S02 Vol 1-1.pdf
PDF 5 MB Posted
- Solicitation number
- 36C24225R0007
About this file
These are civil/site engineering construction drawings for an emergency generator upgrade project at the Northport VA Medical Center. The drawing set includes demolition plans, layout and materials plans, grading/drainage/utilities plans, and construction details.
The drawings detail the removal of existing generators, radiator enclosures, underground fuel tanks, concrete retaining walls, and associated infrastructure to make way for new emergency generator facilities. Key new construction elements include a 1,500 SF generator building addition, new underground fuel storage tanks, temporary generators during construction, concrete pads, bollards, utilities modifications, and site improvements. Specific technical details are provided for concrete work, drainage structures, pavement sections, thrust blocks, and fuel tank installations. The drawings include precise dimensions, elevations, and specifications for all site work components. Sheet C-0.0 through C-3.2 provide comprehensive construction documentation for the civil/site portion of this VA healthcare facility upgrade project dated November 9, 2023.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24224R0033 PROPOSAL ITEMS.docx | DOCX document | |
| S06_Custom Soil Resource Report.pdf | ||
| 36C24225R0007 0003.docx | DOCX document | |
| Site Visit Sign Sheet.doc | DOC document | |
| S06_Drawing_Amend.pdf | ||
| P07_Wage Determination.txt | TXT text file | |
| Construction Cost Breakdown Sheet.pdf | ||
| 36C24225R0007 0002.docx | DOCX document | |
| 36C24225R0007 0001.docx | DOCX document | |
| Wage Determination.pdf | ||
| S02 Vol 1-0.pdf | ||
| S02 Vol 1-2.pdf | ||
| FAR 52.225-2 Buy American Certification.pdf | ||
| 013200 Construction Documentation.docx | DOCX document | |
| S02 Vol 3-1.pdf | ||
| 852.219-77 VA Notice of Limitations on Subcontracting.docx | DOCX document | |
| S02 Vol 1-3.pdf | ||
| 36C24225R0007.docx | DOCX document | |
| S02 Vol 3-0.pdf | ||
| Past Performace Questionaire_PPQ.pdf | ||
| S02 Vol 1.pdf | ||
| S02 Vol 2.pdf | ||
| S02 Vol 3-2.pdf | ||
| S02 Vol 2-0.pdf | ||
| S02 Vol 2-1.pdf |
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DEMOLITION LEGEND
LARGE OBJECT TO BE REMOVED
SMALL OBJECT TO BE REMOVED
REMOVE BITUMINOUS CONCRETE
PAVEMENT PROFILE
REMOVE CONCRETE PAVEMENT
AREA OF BUILDING TO BE REMOVED
REMOVE CHAIN LINK FENCE,
CURB, OR PIPING
LIMIT OF DISTURBANCE
xxxxxxxxxxx x x x x x x x x x x x x x x x x x x x x x x xxxxxxx x x x x x x x x x x x x x x x x x x x x x x x x x x
EXISTING CONCRETE RETAINING WALL TO BE REMOVED
EXISTING GENERATOR RADIATOR ENCLOSURE TO BE
REMOVED AND PROPERLY DISPOSED OF
EXISTING METAL GRATE AREAWAY TO REMAIN AND
BE PROTECTED
EXISTING ABOVE GROUND RADIATOR PIPING TO BE
REMOVED AND PROPERLY DISPOSED OF PER ALL
APPLICABLE CODES
EXISTING UNDERGROUND FUEL TANK TO BE REMOVED
AND PROPERLY DISPOSED OF
EXISTING ABOVE GROUND PIPING TO BE REMOVED
EXISTING AC UNIT TO BE REMOVED (TYP.)
EXISTING CONCRETE CURBING TO BE REMOVED
EXISTING WATER LINE TO BE REMOVED
CUT AND CAP EXISTING WATER LINE
EXISTING UTILITIES TO BE REMOVED
EXISTING CONCRETE RETAINING WALL TO REMAIN AND BE
PROTECTED
CLEAR AREA EAST OF RETAINING WALL OF
DEBRIS AND EQUIPMENT
TEMPORARY CHAIN LINK FENCE TO BE REMOVED
EXISTING CONCRETE WALL TO BE DEMOLISHED,
SEE SHEET ASD01
AREA OF EXISTING BUILDING TO BE DEMOLISHED,
SEE SHEET ASD01
PROTECT FIRE PROTECTION AND WATER LINE
PROTECT EXISTING ELECTRICAL DUCT BANK
MAINTAIN AND PROTECT EXISTING 12" RCP
REMOVE CONCRETE SIDEWALK
OWNER TO RELOCATE EXISTING STORAGE CONTAINER
OUT OF LIMIT OF DISTURBANCE
4'-1" 3'-0"
SAWCUT LINE (TYP.)
CONTRACTOR TO PROVIDE STEEL PLATE TO ALLOW
CONTINUOUS HS20-LOADED VEHICULAR TRAFFIC
AT ALL TIMES
3' (TYP.)
6' (TYP.)
4' (TYP.)
