S02 - Drawings Part 3.pdf
PDF 16 MB Posted
- Solicitation number
- 36C25921R0082
About this file
This document outlines a federal contract opportunity from the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 19. The solicitation seeks to install partitions at check-in desks, as outlined in solicitation number 36C25921R0082. Responses are due for providing the installation of partitions at check-in areas to improve privacy and workflow. The selected contractor will carry out the installation work for the agency. Relevant details such as response dates, pricing requirements, and points of contact are provided in the full solicitation document.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amend 08 - Drawings for RFI 2 project 554-20-103.pdf | ||
| 36C25921R0082 0008.docx | DOCX document | |
| 36C25921R0082 0007.docx | DOCX document | |
| 36C25921R0082 0006.docx | DOCX document | |
| 36C25921R0082 0005.docx | DOCX document | |
| 36C25921R0082 0004.docx | DOCX document | |
| Amendment 03 - 36C25921R0082 0003.docx | DOCX document | |
| Amendment 02 - 36C25921R0082 0002.docx | DOCX document | |
| S04 - 2022-01-28-RFI_No_1-Project_554-20-103_Install_Partitions_at_Check-In_Desks-VEG-20-16.pdf | ||
| S04 - Site Visit Attendance.pdf | ||
| S06 - Amend 0001 - 36C25921R0082 0001.docx | DOCX document | |
| S02 - Drawings Part 4.pdf | ||
| S02 - Drawings Part 2.pdf | ||
| S02 - Drawings Part 1.pdf | ||
| S02 - Specifications.pdf | ||
| S02 - Solicitation - 36C25921R0082.docx | DOCX document | |
| S02 - ICRA.pdf |
Show all 17
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Issued:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
C R e v it
\5
-2
-1
C h e c k -I n A
R C
H R c jo h n s to n Y
W
N
.r v t
/5
/2
:0
:0
P
M
I-903
PERSPECTIVES BLDG G LEVEL 3 INSTALL PARTITIONS AT CHECK-IN
DESKS
1700 N WHEELING ST, AURORA, CO 80045
554-20-103
02/15/2021 TW CJ
100% CONSTRUCTION
DOCUMENTS
VEG 20.17 02/08/2021
COMMUNICATION GENERAL NOTES
A. FOR WHEEL CHAIR PATIENT USE MOUNT TELEPHONE OUTLET 35" AFF TO BOTTOM OF OUTLET BOX.
B. DESK PHONES - MOUNT OUTLET 1'-6" AFF
C. HEIGHT OF TELECART OUTLETS SHALL BE AS INDICATED ON BED WALLS OR PBPU DETAILS.
D. SEE VA BARRIER FREE DESIGN GUIDE PG-18-13
ELECTRICAL GENERAL NOTES - DEMOLITION
A. SEE ARCHITECTURAL DRAWINGS AND SPECIFICATIONS FOR PHASES OF DEMOLITION AND
CONSTRUCTION. COORDINATE WITH GENERAL CONSTRUCTION.
B. DISCONNECT AND REMOVE ALL ELECTRICAL DEVICES AND LIGHTING FIXTURES IN DEMOLITION AREAS UNLESS NOTED OTHERWISE. DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRE BACK TO OVERCURRENT PROTECTIVE DEVICE. COMPLETELY CUT/CAP CONDUITS IN CONCRETE SLAB AND IN THE AREA OF WORK PERIMETER. DISCONNECT AND REMOVE ALL ABANDONED CIRCUITS AND CONDUITS.
PROVIDE CONDUIT AND WIRE AS REQUIRED FOR CONTINUITY OF CIRCUITS TO ANY EXISTING DEVICES TO
REMAIN. COORDINATE AND VERIFY REQUIREMENTS WITHIN NEW AREA OF WORK.
ELECTRICAL GENERAL NOTES
A. SPECIFICATIONS TAKE PRECEDENT OVER DRAWINGS.
B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH
WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
C. CORE DRILL AND SAW CUT, AS REQUIRED, FOR FLOOR AND WALL PENETRATIONS. SEAL REMAINING
ANNULUS WITH FIRE CAULK.
