S02 631-451 Part 5.pdf
PDF 8 MB Posted
- Attached to
- Z2DA--631-451 Upgrade Primary Care
- Solicitation number
- 36C24120R005_1
About this file
This solicitation is for an upgrade to the primary care clinic at a Veterans Affairs medical center. Key requirements include renovations and additions to the existing facility, including upgrades to electrical, lighting, and fire alarm systems as well as low voltage systems. The work involves renovating and adding to exam rooms, waiting areas, offices, and support spaces. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The response due date is within 30 days and award is expected within 90 days of solicitation issuance. Pricing will be fixed price with payment terms of net 30. No set-asides or socioeconomic requirements are specified. The incumbent contractor was not identified.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24120R0053 0005.pdf | ||
| B1-Basement Plan.pdf | ||
| DSCN0133.JPG | JPG image | |
| DSCN0134.JPG | JPG image | |
| 36C24120R0053 0004.pdf | ||
| 36C24120R0053 0003.pdf | ||
| S06 Appendices Final 7-21-2020.pdf | ||
| S06 Site Visit 1 Roster.pdf | ||
| 36C24120R0053 0002.pdf | ||
| S06 Attachment Spec 07 44 00.pdf | ||
| S06 Site Visit 2 Roster.pdf | ||
| 36C24120R0053 0001.pdf | ||
| S02 SOW Primary Care.pdf | ||
| S02 Primary Care Spec Sections 0-23.pdf | ||
| S02 Primary Care Spec Sections 26-33.pdf | ||
| S02 631-451 Part 1.pdf | ||
| S02 631-451 Part 4.pdf | ||
| S02 631-451 Part 3.pdf | ||
| S02 631-451 Part 2.pdf | ||
| 36C24120R0053_1.docx | DOCX document |
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRST FLOOR
FIRE ALARM RISER DIAGRAM
N.T.S.SCALE:
ALL FIELD WIRING AND EQUIPMENT SHALL BE AS REQUIRED PER
MANUFACTURERS WIRING DIAGRAMS.
CEILING MOUNTED SMOKE DETECTORS SHALL NOT BE LOCATED CLOSER
THAN 3 FT. FROM AIR SUPPLY FROM AIR SUPPLY DIFFUSERS.
PROVIDE A REMOTE TEST STATION FOR ALL DUCT MOUNTED SMOKE DETECTORS.
REFER TO ELECTRICAL DRAWINGS FOR EXACT QUANTITIES OF FIRE ALARM DEVICES.
ELECTRICAL CONTRACTOR SHALL PROGRAM, TEST AND CERTIFY FIRE
ALARM SYSTEM UPON COMPLETION WORK.
FIRE ALARM SYSTEM AND INSTALLATION SHALL COMPLY WITH APPLICABLE
REGULATIONS OF NFPA #72, LIFE-SAFETY CODE #101, NATIONAL ELECTRIC
CODE AND LOCAL FIRE DEPARTMENT.
FIRE ALARM WIRING TERMINATIONS SHALL BE MADE ON TERMINAL
BLOCKS, NO SPLICES WILL BE ALLOWED.
ELECTRICAL CONTRACTOR SHALL FIELD CONFIRM THAT ENOUGH BATTERY
CAPACITY EXISTS FOR THE FIRE ALARM SYSTEM TO OPERATE FOR 24 HOURS
IN NON-ALARM CONDITION AND CAPABLE OF OPERATING IN ALARM FOR 5
MINUTES AT THE END OF THE 24 HOUR PERIOD. FIRE ALARM VENDOR TO
PROVIDE BATTERY AMP-HOUR CALCULATIONS, RISERS AND WIRING
SCHEMATICS WITH SUBMISSION.
SYSTEM MANUFACTURER SHALL PROVIDE INSTALLATION WIRING DIAGRAM
OF THE FIRE ALARM SYSTEM, AND VERIFICATION CERTIFICATE OF SYSTEM
OPERATING PRIOR TO FINAL ACCEPTANCE.
ALL FIRE ALARM WIRING SHALL BE CLASS A (OUTGOING AND RETURNING
CIRCUITS SHALL NOT BE PHYSICALLY INSTALLED IN THE SAME RACEWAY),
FAULT ISOLATOR MODULES SHALL BE INSTALLED IN THE FACP. ALSO, FAULT
ISOLATOR MODULES WILL BE PROVIDED FOR EVERY 18 ADDRESSABLE FIRE
ALARM DEVICES. NOTIFICATION DEVICE CIRCUITS SHALL BE INSTALLED IN
SEPARATE RACEWAYS FROM SIGNALING LINE CIRCUITS.
FIRE ALARM SYSTEMNOTES:
FA1.
FA2.
FA3.
FA4.
FA5.
FA6.
FA7.
FA8.
FA9.
FA10.
TYPICAL
UTILITY
CLOSET
LINEN
CLOSET
STORAGE
CLOSET
S S S SS FSTS H F
DENOTES TO
ADDITIONAL
DEVICES
(TYPICAL)
TYPICAL STROBE
ONLY
NOTIFICATION
APPLIANCE CIRCUIT,
TYPICAL
NOTIFICATION
APPLIANCE CIRCUIT,
TYPICAL SIGNALING LINE CIRCUIT,
TYPICAL
SPRINKLER RISER
STACK
SD
ELECTRIC
CLOSET
S S
SOILED &
STERILE
SUPPLY
F F V V VF
EXISTING NOTIFIER
NFS2-3030
FIRE ALARM
CONTROL PANEL
SM PS
CM
CM
TYPICAL
UTILITY
CLOSET
LINEN
CLOSET
STORAGE
CLOSET
SSSS SFS TSHF
DENOTES TO
ADDITIONAL
DEVICES
(TYPICAL)
TYPICAL
SPRINKLER RISER
STACK
CM
FSD
24V J
SD
FIRE/SMOKE
DAMPER
ELECTRIC
CLOSET
SS
SOILED &
STERILE
SUPPLY
FFVVV F
INCOMING FIRE
MUNICIPAL FIRE
ALARM
CONNECTION
EEEE
NEW WIRING SHALL MATCH EXISTING SYSTEM METHOD.FA11.
CONNECT FIRE ALARM SYSTEM TO SENSOR CONTROLLED EGRESS SYSTEM
FOR AUTOMATIC RELEASE OF DOORS UPON FIRE ALARM ACTIVATION.
FA12.
FULLY TEST EXISTING FIRE ALARM SYSTEM PRIOR TO DEMO AND NEW WORK.
IDENTIFY ALL EXISTING FAULTS, WARNINGS, AND FAILURES TO ENGINEER AND
ARCHITECT.
FA13.
