S02 - Taylor Panel Breaker Survey.xlsx
XLSX spreadsheet 36 KB Posted
- Attached to
- J059--Triennial Electical Panel Maintenance and Survey Federal contract opportunity
- Solicitation number
- 36C25226Q0359
About this file
This is a survey spreadsheet documenting electrical panel breaker information for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12 (VISN 12). The file appears to be a data collection tool used to inventory and track the condition and specifications of electrical panels and breakers at VA facilities as part of the Triennial Electrical Panel Maintenance and Survey solicitation (36C25226Q0359).
The spreadsheet serves as a reference document for contractors responding to this maintenance and survey requirement, enabling them to understand the scope of electrical infrastructure that requires inspection and maintenance across VISN 12 locations. The survey data would inform contractors' proposals regarding the number, type, and condition of panels requiring service during the three-year contract period. This inventory information is critical for bidders to accurately price their services and develop realistic maintenance schedules for the triennial inspection and maintenance activities required under the solicitation.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1st
| BUILDING 11A: Taylor 1st floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | 1st | 12E1 | Normal | GECC | 1 | Unknown | None |
| 2 | 1st | 12E1 | Normal | Panel#1 Inside Pharmacy | Unknown | No panel directory | |
| 3 | 1st | 12E1 | Normal | Panel#2 Inside Pharmacy | Panel #1 | None | |
| 4 | 1st | 12E2 | Emergency | GEAA | 1 | GEO | Breakers on and not labeled: #21 |
| 5 | 1st | 12E2 | Emergency | GEA | GEO | None | |
| 6 | 1st | 12E2 | Normal | GA | 1 | SS4 - CB2B | Breakers on and not labeled: #15,23 |
| 7 | 1st | 12E4 | Normal | Unknown | 1 | Unknown | No panel directory |
| 8 | 1st | 1258 | Normal | GB | 1 | Unknown | No panel directory |
| 9 | 1st | 1258 | Normal | GB-1G | GB | None | |
| 10 | 1st | Inside Dialysis | Emergency | CR1 + CR2 | 1 | SS4 | Breakers on and not labeled: #70,72,74 |
| 11 | 1st | Inside Dialysis Next to 1265 | Normal | N1 | 1 | Unknown | No panel directory. Breakers on # 1 to 23,27,29 and 2 to 24 Breakers off and wired: #21,26 |
| 12 | 1st | 12E4 | Normal | Unknown | 1 | Unknown | Breakers off and labeled: #13,15,17 No panel directory |
| 13 | 1st | 12E3 | Normal | GKD3 | 1PD-A1 | None | |
| 14 | 1st | 12E3 | Normal | GKD | SS11 - CB26 | None | |
| 15 | 1st | 12E3 | Normal | GKD2 | 1 | SS4 - CB37 | Breakers on and not labeled: #(37,39,41) |
| 16 | 1st | 12E3 kitchen | Normal | GKD1 | 1 | SS4 - CB37 | Breakers on and nor labeled: #6 Breakers off and labeled: #2 |
| 10 |
2nd & 3rd
| BUILDING 11A: Taylor 2nd & 3rd floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | 2nd | 2281A | Normal | 1PD-A1 | 1 | SS4 - CB8 | Breakers off and labeled: # (1,3),11,13,15 (17,19),(21,23),25,27 |
| 2 | 2nd | 22E2 | Normal | 1A | SS4 - CB2B | None | |
| 3 | 2nd | 22E2 | Normal | 1A - 1G | 1 | 1A | Breakers on and not labeled: #11,14 |
| 4 | 2nd | 2281A | Normal | 1PD | 1 | SS11/CB27 | Breakers off and wired: (13,15,17), (19,21,23), (2,4,6), (20,22,24) |
| 5 | 2nd | 22E5 | Normal | 1DR | SS4/CB27 | None | |
| 6 | 2nd | 22E5 | Normal | 1DL | 1 | Unknown | Breakers off and wired: #34,36,38,40,42 Breakers on and not labeled: #25,27,29,31,32,33 |
| 7 | 2nd | 22E1 | Normal | 1C | 1 | Unknown | Breakers on and not labeled: #37 |
| 8 | 2nd | Hallway next to Rm 2257 | Normal | 1-1A | 1 | Unknown | Breakers on and not labeled: #1 |
