S02 - SOW Attachment 1 Scope Table 554-24-106.pdf

PDF 486 KB Posted

Attached to
Z2DA--554-24-106 Correct Electrical Deficiencies Federal contract opportunity
Solicitation number
36C25924R0099
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This document is a Statement of Work (SOW) for a federal contract opportunity to correct electrical deficiencies at the Rocky Mountain Regional Veterans Affairs Medical Center (RMR VAMC) in Aurora, Colorado.

The SOW details the requirement to replace various substation components, including 9 breaker units, 5 power quality meters, and 3 power relays that have reached the end of their service life. The work also includes integrating a new surge detection system to monitor and record surge trips across 31 existing switchgears in the substations. The contractor will be required to provide new components as drop-in replacements or equal/better substitutes, as well as rebuild 8 of the existing breakers. All work must be performed by qualified personnel using proper safety protocols and coordinated with the VA to minimize disruption to facility operations. Contractor qualifications, documentation, and scheduling requirements are specified. The period of performance is 300 days from notice to proceed.

View the file

Other files for this federal contract opportunity

Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOW ATTACHMENT 1

VAECHCS

SCOPE TABLE

PROJECT #

554-24-106

CORRECT ELECTRICAL DEFICIENCIES

Summary Required work on unit Base Bid Option Quantity Summary Required work on unit Base Bid Option Quantity

Breaker Replace Base Bid NA 9 Other Base Bid: New nameplate Base Bid NA 1

PQM Replace Base Bid NA 5 Other Program BACNET CNX NA Option 1 31 Multilin Replace Base Bid NA 3 Other Rebuild GE Breakers NA Option 2 8

CED

Scope # Building Location

Equipment Designation Anomaly TYPE TYPE (detail) Voltage

Amps (max rated)

Amps (max operating) Required work on unit

ED01 Building A 10-NDCP Breaker: 7-SWBD-10

MDP

Elevated contact resistance and dev. Breaker

Eaton Digitrip 520 LV Breaker 277/480 1600 1600

Base Bid: Replace with new Return old breaker to VA

ED02 Building B 02-EMDCP Breaker: SPARE Captive washer missing Breaker GE Micro Entelliguard WPX- 08 277/480 800 600

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED03 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-LS1 Alarm on ATS PQM PQM II - GE ZBTSD0B00060F 480 Base Bid: Replace

ED04 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-EQ7 Name plate sticker missing ATS GE ATS 480 800

Base Bid: Get new nameplate from manufacturer - install nameplate on existing ATS

ED05 Building E 09-NDCP Breaker: 09-ATS-LS1 Missing rivets in cell shutter. Breaker

GE Micro Entelliguard WPX- 08 277/480 150 100

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED06 Building G 08-EMDCP Breaker: 08-ATS-CR2 Mechanical problem see notes Breaker

GE Micro Entelliguard WPX- 08 277/480 800 800

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED07 Building G 08-EMDCP Breaker: 08-ATS-

EQ1

Operational Failure see notes Breaker

GE Micro Entelliguard WPX- 08 277/480 800 500

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED08 Building G 08-EMDCP DIST BREAKER S1 Meter is not operational Multilin GE Multilin 350 480 Base Bid: Replace

ED09 Building K Building 5-K-Inpatient North ATS: 05-ATS-CR1 Mechanical problem see notes PQM PQM II - GE ZBTSD0B00080F 480 Base Bid: Replace

ED10 Building K Building 5-K-Inpatient North ATS: 05-ATS-EQ2 Mechanical problem see notes PQM PQM II - GE ZBTSD0B00120F 480 Base Bid: Replace

ED11 PSN

Building 11-PE-Staff Parking North ATS: 11-ATS-EQ1 Mechanical link bent PQM PQM II - GE ZBTSD0B00040F 480 Base Bid: Replace

ED12 PSN 11-EMDCP PQM: 11-ATS-LS1

Voltage inputs not wired correctly PQM PQM II - GE T20-C-A 480 Base Bid: Replace

ED13

Building L - NORMAL 06-NDCP1 Breaker: SPARE Damaged breaker stabs Breaker

GE Micro Entelliguard WPF- 08 277/480 800 800

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED14

Building L -

NORMAL 06-NDCP2

Breaker: PANEL 06- NHDP11 Trip unit display damaged Breaker

GE Micro Entelliguard WPF- 08 277/480 400 200

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED15 NA – No work NA – No work

ED16

Building L - NORMAL 06-NDCP2 Relay: DIST BKR-S1 Relay not operational Multilin GE Multilin 350 480 Base Bid: Replace

ED17

Building L - NORMAL 06-NDCP1 Relay - Dist Breaker Relay not operational Multilin GE Multilin 350 480 Base Bid: Replace

ED18

Building L - EMERGENCY 06-EMDCP2 Breaker: MAIN

Mechanical problem see notes Breaker

GE Micro Entelliguard WPX- 32 277/480 3200 3000

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED19

Building L -

EMERGENCY 06-EMDCP4

Breaker: 06-ATS-

CH4

Breaker Fails LT,ST,INST,GF P/U Breaker

GE Micro Entelliguard WPF- 16 277/480 1600 1000

Base Bid: Replace with new Option 2: Rebuild old Breaker

ED20

ALL

SUBSTATIONS

ALL SUBSTATION

SWITCHGEAR - DETECT

SURGE TRIPS

All existing Switchgear -both sides Surge Trip capture

Switchgear trip sensor

QTY 65 Switchgear ea side -total of 31 sensors to connect to BACNET Multiple

Option 1:

PROGRAM BACNET CONNECTION

File details come from the government source that posted it. Updated .