D. FURNISH ACCESS DOORS OR PANELS FOR INSTALLATION BY GENERAL CONTRACTOR IN WALLS AND
CEILINGS WHERE ACCESS IS REQUIRED TO CONCEALED ELECTRICAL BOXES AND DEVICES.
E. ARMORED CABLE (AC) MAY BE USED FOR LAY-IN FIXTURE PIGTAILS. ARMORED CABLE (AC) SHALL NOT BE USED FOR BRANCH CIRCUIT HOMERUNS. ARMORED CABLE (AC) SHALL NOT BE USED WHERE MORE THAN THREE CONDUCTORS (PHASE/NEUTRAL/GROUND) ARE REQUIRED, WHERE EXPOSED; OR IN LENGTHS
EXCEEDING 20 FEET EXCEPT FOR TEMPORARY WIRING.
F. PROVIDE ALL ELECTRICAL WORK IN ACCORDANCE WITH THE SPECIFICATIONS OF THE VHA.
G. COORDINATE ALL OUTAGES WITH VHA COR PER SPECS PRIOR TO WORK BEING DONE.
KEYNOTES
KEYNOTE00
NEW - EXISTING AND DEMO LINE TYPES
NEW LINE TYPE
EXISTING LINE TYPE
DEMO LINE TYPE
DEMO HATCH
LIGHTING GENERAL NOTES
A. ALL RECESSED LIGHTING FIXTURE IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6' LONG FLEXIBLE METAL
CONDUIT.
B. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE FIXTURES UNLESS
INDICATED OTHERWISE.
C. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR LIGHTING FIXTURES.
D. CIRCUIT WIRING IS NOT SHOWN. SWITCH AND CIRCUITING INTENT SHALL BE AS DESIGNATED AT
EACH LIGHT FIXTURE.
E. PROVIDE PROPER NUMBER OF CONDUCTORS TO ACHIEVE CIRCUITING AND SWITCHING SHOWN.
F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE PANELBOARD
SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE CIRCUIT BREAKER RATING, UNLESS
INDICATED OTHERWISE ON THE ELECTRICAL EQUIPMENT SCHEDULE.
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Issued:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
C R e v it
\5
-2 -1
C h e c k -I n
E L
E C
R m lu g o W
Q
P M
.r v t
/1
/2
:3
:1
A
M
E-001
ELECTRICAL ABBREVIATIONS AND
GENERAL NOTES
INSTALL PARTITIONS AT CHECK-IN
DESKS
1700 N WHEELING ST, AURORA, CO 80045
554-20-103
02/15/2021 CPR MLS
100% CONSTRUCTION
DOCUMENTS
VEG 20.17
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
N
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS
ASSOCIATION
NEUT OR N NEUTRAL
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NS NO SCALE
NTS NOT TO SCALE
O
OC ON CENTER
OD OUTSIDE DIAMETER
OL OVERLOAD
P
P POLE
PA PUBLIC ADDRESS
PB PULL BOX OR PANEL BOARD
PBPU PREFABRICATED BEDSIDE PATIENT UNIT
PCB POLYCHLORINATED BIPHENYL
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
R
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
REQ REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
S
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SES SERVICE ENTRANCE SECTION
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
T
TEL TELEPHONE
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TYP TYPICAL
U
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTIL UTILITY
V
V VOLT
VA VOLT-AMPERE
VAR VOLT-AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W
W WATT
WH WATER HEATER
WP WEATHERPROOF
X
XFER TRANSFER
XFMR TRANSFORMER
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
E
EL ELEVATION
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMCP EMERGENCY MONITORING CONTROL PANEL
EMER EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXST EXISTING
F
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FABL FIRE ALARM BELL
FABX FIRE ALARM BOX
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FIXT FIXTURE
FLA FULL LOAD AMPS
FLEX FLEXIBLE METALLIC CONDUIT
FLT FLOODLIGHT
FLUOR FLUORESCENT
FLUOR FIXT FLUORESCENT FIXTURE
FOUTT TELEPHONE FLOOR OUTLET
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G
G OR GND ELECTRICAL GROUND
GC GENERAL CONTRACTOR