36'
59'
BACKFILL AND COMPACT HOLE LEFT BY THE REMOVED
UNDERGROUND FUEL TANKS
EXISTING ELECTRICAL SERVICE TO BE REMOVED
EXISTING UNDERGROUND FUEL TANK TO BE REMOVED
AND PROPERLY DISPOSED OF
DEMOLITION NOTES:
1. CONTRACTOR SHALL NOTIFY “NEW YORK 811” (1-800-272-4480) AND VERIFY UTILITY MARK-OUT WITH
THE OWNER PRIOR TO THE INITIATION OF ANY SITE DISTURBANCE.
2. DEMOLITION SCOPE DESCRIBED ON THIS PLAN IS FOR SITE WORK ONLY.
3. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR VERIFICATION OF THE LOCATION AND NATURE OF
ALL SUBSURFACE UTILITIES AT THE PROJECT WHICH MAY BE AFFECTED BY THE WORK.
COORDINATE WITH RESPECTIVE UTILITY OWNERS AND PERFORM VERIFICATION OF TYPE,
LOCATION, AND INVERTS AS REQUIRED.
4. THE CONTRACTOR SHALL NOTIFY THE ENGINEER OF ANY AND ALL DISCREPANCIES BETWEEN
EXISTING CONDITIONS AND THE CONTRACT DOCUMENTS BEFORE PROCEEDING WITH THAT
PORTION OF THE WORK.
5. PROTECT ALL IMPROVEMENTS NOT INCLUDED IN THE SCOPE OF SITE DEMOLITION. ANY
IMPROVEMENT WHICH IS DAMAGED SHALL BE REPAIRED OR REPLACED IN-KIND TO THE OWNER'S
SATISFACTION.
6. DURING DEMOLITION & PAVEMENT REMOVAL PROTECT ALL ADJACENT CURBING, SIDEWALKS,
RAMPS, ABOVE-GRADE AND BELOW-GRADE UTILITIES, DRAINAGE STRUCTURES, LIGHT BASES, AND OTHER IMPROVEMENTS POTENTIALLY AFFECTED BY THE WORK. CLEARLY DELINEATE THE LIMITS OF WORK AND MARK, BARRICADE, OR OTHERWISE IDENTIFY THOSE IMPROVEMENTS THAT ARE TO BE
PROTECTED AND/OR AVOIDED. ANY IMPROVEMENT WHICH IS DAMAGED SHALL BE REPAIRED OR
REPLACED IN-KIND TO THE OWNER'S SATISFACTION.
7. THE LOCATIONS OF EXISTING SITE FEATURES AS SHOWN HAVE BEEN OBTAINED FROM MAPS, SURVEYS, FIELD INSPECTIONS, AND OTHER AVAILABLE INFORMATION. THEY MUST BE CONSIDERED
APPROXIMATE BOTH TO LOCATION, SIZE, AND AS-BUILT CONDITION AND ARE PROVIDED FOR
INFORMATIONAL PURPOSES ONLY. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR DETERMINING
ACTUAL FIELD CONDITIONS.
8. IMPLEMENTING WORKER SAFETY AND/OR HEALTH PROTOCOLS THAT ADDRESS COMPLIANCE WITH RULES, LAWS, AND REGULATIONS PERTAINING TO CONSTRUCTION SAFETY AND/OR THE POTENTIAL
AND/OR ACTUAL RISK OF EXPOSURE TO SITE-SPECIFIC PHYSICAL OR CHEMICAL HAZARDS IS
SOLELY THE RESPONSIBILITY OF THE CONTRACTOR.
9. PRIOR TO THE TERMINATION, ABANDONMENT, OR REMOVAL OF ANY UTILITY, VERIFY THAT
APPLICABLE NOTIFICATIONS HAVE BEEN MADE TO THE UTILITY OWNER/OPERATOR AND THAT THE
UTILITY HAS BEEN PROPERLY TERMINATED, CAPPED, OR PLUGGED AS REQUIRED.
10. PROVIDE PAVEMENT SAWCUT AT THE EDGE OF EACH PAVEMENT REMOVAL OR PAVEMENT RECLAIM AREA TO ESTABLISH A CLEAN EDGE WHERE NEW WORK WILL MEET EXISTING PAVEMENT. SAWCUT SHALL BE A MINIMUM OF 12 INCHES FROM EDGE OF PAVEMENT REMOVAL OR PAVEMENT RECLAIM
AREA.
11. SAWCUT LINES ARE FOR REFERENCE ONLY. CONTRACTOR TO PROVIDE SAWCUT AND TRENCHING
AS NECESSARY TO COMPLETE THE WORK.
12. FOR ADDITIONAL DEMOLITION INFORMATION, SEE SHEET AD001.
UPGRADE EMERGENCY
632-16-101
GENERATORS
FULLY SPRINKLERED
BID DOCUMENTS
DEMOLTION PLAN
C-0.0
NOVEMBER 9, 2023
LAYOUT & MATERIALS LEGEND
CURBING
FENCE
LIMIT OF DISTURBANCE
BITUMINOUS CONCRETE PAVEMENT
CONCRETE SIDEWALK / PAD
PAVEMENT SAWCUT LINE
LAWN / LANDSCAPED AREA
YELLOW ROAD STRIPING
TEMPORARY EARTH RETAINING SYSTEM
xxxxxxxxxxx x x x x x x x x x x x x x x x x x x x x x x xxxxxxx x x x x x x x x x x x x x x x x x x x x x x x x x x
CONCRETE SIDEWALK (TYP.)
