S02 631-451 Part 5.pdf

PDF 8 MB Posted

Attached to
Z2DA--631-451 Upgrade Primary Care
Solicitation number
36C24120R005_1
Issued by

About this file

This solicitation is for an upgrade to the primary care clinic at a Veterans Affairs medical center. Key requirements include renovations and additions to the existing facility, including upgrades to electrical, lighting, and fire alarm systems as well as low voltage systems. The work involves renovating and adding to exam rooms, waiting areas, offices, and support spaces. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The response due date is within 30 days and award is expected within 90 days of solicitation issuance. Pricing will be fixed price with payment terms of net 30. No set-asides or socioeconomic requirements are specified. The incumbent contractor was not identified.

View the file

Other files

File Type Posted
36C24120R0053 0005.pdf PDF
B1-Basement Plan.pdf PDF
DSCN0133.JPG JPG image
DSCN0134.JPG JPG image
36C24120R0053 0004.pdf PDF
36C24120R0053 0003.pdf PDF
S06 Appendices Final 7-21-2020.pdf PDF
S06 Site Visit 1 Roster.pdf PDF
36C24120R0053 0002.pdf PDF
S06 Attachment Spec 07 44 00.pdf PDF
S06 Site Visit 2 Roster.pdf PDF
36C24120R0053 0001.pdf PDF
S02 SOW Primary Care.pdf PDF
S02 Primary Care Spec Sections 0-23.pdf PDF
S02 Primary Care Spec Sections 26-33.pdf PDF
S02 631-451 Part 1.pdf PDF
S02 631-451 Part 4.pdf PDF
S02 631-451 Part 3.pdf PDF
S02 631-451 Part 2.pdf PDF
36C24120R0053_1.docx DOCX document
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRST FLOOR

FIRE ALARM RISER DIAGRAM

N.T.S.SCALE:

ALL FIELD WIRING AND EQUIPMENT SHALL BE AS REQUIRED PER

MANUFACTURERS WIRING DIAGRAMS.

CEILING MOUNTED SMOKE DETECTORS SHALL NOT BE LOCATED CLOSER

THAN 3 FT. FROM AIR SUPPLY FROM AIR SUPPLY DIFFUSERS.

PROVIDE A REMOTE TEST STATION FOR ALL DUCT MOUNTED SMOKE DETECTORS.

REFER TO ELECTRICAL DRAWINGS FOR EXACT QUANTITIES OF FIRE ALARM DEVICES.

ELECTRICAL CONTRACTOR SHALL PROGRAM, TEST AND CERTIFY FIRE

ALARM SYSTEM UPON COMPLETION WORK.

FIRE ALARM SYSTEM AND INSTALLATION SHALL COMPLY WITH APPLICABLE

REGULATIONS OF NFPA #72, LIFE-SAFETY CODE #101, NATIONAL ELECTRIC

CODE AND LOCAL FIRE DEPARTMENT.

FIRE ALARM WIRING TERMINATIONS SHALL BE MADE ON TERMINAL

BLOCKS, NO SPLICES WILL BE ALLOWED.

ELECTRICAL CONTRACTOR SHALL FIELD CONFIRM THAT ENOUGH BATTERY

CAPACITY EXISTS FOR THE FIRE ALARM SYSTEM TO OPERATE FOR 24 HOURS

IN NON-ALARM CONDITION AND CAPABLE OF OPERATING IN ALARM FOR 5

MINUTES AT THE END OF THE 24 HOUR PERIOD. FIRE ALARM VENDOR TO

PROVIDE BATTERY AMP-HOUR CALCULATIONS, RISERS AND WIRING

SCHEMATICS WITH SUBMISSION.

SYSTEM MANUFACTURER SHALL PROVIDE INSTALLATION WIRING DIAGRAM

OF THE FIRE ALARM SYSTEM, AND VERIFICATION CERTIFICATE OF SYSTEM

OPERATING PRIOR TO FINAL ACCEPTANCE.

ALL FIRE ALARM WIRING SHALL BE CLASS A (OUTGOING AND RETURNING

CIRCUITS SHALL NOT BE PHYSICALLY INSTALLED IN THE SAME RACEWAY),

FAULT ISOLATOR MODULES SHALL BE INSTALLED IN THE FACP. ALSO, FAULT

ISOLATOR MODULES WILL BE PROVIDED FOR EVERY 18 ADDRESSABLE FIRE

ALARM DEVICES. NOTIFICATION DEVICE CIRCUITS SHALL BE INSTALLED IN

SEPARATE RACEWAYS FROM SIGNALING LINE CIRCUITS.

FIRE ALARM SYSTEMNOTES:

FA1.

FA2.

FA3.

FA4.

FA5.

FA6.

FA7.

FA8.

FA9.

FA10.

TYPICAL

UTILITY

CLOSET

LINEN

CLOSET

STORAGE

CLOSET

S S S SS FSTS H F

DENOTES TO

ADDITIONAL

DEVICES

(TYPICAL)

TYPICAL STROBE

ONLY

NOTIFICATION

APPLIANCE CIRCUIT,

TYPICAL

NOTIFICATION

APPLIANCE CIRCUIT,

TYPICAL SIGNALING LINE CIRCUIT,

TYPICAL

SPRINKLER RISER

STACK

SD

ELECTRIC

CLOSET

S S

SOILED &

STERILE

SUPPLY

F F V V VF

EXISTING NOTIFIER

NFS2-3030

FIRE ALARM

CONTROL PANEL

SM PS

CM

CM

TYPICAL

UTILITY

CLOSET

LINEN

CLOSET

STORAGE

CLOSET

SSSS SFS TSHF

DENOTES TO

ADDITIONAL

DEVICES

(TYPICAL)

TYPICAL

SPRINKLER RISER

STACK

CM

FSD

24V J

SD

FIRE/SMOKE

DAMPER

ELECTRIC

CLOSET

SS

SOILED &

STERILE

SUPPLY

FFVVV F

INCOMING FIRE

MUNICIPAL FIRE

ALARM

CONNECTION

EEEE

NEW WIRING SHALL MATCH EXISTING SYSTEM METHOD.FA11.

CONNECT FIRE ALARM SYSTEM TO SENSOR CONTROLLED EGRESS SYSTEM

FOR AUTOMATIC RELEASE OF DOORS UPON FIRE ALARM ACTIVATION.

FA12.

FULLY TEST EXISTING FIRE ALARM SYSTEM PRIOR TO DEMO AND NEW WORK.

IDENTIFY ALL EXISTING FAULTS, WARNINGS, AND FAILURES TO ENGINEER AND

ARCHITECT.

FA13.

OBTAIN SERVICES OF NHVA CONTRACTED FIRE ALARM CONTRACTOR FOR ALL

TERMINATIONS AND ALL SYSTEM PROGRAMMING CHANGES.

FA14.