GEN GENERATOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GTB GROUND TERMINAL BOX
H
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
I
IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH
AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J
J-BOX JUNCTION BOX
K
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAH KILOVOLT-AMPERE PER HOUR
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
L
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LM LUMEN
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
M
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MG MOTOR GENERATOR
MH MANHOLE
1P SINGLE POLE
1PH SINGLE PHASE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE PHASE
4/C FOUR-CONDUCTOR
4W FOUR WIRE
A
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT / ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT OR ADJOINING
ADO AUTOMATIC DOOR OPENER
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE FAULT
CURRENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE-HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB OR A AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
B
BAT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BIL BASIC INSULATION LEVEL
BLDG BUILDING
BPIP BOILER PLANT INSTRUMENTATION PANEL
BRKR BREAKER
BYP BYPASS
C
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA OR CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED / CONTRACTOR
INSTALLED
CF/OI CONTRACTOR FURNISHED / OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
CKT BRKR CIRCUIT BREAKER
CLF CURRENT LIMITING FUSE
CLG CEILING
CMU CONCRETE MASONRY UNIT
CO CONTRACTING OFFICER
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CU FT CUBIC FEET
CUR CURRENT
D
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DISTR DISTRIBUTION
DISTR PNL DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DN DOWN
ELECTRICAL ABBREVIATIONS
CARD READERBRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER OF
CIRCUITS,NEUTRAL, AND SWITCH LEG CONDUCTORS. ONE
SEPARATE GREEN GROUNDING CONDUCTOR SHALL BE
PROVIDED FOR EACH HOMERUN; NOT SHOWN
P
A bx
A b x
A b x
A b x
DT
ELECTRICAL SYMBOLS - DIAGRAM COMMUNICATION SYMBOLS: ELECTRICAL SYMBOLS - LIGHTING PLANELECTRICAL SYMBOLS - POWER PLAN
SWITCH, MULTIPOSITION
SWITCH, NORMALLY CLOSED FLOAT
SWITCH, NORMALLY CLOSED FOOT OPERATED
SWITCH, NORMALLY CLOSED LIMIT
SWITCH, NORMALLY CLOSED TIME DELAY
SWITCH, NORMALLY CLOSED TEMPERATURE
ACTIVATED
SWITCH, NORMALLY OPEN FLOAT
SWITCH, NORMALLY OPEN LIMIT
SWITCH, NORMALLY OPEN TEMPERATURE
ACTIVATED
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
PULL BOX
PRESSURE SWITCH-CLOSE ON INCREASE
PRESSURE SWITCH-OPEN ON INCREASE
MANHOLE
TIME CLOCK
VENTILATOR OR FAN COIL UNIT OUTLET
CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR
EXTENSION TO EQUIPMENT AS DIRECTED.
CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED
FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.
RECEPTACLE,
SWITCHED DUPLEX
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE
CORD (CENTER LINE OF OUTLET: 6'-6" AFF. (MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" CENTERS OR AS
DESIGNATED ON DRAWINGS), MTD 3'-6" AFF OR AS INDICATED.
3-GANG COMPARTMENT BOX IN FLOOR FOR
TELEPHONE, DATA & RECEPTACLE.
RECEPTACLE, SPECIAL PURPOSE
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
ELECTRIC DOOR STRIKE
MAGNETIC DOOR POSITION SWITCH
VANDAL RESISTANT 1080P DOME IP CAMERA
FOUR SQUARE JUNCTION BOX
SECURITRON IMXDA MAGNETIC LOCK
OUTLET, COMBINATION TELEPHONE/DATA
COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV.