| 9 | 2nd | Hallway next to Rm 2257 | Normal | 1-2A | 1-1A | None | |
| 10 | 2nd | 22E1 | Normal | 1C - 1G | 1C | None | |
| 11 | 2nd | Mech by men bathroom | Normal | 1DG | SS11/CB17 | None | |
| 12 | 2nd | Mech by men bathroom | Normal | 1G | 1 | 1DG | Breakers on: #13,15,19,23,(25,27), 20,26,28 No Panel Schedule |
| 13 | 3rd | 32E1 | Normal | 2C | 1 | Unknown | Breakers on and not labeled: #15 to 37 Breakers off and labeled: #25 |
| 14 | 3rd | 32E2 | Emergency | 2EA | GEO | None | |
| 15 | 3rd | 32E2 | Normal | 2A | SS4 - CB38 | None | |
| 16 | 3rd | 32E3 | Normal | 2B | 1 | Unknown | Breakers on and not labeled: #20 |
| 17 | 3rd | 32E5 | Normal | 2DL | 1 | 2F | Breakers off and labeled: #27,29,35,37,39,41 (32,34,36) |
| 18 | 3rd | 32E5 | Normal | 2DR | Unknown | None | |
| 19 | 3rd | 3229 | Normal | 2BA | 1 | Unknown | Breakers on and not labeled: #32, 34 |
| 11 |
4th & 5th
| BUILDING 11A: Taylor 4th & 5th floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | 4th | 42E4 | Normal | 3PD | SS4 - CB9 | None | |
| 2 | 4th | 42E4 | Normal | 3DL | 1 | Unknown | Breakers on and not labeled: #11,26,27,29 |
| 3 | 4th | 42E4 | Normal | 3DAR | 1 | 3PD | Breakers on and not labeled: #18, 35 |
| 4 | 4th | 42E4 | Normal | 3DR | 1 | Unknown | Breakers on and not labeled: #6 Breakers off and labeled: #2,4 |
| 5 | 4th | 42E4 | Normal | 3DAL | 1 | 3DP | Breakers on and not labeled: #13 to 23, 12,30,32 |
| 6 | 4th | 42E3 | Normal | 3B | 1 | Unknown | Breakers on and not labeled: #29,31,35,37,39,41,42 Missing panel mat |
| 7 | 4th | 42E1 | Normal | 3C | 1 | Unknown | Old Panel directory, needs new panel schedule |
| 8 | 4th | 42E2 | Normal | 3A | 1 | SS4 - CB38 | Breakers on and not labeled: #25,27 |
| 9 | 5th | 22E5 | Normal | 1DR | SS4/CB27 | None | |
| 10 | 5th | 52E1 | Normal | 4C | 1 | Unknown | Breakers on and not labeled: #29,31,33,35,37,30,32,34 |
| 11 | 5th | 52E3 | Normal | 4B | 1 | Unknown | Breakers on and not labeled: #2,4,8,12,14,16,20,22,24,26 (35,37) Breakers off and labeled: #25 |
| 12 | 5th | 52E3 | Normal | 4BA | 1 | 4B | No panel directory Breakers on and not labeled: #16,18,23,25,39,41 |
| 13 | 5th | 5242 | Normal | 4AA | 4A | None | |
| 14 | 5th | 5242 | Normal | 4A | SS4 - CB3B | None | |
| 15 | 5th | 5275 | Normal | 4D-1 | 1 | Unknown | Breakers off and labeled: #14,17,25 |
| 17 | 5th | 5278 | Normal | 4D-5 | 1 | Unknown | Breakers on and not labeled: #32,27,41 Breakers off and labeled: #30 |
| 18 | 5th | 5281 | Normal | 4D-2 | Unknown | None | |
| 19 | 5th | 5285 | Normal | 4D-3 | 1 | Unknown | Breakers off and labeled: #13,14 |
| 20 | 5th | 5285 | Normal | 4DR | 1 | Unknown | Breakers on and not labeled: # (21,23),(25,27)(29,31),(33,35) Breakers off and labeled: # (1,3),(5,7),(9,11),(13,15),(17,19) |
| 21 | 5th | 5285 | Normal | 4DL | 1 | Unknown | Breakers on and not labeled: #10,32,34,36 |
| 22 | 5th | 5293 | Normal | 4D-4 | 1 | Unknown | Breakers off and labeled: #14 |
| 23 | 5th | 52E4 | Normal | 4DD | 3PD | None | |
| 24 | 5th | Next to Rm 5278 | Distribution Panel | 4D | 0 | Unknown | None |
| 16 |
6th
| BUILDING 11A: Taylor 6th floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | 6th | 62E1 | Normal | 5C | 1 | Unknown | Breakers on and not labeled: #(39,41) |
| 2 | 6th | 62E2 | Normal | 5A | SS4-CB5A | None | |
| 3 | 6th | 62E2 | Emergency | 5EA | 1 | GED | Breakers on and not labeled: #5 |
| 4 | 6th | 62E3 | Normal | 5B | 1 | Unknown | Breakers on and not labeled: #1 to19 and 2 to 20, (34,36), 40 Breakers off and labeled: #23 to 33 |
| 5 | 6th | 62E4 | Normal | 5DL | Unknown | None | |
