S06 - REVISED Scope Table 554-24-106.pdf
PDF 528 KB Posted
- Attached to
- Z2DA--554-24-106 Correct Electrical Deficiencies Federal contract opportunity
- Solicitation number
- 36C25924R0099
About this file
This document appears to be a Statement of Work (SOW) for a solicitation to "Correct Electrical Deficiencies" at the Rocky Mountain Regional Veterans Affairs Medical Center (RMR VAMC) in Aurora, Colorado.
The key requirements include replacing 9 substation breaker units, 5 Power Quality Meters (PQMs), and 3 power relays that have reached the end of their service life. Additionally, the contractor must install surge detection equipment to monitor and record surge events on the facility's 31 substations. The contractor must provide new components as drop-in replacements or approved equals, and rebuild the existing GE circuit breakers. All work must be completed within 300 days of the notice to proceed, with strict safety, quality, and scheduling requirements. The contractor must follow all applicable federal, state, and local regulations, as well as VA specifications. Certain work may be required to be performed during off-hours and will need to be coordinated with the Contracting Officer's Representative (COR).
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25924R0099 0003.docx | DOCX document | |
| S06 - REVISED Scope Table 554-24-106 - REATTACHED.pdf | ||
| 36C25924R0099 0002.docx | DOCX document | |
| S05 - Additional RFI ANSWER 554-24-106 Correct Electrical Deficiencies.pdf | ||
| S04 - Site Visit Attendance.pdf | ||
| S05 - RFI ANSWERS 554-24-106 Correct Electrical Deficiencies.pdf | ||
| 36C25924R0099 0001.docx | DOCX document | |
| S22- 852.219-75 LOS Certificate - GC.docx | DOCX document | |
| 36C25924R0099_1.docx | DOCX document | |
| S02 - Past Performance Questionnaire.docx | DOCX document | |
| S02 - SOW Attachment 4 DRAFT ICRA - PCRA Electrical Closet Substations.pdf | ||
| S02 - SOW Attachment 3 Specifications 554-24-106.pdf | ||
| S02 - SOW Attachment 2 Deficiency reports 554-24-106.pdf | ||
| S02 - SOW Attachment 1 Scope Table 554-24-106.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SOW ATTACHMENT 1
VAECHCS
SCOPE TABLE
PROJECT #
554-24-106
CORRECT ELECTRICAL DEFICIENCIES
Summary Required work on unit Quantity Summary Required work on unit Quantity
Breaker Replace 9 Other Base Bid: New nameplate 1
PQM Replace 9 Other Program BACNET CNX 31 Multilin Replace 3 Other Rebuild GE Breakers 11
Scope # Building Location CED Equipment Designation
Anomaly TYPE TYPE (detail) Voltage Amps (max rated)
Amps (max operating)
Required work on unit
ED01 Building A 10-NDCP Breaker: 7-SWBD-10
MDP
Elevated contact resistance and dev.
Breaker Eaton Digitrip 520 LV Breaker
277/480 1600 1600 Replace with new breaker Return old breaker to VA DO NOT
REBUILD EATON BREAKER
ED02 Building B 02-EMDCP Breaker: SPARE Captive washer missing Breaker GE Micro Entelliguard WPX-
277/480 800 600 Replace with new breaker Rebuild old Breaker
ED03 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-LS1 Alarm on ATS PQM PQM II - GE ZBTSD0B00060F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT
ED04 Building D BUILDING 3/D/DAT SOUTH ATS:03-ATS-EQ7 Name plate sticker missing ATS GE ATS 480 800 Get new nameplate from manufacturer - install nameplate on existing ATS
ED05 Building E 09-NDCP Breaker: 09-ATS-LS1 Missing rivets in cell shutter.