CM

J

CM

J

PUSH TO RELEASE

REQUEST TO EXIT

S

ELEVATOR

RECALL

MMMMMMMMMMMM

BDA

ADD ALTERNATE IF REQUIRED

110 V

CONNECT TO THE FIRE ALARM PANEL.

6 SUPERVISORY INPUTS REQUIRED:

BDA ANTENNA TROUBLE

BDA TROUBLE

BDA POWER LOSS

BDA CHARGER TROUBLE

BDA LOW BATTERY

BDA ANNUNCIATOR TROUBLE24V BATTERY

BACKUP

UL2524

LISTED BDA

DAS CABLE, ANTENNAS AND COUPLERS ARE

SHOWN FOR ILLUSTRATION PURPOSES ONLY.

CABLE ROUTES, EQUIPMENT LOCATIONS AND

THEIR QUANTITIES SHALL BE DETERMINED AN

SPECIFIED DURING THE SYSTEM DESIGN

STAGE.

½” PLENUM RATED COAXIAL CABLE SHOULD BE INSTALLED

FOLLOWING THE ELECTRICAL CODE. THE COAX SHOULD

BE SELF-SUPPORTED EVERY FOUR FEET USING CLIPS. IN

ADDITION, ZIP TIES ARE NOT TO BE USED TO SECURE ANY

PART OF THE ANTENNA SYSTEM.

BDA STATUS ANNUNCIATOR PROVIDED BY VENDOR,

MOUNTED BY FIRE ALARM CONTRACTOR IN FIRE

COMMAND ROOM OR OTHER LOCATION AS DESIGNATED

BY AHJ.

8 CONDUCTOR WIRE (CAT5E / CAT6E) FOR

CONNECTION FROM BDA TO ANNUNCIATOR. REF.

MANUFACTURERS SPECS.

ANTENNA MAST TO BE BONDED / GROUNDED TO BUILDING

STEEL IN COMPLIANCE WITH NFPA70 – ARTICLE 810

FOR USE WITH AN ARTICLE 250 APPROVED GROUNDING

ELECTRODE SYSTEM. SUPPLIED AND INSTALLED BY EC

LIGHTNING ARRESTOR, GROUNDED.

LOCATED OUTSIDE, BEFORE THE

CABLE BUILDING ENTRY

DONOR ANTENNA

DIRECTION – TBD

ROOF

1. DISTRIBUTED ANTENNA SYSTEM (DAS) CABLE, ANTENNAS

AND COUPLERS ARE SHOWN FOR ILLUSTRATION PURPOSES

ONLY. CABLE ROUTES, EQUIPMENT LOCATIONS AND THEIR

QUANTITIES SHALL BE DETERMINED BY VENDOR DURING

THE SYSTEM DESIGN STAGE.

2. THE FIRE ALARM CONTRACTOR, ENGINEER, AND ARCHITECT

SHALL REVIEW AND APPROVE THE PROPOSED EQUIPMENT

AND CABLE RISER LOCATIONS AND FIRE SURVIVABILITY

REQUIREMENTS.

3. BDA AND THE COAXIAL RISER CABLE AND ANNUNCIATOR

CABLE SHALL BE LOCATED IN A 2-HOUR FIRE RATED SPACE.

GENERAL NOTE:

ANTENNA (TYP)

FLOOR TYPICAL

#6 GROUND WIRE

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic e of

F ac il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

12" = 1'-0"

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:2

A

M

CMB

FIRE ALARM RISER DIAGRAM

1-EFA-200

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5 South Burlington, VT 05403

802-658-6100

HYD

TSV

REL

OCA

TED

LIG

HT

POL

E A

ND

ELEC

BO

X

6"X" 8 T

APP

ING

SLEE

VE

AND

VAL

VE

"W

"ó

D

REL

OCA

TED

HY

D

HH

EXIS

TING

FO

UND

ATIO

N

DRA

IN T

O R

EMA

IN

VAN

VAN

A M

B U

L A

N C

E O

N L Y

18'

12'

5'

8'

21.

5'

8'

8'

8'

8'

5'

8'

8'

5'

8'

1.5%

SLO

PE

PRO

POS

ED

LOA

DING

DO

CK

BIT

DRIV

EWA

Y

BIT

PAR

KING

CON

C W

ALK

INFILL

1,994 SF

HH H

HH

H H

H H

H H

H H

H

CO

CO

C

C

Fib er O pt ic Co m m s ee -4 co nd uit s in du ct ba nk

Elec tric

#20, 2 4

" co ndui ts

C

C

C

C

C unknown Com m line picked up by verizon apr 2009

Telephone Line

W

-A

E

-A

Loading Dock

COOLER CHILLER UNIT

Un kn ow n U til ity s ee d ra wi ng S /S

C al le d ou t as

FM

YD H

EB

O X

S

D

D

EBO

X

MH

HH

HH

HH

HH

HH

HH

HH

HH

HH

HH

EXISTING

MAIN IT ROOM

EXISTING IT

ROOM E-102

NEW IT CLOSET 1247

EXISTING

TELEPHONE CLOSET

B108A

E

EXISTING PAD

MOUNTED

TRANSFORMER

J

E

EXISTING

GENERATOR

BUILDING

LB1

LB1

LB1

LB1

LB1

LB1

LB1

LB1

LB1

LB1

NEW FIBER IN INNERDUCT SHALL RUN OVERHEAD IN

EXISTING CONDUITS TO ADJACENT STORAGE ROOM.

EXISTING JUNCTION BOX (IN STORAGE ROOM ADJACENT TO

DATA ROOM) WHERE EXISTING CONDUIT TURN DOWN TO

BASEMENT AND OUT OF THE BUILDING. COORDINATE EXACT

LOCATION IN THE FIELD.

SITE PLAN KEYED NOTES

PROVIDE NEW FIBER RUN FROM DATA ROOM IN BUILDING 2

TO NEW IT ROOM 1247 IN RENOVATION AREA OF BUILDING 1.

PROVIDE (2) 12 STRAND MULTI-MODE AND (1) 12 STRAND

SINGLE-MODE FIBER CABLES. NEW FIBER TERMINATION

SHALL BE INSTALLED IN NEW RACK IN EXISTING DATA ROOM

IN BUILDING 2. CONTRACTOR TO TERMINATE AND TEST NEW

FIBER RUN. HOSPITAL'S PERSONNEL TO MAKE ALL FINAL

CROSS CONNECTIONS. PROVIDE (2) COPPER LINES TO AOD

LOCATION IN CHECKIN/CHECK OUT AREAS.

NEW FIBER SHALL BE PROVIDED IN NEW INNERDUCT WITHIN

EXISTING CONDUIT IN DUCTBANK.

PROVIDE NEW FIBER IN NEW INNERDUCT IN EXISTING CONDUIT

IN BASEMENT CEILING. CONFIRM ROUNTING IN THE FIELD.

