PWS Attachment 5 - TAB Data Spreadsheet Template.xls

XLS spreadsheet 859 KB Posted

Attached to
Heating, Ventilation and Air Conditioning (HVAC) Recommissioning and Energy Optimization Services (REOS)
Solicitation number
FA805125R4001
Issued by

About this file

This document is a comprehensive Air Handling Unit (AHU) Air Apparatus Test Report for multiple HVAC systems (AHU 1, AHU 2, AHU 4, AHU 6, AHU 7, and AHU 8). The detailed report includes extensive technical measurements and performance data for supply fans, return fans, variable air volume (VAV) boxes, air volumes, fan specifications, motor data, and system configurations. Each AHU section provides granular information such as manufacturer details, motor specifications, fan RPM, voltage readings, air flow measurements, static pressure drops, and performance metrics for individual VAV diffusers and grills.

The test report reveals technical nuances for each HVAC system, including design and actual airflow rates, fan performance characteristics, and system efficiency variations. Notable observations include instances of equipment requiring maintenance, such as loose belts, worn pulleys, and VAV boxes with calibration challenges. The documentation captures detailed traversal point layouts, air volume measurements, and performance percentages for each system component, providing a comprehensive technical assessment of the HVAC infrastructure's current operational status and potential optimization opportunities.

View the file

Other files

File Type Posted
Questions and Answers - HVAC REOS rv1_2 Feb 26.pdf PDF
Combined Synopsis FA805125R4001 - HVAC REOS final rv1_2 Feb 26.pdf PDF
RFP Attachment 1 - Provisions and Clauses rv1_2 Feb 26.pdf PDF
Questions and Answers - HVAC REOS.pdf PDF
RFP Attachment 3 - Price Sheet.xlsx XLSX spreadsheet
Task Order Attachment 2 - Price Sheet.xlsx XLSX spreadsheet
RFP Attachment 3 - Price Sheet.xlsx XLSX spreadsheet
Task Order Attachment 2 - Price Sheet.xlsx XLSX spreadsheet
PWS Attachment 3 - Request to Purchase Materials.xlsx XLSX spreadsheet
RFP Attachment 3 - Price Sheet.xlsx XLSX spreadsheet
RFP Attachment 4 - Task Order PWS final.pdf PDF
Combined Synopsis FA805125R4001 - HVAC REOS final.pdf PDF
PWS Attachment 2 - Acceptable Repairable Replaceable HVAC Items.pdf PDF
PWS Attachment 1 - Qualifications and Experience.pdf PDF
PWS Attachment 4 - Request for Task Order Proposal.pdf PDF
Exhibit A_CDRL A003 - Monthly Status Report.pdf PDF
RFP Attachment 1 - Provisions and Clauses.pdf PDF
RFP Attachment 2 - Basic PWS_HVAC REOS final.pdf PDF
Task Order Attachment 1 - Wage Determination.pdf PDF
Task Order Attachment 2 - Price Sheet.xlsx XLSX spreadsheet
Exhibit A_CDRL A001 - Work Progress Schedule.pdf PDF
Exhibit A_CDRL A002 - Report of Visit.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AHU 1 AIR APPARATUS

AIR APPARATUS TEST REPORT
BASEW/O#
SYSTEMAHU 1BUILDINGDATENAME
TYPE EQUIPMENTAHUSUPPLY FANEXHAUSTRETURN
TYPE OF SYSTEMCVVAVMULITZONEDUAL DUCTREHEAT
FAN DATAMOTOR DATA
MANUFACTURERTraneMANUFACTURERBaldor
MODEL NUMBERMCCA025GAM0ABCMODEL NUMBEREM2513T-G
WHEEL TYPEAIR FOILFORWARD CURVENAME PLATE HORSE POWER15NAME PLATE RPMS1765
BACKWARDS INCLINEOTHEREFFICIENCY93POWER FACTOR86
BELT SIZEB-77 2eaSHAFT SIZE2 3/16SHAFT SIZE1 5/8AS FOUNDFINAL
PULLEY FAN OD11 1/2MOTOR OD6 3/8RPM
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT26BHP
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT
DESIGNAS FOUNDFINALDESIGNACTUALFINAL
FAN CFMVOLTAGE A-B460
FAN RPMVOLTAGE B-C
DISCHARGE S.P.VOLTAGE C-A
EXTERNAL S.P.AMPERAGE A17.7
REMARKSAMPERAGE B
Beltts loose and shives worn (needs replaced)AMPERAGE C
Total Static 3.77AIR VOLUMES
Connected load 26,235 full coolingDESIGNAS FOUNDFINAL
Minimum air flow required 10,480 min cool and heatMAXMINMAXMINMAXMIN
Oa design 40% of 16,800 = 6,720O/A CFM
R/AS/AAFTER CC/AR/A CFM
O/A TEMPR/A TEMPM/A TEMP
STATIC PRESSURE DROPS
COIL NAME AND DESIGN S.P. DROPAS FOUNDFINALAS FOUNDFINALAS FOUNDFINAL
Cooling coil
Heating coil