Breaker GE Micro Entelliguard WPX-
277/480 150 100 Replace with new breaker Rebuild old Breaker
ED06 Building G 08-EMDCP Breaker: 08-ATS-CR2 Mechanical problem see notes
Breaker GE Micro Entelliguard WPX-
277/480 800 800 Replace with new breaker Rebuild old Breaker
ED07 Building G 08-EMDCP Breaker: 08-ATS-
EQ1
Operational Failure see notes
Breaker GE Micro Entelliguard WPX-
277/480 800 500 Replace with new breaker Rebuild old Breaker
ED08 Building G 08-EMDCP DIST BREAKER S1 Meter is not operational Multilin GE Multilin 350 480 Replace with new Multilin Return Existing Multilin to GOVT
ED09 Building K Building 5-K-Inpatient North ATS: 05-ATS-CR1 Mechanical problem see notes
PQM PQM II - GE ZBTSD0B00080F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT
ED10 Building K Building 5-K-Inpatient North ATS: 05-ATS-EQ2 Mechanical problem see notes
PQM PQM II - GE ZBTSD0B00120F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT
ED11 PSN Building 11-PE-Staff Parking North
ATS: 11-ATS-EQ1 Mechanical link bent PQM PQM II - GE ZBTSD0B00040F 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT
ED12 PSN 11-EMDCP ATS: 11-ATS-LS1 Voltage inputs not wired correctly
PQM PQM II - GE T20-C-A 480 Replace WITH NEW PQM Repair ATS Return Existing PQM to GOVT
ED13 Building L -
NORMAL
06-NDCP1 Breaker: SPARE Damaged breaker stabs Breaker GE Micro Entelliguard WPF-
277/480 800 800 Replace with new breaker Rebuild old Breaker
ED14 Building L -
NORMAL
06-NDCP2 Breaker: PANEL 06-
NHDP11
Trip unit display damaged Breaker GE Micro Entelliguard WPF-
277/480 400 200 Replace with new breaker Rebuild old Breaker
ED15 NA – No work NA – No work
ED16 Building L -
NORMAL
06-NDCP2 Relay: DIST BKR-S1 Relay not operational Multilin GE Multilin 350 480 Replace with new Multilin Return Existing Multilin to GOVT
ED17 Building L -
NORMAL
06-NDCP1 Relay - Dist Breaker Relay not operational Multilin GE Multilin 350 480 Replace with new Multilin Return Existing Multilin to GOVT
ED18 Building L -
EMERGENCY
06-EMDCP2 Breaker: MAIN Mechanical problem see notes
Breaker GE Micro Entelliguard WPX-
277/480 3200 3000 Replace with new breaker Rebuild old Breaker
ED19 Building L -
EMERGENCY
06-EMDCP4 Breaker: 06-ATS-
CH4
Breaker Fails LT,ST,INST,GF P/U
Breaker GE Micro Entelliguard WPF-
277/480 1600 1000 Replace with new breaker Rebuild old Breaker
Scope # Building Location CED Equipment Designation
Anomaly TYPE TYPE (detail) Voltage Amps (max rated)
Amps (max operating)
Required work on unit
ED20 ALL
SUBSTATIONS
ALL SUBSTATION
SWITCHGEAR - DETECT
SURGE TRIPS
All existing Switchgear -both sides
Surge Trip capture Switchgear trip sensor
QTY 65 Switchgear ea side -total of 31 sensors to connect to BACNET
Multiple PROGRAM SCADA CONNECTION
NO # SPARE BREAKER
FOR REBUILD
SPARE – GOVT WILL PROVIDE
TO CONTRACTOR
GOVT WILL PROVIDE
TO CONTRACTOR
Mechanical / electrical damage
Breaker GE Micro Entelliguard WPX-
277/480 Rebuild existing breaker
NO #
SPARE BREAKER
FOR REBUILD
SPARE – GOVT WILL PROVIDE
TO CONTRACTOR
GOVT WILL PROVIDE
TO CONTRACTOR
Mechanical / electrical damage
Breaker GE Micro Entelliguard WPX-
277/480 Rebuild existing breaker
NO # SPARE BREAKER
FOR REBUILD
SPARE – GOVT WILL PROVIDE
TO CONTRACTOR
GOVT WILL PROVIDE
TO CONTRACTOR
Mechanical / electrical damage
Breaker GE Micro Entelliguard WPX-
277/480 Rebuild existing breaker
NO #
BUILDING B
ADDITIONAL
PQM FOR
REPLACEMENT
ATS EQ 3 02-ATS-EQ3 Display is erratic PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM Return Existing PQM to GOVT
NO # BUILDING E
PQM FOR
REPLACEMENT
ATS EQ 1 06-ATS-EQ1 Stuck in Self Test Mode PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM
NO # BUILDING F
PQM FOR
REPLACEMENT
ATS EQ 5 03 N ATS-EQ5 Stuck in Self Test Mode PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM
NO # BUILDING K
PQM FOR
REPLACEMENT
ATS CR 1 05 ATS-CR1 Flashing Error Message PQM PQM II - GE ZBTSD0B 480 Replace WITH NEW PQM