OBTAIN SERVICES OF NHVA CONTRACTED FIRE ALARM CONTRACTOR FOR ALL
TERMINATIONS AND ALL SYSTEM PROGRAMMING CHANGES.
FA14.
CM
J
CM
J
PUSH TO RELEASE
REQUEST TO EXIT
S
ELEVATOR
RECALL
MMMMMMMMMMMM
BDA
ADD ALTERNATE IF REQUIRED
110 V
CONNECT TO THE FIRE ALARM PANEL.
6 SUPERVISORY INPUTS REQUIRED:
BDA ANTENNA TROUBLE
BDA TROUBLE
BDA POWER LOSS
BDA CHARGER TROUBLE
BDA LOW BATTERY
BDA ANNUNCIATOR TROUBLE24V BATTERY
BACKUP
UL2524
LISTED BDA
DAS CABLE, ANTENNAS AND COUPLERS ARE
SHOWN FOR ILLUSTRATION PURPOSES ONLY.
CABLE ROUTES, EQUIPMENT LOCATIONS AND
THEIR QUANTITIES SHALL BE DETERMINED AN
SPECIFIED DURING THE SYSTEM DESIGN
STAGE.
½” PLENUM RATED COAXIAL CABLE SHOULD BE INSTALLED
FOLLOWING THE ELECTRICAL CODE. THE COAX SHOULD
BE SELF-SUPPORTED EVERY FOUR FEET USING CLIPS. IN
ADDITION, ZIP TIES ARE NOT TO BE USED TO SECURE ANY
PART OF THE ANTENNA SYSTEM.
BDA STATUS ANNUNCIATOR PROVIDED BY VENDOR,
MOUNTED BY FIRE ALARM CONTRACTOR IN FIRE
COMMAND ROOM OR OTHER LOCATION AS DESIGNATED
BY AHJ.
8 CONDUCTOR WIRE (CAT5E / CAT6E) FOR
CONNECTION FROM BDA TO ANNUNCIATOR. REF.
MANUFACTURERS SPECS.
ANTENNA MAST TO BE BONDED / GROUNDED TO BUILDING
STEEL IN COMPLIANCE WITH NFPA70 – ARTICLE 810
FOR USE WITH AN ARTICLE 250 APPROVED GROUNDING
ELECTRODE SYSTEM. SUPPLIED AND INSTALLED BY EC
LIGHTNING ARRESTOR, GROUNDED.
LOCATED OUTSIDE, BEFORE THE
CABLE BUILDING ENTRY
DONOR ANTENNA
DIRECTION – TBD
ROOF
1. DISTRIBUTED ANTENNA SYSTEM (DAS) CABLE, ANTENNAS
AND COUPLERS ARE SHOWN FOR ILLUSTRATION PURPOSES
ONLY. CABLE ROUTES, EQUIPMENT LOCATIONS AND THEIR
QUANTITIES SHALL BE DETERMINED BY VENDOR DURING
THE SYSTEM DESIGN STAGE.
2. THE FIRE ALARM CONTRACTOR, ENGINEER, AND ARCHITECT
SHALL REVIEW AND APPROVE THE PROPOSED EQUIPMENT
AND CABLE RISER LOCATIONS AND FIRE SURVIVABILITY
REQUIREMENTS.
3. BDA AND THE COAXIAL RISER CABLE AND ANNUNCIATOR
CABLE SHALL BE LOCATED IN A 2-HOUR FIRE RATED SPACE.
GENERAL NOTE:
ANTENNA (TYP)
FLOOR TYPICAL
#6 GROUND WIRE
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic e of
F ac il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
12" = 1'-0"
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:2
A
M
CMB
FIRE ALARM RISER DIAGRAM
1-EFA-200
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5 South Burlington, VT 05403
802-658-6100
HYD
TSV
REL
OCA
TED
LIG
HT
POL
E A
ND
ELEC
BO
X
6"X" 8 T
APP
ING
SLEE
VE
AND
VAL
VE
"W
"ó
D
REL
OCA
TED
HY
D
HH
EXIS
TING
FO
UND
ATIO
N
DRA
IN T
O R
EMA
IN
VAN
VAN
A M
B U
L A
N C
E O
N L Y
18'
12'
5'
8'
21.
5'
8'
8'
8'
8'
5'
8'
8'
5'
8'
1.5%
SLO
PE
PRO
POS
ED
LOA
DING
DO
CK
BIT
DRIV
EWA
Y
BIT
PAR
KING
CON
C W
ALK
INFILL
1,994 SF
HH H
HH
H H
H H
H H
H H
H
CO
CO
C
C
Fib er O pt ic Co m m s ee -4 co nd uit s in du ct ba nk
Elec tric
#20, 2 4
" co ndui ts
C
C
C
C
C unknown Com m line picked up by verizon apr 2009
Telephone Line
W
-A
E
-A
Loading Dock
COOLER CHILLER UNIT
Un kn ow n U til ity s ee d ra wi ng S /S
C al le d ou t as
FM
YD H
EB
O X
S
D
D
EBO
X
MH
HH
HH
HH
HH
HH
HH
HH
HH
HH
HH
EXISTING
MAIN IT ROOM
EXISTING IT
ROOM E-102
NEW IT CLOSET 1247
EXISTING
TELEPHONE CLOSET
B108A
E
EXISTING PAD
MOUNTED
TRANSFORMER
J
E
EXISTING
GENERATOR
BUILDING
LB1
LB1
LB1
LB1
LB1
LB1
LB1
LB1
LB1
LB1
NEW FIBER IN INNERDUCT SHALL RUN OVERHEAD IN
EXISTING CONDUITS TO ADJACENT STORAGE ROOM.
EXISTING JUNCTION BOX (IN STORAGE ROOM ADJACENT TO
DATA ROOM) WHERE EXISTING CONDUIT TURN DOWN TO
BASEMENT AND OUT OF THE BUILDING. COORDINATE EXACT
LOCATION IN THE FIELD.
SITE PLAN KEYED NOTES
PROVIDE NEW FIBER RUN FROM DATA ROOM IN BUILDING 2
TO NEW IT ROOM 1247 IN RENOVATION AREA OF BUILDING 1.
PROVIDE (2) 12 STRAND MULTI-MODE AND (1) 12 STRAND
SINGLE-MODE FIBER CABLES. NEW FIBER TERMINATION
SHALL BE INSTALLED IN NEW RACK IN EXISTING DATA ROOM
IN BUILDING 2. CONTRACTOR TO TERMINATE AND TEST NEW
FIBER RUN. HOSPITAL'S PERSONNEL TO MAKE ALL FINAL
CROSS CONNECTIONS. PROVIDE (2) COPPER LINES TO AOD
LOCATION IN CHECKIN/CHECK OUT AREAS.
