S02 - Damen 1-A Panel Breaker Survey.xlsx
XLSX spreadsheet 36 KB Posted
- Attached to
- J059--Triennial Electical Panel Maintenance and Survey Federal contract opportunity
- Solicitation number
- 36C25226Q0359
About this file
This is an electrical panel breaker survey document for Building 1-A (Damen) at a Department of Veterans Affairs facility, dated January 2, 2025. The survey comprehensively catalogs circuit breaker panels across ten floors, documenting panel locations, types (normal, emergency, or distribution), panel names, number of breakers, and associated deficiencies requiring remediation. The survey identifies specific deficiencies including unlabeled breakers that are energized, missing filler plates, and discrepancies between breaker status and labeling across multiple rooms and floors. Deficiencies are concentrated in panels designated as GK, GB, GV, GBA, GBB, GECM-2, DGV, EGV, and various numbered panels (CB panels), with the most significant issues noted in emergency and normal panels on the 1st, 3rd, 4th, and 5th floors.
The document appears to support the triennial electrical panel maintenance and survey solicitation (36C25226Q0359) issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12. The survey results provide detailed baseline data for identifying required corrective actions, including breaker labeling, installation of filler plates, and verification of panel operation status. This survey documentation would be essential for contractors responding to the maintenance solicitation to understand the scope of work required across the facility's electrical infrastructure and to develop accurate proposals for bringing all panels into compliance with federal safety standards.
View the file
Other files for this federal contract opportunity
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1st
| BUILDING 1-A: Damen 1st Floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # E Panels | FED FROM | DEFICIENCY |
| 1 | 1st | 1508 | Normal | GK1 | 1 | GK | Breakers on and no labeled: #30 |
| 2 | 1st | Polk Dock | Normal | GK | 1 | SS2/CB#14 | Breakers on and no labeled: #7,9,(8,10),12,14 |
| 3 | 1st | 15E2 | Normal | GB | 1 | SS2/CB12 | Breakers on and no labeled: #6,34,36,38 |
| 4 | 1st | 15E4 | Emergency | EGB | EDGV | None | |
| 5 | 1st | 15E4 | Normal | CV1 SEC1 | CDGV | Needs (5) fillers | |
| 6 | 1st | 15E4 | Normal | CV1 SEC2 | CDGV | Needs (1) filler | |
| 7 | 1st | 15E4 | Normal | GL1 | SS2 1573 F6B | None | |
| 8 | 1st | 15E4 | Normal | GV2 | 1 | SS2 1573 DGV | Breakers on and no labeled: #14,16, 18, 19,20,22 |
| 9 | 1st | 1555 | Normal | No Name | GECM-2 | None | |
| 10 | 1st | 1555 | Normal | GBB | DGV | None | |
| 11 | 1st | 1576 | Normal | GBA | DGV | None | |
| 12 | 1st | 15E3 | Distribution Emergency | EDGV | SS2-CB19 | None | |
| 13 | 1st | 15E3 | Normal | GV1 | 1 | SS2-CB29 | Breakers on and no labeled: #2,4,6,8,10,12 |
| 14 | 1st | 15E3 | Emergency | EGV | 1 | EDGV | Breakers on and no labeled: #25,27,29,31,33,30,34,36,38 |
| 15 | 1st | 15E3 | Emergency | SPS TRAILER | 1 | EDGV | Breakers on and no labeled: #12 |
| 16 | 1st | 15E3 | Normal | DGV | SS2-CB29 | None | |
| 7 |
2nd & 3rd
| BUILDING 1-A: Damen 2nd & 3rd Floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # E Panels | FED FROM | DEFICIENCY |
| 1 | 2nd | 25E2 | Normal | 1BL | D1B | None | |
| 2 | 2nd | 25E1 | Normal | 1BR | SS-2 CBF-12-D | None | |
| 3 | 2nd | Next to 25E1 | Emergency | C1B | 1 | CDGV | Breakers on and no labeled: #3,6 |
| 4 | 2nd | 25E3 | Normal | 1L1 | L1 | None | |
| 5 | 2nd | 25E2 | Normal | D1B5 | 1 | SS2 CB21-D1B | Breakers on and no labeled: #7,9,20,24 |
| 6 | 2nd | 25E2 | Distribution Normal | DIB | SS2 CB21 | None | |
| 7 | 3rd | 3560A | Normal | CB41 | 1 | SS2 | Breakers on and no labeled: #1,3,5,29,24 |
| 8 | 3rd | 3560A | Normal | CB42 | 1 | SS2 | Breakers on and no labeled: #(21,23), 25,(16,18) Needs (1) Filler |
| 9 | 3rd | 3547 | Normal | 2L1 | 1 | SS2 - CB#6 | Breakers on and no labeled: #12,19,21 |