EXISTING TELEPHONE CLOSET B108A WITH INCOMING 2450

PAIRS AND PUNCHDOWNS. ALL NEW TELEPHONE DEVICES

DROPS IN PROJECT SCOPE SHALL TERMINATE IN THIS ROOM

AND EXISTING PUNCHDOWNS.

6 EXISTING CONDUIT ENTERS BUILDING 1 IN BASEMENT

FLOOR. COORDINATE EXACT LOCATION IN THE FIELD.

7 LOCATION OF SECONDARY FEEDERS ENTERING THE

BUILDING UNDERGROUND. ELECTRICAL CONTRACTOR SHALL

PROVIDE TEMPORARY SUPPORT AND PROTECTION

REQUIRED FOR INFILL CONSTRUCTION.

8 PROVIDE 2#10, 1#10G, 3/4"C FOR EXTERIOR LIGHTING

CIRCUIT. SITE LIGHTING TO BE CONTROLLED BY A

PHOTOCELL.

GRAPHIC SCALE

20' 10' 0 20' 40' 60'

SCALE: 1" = 20' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:3

A

M

CMB

ELECTRICAL SITE PLAN

1-ES-001

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1" = 20'-0"1-ES-001

1 ELECTRICAL - SITE PLAN

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

OS

OS

OS

OS

DCB

20212223

A

NIC

REFER TO DRAWING

1-ES-101B FOR

CONTINUATION

REFER TO DRAWING

1-ES-101C FOR

CONTINUATION

LR1 LR1

LR1

LR1 LR1 LR1

LR1

LR1

LR1 LR1

LR1 LR1

LR1

LR1 LR1

LR1

LD1

LR1

D ,O

S D

,O S

D ,O

S

D,OS

D ,O

S

EX1

EX1

EX1

EX1

EX1

1 1

1 2

2 1

2 1

2 1

2 1

21S-LP1A -

EX1

1 1

D ,O

S

GARAGE

EXIST. STAIR

S-100

POLICE

TREAT

TREAT

TREAT

MH VIEW

MH WAITING

TREAT

TREAT

TREAT

TREAT

CHECK-IN/OUT

PAT. TLT

EXAM

VEST.

LR1 LR1

- 1E1W-101

LR1 LR1

2 1

D ,O

S

D,OS

D,OS

D,OS

LR4

LR4

LR4

LR4

LR4

LR4

1c

2c

1c

2b

1b

2b a D b D c D d D aD bD cD dD

OS

TREAT

LR3 LR3

2a 1a

LD1

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LD1

LD1

2d

LD1

2d

LD1

2d

LD1

2d

LR2

1a

LR2

2a

LR2

2a

LR2

2a

LR2

1a

LR2

2a

LR2

2a

CHECK-IN/OUT

PCMHI EXAM

PCMHI EXAM

PCMHI EXAM

WAITING

CHECK-IN/OUT

LR2

LR2

2a

2a

LD1 LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

LD1

2b

1b

2b

2b

2b

2b

2b

2b

2b

2c

2c

2c

2c 2c

CORRIDOR

C101

LD1

CORRIDOR

C101

D ,O

S

D,OS

a

3D

3D

3D

3D

EX1

1 1

LD1

LD1 LD1

LD1

LD1

LD1

LD1

2b

2b

2b

LD1

1c

2c 2c

LD1 LD1

LW4

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL

BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"

SOURCE AS INDICATED.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS

LIGHTING PLAN NOTES

1.

2.

3.

CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE

PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND

100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND

LIGHTING LEVELS TO BECOORDINATED WITH THE COR.

LOCAL SWITCHES CONTROLLING CORRIDOR LIGHT FIXTURES

SHALL BE NON-FUNCTIONING DURING THE PROGRAMMED

DAY TIME HOURS BUT SHALL OVERRIDE THE SCENE

CONTROL DURING PROGRAMMED NIGHT TIME HOURS.

4.

LIGHTING PLAN KEYED NOTES

PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING

NORMAL BRANCH CIRCUITRY IN AREA TO NEW 2X2 SURFACE

MOUNTED LIGHT FIXTURES IN CORRIDOR. NEW WIRE AND

CONDUIT SHALL MATCH EXISTING IN ALL RESPECTS.

EXISTING CONTROL LOOP SHALL BE EXTENDED TO NEW

LIGHT FIXTURES.

PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING LIFE

SAFETY BRANCH CIRCUITRY IN AREA TO SURFACE MOUNTED

EXIT SIGNS IN CORRIDOR. NEW WIRE AND CONDUIT SHALL

MATCH EXISTING IN ALL RESPECTS.

PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING LIFE

SAFETY BRANCH CIRCUITRY IN AREA TO NEW LS1 FIXTURES

MECHANICAL ROOMS. NEW WIRE AND CONDUIT SHALL

MATCH EXISTING IN ALL RESPECTS.

PROVIDE ALL CONDUIT AND WIRE TO EXTEND EXISTING LIFE

SAFETY BRANCH CIRCUITRY IN AREA TO NEW 2X2 SURFACE

MOUNTED LIGHT FIXTURES IN CORRIDOR. NEW WIRE AND

CONDUIT SHALL MATCH EXISTING IN ALL RESPECTS.

EXISTING CONTROL LOOP SHALL BE EXTENDED TO NEW

LIGHT FIXTURES.

LOW VOLTAGE SWITCH CONTROLLING LIGHT FIXTURES IN

ROOM IS LOCATED IN NURSE STATION 1108.

EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN

ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF

THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING

DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS

RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING

CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND

INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS

RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH

EMERGENCY LIGHTING (LIFE SAFETY). THIS INCLUDES

PROVIDING A MINIMUM OF ONE BYPASS RELAY PER LIGHTING

CONTROL DEVICE (E.G. SWITCH, DIMMER, OCCUPANCY

SENSOR, ETC.) SERVING EMERGENCY LIGHTS TO

AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN

NORMAL POWER IS LOST AND TURN THE EMERGENCY

LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR

SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE

LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES

PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING

SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE

REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100

AS MANUFACTURED BY WATTSTOPPER OR EQUAL.

5.

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 50%:

• CONFERENCE ROOM

• BREAK ROOMS

• OFFICES

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 100%:

• LOBBIES

• RESTROMS

• EXAM ROOMS

• CONSULT ROOMS

• WAITING ROOMS

OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN

OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL

MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC

LIGHTING CONTROL.

CANOPY LIGHTING TO BE CONTROLLED VIA LIGHTING

CONTROL PANEL AND COMBINATION PHOTOCELL.

6.

7.