NEW FIBER SHALL BE PROVIDED IN NEW INNERDUCT WITHIN
EXISTING CONDUIT IN DUCTBANK.
PROVIDE NEW FIBER IN NEW INNERDUCT IN EXISTING CONDUIT
IN BASEMENT CEILING. CONFIRM ROUNTING IN THE FIELD.
EXISTING TELEPHONE CLOSET B108A WITH INCOMING 2450
PAIRS AND PUNCHDOWNS. ALL NEW TELEPHONE DEVICES
DROPS IN PROJECT SCOPE SHALL TERMINATE IN THIS ROOM
AND EXISTING PUNCHDOWNS.
6 EXISTING CONDUIT ENTERS BUILDING 1 IN BASEMENT
FLOOR. COORDINATE EXACT LOCATION IN THE FIELD.
7 LOCATION OF SECONDARY FEEDERS ENTERING THE
BUILDING UNDERGROUND. ELECTRICAL CONTRACTOR SHALL
PROVIDE TEMPORARY SUPPORT AND PROTECTION
REQUIRED FOR INFILL CONSTRUCTION.
8 PROVIDE 2#10, 1#10G, 3/4"C FOR EXTERIOR LIGHTING
CIRCUIT. SITE LIGHTING TO BE CONTROLLED BY A
PHOTOCELL.
GRAPHIC SCALE
20' 10' 0 20' 40' 60'
SCALE: 1" = 20' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:3
A
M
CMB
ELECTRICAL SITE PLAN
1-ES-001
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1" = 20'-0"1-ES-001
1 ELECTRICAL - SITE PLAN
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
OS
OS
OS
OS
DCB
20212223
A
NIC
REFER TO DRAWING
1-ES-101B FOR
CONTINUATION
REFER TO DRAWING
1-ES-101C FOR
CONTINUATION
LR1 LR1
LR1
LR1 LR1 LR1
LR1
LR1
LR1 LR1
LR1 LR1
LR1
LR1 LR1
LR1
LD1
LR1
D ,O
S D
,O S
D ,O
S
D,OS
D ,O
S
EX1
EX1
EX1
EX1
EX1
1 1
1 2
2 1
2 1
2 1
2 1
21S-LP1A -
EX1
1 1
D ,O
S
GARAGE
EXIST. STAIR
S-100
POLICE
TREAT
TREAT
TREAT
MH VIEW
MH WAITING
TREAT
TREAT
TREAT
TREAT
CHECK-IN/OUT
PAT. TLT
EXAM
VEST.
LR1 LR1
- 1E1W-101
LR1 LR1
2 1
D ,O
S
D,OS
D,OS
D,OS
LR4
LR4
LR4
LR4
LR4
LR4
1c
2c
1c
2b
1b
2b a D b D c D d D aD bD cD dD
OS
TREAT
LR3 LR3
2a 1a
LD1
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LD1
LD1
2d
LD1
2d
LD1
2d
LD1
2d
LR2
1a
LR2
2a
LR2
2a
LR2
2a
LR2
1a
LR2
2a
LR2
2a
CHECK-IN/OUT
PCMHI EXAM
PCMHI EXAM
PCMHI EXAM
WAITING
CHECK-IN/OUT
LR2
LR2
2a
2a
LD1 LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
LD1
2b
1b
2b
2b
2b
2b
2b
2b
2b
2c
2c
2c
2c 2c
CORRIDOR
C101
LD1
CORRIDOR
C101
D ,O
S
D,OS
a
3D
3D
3D
3D
EX1
1 1
LD1
LD1 LD1
LD1
LD1
LD1
LD1
2b
2b
2b
LD1
1c
2c 2c
LD1 LD1
LW4
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL
BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"
SOURCE AS INDICATED.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS
LIGHTING PLAN NOTES
1.
2.
3.
CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE
PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND
100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND
LIGHTING LEVELS TO BECOORDINATED WITH THE COR.
LOCAL SWITCHES CONTROLLING CORRIDOR LIGHT FIXTURES
SHALL BE NON-FUNCTIONING DURING THE PROGRAMMED
DAY TIME HOURS BUT SHALL OVERRIDE THE SCENE
CONTROL DURING PROGRAMMED NIGHT TIME HOURS.
4.
LIGHTING PLAN KEYED NOTES
PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING
NORMAL BRANCH CIRCUITRY IN AREA TO NEW 2X2 SURFACE
MOUNTED LIGHT FIXTURES IN CORRIDOR. NEW WIRE AND
CONDUIT SHALL MATCH EXISTING IN ALL RESPECTS.
EXISTING CONTROL LOOP SHALL BE EXTENDED TO NEW
LIGHT FIXTURES.
PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING LIFE
SAFETY BRANCH CIRCUITRY IN AREA TO SURFACE MOUNTED
EXIT SIGNS IN CORRIDOR. NEW WIRE AND CONDUIT SHALL
MATCH EXISTING IN ALL RESPECTS.
PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING LIFE
SAFETY BRANCH CIRCUITRY IN AREA TO NEW LS1 FIXTURES
MECHANICAL ROOMS. NEW WIRE AND CONDUIT SHALL
MATCH EXISTING IN ALL RESPECTS.
PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING LIFE
SAFETY BRANCH CIRCUITRY IN AREA TO NEW 2X2 SURFACE
MOUNTED LIGHT FIXTURES IN CORRIDOR. NEW WIRE AND
CONDUIT SHALL MATCH EXISTING IN ALL RESPECTS.
EXISTING CONTROL LOOP SHALL BE EXTENDED TO NEW
LIGHT FIXTURES.
LOW VOLTAGE SWITCH CONTROLLING LIGHT FIXTURES IN
ROOM IS LOCATED IN NURSE STATION 1108.
EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN
ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF
THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING
DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS
RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING
CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND
INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS
RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH
EMERGENCY LIGHTING (LIFE SAFETY). THIS INCLUDES
PROVIDING A MINIMUM OF ONE BYPASS RELAY PER LIGHTING
CONTROL DEVICE (E.G. SWITCH, DIMMER, OCCUPANCY
SENSOR, ETC.) SERVING EMERGENCY LIGHTS TO
AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN
NORMAL POWER IS LOST AND TURN THE EMERGENCY
LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR
SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE
LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES
PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING
SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE
REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100
AS MANUFACTURED BY WATTSTOPPER OR EQUAL.
5.
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 50%:
• CONFERENCE ROOM
• BREAK ROOMS
• OFFICES
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 100%:
• LOBBIES
• RESTROMS
• EXAM ROOMS
• CONSULT ROOMS
• WAITING ROOMS
OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN
OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL
MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC
LIGHTING CONTROL.