Page &P of &N x x X

AHU 1 2nd floor Supply Air

PITOT TUBE TRAVERSE LARGE ROUND DUCT
BASE:JOB NO.:DATE:
LOCATION:SYSTEM:
LOCATION OF DUCT:AREA SERVED:DUCT TEMP.:DUCT S.P.:
DUCT SIZE:18"REQUIRED CFM:REQUIRED FPM:PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM
DUCT AREA IN SQ.FT.:ACTUAL CFM:ACTUAL FPM:
TRAVERSE POINTSREADINGS
2nd Floor VAVS in Max2nd Floor VAVS in Min
FPMFPMFPMFPM
11956
22024
31771
41789
52092
62751
72839
82981
93008
103020
12918
22856
DUCT DIA12345678910
32709
123/811 3/42 3/44 1/87 7/89 1/410 1/41111 5/8
133/811 7/82 7/84 1/28 1/210 1/811 1/81212 5/842557
143/81 1/823 1/84 3/49 1/410 7/81212 7/813 5/8
153/81 1/42 1/43 3/85 1/89 7/811 5/812 3/413 3/414 5/852329
163/81 1/42 3/83 5/85 1/210 1/212 3/813 5/814 3/415 5/8
171/21 3/82 1/23 7/85 3/411 1/413 1/814 1/215 5/816 1/262223
181/21 1/22 5/84 1/86 1/811 7/814 1/215 3/816 1/217 1/2
191/21 1/22 3/44 1/46 1/212 1/215 3/416 1/417 1/218 1/272186
201/21 5/82 7/84 1/26 7/813 1/817 1/817 1/818 1/219 1/2
225/81 3/43 1/457 1/214 1/21718 3/420 1/221 3/882124
245/823 1/25 1/28 1/815 3/418 1/220 1/22223 3/8
265/82 1/83 3/45 7/88 7/817 1/820 1/822 1/423 3/825 3/892070
283/42 1/44 1/86 3/89 5/818 3/821 5/823 7/825 3/427 1/4
303/42 1/24 3/86 3/410 1/419 3/423 1/425 5/827 1/219 1/4101683
327/82 5/84 5/87 1/4112124 3/427 3/829 3/831 1/4
347/82 3/457 3/411 5/822 3/826 1/42931 1/433 1/8TOTAL FPM47886000
36135 1/48 1/812 3/823 5/827 7/830 3/43335
3813 1/85 1/28 5/8132529 3/832 1/234 7/837Divided by 202394.3000
4013 1/45 7/8913 5/826 3/83134 1/836 3/439
421 1/83 3/86 1/89 1/214 3/827 5/832 1/235 7/838 5/840 1/8Times Duct Area1.761.761.761.76
441 1/83 5/86 3/81015293437 5/840 3/842 7/8
461 1/43 3/46 3/410 3/815 3/430 1/435 5/839 1/440 1/444 3/4= Total CFM4213.9700.000
481 1/44710 7/816 3/831 5/837 1/8414446 3/4
VAVs 1-11 1-12 1-271206
5419.9680