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

F

LS1LS1

LS1

LS1

LS1

LS1

c d

17d 17c

17c

17d c

LW3

LW3 17

MECH ROM

CORRIDOR

DC

LD1 LD1

LD1 LD1

2 7

- 7E1W-102A

08' 4'

GRAPHIC SCALE

8' 16' 24'

SCALE: 1/8" = 1' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:3

A

M

CMB

ELECTRICAL SECOND & FIRST FLOOR

LIGHTING PLAN – PART A

1-ES-101A

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-101A

1 FIRST FLOOR LIGHTING PLAN - PART A

1/8" = 1'-0"1-ES-101A

2 SECOND FLOOR LIGHTING PART PLAN 1

1/4" = 1'-0"1-ES-101A

4 FIRST FLOOR LIGHTING PLAN - CANOPY

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

OS OS OS OS

OSOSOS

OSOSOS

OS

OS

OS OS OS OS

OS

OS

OS

OS

OS

OS

OS

OS OS

OS

OS

OS OS OS OSOS

OS OS OS OS OS

OS

OS

OS

OS

OS

OS

1x 2xE

42 43

F

3X

NIC

REFER TO DRAWING

1-ES-101A FOR

CONTINUATION

REFER TO DRAWING 1-

ES-101A FOR CONTINUATION

REFER TO DRAWING 1-

ES-101C FOR CONTINUATION

REFER TO DRAWING

1-ES-101C FOR

CONTINUATION

LR1 LR1 LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1 LR1

LR1LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR1

LR2

LR2 LR1

LR1 LR1

LR1

LD1

LD1

LR1

LR1

LR1

D

OS

3D3D3D3D

3D3D

3D 3D 3D 3D 3D

3D

EX1

EX1

LR1

6 2 2 6

2E1W-101 -

6 6 6 6

6 6

2 2

2 2

EX1

LR1

D

LR1

OS

LD1

LR1

LR1

LR1

LR1

LR1

LR1

LR2

NIC

LR1

LR1

LR1

LR1

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR1

LR1

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR1

LR1

LR1

LR1

LD1

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LD1

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR4 LR4 LR4

6 6 6

PCMHI EXAM

PAT. TLT

STAFF TLT

EXAM

EXAM

EXAM

CONSULT

CONSULT

EXAM

PROCEDURE

EXAM

EXAM

CONSULT

EXAM

EXAM

EXAM

EXAM

EXAM

PCMHI EXAM

PCMHI EXAM

CONSULT

EXAM

EXAM

EXAM

CONSULT

1224 CONSULT

EXAM

PROCEDURE

SHARED APPT.

PAT. TLT

SOILED UTILITY

TEAM WORK

C102

TEAM WORK

C104

CLEAN UTILITY

MEDS

MEDS

WAITING

PUB TLT

1101C

TLT

1227A

CORRIDOR

C105

CORRIDOR

C103

LINEN

LR4

OS

D

3D

D

OS

TOILET

1209A

LR2

3D

3D3D

3D 3D

3D

3D3D

3D

3D

3D

3D

3D

3D3D

3D 3D 3D 3D 3D 3D 3D 3D

3D

3D 3D 3D

3D

3D3D 3D3D

LR2

LD1

LD1

3D

LW4

LW4

LW4

LD1

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL

BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"

SOURCE AS INDICATED.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS

LIGHTING PLAN NOTES

1.

2.

3.

CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE

PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND

100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND

LIGHTING LEVELS TO BECOORDINATED WITH ARCHITECT

AND OWNER. LOCAL SWITCHES CONTROLLING CORRIDOR

LIGHT FIXTURES SHALL BE NON-FUNCTIONING DURING THE

PROGRAMMED DAY TIME HOURS BUT SHALL OVERRIDE THE

SCENE CONTROL DURING PROGRAMMED NIGHT TIME

HOURS.

4.

EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN

ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF

THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING

DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS

RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING

CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND

INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS

RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH

EMERGENCY LIGHTING (LIFE SAFETY). THIS INCLUDES

PROVIDING A MINIMUM OF ONE BYPASS RELAY PER LIGHTING

CONTROL DEVICE (E.G. SWITCH, DIMMER, OCCUPANCY

SENSOR, ETC.) SERVING EMERGENCY LIGHTS TO

AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN

NORMAL POWER IS LOST AND TURN THE EMERGENCY

LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR

SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE

LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES

PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING

SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE

REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100

AS MANUFACTURED BY WATTSTOPPER OR EQUAL.

5.

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 50%:

• CONFERENCE ROOM

• BREAK ROOMS

• OFFICES

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 100%:

• LOBBIES

• RESTROOMS

• OFFICES

• EXAM ROOMS

• CONSULT ROOMS

• WAITING ROOMS

OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN

OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL

MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC

LIGHTING CONTROL.

6.

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:5

A

M

CMB

ELECTRICAL FIRST FLOOR LIGHTING

PLAN – PART B

1-ES-101B

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-101B

1 FIRST FLOOR LIGHTING PLAN - PART B

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

OS

OS

OS OS

OS OS OS

OS

OS

OS

OS

OS

OS

OS OS

PC

OS OS

OS

OS OS

OS OS OS OS

OS

1x

2x

1920212223 33 34

41 49

F

REFER TO DRAWING

1-ES-101C FOR

CONTINUATION

NIC

LR1

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR1

LD1

LD1

LR4

LD1

LD1

LD1

D,OS D,OS D

OS

OS

OS

EX1

EX1

EX1

EX1

EX1

3 3

EX1

LR1

LR1

ELEV.

M101

HSKP

OFFICE SUPPLY

STAF TLT

STORAGE

TELE-HEALTH

CORRIDOR

C100

STAFF BREAK

1240LOCKERS

1240A

ON CALL

ON CALL

IT CLOSET

ELEC.

E100

BARI TLT

1101A

VENDING

OFFICE

PUB TLT

1101B

CONFERENCE

OFFICE

OFFICE

LR2 LR2

LR2LR2

D

LR2

LR2

LR2

LR2 LR2

LR2

4 3

LR4

LD1

LD1

LP2

LP2

LR1

LD1

LD1

LR2 LR2

LR2LR2

4 4

LD1

OS OS

LR1

LR1

LP2

LP2

STAFF TLT

NIC

ELEV.

M101

TELE-HEALTH

PUB TLT

1101D

ELEV.

M101

TELE-HEALTH

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LD1

O S

O S

- 3E1W-101

- 41S-LP1A

LR2

LR2

LR2

LR2

LR4

LR4

LR4

4LR2

LR2

LR4

LR4

OS

LR4

LR4

LR4

ELEV.

M101

TELE-HEALTH

TELE-HEALTH

PAT. TLT

SOILED UTILITY

PUB TLT

1101C

ELEV.

M101

TELE-HEALTH

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LW1

LW1

LW1 4

LW1

LW1

LW1 4

ELEC

E101

CORRIDOR

C100

D

EX1

EX1

3D3D

1x 2x 42 43 44 45

REFER TO DRAWING

1-ES-101C FOR

CONTINUATION

REFER TO DRAWING

1-ES-101B FOR

CONTINUATION

LR2

LR2 LR2

LR2 LR2

LR2 LR2

LR2

D

41S-LP1A -

3E1W-101 -

LS2 LS2

4 4

3D

STAFF TLT

STAFF TLT

HSKP

MED EQUIP

SHARED APPT. STOR.