| 6 | 6th | 62E4 | Normal | 5DR | 1 | Unknown | Breakers on and not labeled: #25 |
| 7 | 6th | 62E4 | Normal | 5DAL | 5PD | None | |
| 8 | 6th | 62E4 | Normal | 5DAR | 1 | 5PD | Breakers on and not labeled: #1,3,5 |
| 9 | 6th | 62E4 | Distribution Panel | 5PD | SS11/CB9 | None | |
| 10 | 6th | Hallway next to Rm 6262 | Normal | 5CB | 1 | Unknown | Breakers on and not labeled: #25,27,29,31,33,26,28,30,32 ,34 |
| 11 | 6th | Hallway next to Rm 6222 | Normal | 5CC | Unknown | None | |
| 12 | 6th | Hallway next to Rm 6227 | Normal | 5CA | 1 | Unknown | Breakers on and not labeled: #(32,34) |
| 13 | 6th | Hallway next to Rm 6228 | Normal | 5AA | 1 | SS4 - CB5A | Breakers on and not labeled: #27 |
| 14 | 6th | Hallway next to Rm 6262 | Normal | 5CB | 1 | Unknown | Breakers on and not labeled: #25,27,29,31,33,35,37,39,41,42 |
| 15 | 6th | Hallway next to Rm 6247 | Normal | G-1 | 1 | Unknown | Breakers on and not labeled: #25,37,39,41,26,28,30,32 Breakers wired , off and no labeled: #(34,36), (27,29),(34,36) |
| 16 | 6th | Hallway next to Rm 6255 | Normal | 5BB | 1 | Unknown | Breakers on and not labeled: #27,29,(31,33),(30 32,34),36 Breakers off and labeled: #35 |
| 11 |
7th
| BUILDING 11A: Taylor 7th floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | 7th | 72E1 | Normal | 6C | 1 | Unknown | Breakers on and not labeled: #13,37 |
| 2 | 7th | 72E1 | Distribution Panel | 6DPC | Unknown | None | |
| 3 | 7th | 72E2 | Emergency | 6EA | GED | None | |
| 4 | 7th | 72E2 | Normal | 6A | 1 | Unknown | Breakers on and not labeled: #17, (37,30,41), (20,22,24) |
| 5 | 7th | 72E3 | Normal | 6BA | DPD | None | |
| 6 | 7th | 72E3 | Normal | 6B | 1 | Unknown | Breakers on and not labeled: #34 |
| 7 | 7th | 72 E4 | Normal | ED | 1 | DPD | Breakers on and not labeled: #1,3,5 |
| 8 | 7th | 72E5 | Normal | 6DR | 1 | Unknown | Breakers on and not labeled: #4,6 |
| 9 | 7th | 72E5 | Normal | 6DL | 1 | Unknown | Breakers on and not labeled: #1,2,20,22,24,(38,40,42) Breakers off and labeled: #14,16,18 |
| 10 | 7th | 72E5 | Normal | JD | 1 | DPD | Breakers off and labeled: #37,39 |
| 11 | 7th | Next to Rm 7214 | Normal | 6CD | 1 | 6DPC | Breakers on and not labeled: #6 |
| 12 | 7th | Next to Rm 7218 | Normal | 6CC | 6DPC | None | |
| 13 | 7th | 7298 | Normal | CD | 1 | DPD | Breakers on and not labeled: #10,1,3,5, 13,15,17,(14,16,18) |
| 14 | 7th | 72E1 | Normal | 6CB | 1 | 6DPC | Breakers on and not labeled: #32 |
| 15 | 7th | Across to Rm 7224 | Normal | 6CA | Unknown | None | |
| 16 | 7th | Hallway next to Rm 7237 | Normal | 6AA | SS4 - CB3B | None | |
| 17 | 7th | Hallway next to Rm 7237 | Normal | 6BB | 0 | Unknown | None |
| 10 |
Penthouse
| BUILDING 11A: Taylor Penthouse | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | Penthouse | North Area | Normal | A | 1 | DPD | Breakers on and not labeled: #23,25,27,(24,26),(18,20,22) Breakers off and labeled: #(33,35,37) |
| 2 | Penthouse | Entrance Area | Normal | P5 | 1 | Unknown | No Panel Directory |
| 3 | Penthouse | Elevator Room | Normal | 8PPHA | 1 | SS11 - CB3A | Breakers off and not labeled: #(37,39,41), (38,40,42) |
| 4 | Penthouse | Penthouse | Emergency | 7EA | 1 | GED | Breakers on and not labeled: #6,16 Breakers off and not labeled: #3 |
| 5 | Penthouse | Near Entrance | Normal | 7A | SS4 - CB6A | None | |
| 6 | Penthouse | Northwest | Normal | 11 -PA | Unknown | None | |
| 7 | Penthouse | Middle Area | Normal | DP-PHA | 1 | Unknown | No Panel Directory; Breakers marked |
| 5 |
File details come from the government source that posted it. Updated .