NEW GENERATOR BUILDING ADDITION
(1,500± SF)
LOCATION OF TEMPORARY
GENERATORS
LOCATION OF NEW UNDERGROUND FUEL TANKS
(SEE PLUMBING PLAN P101 FOR TRENCHING)
TEMPORARY CONSTRUCTION FENCE (TYP.)
CONCRETE CURB (TYP.)
R25'
4" STEEL BOLLARDS (TYP. OF 7
& 4.75' ON CENTER SPACING)CONTRACTOR STORAGE AREA
SAWCUT 2' FROM CURB LINE AND
PROVIDE NEW PAVEMENT
LIMIT OF DISTURBANCE (TYP.)
LOAM & SEED (TYP.)
TEMPORARY EARTH RETAINING SYSTEM
(TO BE LEFT IN PLACE ON WEST OF TANKS)
SAWCUT AND BITUMINOUS
PAVEMENT PATCH(TYP.)
CONTRACTOR TO PROVIDE
STEELPLATE TO ALLOW
CONTINUOUS HS20-LOADED
VEHICULAR TRAFFIC AT ALL
TIMES
SAWCUT AND CONCRETE PATCH (TYP.)
TEMPORARY EARTH RETAINING SYSTEM (TYP.)
CONCRETE ANCHOR PAD
36'
PAD
59'
PAD
LAYOUT NOTES:
1. THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE FEDERAL REGULATIONS.
2. MATERIALS AND CONSTRUCTION PROCEDURES SHALL COMPLY WITH NYSDOT STANDARD
SPECIFICATIONS FOR CONSTRUCTION AND MATERIALS (LATEST EDITION).
3. NEW PAVEMENT TO MEET LINE & GRADE OF EXISTING PAVEMENTS.
4. CONTRACTOR IS RESPONSIBLE FOR ANY DAMAGE DUE TO CONSTRUCTION ACTIVITIES.
5. ALL LINES AND DIMENSIONS ARE PARALLEL OR PERPENDICULAR TO THE LINES FROM WHICH THEY ARE
MEASURED UNLESS OTHERWISE NOTED.
6. ALL LOCATIONS WHERE EXISTING CURBING, BITUMINOUS CONCRETE ROADWAY OR CONCRETE
ROADWAY OR CONCRETE SIDEWALK ABUT NEW CONSTRUCTION, THE EDGE OF THE EXISTING CURB OR PAVEMENT SHALL BE SAW CUT TO PROVIDE A CLEAN, SMOOTH EDGE. TACK COAT EXPOSED EDGES OF
EXISTING CONCRETE PRIOR TO PLACEMENT OF NEW BITUMINOUS CONCRETE PAVEMENT.
7. FIELD ADJUSTMENTS MUST BE APPROVED BY THE OWNER'S REPRESENTATIVE PRIOR TO
CONSTRUCTION.
8. CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE VERTICAL AND HORIZONTAL POSITION OF EXISTING
UTILITIES PRIOR TO CONSTRUCTION.
9. MANUFACTURED ITEMS SHALL BE INSTALLED, CONNECTED AND CLEANED ACCORDING TO THE
MANUFACTURERS DIRECTIONS.
10. PRIOR TO PROJECT CLOSE-OUT, CONTRACTOR SHALL REMOVE ALL DEBRIS AND EXCESS MATERIALS FROM SITE. ALSO, ANY DAMAGE TO FIELD OR FACTORY APPLIED FINISHES SHALL BE REPAIRED.
11. EXPANSION AND SCORE JOINTS FOR NEW CONCRETE WALKS SHALL BLEND TO MATCH EXISTING
PATTERNS.
12. PROVIDE EXPANSION JOINTS FOR NEW CONCRETE PAVING AT ALL CURBS, TREE GRATES, BUILDING WALLS, SITE WALLS, STAIRS, LIGHT POLE BASES, MANHOLES, GRATES/VAULTS, EXISTING CONCRETE PAVING, STOP LIGHTS, FIRE HYDRANTS AND ALL OTHER FIXED MATERIALS. MAXIMUM DISTANCE
BETWEEN EXPANSION JOINTS SHALL NOT EXCEED 25 FEET.
13. NEW LAWN AREAS TO CONSIST OF MINIMUM SIX (6) INCHES LOAM AND SEED.
14. THE CONTRACTOR SHALL PROVIDE A SUBMITTAL DETAIL OF THE SHEET PILE SHORING FOR
EXCAVATION IN CLOSE PROXIMITY TO THE EXISTING RETAINING WALL AND RCP PIPE.
15. TEMPORARY EARTH RETAINING SYSTEM TO BE REMOVED AFTER BACKFILL UNLESS OTHERWISE NOTED.
UPGRADE EMERGENCY
632-16-101
GENERATORS
FULLY SPRINKLERED
BID DOCUMENTS
LAYOUT AND
MATERIALS PLAN
C-1.0 xxxxxxxxxxx x x x x x x x x x x x x x x x x x x x x x x xxxxxxx x x x x x x x x x x x x x x x x x x x x x x x x x x
STK
CWA
CONNECT TO EXISTING WATER SERVICE
SILT SACK (TYP.)
