTRICAL AND MECHANICAL CONNECTIONS IF PROPER CONDENSATE DRAIN SLOPE TO DISPOSAL POINT IS NOT POSSIBLE TO ACHIEVE, PROVIDE CONDENSATE PUMP AND ALL ELECTRICAL AND MECHANICAL CONNECTIONS FOR PROPER OPERATION. 30. ALL THERMOSTAT'S SHALL BE PROGRAMMABLE ALL THERMOSTAT'S SHALL BE PROGRAMMABLE 31. MOUNT OR HANG FANS USING SPRING VIBRATION ISOLATORS WITH 1" MINIMUM DEFLECTION. VIBRATION ISOLATORS MUST HAVE ALL STEEL PARTS HOT DIP GALVANIZED, ALL MOUNT OR HANG FANS USING SPRING VIBRATION ISOLATORS WITH 1" MINIMUM DEFLECTION. VIBRATION ISOLATORS MUST HAVE ALL STEEL PARTS HOT DIP GALVANIZED, ALL NUTS AND BOLTS CADMIUM PLATED AND ALL SPRINGS CADMIUM PLATED AND NEOPRENE COATED. 32. PROVIDE DUCT SMOKE DETECTORS IN SUPPLY DUCTS 2,000 CFM AND ABOVE AND FOR RETURN DUCTS 15,000 CFM AND ABOVE. PROVIDE DUCT SMOKE DETECTORS IN SUPPLY DUCTS 2,000 CFM AND ABOVE AND FOR RETURN DUCTS 15,000 CFM AND ABOVE. 33. PROVIDE R-6 MINIMUM INSULATION FOR SUPPLY DUCT AND R-4.2 MINIMUM INSULATION FOR EXHAUST AIR DUCT IN MEZANINE PLENUM SPACE. EXTERNALLY INSULATE DUCTS PROVIDE R-6 MINIMUM INSULATION FOR SUPPLY DUCT AND R-4.2 MINIMUM INSULATION FOR EXHAUST AIR DUCT IN MEZANINE PLENUM SPACE. EXTERNALLY INSULATE DUCTS WITH FIBERGLASS BLANKET TYPE THERMAL INSULATION WITH A MINIMUM R-REQUIRED AND EXTERIOR ALUMINUM FOIL FACED. PROVIDE INTERIOR ACUSTICAL ISOLATION FOR MAIN RETURN. EXHAUST DUCTS FROM BATHROOMS AND JANITOS NOT REQUIRE INSULATION. AIR DUCT VAPOR SEAL ALL JOINTS WITH TWO COATS OF VAPOR RETARDED MASTIC REINFORCED WITH TWO LAYERS OF 6" WIDE OPEN WEAVE GLASS FABRIC. INSULATION MATERIAL SHALL BE AS MANUFACTURED BY SCHULLER MODEL MICROLITE TYPE 150 OR APPROVED EQUAL. VAPOR SEALANT MASTIC SHALL BE AS MANUFACTURED BY FOSTER MODEL 30-36 OR APPROVED EQUAL. 34. NO PIPING OR MECHANICAL DUCTS SHALL BE INSTALLED DIRECTLY ABOVE ELECTRICAL EQUIPMENT. COORDINATE WITH ELECTRICAL PLANS. NO PIPING OR MECHANICAL DUCTS SHALL BE INSTALLED DIRECTLY ABOVE ELECTRICAL EQUIPMENT. COORDINATE WITH ELECTRICAL PLANS. 