MINIMUM 1" CONDUIT
FIBER OPTICS LINE = FO
FLOOR RECEPTACLE, TELEPHONE
OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE,
PROVIDE SCHEDULE ON LEGEND. MTD.
7'-6" AFF UNLESS OTHERWISE NOTED.
OUTLET DATA ONLY
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" CONDUIT.
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
RADIO CONDUIT RUN, MINIMUM 3/4" CONDUIT.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6"
AFF UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL MTD. 4'-6" AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK= 4 11/16" MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" AFF
M = MONITOR (CCTV SYSTEM).
NURSE'S CALL MASTER STATION MTD ON NURSE'S COUNTER
TOP UNLESS OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS
AT MASTER STATION) MTD 5'-0" AFF UNLESS OTHERWISE NOTED.
D = DUTY STATION. MTD 5'-0" AFF UNLESS NOTED OTHERWISE.
E = MTD 6'-0" AFF FOR SHOWER LOCATION, MTD 4'-6" AFF FOR TUB
LOCATION, & MTD 3'-0" AFF FOR TOILET LOCATION.
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
S = AUDIO VISUAL WALL STATION (STAFF) MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
U = UTILITY CALL STATION, MTD 5'-0" AFF UNLESS OTHERWISE NOTED.
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF LAMP)
MTD 6" ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" AFF.
REMOTE DICTATING OUTLET MTD 1'-6" AFF. UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL OPERATION
OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
TELECOMMUNICATIONS MANHOLE
DATA BOX
DURESS BUTTON
CCTV SYSTEM WORKSTATION
REQUEST TO EXIT MOTION DETECTOR
USP HUB2SA REMOTE DOOR RELEASE BUTTON
CODE BLUE BUTTON INTEGRATED NURSE CALL SYSTEM
NURSE CALL MASTER CONSOLE
ETHERNET NETWORK SWITCH
WIRELESS ACCESS POINT
SWITCH
F = FUSED SWITCH
K = KEY OPERATED
L = LOCK
LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING
MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT
P = WITH PILOT LIGHT (THERMAL TYPE)
X = EXPLOSION PROOF
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE
LVD = LOW VOLTAGE DIMMER
LV= LOW VOLTAGE SWITCH
GS= GRAPHIC SCREEN CONTROL STATION
PB= PUSH BUTTON STATION
WP= WEATHER PROOF
T = TIMER OPERATED
LOS= OCCUPANCY SENSOR
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
STREET LIGHT WITH BRACKET
LIGHT POLE, ONE MAST ARM, ONE LUMINAIRE
LIGHT POLE, TWO MAST ARMS, TWO LUMINAIRES
LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHT POLE, ONE LUMINAIRE
LIGHTING, EXTERIOR BUILDING
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL
ARROWS AND FACES AS SHOWN
LIGHT POLE, TWO LUMINAIRES
RECESSED DOWNLIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
JUNCTION BOX
TRANSFORMER, PLAN
WYE CONNECTION
DUCT, CELL FLOOR HEADER
DUCT, TROLLEY
DUCT, UNDERFLOOR
JUNCTION BOX
EARTH GROUND
LADDER CABLE TRAY
WIREWAY
RIGID CONDUIT LINE = RC
SUBSTATION
BUSWAY
FLOOR OUTLET, DATA COMMUNICATION
OUTLET, DATA COMMUNICATION
PUSH BUTTON / EMERGENCY SHUT OFF
DISTRIBUTION PANEL
LIGHTING PANEL
PANELBOARD CABINET, FLUSH MOUNTED
PANELBOARD CABINET, SURFACE MOUNTED