CANOPY LIGHTING TO BE CONTROLLED VIA LIGHTING
CONTROL PANEL AND COMBINATION PHOTOCELL.
6.
7.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
F
LS1LS1
LS1
LS1
LS1
LS1
c d
17d 17c
17c
17d c
LW3
LW3 17
MECH ROM
CORRIDOR
DC
LD1 LD1
LD1 LD1
2 7
- 7E1W-102A
08' 4'
GRAPHIC SCALE
8' 16' 24'
SCALE: 1/8" = 1' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:3
A
M
CMB
ELECTRICAL SECOND & FIRST FLOOR
LIGHTING PLAN – PART A
1-ES-101A
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-101A
1 FIRST FLOOR LIGHTING PLAN - PART A
1/8" = 1'-0"1-ES-101A
2 SECOND FLOOR LIGHTING PART PLAN 1
1/4" = 1'-0"1-ES-101A
4 FIRST FLOOR LIGHTING PLAN - CANOPY
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
OS OS OS OS
OSOSOS
OSOSOS
OS
OS
OS OS OS OS
OS
OS
OS
OS
OS
OS
OS
OS OS
OS
OS
OS OS OS OSOS
OS OS OS OS OS
OS
OS
OS
OS
OS
OS
1x 2xE
42 43
F
3X
NIC
REFER TO DRAWING
1-ES-101A FOR
CONTINUATION
REFER TO DRAWING 1-
ES-101A FOR CONTINUATION
REFER TO DRAWING 1-
ES-101C FOR CONTINUATION
REFER TO DRAWING
1-ES-101C FOR
CONTINUATION
LR1 LR1 LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1 LR1
LR1LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR1
LR2
LR2 LR1
LR1 LR1
LR1
LD1
LD1
LR1
LR1
LR1
D
OS
3D3D3D3D
3D3D
3D 3D 3D 3D 3D
3D
EX1
EX1
LR1
6 2 2 6
2E1W-101 -
6 6 6 6
6 6
2 2
2 2
EX1
LR1
D
LR1
OS
LD1
LR1
LR1
LR1
LR1
LR1
LR1
LR2
NIC
LR1
LR1
LR1
LR1
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR1
LR1
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR1
LR1
LR1
LR1
LD1
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LD1
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR4 LR4 LR4
6 6 6
PCMHI EXAM
PAT. TLT
STAFF TLT
EXAM
EXAM
EXAM
CONSULT
CONSULT
EXAM
PROCEDURE
EXAM
EXAM
CONSULT
EXAM
EXAM
EXAM
EXAM
EXAM
PCMHI EXAM
PCMHI EXAM
CONSULT
EXAM
EXAM
EXAM
CONSULT
1224 CONSULT
EXAM
PROCEDURE
SHARED APPT.
PAT. TLT
SOILED UTILITY
TEAM WORK
C102
TEAM WORK
C104
CLEAN UTILITY
MEDS
MEDS
WAITING
PUB TLT
1101C
TLT
1227A
CORRIDOR
C105
CORRIDOR
C103
LINEN
LR4
OS
D
3D
D
OS
TOILET
1209A
LR2
3D
3D3D
3D 3D
3D
3D3D
3D
3D
3D
3D
3D
3D3D
3D 3D 3D 3D 3D 3D 3D 3D
3D
3D 3D 3D
3D
3D3D 3D3D
LR2
LD1
LD1
3D
LW4
LW4
LW4
LD1
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL
BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"
SOURCE AS INDICATED.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS
LIGHTING PLAN NOTES
1.
2.
3.
CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE
PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND
100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND
LIGHTING LEVELS TO BECOORDINATED WITH ARCHITECT
AND OWNER. LOCAL SWITCHES CONTROLLING CORRIDOR
LIGHT FIXTURES SHALL BE NON-FUNCTIONING DURING THE
PROGRAMMED DAY TIME HOURS BUT SHALL OVERRIDE THE
SCENE CONTROL DURING PROGRAMMED NIGHT TIME
HOURS.
4.
EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN
ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF
THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING
DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS
RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING
CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND
INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS
RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH
EMERGENCY LIGHTING (LIFE SAFETY). THIS INCLUDES
PROVIDING A MINIMUM OF ONE BYPASS RELAY PER LIGHTING
CONTROL DEVICE (E.G. SWITCH, DIMMER, OCCUPANCY
SENSOR, ETC.) SERVING EMERGENCY LIGHTS TO
AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN
NORMAL POWER IS LOST AND TURN THE EMERGENCY
LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR
SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE
LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES
PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING
SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE
REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100
AS MANUFACTURED BY WATTSTOPPER OR EQUAL.
5.
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 50%:
• CONFERENCE ROOM
• BREAK ROOMS
• OFFICES
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 100%:
• LOBBIES
• RESTROOMS
• OFFICES
• EXAM ROOMS
• CONSULT ROOMS
• WAITING ROOMS
OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN
OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL
MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC
LIGHTING CONTROL.
6.
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:5
A
M
CMB
ELECTRICAL FIRST FLOOR LIGHTING
PLAN – PART B
1-ES-101B
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-101B
1 FIRST FLOOR LIGHTING PLAN - PART B
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
OS
OS
OS OS
OS OS OS
OS
OS
OS
OS
OS
OS
OS OS
PC
OS OS
OS
OS OS
OS OS OS OS
OS
1x
2x
1920212223 33 34
41 49
F
REFER TO DRAWING
1-ES-101C FOR
CONTINUATION
NIC
LR1
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR1
LD1
LD1
LR4
LD1
LD1
LD1
D,OS D,OS D
OS
OS
OS
EX1
EX1
EX1
EX1
EX1
3 3
EX1
LR1
LR1
ELEV.
M101
HSKP
OFFICE SUPPLY
STAF TLT
STORAGE
TELE-HEALTH
CORRIDOR
C100
STAFF BREAK
1240LOCKERS
1240A
ON CALL
ON CALL
IT CLOSET
ELEC.
E100
BARI TLT
1101A
VENDING
OFFICE
PUB TLT
1101B
CONFERENCE
OFFICE
OFFICE
LR2 LR2
LR2LR2
D
LR2
LR2
LR2
LR2 LR2
LR2
4 3
LR4
LD1
LD1
LP2
LP2
LR1
LD1
LD1
LR2 LR2
LR2LR2
4 4
LD1
OS OS
LR1
LR1
LP2
LP2
STAFF TLT
NIC
ELEV.
M101
TELE-HEALTH
PUB TLT
1101D
ELEV.
M101
TELE-HEALTH
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LD1
O S
O S
- 3E1W-101
- 41S-LP1A
LR2
LR2
LR2
LR2
LR4
LR4
LR4
4LR2
LR2
LR4
LR4
OS
LR4
LR4
LR4
ELEV.