Page &P of &N

TRAVERSE POINT LAYOUT

6 7 8 9 10 1 2 3 4 5

RET FAN 1 AIR APPARATUS

AIR APPARATUS TEST REPORT
BASEW/O#
SYSTEMRet Fan 1BUILDINGDATENAME
TYPE EQUIPMENTAHUSUPPLY FANEXHAUSTRETURN
TYPE OF SYSTEMCVVAVMULITZONEDUAL DUCTREHEAT
FAN DATAMOTOR DATA
MANUFACTURERTraneMANUFACTURERGE
MODEL NUMBERFNA 309MODEL NUMBER5KS184LAB208
WHEEL TYPEAIR FOILFORWARD CURVENAME PLATE HORSE POWER5NAME PLATE RPMS1755
BACKWARDS INCLINEOTHEREFFICIENCY89.5POWER FACTOR78.5
BELT SIZEA-78SHAFT SIZE1 3/16SHAFT SIZE1 1/8AS FOUNDFINAL
PULLEY FAN OD8 1/4MOTOR OD6 3/4RPM
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT28 1/4BHP
DESIGNAS FOUNDFINALDESIGNACTUALFINAL
FAN CFMVOLTAGE A-B460
FAN RPMVOLTAGE B-C460
DISCHARGE S.P.VOLTAGE C-A460
EXTERNAL S.P.AMPERAGE A6.7
REMARKSAMPERAGE B6.7
AMPERAGE C6.7
AIR VOLUMES
DESIGNAS FOUNDFINAL
MAXMINMAXMINMAXMIN
O/A CFM
R/AS/AAFTER CC/AR/A CFM
O/A TEMPR/A TEMPM/A TEMP
STATIC PRESSURE DROPS
COIL NAME AND DESIGN S.P. DROPAS FOUNDFINALAS FOUNDFINALAS FOUNDFINAL

Page &P of &N X x

AHU 1 RET & OA TRAVERSE

BASE:SYSTEM:LOCATION:
1234567891011121314151617
A625664647810897856753
B758761698803859864868
C744723722703825874864
D699722678705708856892
E
F
G
HReturn air 1st FloorOutside Air
ITotal FPM =21578Total FPM =0
JFt per Minute Average =770.6428571429Ft per Minute Average =0
KArea K (17" X 33") /144 =4.25Area K (34" X 60") /144 =14.166
LCubic Ft. per Minute =3,275Cubic Ft. per Minute =0
M
N
O389490409422453488
P542440558519508460
Q479568559566501503
R555430546563537529
S
T
U
V
WReturn air 2nd FloorOutside Air
XTotal FPM =12014Total FPM =0
YFt per Minute Average =500.5833333333Ft per Minute Average =0
ZArea K (23" X 31") /144 =4.81Area K (34" X 60") /144 =14.166
Cubic Ft. per Minute =2407.8058333333Cubic Ft. per Minute =0
Ribs Ret159
2566.8058333333
5841

AHU1 VAV

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 1TESTED BYDATE
ROOM T-STATCO-2 LEVELSAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 1-165026050778.0%20277.7%745115%25899.2%667103%25899.2%
1120125010022590.0%7575.0%355142.0%9292.0%260104.0%9292.0%
111721405610272.9%4682.1%12891.4%65116.1%147105.0%65116.1%
CC sec3120488873.3%3572.9%142118.3%4593.8%125104.2%4593.8%
11154140569265.7%4682.1%12085.7%56100.0%13596.4%56100.0%
VAV 1-231012530096.8%128102%0.0%0.0%30096.8%128102%
1115131012530096.8%128102.4%0.0%0.0%30096.8%128102.4%
VAV 1-376030572295.0%29396.1%0.0%0.0%0.0%0.0%
111411907613470.5%5065.8%0.0%0.0%0.0%0.0%
11142285114298104.6%120105.3%0.0%0.0%0.0%0.0%
11143285114290101.8%123107.9%0.0%0.0%0.0%0.0%
VAV 1-410040100100%0.0%0.0%43108%100100%43108%
1112110040100100.0%3075.0%0.0%43107.5%100100.0%43107.5%
RM NOT TESTED. LOCKED BUT ZEROED
VAV 1-5670268887132%300112%53579.9%0.0%65898.2%283106%
119036130144.4%4550.0%7583.3%0.0%100111.1%3597.2%
2214558152104.8%5086.2%9565.5%0.0%11579.3%5086.2%
3314558200137.9%70120.7%12586.2%0.0%145100.0%65112.1%
4414558205141.4%70120.7%12082.8%0.0%150103.4%68117.2%
5514558200137.9%65112.1%12082.8%0.0%148102.1%65112.1%