RECEPTACLE, CLOCK HANGER
RECEPTACLE, DUPLEX (MOUNT 18"AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, DUPLEX ON EMERGENCY POWER
(MOUNT 18" AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER (MOUNT 18" AFF. UNLESS NOTED OTHERWISE)
RECEPTACLE, QUADRAPLEX
RECEPTACLE, SINGLE
RECEPTACLE, SINGLE WITH SWITCH
DIRECT BURIAL CABLE = DB
POWER DUCT = P
HI VOLTAGE SWITCH ON CONCRETE PAD
LOW VOLTAGE SWITCH ON CONCRETE PAD
DUAL POWER AND TELECOMMUNICATIONS MANHOLE
SWITCH, NORMALLY OPEN TIME DELAY
SWITCH, SINGLE BREAK
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
MOLDED CASE CIRCUIT BREAKER
LOW-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
MEDIUM-VOLTAGE OIL CIRCUIT BREAKER
MEDIUM-VOLTAGE DRAWOUT AIR CIRCUIT BREAKER
SWITCH AND FUSE UNIT
FUSED DRAWOUT POTENTIAL TRANSFORMER
FUSIBLE LINK
VARIABLE FREQUENCY DRIVE
GENERATOR, POWER
BATTERY
CAPACITOR
LIGHTNING ARRESTOR
RECTIFIER, CATHODIC PROTECTION
RELAY; LETTER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE
51 = AC-TIME OVERCURRENT
67 = AC-DIRECTIONAL OVERCURRENT
86 = LOCK OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED, VAV
STARTER, COMBINATION W/DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
POTHEAD
STRESS CONE
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
RECEPTACLE, DUPLEX COUNTER HEIGHT
BLANK OUTLET BOX
RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER
(MOUNT 18" AFF. UNLESS NOTED OTHERWISE
DUAL PASSIVE INFRARED / MICROPHONIC
TECHNOLOGY (ULTRASONIC NOT ALLOWED)
FLOOR OUTLET, RECEPTACLE
GROUNDING BAR
HEADWALL
LIGHT FIXTURE POWER CONNECTION DESIGNATIONS:
OPEN - NORMAL POWER CIRCUIT
SHADED - LIFE SAFETY EMERGENCY POWER CIRCUIT
HATCHED - CRITICAL POWER CIRCUIT
RECESSED TROFFER LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULES FOR MORE
INFORMATION.
CEILING SURFACE MOUNTED LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
WALL SURFACE MOUNTED LIGHT FIXTURE.
NOMENCLATURE EXAMPLE :
('A' DESIGNATES LIGHT FIXTURE TYPE, 'b' DESIGNATES SWITCHLEG, x DESIGNATES CIRCUIT NUMBER) REFER TO
DRAWINGS AND LIGHT FIXTURE SCHEDULE FOR MORE
INFORMATION.
EXTERIOR FLOOD LIGHT
LIGHT FIXTURE, BOLLARD
LIGHT FIXTURE, DIRECTIONAL
DUEL TECHNOLOGY (NOT ULTRA SONIC)
M
PB
P
VFD
G
R
A
V
W
WH
T
T T
J
C C
W W
RC
DB
P
S
HVS
LVS
P T
B B
DP#__
LP
C
C
S
H
S
TC
M
CR
ES
F
FIX
J
ML
RRB
RX
WS
DB
CB
NCM
NWS
WAP
CATV
CCTV
FO
T
I
S
NC
R
$x
$x
B
C w
X S
X S
R
R M
C
NCM
NCT
N D
N
TTB
R M
S
DT
M
OCB
D
GFCI
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Issued:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
C R e v it
\5
-2 -1
C h e c k -I n
E L
E C
R m lu g o W
Q
P M
.r v t
/1
/2
:3
:1
A
M
E-002
ELECTRICAL SYMBOLS INSTALL PARTITIONS AT CHECK-IN
DESKS
1700 N WHEELING ST, AURORA, CO 80045
554-20-103
02/15/2021 CPR MLS
100% CONSTRUCTION
DOCUMENTS
VEG 20.17
| INTERIORS |
| I-903 - PERSPECTIVES BLDG G LEVEL 3 |
| ELECTRICAL |
| E-001 - ELECTRICAL ABBREVIATIONS AND GENERAL NOTES |
| E-002 - ELECTRICAL SYMBOLS |
File details come from the government source that posted it. Updated .