35. TEST & BALANCE TO BE PERFORMED BY AN INDEPENDENT TEST AND BALANCE AGENCY SELECTED BY OWNER AND CONTRACTED BY CONTRACTOR. ADJUST DAMPER AND FANS TEST & BALANCE TO BE PERFORMED BY AN INDEPENDENT TEST AND BALANCE AGENCY SELECTED BY OWNER AND CONTRACTED BY CONTRACTOR. ADJUST DAMPER AND FANS TO OBTAIN AIR QUANTITIES WITHIN 10% OF THOSE INDICATED ON THE DRAWINGS. OBTAIN FULL LOAD AMPS READING FOR ALL MOTORS AT BALANCED CONDITIONS. RECORD OUTDOOR AND INDOOR DRY AND WET BULB TEMPERATURES AT BALANCED CONDITIONS, PROVIDE HYDRALIC DATA. SUBMIT ALL TEST AND BALANCE REPORTS TO ARCHITECT FOR APPROVAL. TEST & BALANCE CONTRACTOR SHALL BE CERTIFIED FOR NATIONAL ENVIRONMENTAL BALANCE BUREAU OR ASSOCIATED AIR BALANCE COUNCIL. 36. CHILLED WATER PIPING SHALL BE BLACK STEEL ELECTRIC RESISTANCE WELD (ERW) SCREWED UP TO 2" AND GROOVED 2 1/2" AND UP. ALL PIPING, FITTINGS, VALVES, CHILLED WATER PIPING SHALL BE BLACK STEEL ELECTRIC RESISTANCE WELD (ERW) SCREWED UP TO 2" AND GROOVED 2 1/2" AND UP. ALL PIPING, FITTINGS, VALVES, ACCESSORIES, AND CONDENSERS, SHALL BE RATED AT A MINIMUM OF 150 PSIG DESIGN WORKING PRESSURE. IN NO CASE PIPING SHALL BE LESS THAN SCHEDULE 40. 37. INSULATE ALL CHILLED WATER PIPING WITH 1-1/2" FOAM GLASS INSULATION. VAPOR SEAL ALL SEAMS WITH FOSTER 30-35 SEALING COMPOUND. COVER PIPE INSULATION INSULATE ALL CHILLED WATER PIPING WITH 1-1/2" FOAM GLASS INSULATION. VAPOR SEAL ALL SEAMS WITH FOSTER 30-35 SEALING COMPOUND. COVER PIPE INSULATION WITH 6 OUNCE CANVAS ADHERED AND SIZED WITH FOSTER 30-36 SEALING COMPOUND. COVER INSULATION WITH ALUMINUM JACKET.
AutoCAD SHX Text NOTAS GENERALES: 1. TODOS LOS TRABAJOS DEBERÁN ESTAR EN CONFORMIDAD CON LOS CÓDIGOS Y NORMAS QUE APLIQUEN, UTILIZAR LAS ULTIMAS PUBLICACIONES DE LOS SIGUIENTES CÓDIGOS Y TODOS LOS TRABAJOS DEBERÁN ESTAR EN CONFORMIDAD CON LOS CÓDIGOS Y NORMAS QUE APLIQUEN, UTILIZAR LAS ULTIMAS PUBLICACIONES DE LOS SIGUIENTES CÓDIGOS Y NORMAS, SIENDO QUE LOS REQUISITOS MÍNIMOS DE ESTAS PUBLICACIONES NO EXONERAN DE LA RESPONSABILIDAD A LOS CONTRATISTAS DE PROVEER CUALQUIER TRABAJO, EQUIPO O SISTEMA ESPECIFICADO AUNQUE SUPERE DICHOS REQUISITOS: CÓDIGO INTERNACIONAL DE CONSTRUCCIÓN 2003./INTERNATIONAL BUILDING CODE 2003(IBC). CÓDIGO INTERNACIONAL DE MECÁNICA 2003./INTENATIONAL MECHANICAL CODE 2003(IMC). ASOCIACIÓN NACIONAL DE PROTECCIÓN CONTRA INCENDIOS 2002./NATIONAL FIRE PROTECTION ASSOCIATION (NFPA), 2002. LABORATORIOS CERTIFICADOS./UNDERWRITERS LABORATORIES, INC. (UL). NORMAS DE AMCA./AMCA STANDARDS. CÓDIGO NACIONAL DE ELECTRICIDAD 2005./NATIONAL ELECTRICAL CODE (NEC), 2005. ASOCIACIÓN AMERICANA DE INGENIEROS MECANICOS./AMERICAN SOCIETY OF MECHANICAL ENGINEERS (ASME). ASOCIACIÓN NACIONAL DE CONTRATISTAS DE CHAPAS METÁLICAS Y AIRE ACONDICIONADO./SHEET METAL AND AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA). NORMAS DE SEGURIDAD DEL TRABAJO./OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION (OSHA). CÓDIGOS Y REQUERIMIENTOS LOCALES. 