GATE VALVE
153.76
FFE = 153.76
153.69
153.50
TC=153.00
BC=152.50
TC=-0.71
BC=-1.21
REROUTE 76' NEW WATER SERVICE
TEMPORARY STOCKPILE
CONCRETE WASHOUT AREA
TEMPORARY CONSTRUCTION FENCE (TYP.)
LIMIT OF DISTURBANCE (TYP.)
91'- 6" HDPE PERIMETER FOUNDATION
DRAIN (INV: 149.43) @ 0.00%
TRENCH DRAIN
TF = 153.45
INV = 149.43
28' - 6" HDPE PERIMETER FOUNDATION
DRAIN @ 0.00%
153.50
CONCRETE THRUST BLOCK
153.76
DMH-2
TF: 154.20
INV: 147.17 N/S
INV: 149.07 E
REROUTE 53' NEW FIRE PROTECTION
SERVICE
INV: 149.43
17' - 6" HDPE PERIMETER FOUNDATION
DRAIN @ 0.00%
36' - 6" HDPE @ 1.00%
CONNECT FOUNDATION DRAIN
TO 3" STORM DRAIN
CONNECT FOUNDATION DRAIN
TO 3" STORM DRAIN
150.90
152.13
152.72154.19
HAY BALE BARRIER
CATCH BASIN FILTER INSERT
TEMPORARY CONCRETE WASHOUT
TEMPORARY STOCKPILE
SEDIMENTATION AND EROSION CONTROL LEGEND
STK
CWA
GRADING AND DRAINAGE LEGEND
LIMIT OF DISTURBANCE LINE
MINOR CONTOUR PROPOSED
PROPOSED DRAINAGE PIPE
PROPOSED AREA DRAIN
PROPOSED SPOT GRADE
FLUSH CONDITION
TC=51.70
BC=51.2047.30
UTILITIES LEGEND
GATE VALVE
THRUST BLOCK
LIMIT OF DISTURBANCE
DRAINAGE NOTES:
1. FUNCTIONAL COMPLETION OF STORM WATER DETENTION SYSTEMS AND STRUCTURES SHALL PRECEDE
SITE DEVELOPMENT OF AREAS, ROADS, OR LOTS CONTRIBUTING TO THESE SYSTEMS.
2. CERTIFIED 'AS-BUILTS' VS 'AS-APPROVED' PLANS OF THE STORM WATER DETENTION-DISCHARGE
SYSTEM SHALL BE SUBMITTED FOLLOWING ITS CONSTRUCTION AND PRIOR TO BOND RELEASE.
3. ALL PIPES ARE TO BE 12" HDPE WITH A MINIMUM 1.0% SLOPE AND 1 FT OF COVER UNLESS OTHERWISE
NOTED.
4. CONTRACTOR IS RESPONSIBLE TO ENSURE ADEQUATE SIZING OF MANHOLES TO ACCEPT PROPOSED
PIPES.
5. ALL EXISTING UTILITY LINES TO BE ABANDONED SHALL BE ABANDONED ACCORDING TO UTILITY
COMPANY REQUIREMENTS.
6. ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH APPLICABLE STANDARDS.
7. DAMAGE TO EXISTING UTILITIES AS A RESULT OF THE CONTRACTOR'S OR ANY OF HIS
SUBCONTRACTOR'S ACTIVITIES DURING THE CONSTRUCTION PROCESS SHALL BE REPAIRED AS
DIRECTED BY THE ENGINEER AT NO ADDITIONAL COST TO THE OWNER.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DEWATERING DURING THE EXECUTION OF HIS
WORK.
9. THE LOCATION OF EXISTING UNDERGROUND UTILITIES IS DEVELOPED FROM THE BEST AVAILABLE INFORMATION. THE ACTUAL LOCATION OF EXISTING UTILITIES SHALL BE VERIFIED BY THE CONTRACTOR
PRIOR TO THE START OF EXCAVATION ACTIVITIES.
10. THE NEW CONCRETE TOP PAD SHALL MATCH GRADES OF THE EXISTING CONCRETE.
EROSION CONTROL NARRATIVE:
THE PROJECT PROPOSES TO REPLACE THE EXISTING GENERATOR AND ADD A NEW GENERATOR ROOM TO THE MEDICAL CENTER. THIS INCLUDES REPLACING EXISTING BITUMINOUS CONCRETE PAVING, RENOVATING AND EXPANDING THE SIDEWALK, REPLACING THE EXISTING CURB, INSTALLING TEMPORARY UNDERGROUND STORAGE TANKS AS WELL AS NEW PERMANENT TANKS FOR THE NEW GENERATOR. WE PLAN TO TIE THE NEW ROOF RAIN LEADER INTO THE EXISTING DRAINAGE SYSTEM. A SMALL PORTION OF THE EXISTING BUILDING WILL BE REMOVED TO CONNECT TO THE NEW GENERATOR ROOM. APPROXIMATELY 0.3 ACRES WILL BE DISTURBED BY THE PROJECT, WHICH WILL PRIMARILY INCLUDE STRIPPING AND REPAVING OF THE EXISTING PARKING AREA AND SITE PREPARATION FOR THE NEW BUILDING, REROUTING ONE WATER MAIN
AND MATCHING GRADES FROM THE NEW LANDSCAPING AND SIDEWALK BY THE ADDITION.