LD1

LD1

LR1

LR1

4 4 3

LR2 LR2

LR2LR2

LR2 LR2 LR2

LR2LR2LR2

3 4

D

OS

OS OS

SHELL SPACE

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR4

LR6

LR6

LR6

LR6

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR2

LR4

LR4

LR4

LR4

LR4

LR4

LR2

LD1

LR4

SHARED APPT.

CORRIDOR

C105

LR3

EX1

LOADING DOCK

C106

LW1 LW1

4 4

3D

EX1

LR2

LR2

EX1

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL

BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"

SOURCE AS INDICATED.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS

LIGHTING PLAN NOTES

1.

2.

3.

LIGHTING PLAN KEYED NOTES

ALL EXISTING LIGHTING AND CONTROLS WITHIN EXISTING IT

ROOM SHALL BE MAINTAINED. INTERCEPT, EXTEND, AND

CONENCT TO NEW LIGHTING CIRCUIT.

CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE

PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND

100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND

LIGHTING LEVELS TO BE COORDINATED WITH ARCHITECT

AND OWNER. LOCAL SWITCHES CONTROLLING CORRIDOR

LIGHT FIXTURES SHALL BE NON-FUNCTIONING DURING THE

PROGRAMMED DAY TIME HOURS BUT SHALL OVERRIDE THE

SCENE CONTROL DURING PROGRAMMED NIGHT TIME

HOURS.

4.

LIGHTING FIXTURE LS2 IN LOADING DOCK TO BE CONTROLLED

VIA WALL MOUNTED PHOTOCELL.

EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN

ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF

THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING

DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS

RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING

CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND

INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS

RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH

EMERGENCY LIGHTING (LIFE SAFETY OR CRITICAL). THIS

INCLUDES PROVIDING A MINIMUM OF ONE BYPASS RELAY

PER LIGHTING CONTROL DEVICE (E.G. SWITCH, DIMMER,

OCCUPANCY SENSOR, ETC.) SERVING EMERGENCY LIGHTS

TO AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN

NORMAL POWER IS LOST AND TURN THE EMERGENCY

LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR

SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE

LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES

PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING

SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE

REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100

AS MANUFACTURED BY WATTSTOPPER OR EQUAL.

5.

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 50%:

• CONFERENCE ROOM

• BREAK ROOMS

• OFFICES

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 100%:

• LOBBIES

• RESTROMS

• EXAM ROOMS

• CONSULT ROOMS

LIGHTING IN CORRIDORS SHALL HAVE LOCAL DIMMING

SWITCH MOUNTED AT ALL ENDS OF THE CORRIDOR TO

OVERIDE DIMMING CAPABILITIES.

OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN

OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL

MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC

LIGHTING CONTROL.

6.

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:0

A

M

CMB

ELECTRICAL FIRST FLOOR LIGHTING

PLAN – PART C

1-ES-101C

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-101C

1 FIRST FLOOR LIGHTING PLAN - PART C-A

1/4" = 1'-0"1-ES-101C

2 FIRST FLOOR LIGHTING PLAN - PART C-B

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

OS

OS

OS

OS

OS OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

OS

1x 2x

REFER TO DRAWING

FOR CONTINUATION

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

STORAGE

MECHANICAL ROOM

STAFF TLT

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HSKP

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

STAFF TLT

OFFICE

OFFICE

LR3 LR3

LR3 LR3

LR3LR3

LR3 LR3

LR3 LR3

LR3 LR3

LR3 LR3 LR3 LR3

LR3 LR3

LR3LR3

LR3 LR3

LR3 LR3

LR3LR3

LR3 LR3

LR3LR3

LR3LR3

LR3LR3

LR3LR3

LD1

OFFICE

OFFICE

1302 OFFICE

LR3

LR3

LR3

LR3

LR3

LR3

LR3

LR3

LR3

LR3

LR3

LR3

LD1

4 4

4 4

4 4

4 4

3 3

4 4

4 4

44 4 4

44 4 4

4 4 4 4

4 4 4 4

D D D

D

OS

D D D

D

D

D D

O S

O S

D

D

DD

D

D

LW1

LW1 4

LR3

LR3LR3

LR3

3 3

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

EXIT SIGNS, FIXTURES DESIGNATED AS NIGHT LIGHTS SHALL

BE CONNECTED TO AN UNSWITCHED, CONSTANT "ON"

SOURCE AS INDICATED.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS

LIGHTING PLAN NOTES

1.

2.

3.

CORRIDOR AND WAITING ROOM LIGHT FIXTURES SHALL BE

PROGRAMMED TO 20% DURING NIGHT TIME HOURS AND

100% DURING DAYTIME HOURS. FINAL SCENES, HOURS AND

LIGHTING LEVELS TO BECOORDINATED WITH ARCHITECT

AND OWNER. LOCAL OCCUPANCY SENSORS CONTROLLING

CORRIDOR LIGHT FIXTURES SHALL BE NON-FUNCTIONING

DURING THE PROGRAMMED DAY TIME HOURS BUT SHALL

OVERRIDE THE SCENE CONTROL DURING PROGRAMMED

NIGHT TIME HOURS.

4.

EMERGENCY LIGHTING BYPASS RELAYS ARE NOT SHOWN

ON THE DRAWINGS. IT SHALL BE THE RESPONSIBILITY OF

THE ELECTRICAL CONTRACTOR TO REVIEW THE LIGHTING

DRAWINGS AND PROVIDE EMERGENCY LIGHTING BYPASS

RELAYS AS REQUIRED TO MEET LOCAL AND STATE BUILDING

CODES. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND

INSTALL A UL 924 LISTED EMERGENCY LIGHTING BYPASS

RELAY DEVICE IN ALL ROOMS AND AREAS INDICATED WITH

EMERGENCY LIGHTING (LIFE SAFETY OR CRITICAL). THIS

INCLUDES PROVIDING A MINIMUM OF ONE BYPASS RELAY

PER LIGHTING CONTROL DEVICE (E.G. SWITCH, DIMMER,

OCCUPANCY SENSOR, ETC.) SERVING EMERGENCY LIGHTS

TO AUTOMATICALLY BYPASS THE LIGHTING CONTROL WHEN

NORMAL POWER IS LOST AND TURN THE EMERGENCY

LIGHTING TO FULL ON. THE ELECTRICAL CONTRACTOR

SHALL COORDINATE EXACT BYPASS RELAY TYPE WITH THE

LIGHTING CONTROL SYSTEM AND LIGHTING FIXTURES

PROVIDED TO ENSURE A FULLY FUNCTIONAL LIGHTING

SYSTEM IS INSTALLED MEETING ALL LOCAL AND STATE

REGULATIONS. BYPASS RELAY SHALL BE MODEL ELCU-100

AS MANUFACTURED BY WATTSTOPPER OR EQUAL.

5.

