S02 - -Bed Tower Panel Breaker Survey r1.xlsx

XLSX spreadsheet 42 KB Posted

Attached to
J059--Triennial Electical Panel Maintenance and Survey Federal contract opportunity
Solicitation number
36C25226Q0359
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12

About this file

This is an electrical panel breaker survey document for Building 40's Bed Tower at a Department of Veterans Affairs facility, dated March 31, 2025. The survey catalogs electrical panels across eight floors (1st through 8th), documenting panel locations, types (Normal and Emergency), panel names, quantities, and identified deficiencies. The document provides a comprehensive inventory of 145 individual panel entries across multiple room locations (16E1, 16E2, SPD, 26E1-26E3, 36E1-36E9, 46E1-46E3, 56E1-56E3, 66E1-66E3, 76E1-76E3, and 8606-8608), detailing which main panels feed each sub-panel.

The survey identifies numerous deficiencies requiring corrective action, primarily involving breakers that are energized but not properly labeled (appearing on nearly every floor), several instances of breakers that are off but wired, missing panel directories on multiple floors, missing fillers in distribution panels, and one instance of a missing panel schedule. Critical deficiencies include: 1st floor panels with unlabeled breakers (#11, #20-22, #22-24, #33-35-37); 2nd floor panel lacking directory and multiple unlabeled breakers (#7, #14-16-18); 3rd floor panels with unlabeled breakers and one breaker off but labeled; 4th floor panels with unlabeled breakers and a panel missing schedule; 5th floor panel lacking directory and unlabeled breaker (#12); 6th floor unlabeled breaker (#24); 7th floor unlabeled breakers (#12, #19); and 8th floor panels requiring four fillers. This survey serves as the baseline documentation for the Department of Veterans Affairs' triennial electrical panel maintenance and survey solicitation (36C25226Q0359).

View the file

Other files for this federal contract opportunity

Other files attached to J059--Triennial Electical Panel Maintenance and Survey, newest first.
File Type Posted
36C25226Q0359 0004.docx DOCX document
S02 - Substations and Switchgears.xlsx XLSX spreadsheet
S02 - Ogden bldg.pdf PDF
S02 - Bed Tower One Line Diagram.pdf PDF
S02 - Bed Tower bldg.pdf PDF
S02 - Taylor bldg.pdf PDF
S02 - One Line Diagram - No Bedtower.pdf PDF
S02 - Damen bldg.pdf PDF
S02 - Atrium.pdf PDF
36C25226Q0359 0003.docx DOCX document
36C25226Q0359 0002.docx DOCX document
36C25226Q0359 0001.docx DOCX document
S02 - Ogden Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Damen 1-B Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Temp Building Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Building 42 Panel Breaker Survey.xlsx XLSX spreadsheet
36C25226Q0359.docx DOCX document
S02 - Electrical Units 3Y Maintenance Total number of brakers.xlsx XLSX spreadsheet
S02 - Damen 1-C Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - -Atrium Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Building Schedule.docx DOCX document
S02 - WD 2015-5017 R 32 D 3.30.26.pdf PDF
S02 - Taylor Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Damen 1-A Panel Breaker Survey.xlsx XLSX spreadsheet
S02 - Building 21-26-27 Panel Breaker Survey.xlsx XLSX spreadsheet
Show all 25

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1st BUILDING 40: Bed Tower 1st floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME# PanelsFED FROMDEFICIENCY
11st16E1NormalR1S-1-21P1S-3-2Breakers on and not labeled: #11
21st16E1EmergencyR1C-1-2A1P1C-3-1Breaker off and wired: #24
31st16E1NormalR1N-1-2A1P1N-3-2Breakers on and not labeled: #(20,22)
41st16E1EmergencyP4E-1-2A4E-1-2 S3N-3-2 S3G-3-1None
51st16E2EmergencyR1C-1-1AP1C-3-1None
61st16E2EmergencyL3C-1-1P3C-3-1None
71st16E2EmergencyL3S-1-1P3S-3-1None
81st16E2NormalR1N-1-1AP1N-3-1None
91st16 E2NormalRIN-1-1BP1N-3-1None
101st16E2NormalL3N-1-1P3N-3-1None
111stSPD/1635EmergencyP1E-1-31P4E-1-3Breakers on and not labeled: # 22,24
121stSPDEmergencyP4E-1-3P4E-3-2Needs (3) fillers
131stSPDEmergencyL3S-1-3P3S-3-3None
141stSPDEmergencyL3C-1-3P3C-3-3None
151stSPDEmergencyR1C-1-3A1P1C-3-3Breakers on and not labeled: # (33,35,37)
171stSPDNormalR1N-1-3AP1N-3-3None
181stSPDNormalR1N-1-3BP1N-3-3None
191stSPDNormalL3N-1-3P3N-3-3None
201stSPDNormalP3N-1-3P3N-3-3None
5