THE SPECIFIC EROSION CONCERNS, AND ASSOCIATED SOLUTIONS, ARE AS FOLLOWS:
· TRACKED SEDIMENT - IT IS CRITICAL THAT SEDIMENT NOT BE ALLOWED TO BE TRACKED ONTO ADJACENT
ROADWAYS AND PARKING AREAS BY CONSTRUCTION VEHICLES. THEREFORE, NO CONSTRUCTION
VEHICLE WILL LEAVE THE SITE WITHOUT GOING OVER A CONSTRUCTION ENTRANCE, CONSISTING OF STONE DESIGNED TO SHAKE THE SEDIMENT LOOSE FROM THE WHEELS PRIOR TO THE VEHICLE LEAVING THE SITE. ADDITIONALLY, ANY TRACKED SEDIMENT SHALL BE SWEPT BY THE CONTRACTOR ON A DAILY
BASIS.
· AIRBORNE DUST MIGRATION - IT IS CRITICAL THAT DUST MIGRATION BE MITIGATED BY PERIODICALLY
DAMPENING EXPOSED SOILS WITH WATER TO PREVENT DUST FROM MIGRATING TO NEIGHBORING
PROPERTIES. ADDITIONALLY, STOCKPILES NOT IN USE FOR 30 DAYS OR LONGER SHOULD BE COVERED WITH TARP OR TEMPORARILY SEEDED TO PREVENT AIRBORNE DUST MIGRATION FROM THE PILE.
· SEDIMENT-LADEN WATER POLLUTION OF THE MUNICIPAL STORM SYSTEM - STORMWATER FROM THE SITE IS CAPTURED IN A SERIES OF CATCH BASINS. IT IS CRITICAL THAT SEDIMENT-LADEN WATER NOT BE ALLOWED TO ENTER ANY STORM FACILITIES ON THE SITE. ALL EXISTING CATCH BASINS SUBJECT TO SITE FLOW SHALL BE FITTED WITH INLET PROTECTION. AS NEW CATCH BASINS ARE CONSTRUCTED ON THE SITE, THEY SHALL BE FITTED WITH INLET PROTECTION. ADDITIONALLY, SEDIMENT BARRIER PROTECTION, EITHER IN THE FORM OF HAY BALES, OR SILT FENCE, SHALL BE MAINTAINED ON THE SOUTH SIDE OF THE SITE. ALL SEDIMENT PROTECTION ITEMS SHALL BE CHECKED ON A WEEKLY BASIS, AND AFTER A STORM GENERATING A RUNOFF, TO ENSURE THEY ARE IN GOOD, WORKING CONDITION, AND FUNCTIONING AS
DESIGNED.
THE GENERAL CONTRACTOR WILL BE RESPONSIBLE FOR THE PLACEMENT AND UPKEEP OF THE EROSION CONTROL MEASURES, AS WELL AS ENSURING SEDIMENT-LADEN WATER DOES NOT ENTER THE RESOURCE
AREAS AND AIRBORNE DUST DOES NOT AFFECT NEIGHBORING PROPERTIES.
FILTER INSERTS IN
DRAINAGE SYSTEM
TEMPORARY E&S MEASURES MAINTENANCE SCHEDULE
TARP TEMPORARY
STOCKPILES
HAY BALES/ SILT
FENCE BARRIER
CLEAN CATCH BASIN GRATE, REMOVE SEDIMENT/DEBRIS FROM FILTER INSERTS
REPAIR/REPLACE WHEN FAILURE OBSERVED, REMOVE SILT WHEN ACCUMULATION
REACHES APPROX. HALF HEIGHT OF BARRIER
ENSURE TARP IS SECURED OVER STOCKPILE AT THE END OF EACH DAY
E&S MEASURE MAINTENANCE MEASURES
UPGRADE EMERGENCY
632-16-101
GENERATORS
FULLY SPRINKLERED
BID DOCUMENTS
GRADING, DRAINAGE
AND UTILITIES PLAN
C-2.0
UTILITY NOTES:
1. ALTHOUGH NOT SHOWN ON THE DRAWINGS, CONTRACTOR SHALL PROVIDE FOR THE INSTALLATION OF
ALL JOINTS COUPLINGS, RESTRAINTS, BENDS, ANGLES, AND OTHER APPURTENANCES FOR THE
INSTALLATION OF THE DOMESTIC AND FIRE PROTECTION WATER SERVICE. CONTRACTOR MAY NEED TO ROUTE THE WATER SERVICE BENEATH THE EXISTING ELECTRICAL DUCT BANK OR OTHER UTILITIES.
Varies 6"
Pipe 1'
6"
4'-6" M
IN
EXCAVATED MATERIAL (UNDER PLANTING)
GRAVEL BACKFILL PLACED AND COMPACTED
IN 12" LAYERS (UNDER PVMNTS.)
COMPLETE ENVELOPE OF FILTER FABRIC WITH
12" OVERLAP REQUIRED WHEN CRUSHED
STONE IS USED AS BEDDING MATERIAL,
FILTER FABRIC REQUIRED IN ROCK
CUT AS DIRECTED BY ENGINEER
COURSE SAND OR
FINE GRAVEL
GRAVEL FILL AS DIRECTED BY
ENGINEER WHEN UNSUITABLE
MATERIAL IS ENCOUNTERED
WARNING
TAPE
PIPE O.D. PLUS
24" OR 3'-0" MIN.
