S02 - Ogden Panel Breaker Survey.xlsx

XLSX spreadsheet 28 KB Posted

Attached to
J059--Triennial Electical Panel Maintenance and Survey Federal contract opportunity
Solicitation number
36C25226Q0359
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12

About this file

This is an electrical panel breaker survey assessment document for Building 11B (Ogden) at a Department of Veterans Affairs facility under the Triennial Electrical Panel Maintenance and Survey contract (Solicitation 36C25226Q0359). The survey, dated January 25, 2025, catalogs electrical panels across multiple floors of the building, identifying deficiencies and maintenance needs.

The survey documents panel conditions across seven sections: the basement (3 items), 1st and 2nd floors (11 items), 3rd through 5th floors (11 items), 6th and 7th floors (11 items), and penthouse (6 items), totaling 42 electrical panels. Deficiencies identified include breakers that are on but not labeled, breakers that are off but labeled, missing panel directories, and one panel requiring a new schedule. The most common deficiency involves unlabeled breakers in the on position, appearing across multiple floors and rooms including basement panel B, first floor panels GF and SS4/CB27, and various panels on upper floors. Several emergency and normal distribution panels are documented with their associated circuit breaker information and feeding sources (primarily SS4 and CB series panels). The document serves as a baseline assessment for maintenance planning and compliance verification under the triennial survey requirement for VA facility electrical systems.

View the file

Other files for this federal contract opportunity

Other files attached to J059--Triennial Electical Panel Maintenance and Survey, newest first.
File Type Posted
36C25226Q0359 0004.docx DOCX document
S02 - Substations and Switchgears.xlsx XLSX spreadsheet
S02 - Ogden bldg.pdf PDF
S02 - Bed Tower One Line Diagram.pdf PDF
S02 - Bed Tower bldg.pdf PDF
S02 - Taylor bldg.pdf PDF
S02 - One Line Diagram - No Bedtower.pdf PDF
S02 - Damen bldg.pdf PDF
S02 - Atrium.pdf PDF
36C25226Q0359 0003.docx DOCX document
36C25226Q0359 0002.docx DOCX document
36C25226Q0359 0001.docx DOCX document
S02 - Damen 1-B Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - WD 2015-5017 R 32 D 3.30.26.pdf PDF
S02 - Taylor Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Damen 1-A Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Building 21-26-27 Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Electrical Units 3Y Maintenance Total number of brakers.xlsx XLSX spreadsheet
S02 - Damen 1-C Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - -Atrium Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - -Bed Tower Panel Breaker Survey r1.xlsx XLSX spreadsheet
S02 - Building Schedule.docx DOCX document
S02 - Temp Building Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Building 42 Panel Breaker Survey.xlsx XLSX spreadsheet
36C25226Q0359.docx DOCX document
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Basement

BUILDING 11B: Ogden Basement
1.2.25
ITEM#FLOORROOMPANEL TYPEPANEL NAME# PANELSFED FROMDEFICIENCY
1BasementB340NormalB1B1Breakers on and not labeled: #11,21,22,23
2BasementB340NormalB1SS4/CB21None
3BasementB340NormalBEES11/CB22None
4BasementB340EmergencyJP-ESubstation 42None
5BasementB340NormalJP-NBldg 11None
6BasementB344NormalHBESS4&11None
7BasementB350EmergencyN208ATS-21None
8BasementB350Emergency Distribution PanelCR-208ATS-21None
9BasementB350Emergency Distribution PanelCR-480ATS-21None
1

1st & 2nd

BUILDING 11B: Ogden 1st & 2nd floor
1.2.25
ITEM#FLOORROOMPANEL TYPEPANEL NAME# PANELSFED FROMDEFICIENCY
11st13E5EmergencyGEF1GEDBreakers off and labeled: #22,24,34
21st1355NormalGF11GFBreakers on and not labeled: #18,20
31st13E2Distribution PanelGPE-XRB-GPE-XRNone
41st13E1Distribution PanelGPEUnknownNone
51st13E5NormalGF1SS4/CB27Breakers on and not labeled: #32,34 Breakers off and labeled: #21,33
61st13E1NormalGE2GPENone
71st13E2EmergencyGE-XRGPE-XRNone
81st13E2EmergencyGEE1GEDBreakers on and not labeled: #1-8; 21-24
91st13E2NormalGE1GPENone
101st13E2NormalGESS4None
111st13E2NormalGECEGECDNone

3rd, 4th & 5th

BUILDING 11B: Ogden 3rd, 4th & 5th floor
1.2.25
ITEM#FLOORROOMPANEL TYPEPANEL NAME# PANELSFED FROMDEFICIENCY
13rd33E3Normal2FSS4/CB27None
23rd33E2Emergency2EF12FNo Panel Directory
33rd3375Normal2FA1SS4/CB29Breakers on and not labeled: #12
43rd33E1Normal2E1SS4/CB17Breakers on and not labeled: #15,17,19,21,23,25,27,29,31
54th43E3Normal3FA3FNone
64th43E1Normal3EL1SS4/CB28Breakers on and not labeled: #15, 17, 19, 28
74th43E1Normal3ER1SS4/CB28Breakers on and not labeled: #15, 20, 22, 31, 35, 33
84th43E3Normal3F1SS4/CB15Breaker on and not labeled: #1
95th53E2Normal4F1SS4/CB15Breakers on and not labeled: #8,10,12,13,18
105th53E1Emergency4EL1SS4/CB28Breaker on and not labeled: #19
115th53E1Normal4ER0SS4/CB28None

6th & 7th

BUILDING 11B: Ogden 6th & 7th floor
1.2.25
ITEM#FLOORROOMPANEL TYPEPANEL NAME# PANELFED FROMDEFICIENCY
16th63E1Normal5E1SS4/CB16Breakers on and not labeled: #19,21,23,24
26th63E2Normal5F1SS4/CB15Breaker on and not labeled: #30
37th73E2Normal6FSS4/CB15None
47th73E2Emergency6EF1UnknownNo panel directory
57thNext to Rm 7369NormalAF1DPFBreaker on and not labeled: #13
67thNext to Rm 7333NormalDPEASS4/CB23None
77thNext to Rm 7338NormalAEDPENone
87thNext to Rm 7325NormalDPESS4/CB22None
97thNext to Rm 7354NormalBEDPENone
107thNext to Rm 7372NormalBFDPFNone
117thNext to Rm 7372NormalCFDPFNone

Penthouse

BUILDING 11B: Ogden Penthouse
1.2.25
ITEM#FLOORROOMPANEL TYPEPANEL NAME# PANELSFED FROMDEFICIENCY
1PenthouseM300EmergencyPHEBEENone
2PenthouseM300Normal8PPHBSS11/CB8None
3PenthouseP350Normal7PPHB1SS11/CB8Needs new panel schedule
4PenthouseP350Normal7BDPENone
5PenthouseP300Normal11PB7PPHBNone
6PenthouseP300Normal7E6ENone
1