M101
TELE-HEALTH
TELE-HEALTH
PAT. TLT
SOILED UTILITY
PUB TLT
1101C
ELEV.
M101
TELE-HEALTH
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LW1
LW1
LW1 4
LW1
LW1
LW1 4
ELEC
E101
CORRIDOR
C100
D
EX1
EX1
3D3D
1x 2x 42 43 44 45
REFER TO DRAWING
1-ES-101C FOR
CONTINUATION
REFER TO DRAWING
1-ES-101B FOR
CONTINUATION
LR2
LR2 LR2
LR2 LR2
LR2 LR2
LR2
D
41S-LP1A -
3E1W-101 -
LS2 LS2
4 4
3D
STAFF TLT
STAFF TLT
HSKP
MED EQUIP
SHARED APPT. STOR.
LD1
LD1
LR1
LR1
4 4 3
LR2 LR2
LR2LR2
LR2 LR2 LR2
LR2LR2LR2
3 4
D
OS
OS OS
SHELL SPACE
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR4
LR6
LR6
LR6
LR6
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR2
LR4
LR4
LR4
LR4
LR4
LR4
LR2
LD1
LR4
SHARED APPT.
CORRIDOR
C105
LR3
EX1
LOADING DOCK
C106
LW1 LW1
4 4
3D
EX1
LR2
LR2
EX1
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL
BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"
SOURCE AS INDICATED.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS
LIGHTING PLAN NOTES
1.
2.
3.
LIGHTING PLAN KEYED NOTES
ALL EXISTING LIGHTING AND CONTROLS WITHIN EXISTING IT
ROOM SHALL BE MAINTAINED. INTERCEPT, EXTEND, AND
CONENCT TO NEW LIGHTING CIRCUIT.
CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE
PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND
100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND
LIGHTING LEVELS TO BE COORDINATED WITH ARCHITECT
AND OWNER. LOCAL SWITCHES CONTROLLING CORRIDOR
LIGHT FIXTURES SHALL BE NON-FUNCTIONING DURING THE
PROGRAMMED DAY TIME HOURS BUT SHALL OVERRIDE THE
SCENE CONTROL DURING PROGRAMMED NIGHT TIME
HOURS.
4.
LIGHTING FIXTURE LS2 IN LOADING DOCK TO BE CONTROLLED
VIA WALL MOUNTED PHOTOCELL.
EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN
ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF
THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING
DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS
RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING
CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND
INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS
RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH
EMERGENCY LIGHTING (LIFE SAFETY OR CRITICAL). THIS
INCLUDES PROVIDING A MINIMUM OF ONE BYPASS RELAY
PER LIGHTING CONTROL DEVICE (E.G. SWITCH, DIMMER,
OCCUPANCY SENSOR, ETC.) SERVING EMERGENCY LIGHTS
TO AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN
NORMAL POWER IS LOST AND TURN THE EMERGENCY
LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR
SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE
LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES
PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING
SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE
REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100
AS MANUFACTURED BY WATTSTOPPER OR EQUAL.
5.
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 50%:
• CONFERENCE ROOM
• BREAK ROOMS
• OFFICES
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 100%:
• LOBBIES
• RESTROMS
• EXAM ROOMS
• CONSULT ROOMS
LIGHTING IN CORRIDORS SHALL HAVE LOCAL DIMMING
SWITCH MOUNTED AT ALL ENDS OF THE CORRIDOR TO
OVERIDE DIMMING CAPABILITIES.
OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN
OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL
MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC
LIGHTING CONTROL.
6.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:0
A
M
CMB
ELECTRICAL FIRST FLOOR LIGHTING
PLAN – PART C
1-ES-101C
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-101C
1 FIRST FLOOR LIGHTING PLAN - PART C-A
1/4" = 1'-0"1-ES-101C
2 FIRST FLOOR LIGHTING PLAN - PART C-B
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
OS
OS
OS
OS
OS OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
OS
1x 2x
REFER TO DRAWING
FOR CONTINUATION
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STORAGE
MECHANICAL ROOM
STAFF TLT
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HSKP
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STAFF TLT
OFFICE
OFFICE
LR3 LR3
LR3 LR3
LR3LR3
LR3 LR3
LR3 LR3
LR3 LR3
LR3 LR3 LR3 LR3
LR3 LR3
LR3LR3
LR3 LR3
LR3 LR3
LR3LR3
LR3 LR3
LR3LR3
LR3LR3
LR3LR3
LR3LR3
LD1
OFFICE
OFFICE
1302 OFFICE
LR3
LR3
LR3
LR3
LR3
LR3
LR3
LR3
LR3
LR3
LR3
LR3
LD1
4 4
4 4
4 4
4 4
3 3
4 4
4 4
44 4 4
44 4 4
4 4 4 4
4 4 4 4
D D D
D
OS
D D D
D
D
D D
O S
O S
D
D
DD
D
D
LW1
LW1 4
LR3
LR3LR3
LR3
3 3
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL
BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"
SOURCE AS INDICATED.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS
LIGHTING PLAN NOTES
1.
2.
3.
CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE
PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND
100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND
LIGHTING LEVELS TO BECOORDINATED WITH ARCHITECT
AND OWNER. LOCAL OCCUPANCY SENSORS CONTROLLING
CORRIDOR LIGHT FIXTURES SHALL BE NON-FUNCTIONING
DURING THE PROGRAMMED DAY TIME HOURS BUT SHALL
OVERRIDE THE SCENE CONTROL DURING PROGRAMMED
NIGHT TIME HOURS.
4.
EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN
ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF
THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING
DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS
RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING
CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND
INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS
RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH
EMERGENCY LIGHTING (LIFE SAFETY OR CRITICAL). THIS
INCLUDES PROVIDING A MINIMUM OF ONE BYPASS RELAY
PER LIGHTING CONTROL DEVICE (E.G. SWITCH, DIMMER,
OCCUPANCY SENSOR, ETC.) SERVING EMERGENCY LIGHTS
TO AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN
NORMAL POWER IS LOST AND TURN THE EMERGENCY
LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR
SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE
LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES
PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING
SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE
REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100
AS MANUFACTURED BY WATTSTOPPER OR EQUAL.
5.
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 50%:
• CONFERENCE ROOM
• BREAK ROOMS
• OFFICES
OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS
SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON
LIGHT FIXTURES TO 100%:
• LOBBIES
• RESTROMS
• EXAM ROOMS
• CONSULT ROOMS
OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN
OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL
MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC
LIGHTING CONTROL.
6.