4" LOAM, FERTILIZE AND SEED WITH
GRASS AND MULCH
BITUMINOUS
CONCRETE
PAVEMENT
VAR
IES
WATER TRENCH
SCALE: NONE
LAWN
SCALE: NONE
1" REBAR FOR BAG
REMOVAL FROM INLET
(REBAR NOT INCLUDED)
OPTIONAL OVERFLOW
SILTSACK®
DUMP LOOPS (REBAR NOT
INCLUDED)
FOAM
INSERT
NOTES:
1. UTILIZE 'SILTSACK' SEDIMENT CONTROL DEVICE,
TERRAFIX GEOSYNTHETICS INC. OR ENGINEER
APPROVED EQUAL.
2. INSTALL AND MAINTAIN IN ACCORDANCE WITH
MANUFACTURERS WRITTEN INSTRUCTIONS.
SILT SACK (SS)
SCALE: NONE
STAKED STRAW BALES
CROSS-SECTION
PLAN VIEW
FIELD VARIABLE
FI
EL
D V
AR
IA
BL
E
10' (MIN.)
OVERLAP
1'
NOTES:
1. CONSTRUCT WASHOUT AREA LARGE ENOUGH TO ENSURE MATERIALS WILL BE CONTAINED WHERE WASTE
CONCRETE CAN SOLIDIFY IN PLACE AND EXCESS WATER CAN SAFELY EVAPORATE.
2. WASHOUT AREA SHALL BE LARGE ENOUGH TO RETAIN ALL LIQUID AND WASTE CONCRETE MATERIALS FROM
WASHOUT OPERATION.
3. WEEKLY INSPECTIONS OF WASHOUT AREAS SHALL BE CONDUCTED TO ASSESS THE HOLDING CAPACITY AND
FUNCTIONALITY OF THE WASHOUT AREA.
NON-WOVEN GEOTEXTILE FILTER
FABRIC
SECURE FABRIC WITH EROSION
CONTROL STAPLES
FILTER FABRIC
2"x11
2"x36" WOOD STAKE OR STEEL
POSTS WITH A MIN. OF 0.5 POUNDS
PER LINEAR FOOT (2 PER HAY
BALE)
FILTER FABRIC
BURY FILTER FABRIC 4"
SCALE: NONE
TEMPORARY CONCRETE WASHOUT AREA
3' -6
" A
BO
VE
FI
N . G
R
AD
E
6"
GRANULAR FILL
CAST-IN-PLACE CLASS A
CONCRETE FOOTING
CONCRETE DUMPSTER PAD
4"Ø GALVANIZED STEEL PIPE
ASTM A53 (STD. WEIGHT) FILLED
WITH 3,000 PSI CONCRETE, COLOR TO BE
SELECTED BY ARCHITECT.
CONCRETE DOME
6"
1'-6"
BOLLARD
SCALE: NONE
BITUMINOUS CONCRETE PAVEMENT
4" PROCESSED AGGREGATE BASE (COMPACT EACH LIFT
TO 95% OF MODIFIED DENSITY PER ASTM D-1557
METHOD C)
1 12" HMA S0.375
8" COMPACTED ROLLED GRANULAR BASE (95% OF
MODIFIED DENSITY PER ASTM D-1557 METHOD C)
COMPACTED SUBGRADE (95% MAXIMUM DRY UNIT
WEIGHT ACCORDING TO ASTM D-1557)
2 12" HMA S0.5
SCALE: NONE
6"
1" 6"
COMPACTED
SUBGRADE
FIN. GRADE
PAVEMENT
CONTRACTION JOINTS 8' O.C.
EXPANSION
JOINTS @ 20' O.C.
HAND RUB
EXPOSED SURFACES
FIN. GRADE
COMPACTED
GRAVEL BASE
1" R
18"
14" 8"
6" 6"7" NO. 4 REBAR
SECTION
NOTE:
CONTRACTOR SHALL SUBMIT
SHOP DRAWING OF PRECAST
CURB FOR APPROVAL.
FRONT SECTION
NO. 4 REBAR
(TYP.)
NO. 5 REBAR PIN
EACH END TYP.
3"
MIN.
3"
MIN.
1/2" PREFORMED
BITUMINOUS EXPANSION
JOINT MATERIAL AT
EACH EXPANSION JOINT
CONCRETE CURB
4,000 PSI
PRECAST CONCRETE CURB
SCALE: NONE
2. CONCRETE SHALL BE CLASS "A"
1. THE DIMENSIONS SHOWN ARE MINIMUM.
PRIOR TO PLACING CONCRETE
TO FIRM MATERIAL IMMEDIATELY
TRENCH SHALL BE EXCAVATED
TRENCH WIDTH
1.0'
D
2.0'
D
2D
90° FITTING
6D
1.0'
2.0'
1.0'
2.0'
D
2D
4D
11.25°, 22.5° AND 45°
1.0'
2.0'
3D
1.5D
ANGLE OF FITTING
D
PLAN
SECTION
PLAN
CONCRETE THRUST BLOCKS
PLAN
SCALE: NONE
D
GATE VALVE
SCALE: NONE
WTR-102-CT
ADJUSTABLE VALVE BOX PER LOCAL WATER
DEPARTMENT STANDARDS
FINISH GRADE
5' M
IN
IM
U M
C O
VE
R
8" GATE VALVE
M.J. FITTINGS (TYP.)