| 10 | 3rd | Next to Stair #3 | Emergency | C2B | 1 | CDGV | Breakers on and no labeled: #5,9,11,15,17,23,25,31,33,35,37 39 41,8,10,16,18,20,24,26,28,32,34,36,38,40,42 |
| 11 | 3rd | 35E1 | Normal | 2BR | 1 | SS2 - CBF-12-D | Breakers on and no labeled: #10 |
| 12 | 3rd | 35E1 | Normal | D1B3 | 1 | D1B | Breakers on and no labeled: #12 |
| 8 |
4th
| BUILDING 1-A: Damen 4th Floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # E Panels | FED FROM | DEFICIENCY |
| 1 | 4th | 45E2 | Normal | D3B1 | 1 | D3B | Breaker on and not labeled: #16 |
| 2 | 4th | 45E2 | Emergency | E3B | 1 | EDGV 13-15-17 | Breaker on and not labeled: #4,16 |
| 3 | 4th | 45E2 | Normal | H3B1 | HDGV72 | None | |
| 4 | 4th | 45E2 | Normal | B305 | 1 | SS2/CB44 | Breakers on and not labeled: #33 Breakers off and labeled:#21,18,40 |
| 5 | 4th | 45E2 | Normal | C3L2 | 1 | C3L | Breakers off and labels: #40,42 Breakers off and labeled:#5,2,4,6,26,28,30 |
| 6 | 4th | 45E2 | Distribution Normal | D3B | SS2 CB22 | None | |
| 7 | 4th | Hallway Next Rm #4588 | Normal | D3B4 | 1 | D3B | Breakers off and labeled: #1,3,11,13,12,14,16,20,30 Needs (4) fillers |
| 8 | 4th | 4549 LAB | Normal | D3B3 | D3B | Construction Area | |
| 9 | 4th | 4549 LAB | Normal | D3B5 | D3B | Construction Area | |
| 10 | 4th | 4549 LAB | Emergency | C3L | 1 | SS2 CB20 | Breakers off and labeled:#35,37,39,34,36 Breakers on and not labeled: #(21,23),32 |
| 11 | 4th | 4549 LAB | Normal | EPP | 1 | CLP - 4 - 1 | Breakers on and not labeled: #22,24,26 |
| 12 | 4th | 4544 | Normal | D3B6 | D3B | Construction Area | |
| 13 | 4th | No RM # In Construction Area | Normal | 3DN | SS2 CB30 | None | |
| 14 | 4th | No RM # In Construction Area | Normal | C3D | CDGV | None | |
| 15 | 4th | 45E1 | Normal | 3BR | 1 | SS2 - F-12-B | Breakers on and not labeled: #29 |
| 16 | 4th | Next to Rm 45E1 | Emergency | C3B | 1 | CDGV | Breakers on and not labeled: #17,19,21,23,31,33,37,39,41,16 18,20,22,24,32,34,36,38 |
| 9 |
5th & 6th
| BUILDING 1-A: Damen 5th & 6th Floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | 5th | 55E2 | Normal | C5B2 | 1 | CD5 | Breakers on and not labeled: #(32,34),(36,38),(40,42) |
| 2 | 5th | 55E2 | Normal | RP-5-2 | 1 | MCC-5L | Breakers on and not labeled: #17,30 |
| 3 | 5th | 55E1 | Normal | 4B | SS-2 F-12-B | None | |
| 4 | 5th | 55E3 | Normal | CD5 | 1 | SS2 - F5B | Breakers on and not labeled: #(10,12),(1,3,5),(7,9,11) |
| 5 | 5th | 55E3 | Emergency | LS | Unknown | None | |
| 6 | 5th | 55E3 | Normal | RP-5-1 | MCC-5L | None | |
| 7 | 5th | 55E3 | Normal | LP-5-1 | 1 | MCC-5L | Breaker on and not labeled: #17 |
| 8 | 5th | 55E3 | Normal | C5B1 | 1 | CD5 | Breakers on and not labeled: #35,37 |
| 9 | 6th | 65E1 | Normal | 5B | 1 | SS-2 F-12-B | Breakers on and not labeled: #20,22,41,42 |
| 10 | 6th | 65E1 | Emergency | E5B | 1 | EDGV | Breaker off and labeled: #17 Breaker on and not labeled: #19 |
| 11 | 6th | Next to Rm 65E1 | Emergency | C5B | 1 | CDGV | Breaker on and not labeled: #17 |
| 12 | 6th | Next to Rm 65E1 | Normal | 5BN | SS2 - CB#5 | None | |
| 8 |
7th & 8th
| BUILDING 1-A: Damen 7th & 8th Floor | |||||||
| 1.2.25 | |||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | # PANELS | FED FROM | DEFICIENCY |
| 1 | 7th | Across From Rm 7554 | Normal | 6B2 | Unknown | None | |
| 2 | 7th | Across From Rm 7554 | Normal | 6B | SS-2 F-12-A | None | |
| 3 | 7th | Across From Rm 7554 | Emergency | C6B | 1 | CDGV | Breaker on and not labeled: #17 |
| 4 | 7th | Across From Rm 7554 | Normal | 6BN | SS2 CB5 | None | |
| 5 | 8th | 8551 | Normal | 7B | SS-2 F-12-A | None | |
| 6 | 8th | Next to Rm 8551 | Normal | C7B | CDGV | None | |
| 7 | 8th | Next to Rm 8551 | Normal | 7BN | SS2 CB5 | None | |
| 1 |
9th & 10th
| BUILDING 1-A: Damen 9th & 10th Floor | |||||||
| # PANELS | 1.2.25 | ||||||
| ITEM# | FLOOR | ROOM | PANEL TYPE | PANEL NAME | FED FROM | DEFICIENCY | |
| 1 | 9th | 95E1 | Normal | 8B | SS-2 F-12-A | None | |
| 2 | 9th | Next to 95E1 | Emergency | C8B | CDGV | None | |
| 3 | 9th | Next to 95E1 | Normal | 8BN | SS2 CB5 | None | |
| 4 | 10th | 10520 | Normal | 9B | 1 | SS-2 F-12-A | Breakers on and not labeled: #26,28 |
| 1 |