7. ALL WORK ASSOCIATED WITH NORTH WING INCLUDING
POWER, LIGHTING, AND FIRE ALARM SHOULD BE A DEDUCT
ALTERNATE.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:0
A
M
CMB
ELECTRICAL FIRST FLOOR LIGHTING
PLAN - PART D
1-ES-101D
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-101D
1 FIRST FLOOR LIGHTING PLAN - PART D
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
J
TV
H
J
J
J
J
M
J
J
J
J
J
J J
J
J
J
DCB
20212223
A
NIC
REFER TO DRAWING
1-ES-201B FOR
CONTINUATION
REFER TO DRAWING
1-ES-201C FOR
CONTINUATION
EF-1
- 21,23,251S-EPP1
ADO
C
H
H
H
10 15
- 231W-102A
- 221W-102A
- 211W-102A
CUH-1
CAP
CAP
CAP
CAP
- 331W-102A
GARAGE
EXIST. STAIR
S-100
POLICE
TREAT
MH VIEW
MH WAITING
TREAT
TREAT
TREAT
CHECK-IN/OUT
PAT. TLT
EXAM
VEST.
TREAT
- 191W-102A
TREAT
TREAT
- 301W-102A
- 141W-102A
H
- 10E1W-102A
- 161W-102A
201A
201A
201A
201A
201A
201A
201A
- 251W-102A
- 351W-102A
- 51W-102B
- 341W-102A
- 311W-102A
- 301W-102A
29 29
- 291W-102A
TREAT
- 361W-102A
- 391W-102A
- 411W-102A
201A
- 421W-102A
39 39
WAITING
CHECK-IN
KIOSK
- 41W-102A
- 151W-102A
- 41W-102C
- 271W-102A
- 181W-102A
1 DATA
2 DATA
AOD
CORRIDOR
C101
- 91W-102C
- 101W-102C
- 131W-102C
ADO
ADO
ADO
- 111W-102C
ADO
- 381S-LP1B
- 5E1W-102A
AOD
- 391W-102B
- 141W-102B
C
EMERGENCY
PHONE
ADO
ADO
EMERGENCY
PHONE
CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF
ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO
ROUGH IN.
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS.
POWER PLAN NOTES
COORDINATE EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION
DRAWINGS.
ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED
WITH GFCI PROTECTION.
1.
2.
3.
4.
5.
POWER PLAN KEYED NOTES
1 POWER FOR EF-1 LOCATED ON ROOF ABOVE SECOND
FLOOR.
CONDUIT FOR DATA AND POWER SHALL RUN IN CEILING
FROM FLOOR BELOW AND PENETRATE UP THROUGH FLOOR
TO NEW RECEPTACLE AND DATA DEVICES. CONTRACTOR
SHALL CORE A HOLE IN FLOOR FOR NEW CONDUIT.
REFER TO ARCHITECTS DRAWING FOR ELEVATIONS.6.
7.
MENTAL HEALTH VIEWING AND WAITING ROOM SHALL HAVE
TAMPER PROOF COVER PLATES AND SCREWS.
8.
COVERPLATES SHALL BE TAMPERPROOF WITHIN MENTAL
HEALTH EXAM AND WAITING ROOMS.
9.
PROVIDE MOTION SENSOR TO OPEN ONE LEAF OF DOUBLE
DOOR UPON ACTIVATION. OPERATION SHALL MATCH
EXISTING CONDITIONS OF EXISTING MOTION DETECTOR.
3 SECURITY CONTRACTOR SHALL REINSTALL EXISTING
KEYPADS REMOVED IN DEMO PHASE. SECURITY
CONTRACTOR SHALL REINSTALL EXISTING KEYPADS WITHIN
NEW CABINET. SECURITY CONTRACTOR IS TO CONSOLIDATE
KEYPADS TO FURTHEST EXTEND POSSIBLE. SECURITY
CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL
PLAN AND COR.
4 TAMPER PROOF SCREWS SHALL BE PROVIDED IN THIS
ROOM.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:1
A
M
CMB
ELECTRICAL FIRST FLOOR POWER
PLAN – PART A
1-ES-201A
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-201A
1 FIRST FLOOR POWER PLAN - PART A
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
J J
J J
J J
J
J
J
J J
JJ
J
J J J
JJ
J J J
J
J
JJ
J
J
J J
J
J J J J
J
J
J
J J
J
J
J
J
J
J
J J
J
J
JJ
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
TV
H
J
J
J
J J J J
J J
J
J
J
J J
J J
J J
J J
J J
J
J
J J
J
J
J
J
1x 2xE
42 43
F
3X
NIC
REFER TO DRAWING
1-ES-201A FOR
CONTINUATION
REFER TO DRAWING
1-ES-201A FOR
CONTINUATION
REFER TO DRAWING
1-ES-201C FOR
CONTINUATION
REFER TO DRAWING
1-ES-201C FOR
CONTINUATION
- 21S-LP1B
- 41S-LP1B
- 61S-LP1B
- 81S-LP1B
- 341S-LP1A
- 311S-LP1A
- 321S-LP1A
22 - 291S-LP1A
- 301S-LP1A
- 271S-LP1A
- 281S-LP1A
- 261S-LP1A
- 251S-LP1A
- 241S-LP1A
- 231S-LP1A
20 6
- 381S-LP1A
- 371S-LP1A
- 7E1S-RP1
- 9E1S-RP1 - 10E1S-RP1
- 11E1S-RP1
- 13E1S-RP1 - 16E1S-RP1
- 17E1S-RP1
- 18E1S-RP1
- 19E1S-RP1
- 11S-LP1A
- 201S-LP1A
- 6E1S-RP1
- 111S-LP1B
- 121S-LP1B
- 21E1S-RP1
- 131S-LP1B
- 141S-LP1B
- 20E1S-RP1
- 5E1S-RP1
- 101S-LP1B
- 91S-LP1B
- 211S-LP1A
- 411S-LP1A
- 15E1S-RP1
- 351S-LP1A
- 361S-LP1A
- 12E1S-RP1
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
201B
- 151S-LP1B
- 161S-LP1B
- 8E1S-RP1
- 191S-LP1A
- 391S-LP1A
- 1E1S-RP1
- 401S-LP1A
- 4E1S-RP1
- 2E1S-RP1
- 161S-LP1A- 201S-LP1B
- 211S-LP1B
- 14E1S-RP1
- 221S-LP1B
- 231S-LP1B
- 81S-LP1A
- 91S-LP1A
- 3E1S-RP1
201B
201B
- 111S-LP1A
- 71S-LP1B
- 22E1S-RP1
- 241S-LP1B
- 23E1S-RP1
- 251S-LP1B
201B
- 181S-LP1A
- 30E1S-RP1
- 121W-102B
NIC
- 25E1S-RP1
- 291S-LP1B
- 26E1S-RP1
- 281S-LP1B
- 341S-LP1B
C
C
C
- 391S-LP1B
201B
- 401S-LP1B
- 411S-LP1B
- 24E1S-RP1
201B
201B
- 421S-LP1B
PCMHI EXAM
PAT. TLT
STAFF TLT
EXAM
EXAM
EXAM
CONSULT
CONSULT
EXAM
PROCEDURE
EXAM
EXAM
CONSULT
EXAM
EXAM
EXAM
EXAM
EXAM
PCMHI EXAM
PCMHI EXAM
CONSULT
EXAM
EXAM
EXAM
CONSULT
CONSULT
EXAM
PROCEDURE
TEAM WORK
C102
TEAM WORK
C104
CLEAN UTILITY
MEDS
MEDS
TLT
1227A
CORRIDOR
C105
CORRIDOR
C103
LINEN
EXAM
1216 - 221S-LP1A
- 27E1S-RP1
- 261S-LP1B
- 271S-LP1B
- 401W-102B
- 411W-102B
- 431S-LP1B
- 28E1S-RP1
C
TOILET
1209A
PROCEDURE
W
CEILING MOUNTED
PATIENT LIFT
- 71W-102A
CEILING MOUNTED
PATIENT LIFT
W
W
REF
REF
- 301S-LP1B
(TYP.)