2. EXAMINE TODOS LOS PLANOS CUIDADOSAMENTE Y VERIFIQUE LAS CONDICIONES EXISTENTES EN EL LUGAR DE ANTES DE PRESENTAR LA COTIZACIÓN O COMENZAR CUALQUIER EXAMINE TODOS LOS PLANOS CUIDADOSAMENTE Y VERIFIQUE LAS CONDICIONES EXISTENTES EN EL LUGAR DE ANTES DE PRESENTAR LA COTIZACIÓN O COMENZAR CUALQUIER TRABAJO. LOS CONTRATISTAS DEBERÁN FABRICAR, INSTALAR Y/O CONECTAR CON LOS SERVICIOS APROPIADOS TODOS LOS EQUIPOS DE AIRE ACONDICIONADOS MOSTRADO EN CUALQUIER PLANO DE ARQUITECTURA, PLOMERÍA, ELÉCTRICO O DE PROTECCIÓN DE INCENDIO SIN COSTOS ADICIONALES PARA EL PROPIETARIO, SI OCURRIERA ALGUNA DISCREPANCIA, CONFLICTO, INTERFERENCIA U OMISIÓN EN LOS PLANOS, NOTIFIQUE POR ESCRITO AL ARQUITECTO/INGENIERO CON TIEMPO SUFICIENTE PARA PERMITIR REVISIONES ANTES DE QUE LAS COTIZACIONES SEAN ENTREGADAS. 3. LOS PLANOS SON CONSIDERADOS DIAGRAMATICOS, NO MUESTRAN NECESARIAMENTE ASPECTOS MENORES EN DETALLE O A ESCALA. A MENOS QUE ESTE ESPECIFICADO, LA LOS PLANOS SON CONSIDERADOS DIAGRAMATICOS, NO MUESTRAN NECESARIAMENTE ASPECTOS MENORES EN DETALLE O A ESCALA. A MENOS QUE ESTE ESPECIFICADO, LA LOCALIZACIÓN EXACTA ESTARÁ REGIDA POR LA ESTRUCTURA, ARQUITECTURA Y LAS CONDICIONES DEL LUGAR. EL CONTRATISTA DEBERÁ SEGUIR LOS PLANOS AL EJECUTAR EL TRABAJO. CHEQUEAR LOS PLANOS DE TODAS LAS DISCIPLINAS PARA VERIFICAR EL ESPACIO FÍSICO EN DONDE SERÁ EJECUTADO EL TRABAJO Y TRATARA DE MANTENER LA MÁXIMA ALTURA POSIBLE Y LA CONDICIONES ADECUADAS DEL ESPACIO EN TODOS SUS PUNTOS, EN DONDE LA ALTURA Y LAS CONDICIONES PAREZCAN INADECUADAS, DEBERÁ NOTIFICAR POR ESCRITO AL ARQUITECTO O AL INGENIERO ANTES DE PROCEDER CON LA INSTALACIÓN, EL CONTRATISTA REALIZARA SIN CARGO ALGUNO LAS MODIFICACIONES QUE SE REQUIERAN EN LOS PLANOS EN LA OBRA PARA PREVENIR CONFLICTOS EN EL TRABAJO Y CON LAS OTRAS DISCIPLINAS. 4. EL CONTRATISTA DEBERÁ PROVEER A LOS INGENIEROS LAS ESPECIFICACIONES TÉCNICAS DE TODOS LOS MATERIALES Y EQUIPOS QUE SE UTILIZARAN PARA APROBACIÓN ANTES DE EL CONTRATISTA DEBERÁ PROVEER A LOS INGENIEROS LAS ESPECIFICACIONES TÉCNICAS DE TODOS LOS MATERIALES Y EQUIPOS QUE SE UTILIZARAN PARA APROBACIÓN ANTES DE SER FABRICADOS Y/O COMPRADOS. 