S06 - REVISED Scope Table 554-24-106 - REATTACHED.pdf

PDF 528 KB Posted

Attached to
Z2DA--554-24-106 Correct Electrical Deficiencies Federal contract opportunity
Solicitation number
36C25924R0099
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19

About this file

This document is a Solicitation for a federal contract opportunity from the Department of Veterans Affairs to correct electrical deficiencies at the Rocky Mountain Regional Veterans Affairs Medical Center. The key details are:

The scope of work requires replacing substation components including 9 breakers, 5 power quality meters, and 3 power relays. It also requires installing surge detection and monitoring equipment to capture and record surge events on the 31 switchgear units throughout the substations. The contractor must provide all materials, labor, and expertise to complete the work. Strict safety, security, and infection control requirements apply. The period of performance is 300 days from notice to proceed. Prospective contractors are encouraged to attend a pre-bid site visit. Bids are due by the RFI deadline, with award to follow. Pricing terms allow up to 10% markup on materials and components.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--554-24-106 Correct Electrical Deficiencies, newest first.
File Type Posted
36C25924R0099 0003.docx DOCX document
S05 - Additional RFI ANSWER 554-24-106 Correct Electrical Deficiencies.pdf PDF
36C25924R0099 0002.docx DOCX document
S04 - Site Visit Attendance.pdf PDF
S06 - REVISED Scope Table 554-24-106.pdf PDF
S05 - RFI ANSWERS 554-24-106 Correct Electrical Deficiencies.pdf PDF
36C25924R0099 0001.docx DOCX document
S02 - Past Performance Questionnaire.docx DOCX document
S02 - SOW Attachment 4 DRAFT ICRA - PCRA Electrical Closet Substations.pdf PDF
S22- 852.219-75 LOS Certificate - GC.docx DOCX document
36C25924R0099_1.docx DOCX document
S02 - SOW Attachment 3 Specifications 554-24-106.pdf PDF
S02 - SOW Attachment 2 Deficiency reports 554-24-106.pdf PDF
S02 - SOW Attachment 1 Scope Table 554-24-106.pdf PDF
Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SOW ATTACHMENT 1

VAECHCS

SCOPE TABLE

PROJECT #

554-24-106

CORRECT ELECTRICAL DEFICIENCIES

Summary Required work on unit Quantity Summary Required work on unit Quantity

Breaker Replace 9 Other Base Bid: New nameplate 1

PQM Replace 9 Other Program BACNET CNX 31 Multilin Replace 3 Other Rebuild GE Breakers 11

Scope # Building Location CED Equipment Designation

Anomaly TYPE TYPE (detail) Voltage Amps (max rated)

Amps (max operating)

Required work on unit

ED01 Building A 10-NDCP Breaker: 7-SWBD-10

MDP

Elevated contact resistance and dev.

Breaker Eaton Digitrip 520 LV Breaker

277/480 1600 1600 Replace with new breaker Return old breaker to VA DO NOT

REBUILD EATON BREAKER

ED02 Building B 02-EMDCP Breaker: SPARE Captive washer missing Breaker GE Micro Entelliguard WPX-

277/480 800 600 Replace with new breaker Rebuild old Breaker

ED03 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-LS1 Alarm on ATS PQM PQM II - GE ZBTSD0B00060F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT

ED04 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-EQ7 Name plate sticker missing ATS GE ATS 480 800 Get new nameplate from manufacturer - install nameplate on existing ATS

ED05 Building E 09-NDCP Breaker: 09-ATS-LS1 Missing rivets in cell shutter.

Breaker GE Micro Entelliguard WPX-

277/480 150 100 Replace with new breaker Rebuild old Breaker

ED06 Building G 08-EMDCP Breaker: 08-ATS-CR2 Mechanical problem see notes

Breaker GE Micro Entelliguard WPX-

277/480 800 800 Replace with new breaker Rebuild old Breaker

ED07 Building G 08-EMDCP Breaker: 08-ATS-

EQ1

Operational Failure see notes

Breaker GE Micro Entelliguard WPX-

277/480 800 500 Replace with new breaker Rebuild old Breaker

ED08 Building G 08-EMDCP DIST BREAKER S1 Meter is not operational Multilin GE Multilin 350 480 Replace with new Multilin Return Existing Multilin to GOVT