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 50%:

• CONFERENCE ROOM

• BREAK ROOMS

• OFFICES

OCCUPANCY SENSORS WITHIN THE FOLLOWING AREAS

SHALL BE PROGRAMMED TO AUTOMATICALLY TURN ON

LIGHT FIXTURES TO 100%:

• LOBBIES

• RESTROMS

• EXAM ROOMS

• CONSULT ROOMS

OCCUPANCY SENSORS SHALL BE PROGRAMMED TO TURN

OFF THE LIGHT FIXTURES AFTER 30 MINUTES. LOCAL WALL

MOUNTED CONTROLS SHALL OVERRIED AUTOMATIC

LIGHTING CONTROL.

6.

7. ALL WORK ASSOCIATED WITH NORTH WING INCLUDING

POWER, LIGHTING, AND FIRE ALARM SHOULD BE A DEDUCT

ALTERNATE.

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:0

A

M

CMB

ELECTRICAL FIRST FLOOR LIGHTING

PLAN - PART D

1-ES-101D

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-101D

1 FIRST FLOOR LIGHTING PLAN - PART D

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

J

TV

H

J

J

J

J

M

J

J

J

J

J

J J

J

J

J

DCB

20212223

A

NIC

REFER TO DRAWING

1-ES-201B FOR

CONTINUATION

REFER TO DRAWING

1-ES-201C FOR

CONTINUATION

EF-1

- 21,23,251S-EPP1

ADO

C

H

H

H

10 15

- 231W-102A

- 221W-102A

- 211W-102A

CUH-1

CAP

CAP

CAP

CAP

- 331W-102A

GARAGE

EXIST. STAIR

S-100

POLICE

TREAT

MH VIEW

MH WAITING

TREAT

TREAT

TREAT

CHECK-IN/OUT

PAT. TLT

EXAM

VEST.

TREAT

- 191W-102A

TREAT

TREAT

- 301W-102A

- 141W-102A

H

- 10E1W-102A

- 161W-102A

201A

201A

201A

201A

201A

201A

201A

- 251W-102A

- 351W-102A

- 51W-102B

- 341W-102A

- 311W-102A

- 301W-102A

29 29

- 291W-102A

TREAT

- 361W-102A

- 391W-102A

- 411W-102A

201A

- 421W-102A

39 39

WAITING

CHECK-IN

KIOSK

- 41W-102A

- 151W-102A

- 41W-102C

- 271W-102A

- 181W-102A

1 DATA

2 DATA

AOD

CORRIDOR

C101

- 91W-102C

- 101W-102C

- 131W-102C

ADO

ADO

ADO

- 111W-102C

ADO

- 381S-LP1B

- 5E1W-102A

AOD

- 391W-102B

- 141W-102B

C

EMERGENCY

PHONE

ADO

ADO

EMERGENCY

PHONE

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED

WITH GFCI PROTECTION.

1.

2.

3.

4.

5.

POWER PLAN KEYED NOTES

1 POWER FOR EF-1 LOCATED ON ROOF ABOVE SECOND

FLOOR.

CONDUIT FOR DATA AND POWER SHALL RUN IN CEILING

FROM FLOOR BELOW AND PENETRATE UP THROUGH FLOOR

TO NEW RECEPTACLE AND DATA DEVICES. CONTRACTOR

SHALL CORE A HOLE IN FLOOR FOR NEW CONDUIT.

REFER TO ARCHITECTS DRAWING FOR ELEVATIONS.6.

7.

MENTAL HEALTH VIEWING AND WAITING ROOM SHALL HAVE

TAMPER PROOF COVER PLATES AND SCREWS.

8.

COVERPLATES SHALL BE TAMPERPROOF WITHIN MENTAL

HEALTH EXAM AND WAITING ROOMS.

9.

PROVIDE MOTION SENSOR TO OPEN ONE LEAF OF DOUBLE

DOOR UPON ACTIVATION. OPERATION SHALL MATCH

EXISTING CONDITIONS OF EXISTING MOTION DETECTOR.

3 SECURITY CONTRACTOR SHALL REINSTALL EXISTING

KEYPADS REMOVED IN DEMO PHASE. SECURITY

CONTRACTOR SHALL REINSTALL EXISTING KEYPADS WITHIN

NEW CABINET. SECURITY CONTRACTOR IS TO CONSOLIDATE

KEYPADS TO FURTHEST EXTEND POSSIBLE. SECURITY

CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL

PLAN AND COR.

4 TAMPER PROOF SCREWS SHALL BE PROVIDED IN THIS

ROOM.

