ATTACHMENT A
Equipment and Safety Device Inventory The contractor shall perform inspection/testing services for the equipment and safety devices listed below, as applicable to the required monthly testing activities and the assigned annual boiler safety device testing/inspection cycle.
A.1 Boiler Plant Equipment
| Equipment/System |
| Manufacturer |
| Model Number |
| Quantity |
| Inspection Type |
| Cleaver Brooks Boiler |
| Cleaver Brooks |
| 3WI 200-300-200ST |
| 3 |
| Operational / Integrity Inspection |
| Boiler Economizers |
| Cain Industries |
| S/N 4849, 4850, 4851 |
| 3 |
| Operational / Integrity Inspection |
| Deaerator Feed Tank |
| Parker Boiler CO. |
| 61466 |
| 1 |
| Integrity Inspection |
| Condensate Feed Tank |
| Parker Boiler CO. |
| 61464 |
| 1 |
| Integrity Inspection |
| Steam Reducing Stations |
| Armstrong |
Spirax Sarco 94115080 71417
A.2 Pressure Vessel Inspections
| Equipment/System |
| Quantity |
| Inspection Type |
| Boiler Vessel Inspection (Waterside/Fireside/Integrity) |
| 3 |
| Pressure Vessel Inspection |
| Deaerator Tank Integrity Inspection |
| 1 |
| Integrity Inspection |
| Condensate Tank Integrity Inspection |
| 1 |
| Integrity Inspection |
A.3 BEI Safety Devices
| Safety Device |
| Quantity |
| BEI Testing Required |
| High Water Alarm on Condensate Tank (HWACT) |
| 1 |
| Yes |
| Low Water Alarm on Condensate Tank (LWACT) |
| 1 |
| Yes |
| High Water Alarm on Deaerator Tank (HWADT) |
| 1 |
| Yes |
| Low Water Alarm on Deaerator Tank (LWADT) |
| 1 |
| Yes |
| Deaerator Overflow Drain System (DAODS) |
| 1 |
| Yes |
| Deaerator Safety Valve (DASV) |
| 1 |
| Yes |
| Safety Valve Following PRV (SVFPRV) – Deaerator |
| 1 |
| Yes |
| Safety Valve Following PRV (SVFPRV) – Other |
| 1 |
| Yes |
| Liquid Relief Valve on Oil Pump Set (LRVOPS) |
| 3 |
| Yes |
| Liquid Relief Valve on Economizer (LRVE) |
| 3 |
| Yes |
| Carbon Monoxide and Combustible Gas Alarms in Boiler Plant (CMCGABP) |
| 3 |
| Yes |
| Emergency Stop Panic Button (ESPB) |
| 4 |
| Yes |
| High Fuel Gas Pressure Alarm on Main Gas Line (HFGPAMG) |
| 1 |
| Yes |
| Low Water Alarm and Cutoffs on Boiler (LWA/LWCO/ALWCO) |
| 3 |
| Yes |
| High Water Alarm on Boiler (HWAB) |
| 3 |
| Yes |
| High / High High Boiler Steam Pressure Limit Switches (HBSPLS & HHBSPLS) |
| 3 |
| Yes |
| Steam Safety Valves on Boiler (SVB) |
| 6 |
| Yes |
| Safety Device |
| Quantity |
| BEI Testing Required |
| Low Fuel Gas Pressure Cutoff Switch (LFGPCS) |
| 3 |
| Yes |
| High Fuel Gas Pressure Cutoff Switch (HFGPCS) |
| 3 |
| Yes |
| Automatic Fuel Gas Shutoff Valves and Solenoid Vent Valve Seat Leakage (AFGSOV & AFGSVV) – Main Gas |
| 3 |
| Yes |
| Automatic Pilot Fuel Gas Shutoff Valves and Solenoid Vent Valve Seat Leakage (APFGSOV & APFGSVV) – Pilot Line |
| 3 |
| Yes |
| Proof of Closure on Automatic Fuel Shutoff Valves (POC-AFGSOV) – Natural Gas |
| 3 |
| Yes |
| Flame Scanner – Main Flame Out (FSMFO) |
| 3 |
| Yes |
| Flame Scanner Not Sensing Igniter Spark (FSNSIS) |
| 3 |
| Yes |
| Igniter Timing (IT) |
| 3 |
| Yes |
| Main Flame Ignition Timing (MFIT) |
| 3 |
| Yes |
| Pre-Purge and Post-Purge Timing (PPT) |
| 3 |
| Yes |
| Low-Fire Proving Switch (LFPS) |
| 3 |
| Yes |
| Forced Draft Damper Wide-Open Pre-Purge Proving Switch (FDDWOPS) |
| 3 |
| Yes |
| Combustion Air Pressure Switch (CAPS) – Variable Speed Fan |
| 3 |
| Yes |
| Purge Airflow Proving Switch (PAPS) |
| 3 |
| Yes |
| Forced Draft Motor Interlock Switches (FDMIS) |
| 3 |
| Yes |
| Outlet Stack Damper Position Interlock Switch (OSDPI) |
| 3 |
| Yes |
| Furnace Pressure Interlock (FPI) |
| 3 |
| Yes |
| Low Pilot Fuel Gas Pressure Cutoff Switch (LPFGPCS) |
| 3 |
| Yes |
| Flue Gas Recirculation Damper Interlock (FGRDI) |
| 3 |
| Yes |
| Low Flue Gas Oxygen Level Interlock (LFGOLI) |
| 3 |
| Yes |
| Low Fuel Oil Pressure Cutoff Switch (LFOPCS) |
| 3 |
| Yes |
| High Fuel Oil Pressure Cutoff Switch (HFOPCS) |
| 3 |
| Yes |
| Low Atomizing Media Pressure Switch (LAMPS) |
| 3 |
| Yes |
| Low Atomizing Media Differential Pressure Switch (LAMDPS) |
| 3 |
| Yes |
| Secondary Low Atomizing Media Pressure Switch (SLAMPS) |
| 1 |
| Yes |
| Automatic Fuel Oil Shutoff Valves (AFOSV) – Seat Leakage |
| 3 |
| Yes |
| Proof of Closure on Automatic Fuel Oil Shutoff Valves (POC-AFOSV) |
| 3 |
| Yes |
| Oil Burner Position Switch (OBPS) |
| 3 |
| Yes |
| Outside Air Damper Interlock with Alarm (OADIA) |
| 1 |
| Yes |
| Outside Air Make Up Unit Interlock with Alarm (OAMUIA) |
| 1 |
| Yes |
| Steam Safety Valves (accumulation test at high fire) |
| 3 |
| Yes |