(TYP.)
- 151W-102C
- 121W-102C
ADO
ADO
ADO
- 381S-LP1B
38 38
- 371S-LP1B
- 361S-LP1B
- 351S-LP1B
- 11W-102C
- 21W-102C
- 31W-102C
- 51W-102C
- 61W-102C
- 321S-LP1B
- 311S-LP1B
- 331S-LP1B
ADO
C
W
W
ADO
- 261W-102A
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF
ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO
ROUGH IN.
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS.
POWER PLAN NOTES
COORDINATE EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION
DRAWINGS.
ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED
WITH GFCI PROTECTION.
1.
2.
3.
4.
5.
POWER PLAN KEYED NOTES
REFER TO PROCEDURE 1208 ON THIS SHEET FOR
TYPICAL EXAM ROOM LAYOUT.
PROVIDE POWER AND DATA CONNECTIONS AS INIDICATED
AT POKE THRU TO PRE-WIRED FURNITURE (BY OTHERS).
COORDINATE EXACT WIRING WITH FURNITURE VENDOR AND
WIRE PER MANUFACTURER'S RECOMMENDATINS. PROVIDE
WIRING FOR TELE/DATA DROPS AS INDICATED ON FLOOR
PLANS. PROVIDE A POKE THRU WITH (1) 2"C (WITH
PULLSTRING) FOR TELE/DATA WIRING. PROVIDE A POKE
THRU WITH (1) 2"C FOR POWER WIRING. POKE THRU SHALL
BE MANUFACTURED BY HUBBELL TYPE S1R6PTFF.
FURNITURE SHALL BE WIRED BY AN 8 WIRES AND 4 CIRCUITS
SYSTEM.
PROVIDE POWER AND DATA CONNECTIONS AS INIDICATED
AT WALL TO PRE-WIRED FURNITURE (BY OTHERS).
COORDINATE EXACT WIRING WITH FURNITURE VENDOR AND
WIRE PER MANUFACTURER'S RECOMMENDATINS. PROVIDE
WIRING FOR TELE/DATA DROPS AS INDICATED ON FLOOR
PLANS. PROVIDE (1) 2"C (WITH PULLSTRING) FOR TELE/DATA
WIRING. FURNITURE SHALL BE WIRED BY AN 8 WIRES AND 4
CIRCUITS SYSTEM.
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:3
A
M
CMB
ELECTRICAL FIRST FLOOR POWER
PLAN – PART B
1-ES-201B
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-201B
1 FIRST FLOOR POWER PLAN - PART B
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
T
VH
T V H
T
VH
M M
M
M
M
J
J
J
J
J
J
J
T V H
T
VH T
V H
T
VH
DN
J
J
T
VH
M
TV
H
TV
H
J
T
VH
Unoccupied Unoccupied
1x
2x
1920212223
41 49
F
E1W-101
E1W-102A
1W-102A
1W-102B
1S-LP1A
E1S-RP1
NIC
C
C
C
REFER TO DRAWING
1-ES-201C FOR
CONTINUATION
CM
REF
MC
8 8
LCP
1S-LP1B
NURSE CALL
HEAD END
GROUND BAR (TYP)
23 1
GROUND
BAR
CUH-2
E1W-102B
1W-102C ELEV.
M101
HSKP
OFFICE SUPPLY
STAF TLT
STORAGE
CORRIDOR
C100
STAFF BREAK
1240LOCKERS
1240A
ON CALL
STAFF TLT
ON CALL
IT CLOSET
ELEC.
E100
PUB TLT
1101D
BARI TLT
1101A
VENDING
OFFICE
PUB TLT
1101B
- 51W-102A
C
C
1 1
- 11W-102B
- 101W-102A
- 61W-102A
- 131W-102A
- 31W-102A
- 81W-102B
- 11W-102A
- 8E1W-102A
H
C
- 12E1W-102A
- 91W-102A
CORRIDOR
C100
CONFERENCE
EXIST. STAIR
S-102
CORRIDOR
C100
CONFERENCE
OFFICE
CORRIDOR
C100
CONFERENCE
OFFICE
NIC
EXIST. STAIR
S-102
ELEV.
M101
TELE-HEALTH
TELE-HEALTH
PAT. TLT
SOILED UTILITY
PUB TLT
1101C
PUB TLT
1101D
EXIST. STAIR
S-102
ELEV.
M101
PUB TLT
1101D
- 111W-102A
- 121W-102A
ATM
- 381W-102A
ELEC
E101
AC-2
AC-1
AC-3
AC-4
ACCU-1 ACCU-2 ACCU-3ACCU-4
VIA ACCU-4
VIA ACCU-3
VIA ACCU-2
VIA ACCU-1
- 2,4E1W-102A - 9,11E1W-102A
- 18,20E1W-102A - 1,3E1W-102A
- 201W-102A
- 81W-102A
- 6E1W-102A
- 231W-102B
- 19E1W-102A
- 21E1W-102A
- 23E1W-102A
- 81W-102C
ATC
ATC
ATC
- 131W-102C
- 131W-102B
- 71W-102C
- 29,31E1S-RP1
UPS
1 DATA
C
C
2 DATA
/ 1 VOICE
C
C
C
1x 2x 42 43 44 45
48 49
NIC
REFER TO DRAWING
1-ES-201C FOR
CONTINUATION
REFER TO DRAWING
FOR CONTINUATION
REFER TO DRAWING
1-ES-201B FOR
CONTINUATION
11 11
ADO
ADO
- 111W-102B
C
C2
- 71W-102B
EXIST. STAIR
S-102
STAFF TLT
STAFF TLT
HSKP
MED EQUIP
LOADING DOCK
C106
SHARED APPT. STOR.