Page &P of &N

AHU1 VAV (2)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 1TESTED BYDATE
ROOM T-STATCO-2 LEVELSAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 1-62209015269.1%6066.7%257117%8796.7%242110%8796.7%
111012209015269.1%6066.7%257116.8%8796.7%242110.0%8796.7%
VAV 1-754522054199%0.0%36466.8%0.0%47086.2%17981.4%
valt18032*0.0%*0.0%**
1108215562184118.7%4267.7%12379.4%0.0%15197.4%6198.4%
1102315562174112.3%4267.7%11674.8%0.0%14895.5%5588.7%
1102415562183118.1%4775.8%12580.6%0.0%171110.3%63101.6%
Unable to read. Secure vault
VAV 1-81380550124690.3%0.0%0.0%0.0%1428103%53096.4%
12309222095.7%0.0%0.0%0.0%244106.1%8997.2%
22309219383.9%0.0%0.0%0.0%22798.7%8896.1%
32309221693.9%0.0%0.0%0.0%22999.6%8896.1%
42309219283.5%0.0%0.0%0.0%22798.7%8491.8%
52309220589.1%0.0%0.0%0.0%257111.7%9199.4%
62309222095.7%0.0%0.0%0.0%244106.1%9098.3%
VAV 1-9111044587178.5%35379.3%1140103%43798.2%1140103%43798.2%
11857414779.5%6486.5%18097.3%7094.6%18097.3%7094.6%
21857416086.5%6283.8%201108.6%7094.6%201108.6%7094.6%
31857414477.8%5979.7%189102.2%74100.0%189102.2%74100.0%
41857414377.3%5878.4%189102.2%78105.4%189102.2%78105.4%
51857413170.8%5574.3%201108.6%6891.9%201108.6%6891.9%
61857414678.9%5574.3%18097.3%77104.1%18097.3%77104.1%

Page &P of &N

AHU1 VAV (3)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 1TESTED BYDATE
ROOM T-STATCO-2 LEVELSAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 1-101180472106490.2%0.0%0.0%0.0%116298.5%46197.7%
134013630288.8%0.0%0.0%12289.7%32294.7%13498.5%
234013629887.6%0.0%0.0%12189.0%32796.2%13297.1%
334013631291.8%0.0%0.0%11886.8%344101.2%13095.6%
41606415295.0%0.0%0.0%5789.1%169105.6%65101.6%
VAV 1-268003181564196%0.0%00%0.0%818102%31298%
1400159900225.0%0.0%0.0%0.0%450112.5%170106.8%
2140568460.0%0.0%0.0%0.0%8862.9%2748.5%
3260103580223.1%0.0%0.0%0.0%280107.7%115111.1%
This VAV serves a single room balance at diffusers is not critical

Page &P of &N

AHU 1 VAV (4)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMTESTED BYDATE
ROOM T-STATCO-2 LEVELSAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 1-11275110352128%9687.3%26797.1%0.0%26797.1%10494.5%
20221275110352128.0%9687.3%26797.1%0.0%26797.1%10494.5%
Found max setpoint at 398cfm
VAV 1-12275110344125%10191.8%27298.9%0.0%27298.9%10191.8%
20221275110344125.1%10191.8%27298.9%0.0%27298.9%10191.8%
Found max setpoint at 398 cfm
VAV 1-13305122320105%0.0%0.0%0.0%320105%140115%
110040110110.0%0.0%0.0%0.0%110110.0%40100.0%
220582210102.4%0.0%0.0%0.0%210102.4%100122.0%
VAV 1-1473529563586.4%23178.4%774105%29098.4%774105%29098.4%
201912309219986.5%7581.3%246107.0%93100.8%246107.0%93100.8%
201922309219986.5%6772.6%240104.3%8996.5%240104.3%8996.5%
2021327511023786.2%8980.7%288104.7%10897.9%288104.7%10897.9%
VAV 1-15580230611105%16471.3%56897.9%21794.3%580100%21794.3%
1290117299103.1%8371.0%28497.9%10993.3%28999.7%10993.3%
2290117312107.6%8169.3%28497.9%10892.4%291100.3%10892.4%
VAV not able to be calibrated. Stops reading airflow at 380 cfm,** shop repaired vav** box calibrated at calculated values
VAV 1-27800320855107%350109%00.0%00.0%805101%350109%
20231400160420105.0%180112.5%0.0%0.0%39598.8%180112.5%
20232400160435108.8%170106.3%0.0%0.0%410102.5%170106.3%