ED09 Building K Building 5-K-Inpatient North ATS: 05-ATS-CR1 Mechanical problem see notes

PQM PQM II - GE ZBTSD0B00080F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT

ED10 Building K Building 5-K-Inpatient North ATS: 05-ATS-EQ2 Mechanical problem see notes

PQM PQM II - GE ZBTSD0B00120F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT

ED11 PSN Building 11-PE-Staff Parking North

ATS: 11-ATS-EQ1 Mechanical link bent PQM PQM II - GE ZBTSD0B00040F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT

ED12 PSN 11-EMDCP ATS: 11-ATS-LS1 Voltage inputs not wired correctly

PQM PQM II - GE T20-C-A 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT

ED13 Building L -

NORMAL

06-NDCP1 Breaker: SPARE Damaged breaker stabs Breaker GE Micro Entelliguard WPF-

277/480 800 800 Replace with new breaker Rebuild old Breaker

ED14 Building L -

NORMAL

06-NDCP2 Breaker: PANEL 06-

NHDP11

Trip unit display damaged Breaker GE Micro Entelliguard WPF-

277/480 400 200 Replace with new breaker Rebuild old Breaker

ED15 NA – No work NA – No work

ED16 Building L -

NORMAL

06-NDCP2 Relay: DIST BKR-S1 Relay not operational Multilin GE Multilin 350 480 Replace with new Multilin Return Existing Multilin to GOVT

ED17 Building L -

NORMAL

06-NDCP1 Relay - Dist Breaker Relay not operational Multilin GE Multilin 350 480 Replace with new Multilin Return Existing Multilin to GOVT

ED18 Building L -

EMERGENCY

06-EMDCP2 Breaker: MAIN Mechanical problem see notes

Breaker GE Micro Entelliguard WPX-

277/480 3200 3000 Replace with new breaker Rebuild old Breaker

ED19 Building L -

EMERGENCY

06-EMDCP4 Breaker: 06-ATS-

CH4

Breaker Fails LT,ST,INST,GF P/U

Breaker GE Micro Entelliguard WPF-

277/480 1600 1000 Replace with new breaker Rebuild old Breaker

Scope # Building Location CED Equipment Designation

Anomaly TYPE TYPE (detail) Voltage Amps (max rated)

Amps (max operating)

Required work on unit

ED20 ALL

SUBSTATIONS

ALL SUBSTATION

SWITCHGEAR - DETECT

SURGE TRIPS

All existing Switchgear -both sides

Surge Trip capture Switchgear trip sensor

QTY 65 Switchgear ea side -total of 31 sensors to connect to BACNET

Multiple PROGRAM SCADA CONNECTION

NO # SPARE BREAKER

FOR REBUILD

SPARE – GOVT WILL PROVIDE

TO CONTRACTOR

GOVT WILL PROVIDE

TO CONTRACTOR

Mechanical / electrical damage

Breaker GE Micro Entelliguard WPX-

277/480 Rebuild existing breaker

NO #

SPARE BREAKER

FOR REBUILD

SPARE – GOVT WILL PROVIDE

TO CONTRACTOR

GOVT WILL PROVIDE

TO CONTRACTOR

Mechanical / electrical damage

Breaker GE Micro Entelliguard WPX-

277/480 Rebuild existing breaker

NO # SPARE BREAKER

FOR REBUILD

SPARE – GOVT WILL PROVIDE

TO CONTRACTOR

GOVT WILL PROVIDE

TO CONTRACTOR

Mechanical / electrical damage

Breaker GE Micro Entelliguard WPX-

277/480 Rebuild existing breaker

NO #

BUILDING B

ADDITIONAL

PQM FOR

REPLACEMENT

ATS EQ 3 02-ATS-EQ3 Display is erratic PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM Return Existing PQM to GOVT

NO # BUILDING E

PQM FOR

REPLACEMENT

ATS EQ 1 06-ATS-EQ1 Stuck in Self Test Mode PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM

NO # BUILDING F

PQM FOR

REPLACEMENT

ATS EQ 5 03 N ATS-EQ5 Stuck in Self Test Mode PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM

NO # BUILDING K

PQM FOR

REPLACEMENT

ATS CR 1 05 ATS-CR1 Flashing Error Message PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM

File details come from the government source that posted it. Updated .