- 61W-102B
- 161W-102B
- 31W-102B
EXIST. STAIR
S-102
SHARED APPT.
SHARED APPT.
CORRIDOR
C105
EXIST. STAIR
S-102
- 21W-102A
- 91W-102B
- 41W-102B
- 201W-102B
CUH-3
- 171W-102A
ADO
- 401W-102A
SHELL SPACE
CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF
ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO
ROUGH IN.
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS.
POWER PLAN NOTES
COORDINATE EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION
DRAWINGS.
ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED
WITH GFCI PROTECTION.
1.
2.
3.
4.
5.
POWER PLAN KEY NOTES
ALL EXISTING ELECTRICAL EQUIPMENT (POWER) IN ROOM
EXISTING IT ROOM SHALL BE MAINTAINED.
DISCONNECT AND MAKE SAFE EXISTING ELEVATOR
DISCONNECT FOR REUSE. INTERCEPT, EXTEND, AND
CONNECT TO EXISTING FEEDERS SERVING THE EXISTING
ELEVATOR FOR REUSE.
MICROWAVE OUTLET SHALL BE MOUNTED AT 64'' ABOVE
FINISHED FLOOR.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:5
A
M
CMB
ELECTRICAL FIRST FLOOR POWER
PLAN – PART C
1-ES-201C
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-201C
1 FIRST FLOOR POWER PLAN - PART C-A
1/4" = 1'-0"1-ES-201C
2 FIRST FLOOR POWER PLAN - PART C-B
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
J
J
J
J
J
J
JJ
J
J
J
J
1x
2x
REFER TO DRAWING
FOR CONTINUATION
OFFICE
OFFICE
OFFICE
STORAGE
MECHANICAL ROOM
STAFF TLT
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
HSKP
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
STAFF TLT
OFFICE
OFFICE
AHU-2
201D
201D
201D
201D
201D
201D
201D
201D
201D
201D
201D
201D
201D
201D
201D
- 181W-102B
- 221W-102B
- 241W-102B
- 251W-102B
- 261W-102B
- 271W-102B
- 361W-102B
- 351W-102B
- 331W-102B
- 341W-102B
- 321W-102B
- 311W-102B
- 301W-102B
- 291W-102B
- 281W-102B
- 371W-102B
- 381W-102B
OFFICE
OFFICE
OFFICE
OFFICE
- 24,26,281S-EPP1
- 27,29,311S-EPP1
VFD
VFD
- 241W-102A
2 DATA
/ 1 VOICE
CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF
ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO
ROUGH IN.
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS.
POWER PLAN NOTES
COORDINATE EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION
DRAWINGS.
ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED
WITH GFCI PROTECTION.
1.
2.
3.
4.
5.
ALL WORK ASSOCIATED WITH NORTH WING INCLUDING
POWER, LIGHTING, AND FIRE ALARM SHOULD BE A DEDUCT
ALTERNATE.
6.
GRAPHIC SCALE
4' 2' 0 4' 8' 12'
SCALE: 1/4" = 1' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:0
A
M
CMB
ELECTRICAL FIRST FLOOR POWER
PLAN - PART D
1-ES-201D
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/4" = 1'-0"1-ES-201D
1 FIRST FLOOR - POWER PLAN - PART D
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
M
CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF
ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO
ROUGH IN.
CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.
EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND
SHALL BE NOTED ON THE CONTRACTORS AS-BUILT
DRAWINGS.
BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND
INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE
DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP
FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL
NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND OPTIONS.
POWER PLAN NOTES
COORDINATE EXACT LOCATIONS OF ALL MECHANICAL
EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION
DRAWINGS.
1.
2.
3.
4.
1x 2x
33 34
42 43 44 45 46
48 49
F
3X
EF-3
AHU-1
HWP-1
HWP-2
SUPPLY
FAN
RETURN
FAN
LIGHTS &
SWITCHES
RCPT
- 7,9,111S-EPP1
- 8,10,121S-EPP1
- 131S-EPP1
- 141S-EPP1
UH-1
NIC
NIC
EF-2
- 16,18,201S-EPP1
- 15,17,191S-EPP1
- 191S-LP1B
WP
VFD
VFD
ACCU-5
- 30,32,341S-EPP1
WP
- 221S-EPP1
- 1,3,51S-EPP1
- 2,4,61S-EPP1
VFD
VFD
WP
WP
08' 4'
GRAPHIC SCALE
8' 16' 24'
SCALE: 1/8" = 1' - 0"
D A T E
T
IM
E P
R
IN
T E D th re e i n c h e s o n e f o o t
A o n e a n d o n e h a lf i n c h e s o n e f o o t
B o n e i n c h o n e f o o t
C th re e q u a rt e rs i n c h o n e f o o t
D o n e h a lf i n c h o n e f o o t
E th re e e ig h th s i n c h o n e f o o t
F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
C
D
E
F
VA FORM 08-6231
Number Date Revision
D e p a r t m e n t o f
V e t e r a n s
A ff a ir s
O ff ic il it ie s
Date
VA Project No.
Drawing No.ScaleBuilding #
Location
Project Title
Approved By:
Approved By:
Approved By:
Drawing Title
N
KEY PLAN
ARCHITECTCONSULTANTS
CIVIL
VHB
One Federal Street Building 103-3N Springfield, MA 01105
T: 413.747.7113 www.vhb.com
STRUCTURAL
Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451
T: 781.907.9000 www.sgh.com
MEP / FP
FITZEMEYER & TOCCI
300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801
T: 781.481.0210 www.f-t.com/
COST
D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801
T: 781.932.3131 www.dgjonesboston.com
185 Talcott Rd.
Williston, VT 05495
T: 802.878.8841 www.e4harchitecture.com
100% DESIGN DOCUMENTS
FULLY SPRINKLERED
631-451
As indicated
C
U se rs \r q u ie to \D o cu m e n ts
\N H
V A
C lin ic R e n o v a ti o n s a n d A d d it io n s_
M E P rq u ie to .r v t
/2
/2
:5
:0
A
M
CMB
ELECTRICAL SECOND FLOOR POWER
PLAN
1-ES-202
UPGRADE PRIMARY CARE FEBRUARY 28, 2020
CMB
CMB
1/8" = 1'-0"1-ES-202
1 SECOND FLOOR POWER PLAN
02/28/2020
VIS Construction Consultants 595 Dorset Street, Suite #5
CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF
ALL DEVICES WITH…