Page &P of &N

AHU 1 VAV (5)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMTESTED BYDATE
ROOM T-STATCO-2 LEVELSAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 1-161200480115796%47999.8%0.0%0.0%115796.4%47999.8%
12409623196.3%96100.0%0.0%0.0%23196.3%96100.0%
22409623095.8%9599.0%0.0%0.0%23095.8%9599.0%
32409623498%98102.1%0.0%0.0%23497.5%98102.1%
42409623698.3%98102.1%0.0%0.0%23698.3%98102.1%
52409622694.2%9295.8%0.0%0.0%22694.2%9295.8%
VAV 1-172409521891%9195.8%23999.6%0.0%239100%9196%
201712409521890.8%9195.8%23999.6%0.0%23999.6%9195.8%
VAV 1-1830012027491.3%120100%311104%00.0%311104%120100%
20191110449283.6%4397.7%113102.7%0.0%113102.7%4397.7%
201921907618295.8%77101.3%198104.2%0.0%198104.2%77101.3%
VAV 1-1963025054987.1%16365.2%649103%24196.4%649103%24196.4%
220811255011592.0%3264.0%132105.6%4896.0%132105.6%4896.0%
220922008017989.5%5366.3%212106.0%7897.5%212106.0%7897.5%
330512225583.6%7863.9%305100.0%11594.3%305100.0%11594.3%
min airflow setpoint was 160 cfm schedule calls for 250 min cfm.
VAV 1-2025510222789%127125%24997.6%119117%24998%109107%
2011125510222789.0%127124.5%24997.6%119116.7%24997.6%109106.9%
print calls for 255 cfm schedule calls for 235 cfm

Page &P of &N

AHU 1 VAV (6)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMTESTED BYDATE
ROOM T-STATCO-2 LEVELSAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 1-21660265678103%432163%714108%273103%714108%273103%
2005119076209110.0%132173.7%207108.9%77101.3%207108.9%77101.3%
2009228011226895.7%175156.3%287102.5%112100.0%287102.5%112100.0%
319076201106%125164.5%220115.8%84110.5%220115.8%84110.5%
VAV 1-221350540113384%49691.9%1379102%53699.3%1379102%53699%
12208819588.6%8495.5%236107.3%91103.4%236107.3%91103.4%
22208819387.7%8394.3%233105.9%88100.0%233105.9%88100.0%
32208817177.7%7585.2%20492.7%8192.0%20492.7%8192.0%
42208817780.5%7888.6%21396.8%8596.6%21396.8%8596.6%
52208819086.4%8394.3%229104.1%91103.4%229104.1%91103.4%
2010625010020782.8%9393.0%264105.6%100100.0%264105.6%100100.0%
VAV 1-2353021046587.7%18990.0%532100%20899.0%532100%20899.0%
12309221392.6%8693.5%245106.5%94102.2%245106.5%94102.2%
2003230012025284.0%10385.8%28795.7%11495.0%28795.7%11495.0%
Damper drive motor needs replace. Squeaking durring operation
VAV 1-2427511026094.5%128116%275100%137125%275100%128116%
2006127511026094.5%128116.4%275100.0%137124.5%275100.0%128116.4%
VAV 1-2550020046092%370185%520104%217109%520104%217109%
200411907616084.2%85111.8%16586.8%6788.2%16586.8%6788.2%
2004231012430096.8%285229.8%355114.5%150121.0%355114.5%150121.0%