5. INSTALAR MATERIALES Y EQUIPOS DE MANERA COMPETENTE Y DE CALIDAD. EL PROPIETARIO SE RESERVA EL DERECHO MANDAR A RETIRAR Y REEMPLAZAR LAS INSTALACIONES QUE INSTALAR MATERIALES Y EQUIPOS DE MANERA COMPETENTE Y DE CALIDAD. EL PROPIETARIO SE RESERVA EL DERECHO MANDAR A RETIRAR Y REEMPLAZAR LAS INSTALACIONES QUE A SU CRITERIO NO PRESENTEN LA CALIDAD REQUERIDA, ESTO SERÁ HECHO INMEDIATAMENTE CUANDO EL PROPIETARIO LO SOLICITE POR ESCRITO Y TODOS LOS GASTOS SERÁN ASUMIDOS POR EL CONTRATISTA. 6. EL COMIENZO DEL TRABAJO POR EL CONTRATISTA SERÁ CONSIDERADO COMO ACEPTACIÓN DE TODOS LOS REQUISITOS E INDICACIONES Y RECLAMACIONES PARA PODER EJECUTAR EL EL COMIENZO DEL TRABAJO POR EL CONTRATISTA SERÁ CONSIDERADO COMO ACEPTACIÓN DE TODOS LOS REQUISITOS E INDICACIONES Y RECLAMACIONES PARA PODER EJECUTAR EL TRABAJO Y QUE HA COORDINADO CON EL RESTO DE LAS DISCIPLINAS ENVUELTAS EN LA OBRA PARA NO TENER IMPEDIMENTO ALGUNO. EL CONTRATISTA SERÁ RESPONSABLE POR LOS GASTOS ORIGINADOS POR EL RETIRO Y REEMPLAZO DE TODAS LAS INSTALACIONES DE AIRE ACONDICIONADO QUE ESTÉN INTERFIRIENDO LAS OTRAS DISCIPLINAS. 7. EL COMIENZO DEL TRABAJO POR EL CONTRATISTA SERÁ CONSIDERADO COMO ACEPTACIÓN DE CUMPLIR CON TODAS LAS ESPECIFICACIONES Y NOTAS INCLUIDAS EN EL CONJUNTO DE EL COMIENZO DEL TRABAJO POR EL CONTRATISTA SERÁ CONSIDERADO COMO ACEPTACIÓN DE CUMPLIR CON TODAS LAS ESPECIFICACIONES Y NOTAS INCLUIDAS EN EL CONJUNTO DE PLANOS DE CONTRATO, ASÍ COMO CON LAS INSTRUCCIONES PROVEÍDAS POR EL INGENIERO A TRAVÉS DE LA CORRESPONDENCIA. 8. TODOS LOS MATERIALES DEBERÁN SER NUEVOS, LIBRES DE DEFECTO, MARCADOS PERMANENTE CON EL NOMBRE DEL FABRICANTE, PESO Y/O CLASE. TODOS LOS MATERIALES DEBERÁN SER NUEVOS, LIBRES DE DEFECTO, MARCADOS PERMANENTE CON EL NOMBRE DEL FABRICANTE, PESO Y/O CLASE. 9. LA PALABRA "AIRE ACONDICIONADO" SIGNIFICA CALEFACCIÓN, VENTILACIÓN, AIRE ACONDICIONADO, CONDUCTOS, TUBERÍAS DE REFRIGERACIÓN, CONTROLES, COMPUERTAS CONTRA LA PALABRA "AIRE ACONDICIONADO" SIGNIFICA CALEFACCIÓN, VENTILACIÓN, AIRE ACONDICIONADO, CONDUCTOS, TUBERÍAS DE REFRIGERACIÓN, CONTROLES, COMPUERTAS CONTRA FUEGO Y HUMO, ECT. 10. PROVEER SIGNIFICA "CONSTRUIR E INSTALAR". PROVEER SIGNIFICA "CONSTRUIR E INSTALAR". 11.