This document specifies the salient characteristics of three transformer products required under a federal contract solicitation.
CLIN 0001 requires a 300 KVA three-phase 120/208VAC Delta Y configuration ABB transformer with 12470 Delta high voltage at 95 kV BIL, equipped with two above and two below taps at 2.5%, and six 200A Wells & Inserts dead front loop feed bushings. The low voltage rating is 208 Y/120 at 30 kV BIL with four 4-hole spade bushings. Specifications include mineral oil fluid, 65°C temperature rise, ONAN cooling class, aluminum conductors, no fusing, 4-position LBOR switch, mild steel tank, and standard cabinet depth. The unit shall include a liquid level gauge, pressure vacuum gauge, dial-type thermometer, grounding provisions, Schrader valve, drain and sample valve, pressure relief valve, padmount green paint finish, and UL listing.
CLIN 0002 requires a 150 KVA three-phase 120/208VAC Delta Y configuration ABB transformer with identical high voltage specifications (12470 Delta, 95 kV BIL) and taps as CLIN 0001, along with the same low voltage configuration and accessories. CLIN 0003 requires a 100 KVA single-phase 120/208VAC pad mount ABB transformer operating at 65°C and 60Hz with standard impedance, 12470Y 7200 primary voltage at 95 kV BIL with loop feed, 240/120 secondary voltage at 30 kV BIL, no primary taps, 200A dead front wells with 15 kV insert primary bushings, 4-hole spade secondary bushings, bayonet fusing with fuse holder assembly, and FR3 insulating fluid.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Vendor Questions - Answered 2.docx | DOCX document | |
| RFQ FA466126Q0111 Ammendment 2.pdf | ||
| Vendor Questions - Answered.docx | DOCX document | |
| RFQ FA466126Q0111 Ammendment 1.pdf | ||
| RFQ FA466126Q0111.pdf | ||
| Atatchement 2 - Provisions and Clauses.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Salient Characteristics of the Requested Transformers CLIN 0001: 300 KVA 3PH 120/208VAC Delta Y configuration ABB Transformer
High Voltage:
12470 Delta, 95 kV BIL
Taps: 2 Above, 2 Below @ 2.5%
HV Bushings: (6) 200A Wells & Inserts (dead front, loop feed)
Low Voltage:
208 Y/ 120, 30 kV BIL
LV Bushings: (4) 4-Hole Spades
Specifications:
Fluid: Mineral Oil
Temperature Rise:
65C Cooling Class:
ONAN Conductor: Al /
Al Fusing: None
Switch: 4 Pos. LBOR
Tank Material: Mild
Steel Arresters: None
Cabinet Depth: Standard
Features and Accessories:
Liquid Level Gauge
Pressure Vacuum Gauge
Dial-Type Thermometer
Grounding Provisions
Schrader Valve
Drain & Sample Valve
Pressure Relief Valve
Padmount Green Paint
UL Listed
CLIN 0002: 150 KVA 3PH 120/208VAC Delta Y configuration ABB Transformer
CLIN 0003 : 100 KVA 1PH 120/208VAC ABB Transformer