2nd BUILDING 40: Bed Tower 2nd floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME# PanelsFED FROMDEFICIENCY
12nd26E1EmergencyR1S-2-21P1S-3-2No Panel Directory
22nd26E1EmergencyR1C-2-2A1P1C-3-2Breakers on and not labeled: #7
32nd26E1NormalR1N-2-2A1P1N-3-2Breakers on and not labeled: #14,16,18
42nd26E1Emergency DistributionP3C-2-2ATS-2Normal feed S3N-3-2 36 E6 EM feed S3G-3-1 36 E3
52nd26E2EmergencyR1C-2-3AP1C-3-3None
62nd26E2EmergencyR1C-2-3BP1C-3-3None
72nd26E2EmergencyL3S-2-3P3S-3-3None
82nd26E2NormalR1N-2-3AP1N-3-3None
92nd26E2EmergencyL3C-2-3P3C-3-3None
102nd26E2NormalL3N-2-3P3N-3-3None
112nd26E2Emergency DistributionP3C-2-3ATS-12Normal feed S3N-3-2 36 E6 EM feed S3G-3-1 36 E3
122nd26E2EmergencyR1C-2-3AP1C-3-3None
132nd26E2EmergencyR1C-2-3BP1C-3-3None
142nd26E2EmergencyL3S-2-3P3S-3-3None
152nd26E2EmergencyL3C-2-3P3C-3-3None
172nd26E2NormalR1N-2-3AP1N-3-3None
182nd26E2NormalL3N-2-3P3N-3-3None
192nd26E2EmergencyP3C-2-3ATS-12Normal feed S3N-3-2 36 E6 EM feed S3G-3-1 36 E3
202nd26E3EmergencyR1C-2-1AP1C-3-1None
212nd26E3EmergencyL3C-2-1P3C-3-1None
222nd26E3EmergencyL3S-2-1P3S-3-1None
232nd26E3NormalR1N-2-1AP1N-3-1None
242nd26E3NormalR1N-2-1BP1N-3-1None
252nd26E3NormalL3N-2-1P3N-3-1None
3

3rd BUILDING 40: Bed Tower 3rd floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME# PANELSFED FROMDEFICIENCY
13rd36E1NormalL3N-3-10P3N-3-1None
23rd36E1NormalR1N-3-1P1N-3-1None
33rd36E1NormalP1N-3-1P3N-3-1None
43rd36E1NormalP3N-3-1S3N-3-1None
53rd36E2EmergencyP3C-3-11P3C-3-2Breakers on and not labeled: #(8,10,12)
63rd36E2EmergencyP3S-3-1P3S-3-2None
73rd36E2EmergencyL3S-3-1P3S-3-1None
83rd36E2EmergencyP1C-3-1P3C-3-1None
93rd36E3EmergencyP4E-3-2S3N-3-2 S3G-3-1None
103rd36E3EmergencyR1S-3-21P1S-3-2Breakers on and not labeled: #12,21 Breakers off and labeled: #34
113rd36E3EmergencyP1S-3-2P35-3-2None
123rd36E3EmergencyR1C-3-2P1C-3-2None
133rd36E3EmergencyP1C-3-2P3C-3-2None
143rd36E3EmergencyP3C-3-2S3N-3-1 S3G-3-1None
153rd36E4NormalP1N-3-2S3N-3-2None
173rd36E4NormalR1N-3-21P1N-3-2Breakers on and not labeled: #36
183rd36E7Emergency DistributionP1C-3-31P3C-3-3No Panel Directory
193rd36E7EmergencyP3C-3-3A3C-3-2ANormal feed S3N-3-1 EM feed S3G-3-1
203rd36E7EmergencyP3S-3-3P3S-3-2None
213rd36E7EmergencyL3S-3-3P3S-3-3None
223rd36E9NormalL3N-3-3P3N-3-3None
233rd36E9NormalR1N-3-3P1N-3-3None
243rd36E9NormalP3N-3-3S3N-3-1None
253rd36E9NormalP1N-3-30T41N-3-3None
4

4th BUILDING 40: Bed Tower 4th floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME# PanelsFED FROMDEFICIENCY
14th46E1EmergencyR1S-4-21P1S-3-2Breakers on and not labeled: #17
24th46E1EmergencyR1C-4-2AP1C-3-2None
34th46E1NormalR1N-4-2AP1N-3-2None
44th46E1NormalR1N-4-2BP1N-3-2None
54th46E2NormalL3N-4-3P3N-3-3None
64th46E2NormalR1N-4-3A1P1N-3-3Breakers on and not labeled: #42
74th46E2NormalR1N-4-3BP1N-3-3None
84th46E2EmergencyL3S-4-3P3S-3-3None
94th46E2EmergencyL3C-4-31P3C-3-3Breakers on and not labeled: #3,22
104th46E2EmergencyRIC-4-3AP1C-3-3None
114th46E2EmergencyRIC-4-3BP1C-3-3None
124th46E2EmergencyRIC-4-3C1P1C-3-3No Panel Schedule Breakers on: #1 to 15, 2,4,8,18,20,24,42
134th46E3EmergencyR1C-4-1CP1C-3-1None
144th46E3EmergencyR1C-4-1B1P1C-3-1Breakers on and not labeled: #34, 41
154th46E3EmergencyR1C-4-1AP1C-3-1None
164th46E3EmergencyL3C-4-1P3C-3-1None
174th46E3EmergencyL3S-4-1P3S-3-1None
184th46E3NormalRIN-4-1AP1N-3-1None
194th46E3NormalRIN-4-1BP1N-3-1None
204th46E3NormalL3N-4-1P3N-3-1None
5