UNDISTURBED MATERIAL
CONCRETE SUPPORT
WATER SERVICES 4" THROUGH 8"
NONESCALE:
PERMANENT PAVEMENT REPAIR DRIVEWAY DETAIL
NONESCALE:
EXISTING GRAVEL BACKFILL
COMPACTED IN 12" LAYERS
(UNDER PVMNTS.)
3" COMPACTED BIT. CONC. WEARING
COURSE CLASS 2 PER
TACK COAT ALL EDGES
STORM DRAINAGE MANHOLE
SCALE: NONE
6" MIN.
4" MIN.
B
AS
E 4'
M
IN
. KNOCKOUTS FOR PIPES
MIN. 4" FROM TOP &
BOTTOM OF BASE
12" CRUSHED STONE
CONCRETE OR BRICK &
MORTAR INVERT
R
IS
ER
V
AR
IE
S 3'
O R
' C
O N
E
4" MIN.
STEP
12" (TYP.)
3" MIN.
4'-0" DIA.
WATERTIGHT
GASKET OR SEALER
LIFTING HOLES (TYP.)
FILL WITH MORTAR
5" WALL
PRECAST REINFORCED CONCRETE TONGUE
AND GROVE RISERS AS REQUIRED
WELDED WIRE FABRIC (TYP.)
PRECAST REINFORCED CONCRETE
MANHOLE ECCENTRIC CONE
ADJUST TO GRADE WITH MAX. OF
FOUR COURSES OF BRICK OR
GRADE RINGS
8" MIN.
2'-6" DIA. MAX.
2'-0" DIA. MIN.
2"
FRAME - SET IN FULL BED OF MORTAR
7"
NOTES:
1. 5' OR 6' DIA. PRECAST BASES MAY BE USED WHEN REQUIRED DUE TO SIZE OR NUMBER OF PIPES AT THE MANHOLE.
PRECAST REDUCERS WILL BE PLACED ABOVE THE 5' OR 6' BASES AS DIRECTED BY THE ENGINEER. WALL THICKNESS TO
INCREASE 1" FOR EACH 1' OF INSIDE DIAMETER INCREASE.
2. FRAME DIAMETER OF 3'-3" WITH 4" FLANGE MUST BE USED WHEN THE TOP DIA. OF THE PRECAST CONE IS LESS THAN 3'-6".
ALL OTHER FRAME DIMENSIONS ARE TO REMAIN THE SAME.
3. MINIMUM CONCRETE COMPRESSIVE STRENGTH OF F'c = 4,000 PSI SHALL BE OBTAINED PRIOR TO SHIPPING.
4" MIN.
7" TYP.
Va rie s
6"
Pi pe
1'
6"
PIPE O.D. PLUS
24" OR 3'-0" MIN.
GRAVEL FILL AS DIRECTED BY
ENGINEER WHEN UNSUITABLE
MATERIAL IS ENCOUNTERED
3/8" TO 3/4" CRUSHED STONE PLACED AND
COMPACTED IN 6" LAYERS. CRUSHED STONE
IN WET INSTALLATIONS
COMPLETE ENVELOPE OF FILTER FABRIC WITH
12" OVERLAP REQUIRED WHEN CRUSHED
STONE IS USED AS BEDDING MATERIAL,
FILTER FABRIC REQUIRED IN ROCK
CUT AS DIRECTED BY ENGINEER
GRAVEL BACKFILL PLACED AND COMPACTED
IN 12" LAYERS (UNDER PVMNTS.)
EXCAVATED MATERIAL (UNDER PLANTING)
WARNING
TAPE
VA
R
IE
S
4" LOAM, FERTILIZE AND SEED WITH
GRASS AND MULCH
BITUMINOUS
CONCRETE
PAVEMENT
PROCESSED STONE
AGGREGATE BASE
OR
1' -6
" M
IN
STORM TRENCH
SCALE: NONE
TRENCH DRAIN
SCALE: NONE
UPGRADE EMERGENCY
632-16-101
GENERATORS
FULLY SPRINKLERED
BID DOCUMENTS
DETAILS
C-3.0
VARIES
(SEE SPECIFICATIONS)
PLAN VIEW (TOP SLAB)
ELEVATION
NOTES:
1. INLET SHALL BE 30"x30" CONCRETE AREA DRAIN, AS MANUFACTURED BY ARROW
CONCRETE, OR ENGINEER APPROVED EQUAL.
2. CONCRETE STRENGTH SHALL BE 4,000 PSI AT 28 DAYS.
3. REINFORCING STEEL - ASTM 615 AND A82 OR A185 SPECIFICATIONS.
4. H-20 DESIGN LOADING PER AASHTO HS-20-44.
5. BUTYL RUBBER JOINT SEALANT - ASTM C990-91.
6. HEIGHT OF DRAIN BOX SHALL BE 3' (MODEL #ADBKO3) UNLESS DEPTH OF INVERT PIPE
OUT REQUIRES THE USE OF 4' DRAIN BOX (MODEL #ADBKO4).
7. FRAME AND GRATE PAIR SHALL BE ONE OF THE FOLLOWING:
A. STANDARD BEEHIVE GRATE SHALL BE NEENAH INLET FRAME/BEEHIVE GRATE
R-2564 OR ENGINEER APPROVED EQUAL.
