S02 - SOW Attachment 1 Scope Table 554-24-106.pdf
PDF 486 KB Posted
- Attached to
- Z2DA--554-24-106 Correct Electrical Deficiencies Federal contract opportunity
- Solicitation number
- 36C25924R0099
About this file
This document is a Statement of Work (SOW) for a federal contract opportunity to correct electrical deficiencies at the Rocky Mountain Regional Veterans Affairs Medical Center (RMR VAMC) in Aurora, Colorado.
The SOW details the requirement to replace various substation components, including 9 breaker units, 5 power quality meters, and 3 power relays that have reached the end of their service life. The work also includes integrating a new surge detection system to monitor and record surge trips across 31 existing switchgears in the substations. The contractor will be required to provide new components as drop-in replacements or equal/better substitutes, as well as rebuild 8 of the existing breakers. All work must be performed by qualified personnel using proper safety protocols and coordinated with the VA to minimize disruption to facility operations. Contractor qualifications, documentation, and scheduling requirements are specified. The period of performance is 300 days from notice to proceed.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25924R0099 0003.docx | DOCX document | |
| S06 - REVISED Scope Table 554-24-106 - REATTACHED.pdf | ||
| 36C25924R0099 0002.docx | DOCX document | |
| S05 - Additional RFI ANSWER 554-24-106 Correct Electrical Deficiencies.pdf | ||
| S06 - REVISED Scope Table 554-24-106.pdf | ||
| S05 - RFI ANSWERS 554-24-106 Correct Electrical Deficiencies.pdf | ||
| 36C25924R0099 0001.docx | DOCX document | |
| S04 - Site Visit Attendance.pdf | ||
| S02 - SOW Attachment 3 Specifications 554-24-106.pdf | ||
| S22- 852.219-75 LOS Certificate - GC.docx | DOCX document | |
| 36C25924R0099_1.docx | DOCX document | |
| S02 - SOW Attachment 2 Deficiency reports 554-24-106.pdf | ||
| S02 - Past Performance Questionnaire.docx | DOCX document | |
| S02 - SOW Attachment 4 DRAFT ICRA - PCRA Electrical Closet Substations.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOW ATTACHMENT 1
VAECHCS
SCOPE TABLE
PROJECT #
554-24-106
CORRECT ELECTRICAL DEFICIENCIES
Summary Required work on unit Base Bid Option Quantity Summary Required work on unit Base Bid Option Quantity
Breaker Replace Base Bid NA 9 Other Base Bid: New nameplate Base Bid NA 1
PQM Replace Base Bid NA 5 Other Program BACNET CNX NA Option 1 31 Multilin Replace Base Bid NA 3 Other Rebuild GE Breakers NA Option 2 8
CED
Scope # Building Location
Equipment Designation Anomaly TYPE TYPE (detail) Voltage
Amps (max rated)
Amps (max operating) Required work on unit
ED01 Building A 10-NDCP Breaker: 7-SWBD-10
MDP
Elevated contact resistance and dev. Breaker
Eaton Digitrip 520 LV Breaker 277/480 1600 1600
Base Bid: Replace with new Return old breaker to VA
ED02 Building B 02-EMDCP Breaker: SPARE Captive washer missing Breaker GE Micro Entelliguard WPX- 08 277/480 800 600
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED03 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-LS1 Alarm on ATS PQM PQM II - GE ZBTSD0B00060F 480 Base Bid: Replace
ED04 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-EQ7 Name plate sticker missing ATS GE ATS 480 800
Base Bid: Get new nameplate from manufacturer - install nameplate on existing ATS
ED05 Building E 09-NDCP Breaker: 09-ATS-LS1 Missing rivets in cell shutter. Breaker
GE Micro Entelliguard WPX- 08 277/480 150 100
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED06 Building G 08-EMDCP Breaker: 08-ATS-CR2 Mechanical problem see notes Breaker
GE Micro Entelliguard WPX- 08 277/480 800 800
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED07 Building G 08-EMDCP Breaker: 08-ATS-
EQ1
Operational Failure see notes Breaker
GE Micro Entelliguard WPX- 08 277/480 800 500
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED08 Building G 08-EMDCP DIST BREAKER S1 Meter is not operational Multilin GE Multilin 350 480 Base Bid: Replace
ED09 Building K Building 5-K-Inpatient North ATS: 05-ATS-CR1 Mechanical problem see notes PQM PQM II - GE ZBTSD0B00080F 480 Base Bid: Replace
ED10 Building K Building 5-K-Inpatient North ATS: 05-ATS-EQ2 Mechanical problem see notes PQM PQM II - GE ZBTSD0B00120F 480 Base Bid: Replace
ED11 PSN
Building 11-PE-Staff Parking North ATS: 11-ATS-EQ1 Mechanical link bent PQM PQM II - GE ZBTSD0B00040F 480 Base Bid: Replace
ED12 PSN 11-EMDCP PQM: 11-ATS-LS1
Voltage inputs not wired correctly PQM PQM II - GE T20-C-A 480 Base Bid: Replace
ED13
Building L - NORMAL 06-NDCP1 Breaker: SPARE Damaged breaker stabs Breaker
GE Micro Entelliguard WPF- 08 277/480 800 800
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED14
Building L -
NORMAL 06-NDCP2
Breaker: PANEL 06- NHDP11 Trip unit display damaged Breaker
GE Micro Entelliguard WPF- 08 277/480 400 200
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED15 NA – No work NA – No work
ED16
Building L - NORMAL 06-NDCP2 Relay: DIST BKR-S1 Relay not operational Multilin GE Multilin 350 480 Base Bid: Replace
ED17
Building L - NORMAL 06-NDCP1 Relay - Dist Breaker Relay not operational Multilin GE Multilin 350 480 Base Bid: Replace
ED18
Building L - EMERGENCY 06-EMDCP2 Breaker: MAIN
Mechanical problem see notes Breaker
GE Micro Entelliguard WPX- 32 277/480 3200 3000
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED19
Building L -
EMERGENCY 06-EMDCP4
Breaker: 06-ATS-
CH4
Breaker Fails LT,ST,INST,GF P/U Breaker
GE Micro Entelliguard WPF- 16 277/480 1600 1000
Base Bid: Replace with new Option 2: Rebuild old Breaker
ED20
ALL
SUBSTATIONS
ALL SUBSTATION
SWITCHGEAR - DETECT
SURGE TRIPS
All existing Switchgear -both sides Surge Trip capture
Switchgear trip sensor
QTY 65 Switchgear ea side -total of 31 sensors to connect to BACNET Multiple
Option 1:
PROGRAM BACNET CONNECTION