5th BUILDING 40: Bed Tower 5th floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME# PanelsFED FROMDEFICIENCY
15th56E1EmergencyR1S-5-21P1S-3-2No panel directory
25th56E1EmergencyR1C-5-2AP1C-3-2Needs one filler
35th56E1NormalR1N-5-2AP1N-3-2None
45th56E1NormalR1N-5-2BP1N-3-2None
55th56E2NormalL3N-5-3P3N-3-3None
65th56E2NormalR1N-5-3AP1N-3-3None
75th56E2NormalR1N-5-3BP1N-3-3None
85th56E2NormalR1N-5-3CP1N-3-3None
95th56E2EmergencyL3S-5-3P3S-3-3None
105th56E2EmergencyL3C-5-3P3C-3-3None
115th56E2EmergencyRIC-5-3AP1C-3-3None
125th56E2EmergencyRIC-5-3B1P1C-3-3Breakers on and not labeled: #12
135th56E3EmergencyR1C-5-1BP1C-3-1None
145th56E3EmergencyR1C-5-1AP1C-3-1None
155th56E3EmergencyL3C-5-1P3C-3-1None
165th56E3EmergencyL3S-5-1P3S-3-1None
175th56E3NormalRIN-5-1AP1N-3-1None
185th56E3NormalRIN-5-1BP1N-3-1None
195th56E3NormalL3N-5-1P3N-3-1None
2

6th BUILDING 40: Bed Tower 6th floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME# PanelsFED FROMDEFICIENCY
16th66E1EmergencyR1S-6-2P1S-3-2None
26th66E1R1C-6-2A2P1C-3-2Breaker on and not Labeled # 24
36th66E1NormalR1N-6-2AP1N-3-2None
46th66E1NormalR1N-6-2BP1N-3-2None
56th66E2NormalL3N-6-3P3N-3-3None
66th66E2NormalR1N-6-3AP1N-3-3None
76th66E2NormalR1N-6-3BP1N-3-3None
86th66E2NormalR1N-6-3CP1N-3-3None
96th66E2EmergencyL3S-6-3P3S-3-3None
106th66E2EmergencyL3C-6-3P3C-3-3None
116th66E2EmergencyRIC-6-3AP1C-3-3None
126th66E2EmergencyRIC-6-3BP1C-3-3None
136th66E3EmergencyR1C-6-1AP1C-3-1None
146th66E3EmergencyR1C-6-1BP1C-3-1None
156th66E3EmergencyL3C-6-1P3C-3-1None
166th66E3EmergencyL3S-6-1P3S-3-1None
176th66E3NormalRIN-6-1AP1N-3-1None
186th66E3NormalRIN-6-1BP1N-3-1None
196th66E3NormalL3N-6-1P3N-3-1None
2

7th BUILDING 40: Bed Tower 7th floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME3 PanelsFED FROMDEFICIENCY
17th76E1EmergencyR1S-7-21P1S-3-2Breakers on and not Labeled # 12
27th76E1EmergencyR1C-7-2AP1C-3-2None
37th76E1NormalR1N-7-2AP1N-3-2None
47th76E2NormalL3N-7-3P3N-3-3None
57th76E2NormalR1N-7-3AP1N-3-3None
67th76E2EmergencyL3S-7-31P3S-3-3Breakers on and not Labeled # 19
77th76E2EmergencyL3C-7-3P3C-3-3None
87th76E2EmergencyR1C-7-3APIC-3-3None
97th76E3EmergencyR1C-7-1AP1C-3-1None
107th76E3EmergencyL3C-7-1P3C-3-1None
117th76E3EmergencyL3S-7-1P3S-3-1None
127th76E3NormalR1N-7-1AP1N-3-3None
137th76E3NormalL3N-7-1P3N-3-1None
2

8th BUILDING 40: Bed Tower 8th floor 3/31/2025

ITEM#FLOORROOMPANEL TYPEPANEL NAME# PanelsFED FROMDEFICIENCY
18th8606EmergencyP4E-P-20A4E-P-2 S3N-P-1 S3G-3-1None
28th8606MCCM4N-P-1None
38th8606MCCM4E-P-1None
58th8608Emergency DistributionP4E-P-1A4E-P-2 S3N-P-1 S3G-3-1None
68th8608NormalL3N-P-2P3N-3-1Needs four fillers
78th8608NormalR1N-P-2P1N-3-2None
0