- SEE PLANS FOR SPECIFIC LOCATIONS OF TYPE SELECTED.
GRATE TO MATCH FRAME
RINGS AS REQUIRED
PRECAST CONCRETE TOP SLAB
PRECAST AREA DRAIN
AREA DRAIN
SCALE: NONE
CRUSHED STONE
KNOCK-OUT PER PIPE CONNECTION
REQUIREMENTS. SEE PLANS.
FRAME-SET IN FULL BED OF MORTAR
UNIT MASONRY OR GRADE
CURB RAMP
SCALE: NONE
CONCRETE SIDEWALK
SCALE: NONE
TRUNCATED DOME TACTILE - WARNING STRIP
SCALE: NONE
UPGRADE EMERGENCY
632-16-101
GENERATORS
FULLY SPRINKLERED
BID DOCUMENTS
DETAILS
C-3.1
X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X X
SCALE 1/4" = 1'-0"2
REFER TO DETAIL 5 ON THIS SHEET
BITUMINOUS ASPHALT
PAVING
ADDITIONAL REINFORCEMENT
AROUND STP MANWAYS SEE
DETAIL 4 ON THIS SHEET
NATIVE SOIL
FILTER FABRIC
DEADMAN ANCHOR STRAPS
AND TURNBUCKLES
SUPPLIED BY TANK MFR.
STEEL SHEETING
(IF REQ'D.)
X X X X X X X X X X X X
ANCHOR STRAP LOCATIONS PER
APPROVED MANUFACTURER
DRAWINGS
CONCRETE ANCHOR
PAD
DEPTH TO BE DETERMINED
ONCE TANK MANUFACTURER IS
SELECTED
TANK CROSS SECTION
42" MIN.
LU
Ø
XXXXXXXXXXXXXX XXXXXXXX
SEE DETAIL 4 ON THIS SHEET
FOR REINFORCEMENT AROUND
STP MANWAYS
2'-0"
MIN.
SELECT FILL PER MFR'S
SPECIFICATION (WASHED
PEA GRAVEL)
NATIVE SOIL
STEEL SHEETING
(IF REQ'D)
SCALE 1/4" = 1'-0"
TANK END SECTION1
2'-0"
MIN.
CONCRETE ANCHOR PAD
SEPARATION OF SELECT FILL
BETWEEN TANK AND CONCRETE
ANCHOR PAD PER
MANUFACTURERS
RECOMMENDATIONS
SEE NOTES
FILTER FABRIC WRAPS
UNDER SELECT FILL
SCALE 1/4" = 1'-0"3 CONCRETE ANCHOR PAD: REBAR PLAN
ANCHORING POINT MATERIAL,
LOCATIONS, AND
SPECIFICATIONS PER
MANUFACTURERS APPROVED
DRAWINGS AND SPECIFICATIONS
#6 REBAR SPACING MAX. 12"
O.C. EACH WAY, CONFIRM WITH
TANK SPECIFICATION
LENGTH VARIES
DEPENDENT ON SELECTED
TANK MANUFACTURER
W
ID
TH
V
AR
IE
S D
EP
EN
D
EN
T O
N
SE
LE
C
TE
D
T
AN
K M
AN
U
FA
C
TU
R
ER
TANK
OVERLAP MAT AND BARS
BY 12" MIN. ALL EDGES
8" C O
N C
. SLAB
#4 REBAR @ 1' CENTERS BOTH
WAYS FOR 2' AROUND MANWAY
IN UPPER 1/3 OF MAT
1/2 TO 1" CROWN FOR
ALL MANWAYS
6 X 6 6/6 WWM IN BOTTOM 13 OF
MAT. OVERLAP 1' MIN WITH REBAR
ABOVE
CONCRETE REINFORCEMENT
@ MANWAY DETAIL
SCALE: 1/2"=1'-0"4
PER MEP DRAWINGS
6"
8" FOR TANK MAT
12" STABILIZED SUBGRADE
COMPACTED TO 95% DENSITY
CONCRETE PAVEMENT AND
EXPANSION JOINT DETAIL
SCALE: 3/4"=1'-0"5
PROVIDE 1/2" X 6" DECK-O-FOAM® PEEL-AWAY TOP
EXPANSION JOINT SEALED WITH SIKAFLEX WHERE CONCRETE
SLAB MEETS CURBS, OR ANOTHER CONCRETE SLAB.
MAINTAIN A MAXIMUM DISTANCE OF 50'-0" OC BETWEEN
JOINTS
CONCRETE SLAB WITH FIBERMESH AND 6" X 6"
W2.9/W2.9 WWM (6/6 WIRE GAUGE) 4000 PSI F'C 28
DAYS
UPGRADE EMERGENCY
632-16-101
GENERATORS
FULLY SPRINKLERED
BID DOCUMENTS
DETAILS
C-3.2
NOTES:
1) HOLD DOWN STRAPS, TURNBUCKLES, WIRE ROPE,
DEADMAN ANCHORS AND ANCHOR POINT LOCATIONS ARE
TO BE PER MANUFACTURERS RECOMMENDATIONS AND
SPECIFICATIONS.
File details come from the government source that posted it. Updated .