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:1

A

M

CMB

ELECTRICAL FIRST FLOOR POWER

PLAN – PART A

1-ES-201A

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-201A

1 FIRST FLOOR POWER PLAN - PART A

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

J J

J J

J J

J

J

J

J J

JJ

J

J J J

JJ

J J J

J

J

JJ

J

J

J J

J

J J J J

J

J

J

J J

J

J

J

J

J

J

J J

J

J

JJ

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

TV

H

J

J

J

J J J J

J J

J

J

J

J J

J J

J J

J J

J J

J

J

J J

J

J

J

J

1x 2xE

42 43

F

3X

NIC

REFER TO DRAWING

1-ES-201A FOR

CONTINUATION

REFER TO DRAWING

1-ES-201A FOR

CONTINUATION

REFER TO DRAWING

1-ES-201C FOR

CONTINUATION

REFER TO DRAWING

1-ES-201C FOR

CONTINUATION

- 21S-LP1B

- 41S-LP1B

- 61S-LP1B

- 81S-LP1B

- 341S-LP1A

- 311S-LP1A

- 321S-LP1A

22 - 291S-LP1A

- 301S-LP1A

- 271S-LP1A

- 281S-LP1A

- 261S-LP1A

- 251S-LP1A

- 241S-LP1A

- 231S-LP1A

20 6

- 381S-LP1A

- 371S-LP1A

- 7E1S-RP1

- 9E1S-RP1 - 10E1S-RP1

- 11E1S-RP1

- 13E1S-RP1 - 16E1S-RP1

- 17E1S-RP1

- 18E1S-RP1

- 19E1S-RP1

- 11S-LP1A

- 201S-LP1A

- 6E1S-RP1

- 111S-LP1B

- 121S-LP1B

- 21E1S-RP1

- 131S-LP1B

- 141S-LP1B

- 20E1S-RP1

- 5E1S-RP1

- 101S-LP1B

- 91S-LP1B

- 211S-LP1A

- 411S-LP1A

- 15E1S-RP1

- 351S-LP1A

- 361S-LP1A

- 12E1S-RP1

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

201B

- 151S-LP1B

- 161S-LP1B

- 8E1S-RP1

- 191S-LP1A

- 391S-LP1A

- 1E1S-RP1

- 401S-LP1A

- 4E1S-RP1

- 2E1S-RP1

- 161S-LP1A- 201S-LP1B

- 211S-LP1B

- 14E1S-RP1

- 221S-LP1B

- 231S-LP1B

- 81S-LP1A

- 91S-LP1A

- 3E1S-RP1

201B

201B

- 111S-LP1A

- 71S-LP1B

- 22E1S-RP1

- 241S-LP1B

- 23E1S-RP1

- 251S-LP1B

201B

- 181S-LP1A

- 30E1S-RP1

- 121W-102B

NIC

- 25E1S-RP1

- 291S-LP1B

- 26E1S-RP1

- 281S-LP1B

- 341S-LP1B

C

C

C

- 391S-LP1B

201B

- 401S-LP1B

- 411S-LP1B

- 24E1S-RP1

201B

201B

- 421S-LP1B

PCMHI EXAM

PAT. TLT

STAFF TLT

EXAM

EXAM

EXAM

CONSULT

CONSULT

EXAM

PROCEDURE

EXAM

EXAM

CONSULT

EXAM

EXAM

EXAM

EXAM

EXAM

PCMHI EXAM

PCMHI EXAM

CONSULT

EXAM

EXAM

EXAM

CONSULT

CONSULT

EXAM

PROCEDURE

TEAM WORK

C102

TEAM WORK

C104

CLEAN UTILITY

MEDS

MEDS

TLT

1227A

CORRIDOR

C105

CORRIDOR

C103

LINEN

EXAM

1216 - 221S-LP1A

- 27E1S-RP1

- 261S-LP1B

- 271S-LP1B

- 401W-102B

- 411W-102B

- 431S-LP1B

- 28E1S-RP1

C

TOILET

1209A

PROCEDURE

W

CEILING MOUNTED

PATIENT LIFT

- 71W-102A

CEILING MOUNTED

PATIENT LIFT

W

W

REF

REF

- 301S-LP1B

(TYP.)

(TYP.)

- 151W-102C

- 121W-102C

ADO

ADO

ADO

- 381S-LP1B

38 38

- 371S-LP1B

- 361S-LP1B

- 351S-LP1B

- 11W-102C

- 21W-102C

- 31W-102C

- 51W-102C

- 61W-102C

- 321S-LP1B

- 311S-LP1B

- 331S-LP1B

ADO

C

W

W

ADO

- 261W-102A

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED

WITH GFCI PROTECTION.

1.

2.

3.

4.

5.

POWER PLAN KEYED NOTES

REFER TO PROCEDURE 1208 ON THIS SHEET FOR

TYPICAL EXAM ROOM LAYOUT.

PROVIDE POWER AND DATA CONNECTIONS AS INIDICATED

AT POKE THRU TO PRE-WIRED FURNITURE (BY OTHERS).

COORDINATE EXACT WIRING WITH FURNITURE VENDOR AND

WIRE PER MANUFACTURER'S RECOMMENDATINS. PROVIDE

WIRING FOR TELE/DATA DROPS AS INDICATED ON FLOOR

PLANS. PROVIDE A POKE THRU WITH (1) 2"C (WITH

PULLSTRING) FOR TELE/DATA WIRING. PROVIDE A POKE

THRU WITH (1) 2"C FOR POWER WIRING. POKE THRU SHALL

BE MANUFACTURED BY HUBBELL TYPE S1R6PTFF.

FURNITURE SHALL BE WIRED BY AN 8 WIRES AND 4 CIRCUITS

SYSTEM.

PROVIDE POWER AND DATA CONNECTIONS AS INIDICATED

AT WALL TO PRE-WIRED FURNITURE (BY OTHERS).

COORDINATE EXACT WIRING WITH FURNITURE VENDOR AND

WIRE PER MANUFACTURER'S RECOMMENDATINS. PROVIDE

WIRING FOR TELE/DATA DROPS AS INDICATED ON FLOOR

PLANS. PROVIDE (1) 2"C (WITH PULLSTRING) FOR TELE/DATA

WIRING. FURNITURE SHALL BE WIRED BY AN 8 WIRES AND 4

CIRCUITS SYSTEM.

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:3

A

M

CMB

ELECTRICAL FIRST FLOOR POWER

PLAN – PART B

1-ES-201B

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-201B

1 FIRST FLOOR POWER PLAN - PART B

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

T

VH

T V H

T

VH

M M

M

M

M

J

J

J

J

J

J

J

T V H

T

VH T

V H

T

VH

DN

J

J

T

VH

M

TV

H

TV

H

J

T

VH

Unoccupied Unoccupied

1x

2x

1920212223

41 49

F

E1W-101

E1W-102A

1W-102A

1W-102B

1S-LP1A

E1S-RP1

NIC

C

C

C

REFER TO DRAWING

1-ES-201C FOR

CONTINUATION

CM

REF

MC

8 8

LCP

1S-LP1B

NURSE CALL

HEAD END

GROUND BAR (TYP)

23 1

GROUND

BAR

CUH-2

E1W-102B

1W-102C ELEV.

M101

HSKP

OFFICE SUPPLY

STAF TLT

STORAGE

CORRIDOR

C100

STAFF BREAK

1240LOCKERS

1240A

ON CALL

STAFF TLT

ON CALL

IT CLOSET

ELEC.

E100

PUB TLT

1101D

BARI TLT

1101A

VENDING

OFFICE

PUB TLT

1101B

- 51W-102A

C

C

1 1

- 11W-102B

- 101W-102A

- 61W-102A

- 131W-102A

- 31W-102A

- 81W-102B

- 11W-102A

- 8E1W-102A

H

C

- 12E1W-102A

- 91W-102A

CORRIDOR

C100

CONFERENCE

EXIST. STAIR

S-102

CORRIDOR

C100

CONFERENCE

OFFICE

CORRIDOR

C100

CONFERENCE

OFFICE

NIC

EXIST. STAIR

S-102

ELEV.

M101

TELE-HEALTH

TELE-HEALTH

PAT. TLT

SOILED UTILITY

PUB TLT

1101C

PUB TLT

1101D

EXIST. STAIR

S-102

ELEV.

M101

PUB TLT

1101D

- 111W-102A

- 121W-102A

ATM

- 381W-102A

ELEC

E101

AC-2

AC-1

AC-3

AC-4

ACCU-1 ACCU-2 ACCU-3ACCU-4

VIA ACCU-4

VIA ACCU-3

VIA ACCU-2

VIA ACCU-1

- 2,4E1W-102A - 9,11E1W-102A

- 18,20E1W-102A - 1,3E1W-102A

- 201W-102A

- 81W-102A

- 6E1W-102A

- 231W-102B

- 19E1W-102A

- 21E1W-102A

- 23E1W-102A

- 81W-102C

ATC

ATC

ATC

- 131W-102C

- 131W-102B

- 71W-102C

- 29,31E1S-RP1

UPS

1 DATA

C

C

2 DATA

/ 1 VOICE

C

C

C

1x 2x 42 43 44 45

48 49

NIC

REFER TO DRAWING

1-ES-201C FOR

CONTINUATION

REFER TO DRAWING

FOR CONTINUATION

REFER TO DRAWING

1-ES-201B FOR

CONTINUATION

11 11

ADO

ADO

- 111W-102B

C

C2

- 71W-102B

EXIST. STAIR

S-102

STAFF TLT

STAFF TLT

HSKP

MED EQUIP

LOADING DOCK

C106

SHARED APPT. STOR.

- 61W-102B

- 161W-102B

- 31W-102B

EXIST. STAIR

S-102

SHARED APPT.

SHARED APPT.

CORRIDOR

C105

EXIST. STAIR

S-102

- 21W-102A

- 91W-102B

- 41W-102B

- 201W-102B

CUH-3

- 171W-102A

ADO

- 401W-102A

SHELL SPACE

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED

WITH GFCI PROTECTION.

1.

2.

3.

4.

5.

POWER PLAN KEY NOTES

ALL EXISTING ELECTRICAL EQUIPMENT (POWER) IN ROOM

EXISTING IT ROOM SHALL BE MAINTAINED.

DISCONNECT AND MAKE SAFE EXISTING ELEVATOR

DISCONNECT FOR REUSE. INTERCEPT, EXTEND, AND

CONNECT TO EXISTING FEEDERS SERVING THE EXISTING

ELEVATOR FOR REUSE.

MICROWAVE OUTLET SHALL BE MOUNTED AT 64'' ABOVE

FINISHED FLOOR.

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:5

A

M

CMB

ELECTRICAL FIRST FLOOR POWER

PLAN – PART C

1-ES-201C

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-201C

1 FIRST FLOOR POWER PLAN - PART C-A

1/4" = 1'-0"1-ES-201C

2 FIRST FLOOR POWER PLAN - PART C-B

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

J

J

J

J

J

J

JJ

J

J

J

J

1x

2x

REFER TO DRAWING

FOR CONTINUATION

OFFICE

OFFICE

OFFICE

STORAGE

MECHANICAL ROOM

STAFF TLT

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

HSKP

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

STAFF TLT

OFFICE

OFFICE

AHU-2

201D

201D

201D

201D

201D

201D

201D

201D

201D

201D

201D

201D

201D

201D

201D

- 181W-102B

- 221W-102B

- 241W-102B

- 251W-102B

- 261W-102B

- 271W-102B

- 361W-102B

- 351W-102B

- 331W-102B

- 341W-102B

- 321W-102B

- 311W-102B

- 301W-102B

- 291W-102B

- 281W-102B

- 371W-102B

- 381W-102B

OFFICE

OFFICE

OFFICE

OFFICE

- 24,26,281S-EPP1

- 27,29,311S-EPP1

VFD

VFD

- 241W-102A

2 DATA

/ 1 VOICE

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

ALL RECEPTACLES WITHIN 6' OF A SINK SHALL BE PROVIDED

WITH GFCI PROTECTION.

1.

2.

3.

4.

5.

ALL WORK ASSOCIATED WITH NORTH WING INCLUDING

POWER, LIGHTING, AND FIRE ALARM SHOULD BE A DEDUCT

ALTERNATE.

6.

GRAPHIC SCALE

4' 2' 0 4' 8' 12'

SCALE: 1/4" = 1' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:0

A

M

CMB

ELECTRICAL FIRST FLOOR POWER

PLAN - PART D

1-ES-201D

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/4" = 1'-0"1-ES-201D

1 FIRST FLOOR - POWER PLAN - PART D

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

M

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH ARCHITECTS DRAWINGS PRIOR TO

ROUGH IN.

CIRCUIT NUMBERS ARE FOR DESCRIPTIVE PURPOSES ONLY.

EXACT NUMBERS SHALL BE DETERMINED IN FIELD AND

SHALL BE NOTED ON THE CONTRACTORS AS-BUILT

DRAWINGS.

BRANCH CIRCUIT CONDUCTORS SHALL BE SIZED AND

INSTALLED FOR A MAXIMUM BRANCH CIRCUIT VOLTAGE

DROP OF 3% FROM PANELBOARD. TOTAL VOLTAGE DROP

FROM SERVICE ENTRY TO LAST DEVICE ON CIRCUIT SHALL

NOT EXCEED 5%. REFER TO SPECIFICATIONS FOR

ADDITIONAL REQUIREMENTS AND OPTIONS.

POWER PLAN NOTES

COORDINATE EXACT LOCATIONS OF ALL MECHANICAL

EQUIPMENT WITH HVAC, PLUMBING, AND FIRE PROTECTION

DRAWINGS.

1.

2.

3.

4.

1x 2x

33 34

42 43 44 45 46

48 49

F

3X

EF-3

AHU-1

HWP-1

HWP-2

SUPPLY

FAN

RETURN

FAN

LIGHTS &

SWITCHES

RCPT

- 7,9,111S-EPP1

- 8,10,121S-EPP1

- 131S-EPP1

- 141S-EPP1

UH-1

NIC

NIC

EF-2

- 16,18,201S-EPP1

- 15,17,191S-EPP1

- 191S-LP1B

WP

VFD

VFD

ACCU-5

- 30,32,341S-EPP1

WP

- 221S-EPP1

- 1,3,51S-EPP1

- 2,4,61S-EPP1

VFD

VFD

WP

WP

08' 4'

GRAPHIC SCALE

8' 16' 24'

SCALE: 1/8" = 1' - 0"

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

ARCHITECTCONSULTANTS

CIVIL

VHB

One Federal Street Building 103-3N Springfield, MA 01105

T: 413.747.7113 www.vhb.com

STRUCTURAL

Simpson Gumpertz & Heger 480 Totten Pond Road Waltham, MA 02451

T: 781.907.9000 www.sgh.com

MEP / FP

FITZEMEYER & TOCCI

300 Unicorn Park Drive, 5th Floor, Woburn, MA 01801

T: 781.481.0210 www.f-t.com/

COST

D.G. Jones 3 Baldwin Green Common Suite 202 Woburn, MA 01801

T: 781.932.3131 www.dgjonesboston.com

185 Talcott Rd.

Williston, VT 05495

T: 802.878.8841 www.e4harchitecture.com

100% DESIGN DOCUMENTS

FULLY SPRINKLERED

631-451

As indicated

C

U se rs \r q u ie to \D o cu m e n ts

\N H

V A

C lin ic R e n o v a ti o n s a n d A d d it io n s_

M E P rq u ie to .r v t

/2

/2

:5

:0

A

M

CMB

ELECTRICAL SECOND FLOOR POWER

PLAN

1-ES-202

UPGRADE PRIMARY CARE FEBRUARY 28, 2020

CMB

CMB

1/8" = 1'-0"1-ES-202

1 SECOND FLOOR POWER PLAN

02/28/2020

VIS Construction Consultants 595 Dorset Street, Suite #5

CONTRACTOR SHALL COORDINATE MOUNTING HEIGHT OF

ALL DEVICES WITH…