Page &P of &N

AHU 2 AIR APPARATUS

AIR APPARATUS TEST REPORT
BASEW/O#
SYSTEMAHU 2BUILDINGDATENAME
TYPE EQUIPMENTAHUSUPPLY FANEXHAUSTRETURN
TYPE OF SYSTEMCVVAVMULITZONEDUAL DUCTREHEAT
FAN DATAMOTOR DATA
MANUFACTURERTraneMANUFACTURERGE
MODEL NUMBERMCCAA035GAM0ACAMODEL NUMBER5KS254SAB205A
WHEEL TYPEAIR FOILFORWARD CURVENAME PLATE HORSE POWER15NAME PLATE RPMS1770
BACKWARDS INCLINEOTHEREFFICIENCY92.4POWER FACTOR84.5
BELT SIZEB-47 2eaSHAFT SIZE2 3/16SHAFT SIZE1 5/8AS FOUNDFINAL
PULLEY FAN OD7 3/8MOTOR OD6 3/4RPM1768
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT14BHP
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT
DESIGNAS FOUNDFINALDESIGNACTUALFINAL
FAN CFM16,80013,798VOLTAGE A-B460479
FAN RPM1633VOLTAGE B-C479
DISCHARGE S.P.2.11VOLTAGE C-A479
EXTERNAL S.P.AMPERAGE A1815.5
REMARKSAMPERAGE B15.9
Total Static 3.77AMPERAGE C16
Connected load 26,235 full cooling
Minimum air flow required 10,480 min cool and heat
Oa design 40% of 16,800 = 6,720AIR VOLUMES
DESIGNAS FOUNDFINAL
MAXMINMAXMINMAXMIN
O/A CFM4,713
R/AS/AAFTER CC/AR/A CFM
O/A TEMPR/A TEMPM/A TEMP
STATIC PRESSURE DROPS
COIL NAME AND DESIGN S.P. DROPAS FOUNDFINALAS FOUNDFINALAS FOUNDFINAL
Cooling coil0.334
Heating coil0.1

Page &P of &N x x x

AHU 2 Total Supply Air

PITOT TUBE TRAVERSE LARGE ROUND DUCT
BASE:JOB NO.:DATE:
LOCATION:SYSTEM:
LOCATION OF DUCT:AREA SERVED:DUCT TEMP.:DUCT S.P.:
DUCT SIZE:XREQUIRED CFM:REQUIRED FPM:PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM
DUCT AREA IN SQ.FT.:ACTUAL CFM:ACTUAL FPM:
TRAVERSE POINTSREADINGS
Total Supply VAVS in MaxTotal Supply VAVS in Min
FPMFPMFPMFPM
120771354
219831595
319921573
419311580
520101541
625511534
724861584
825881539
926171467
1021501294
121141218
222971248
DUCT DIA12345678910
325421241
123/811 3/42 3/44 1/87 7/89 1/410 1/41111 5/8
133/811 7/82 7/84 1/28 1/210 1/811 1/81212 5/8425821243
143/81 1/823 1/84 3/49 1/410 7/81212 7/813 5/8
153/81 1/42 1/43 3/85 1/89 7/811 5/812 3/413 3/414 5/8524071325
163/81 1/42 3/83 5/85 1/210 1/212 3/813 5/814 3/415 5/8
171/21 3/82 1/23 7/85 3/411 1/413 1/814 1/215 5/816 1/2624411625
181/21 1/22 5/84 1/86 1/811 7/814 1/215 3/816 1/217 1/2
191/21 1/22 3/44 1/46 1/212 1/215 3/416 1/417 1/218 1/2725761582
201/21 5/82 7/84 1/26 7/813 1/817 1/817 1/818 1/219 1/2
225/81 3/43 1/457 1/214 1/21718 3/420 1/221 3/8826031664
245/823 1/25 1/28 1/815 3/418 1/220 1/22223 3/8
265/82 1/83 3/45 7/88 7/817 1/820 1/822 1/423 3/825 3/8923561668
283/42 1/44 1/86 3/89 5/818 3/821 5/823 7/825 3/427 1/4
303/42 1/24 3/86 3/410 1/419 3/423 1/425 5/827 1/219 1/41020981422
327/82 5/84 5/87 1/4112124 3/427 3/829 3/831 1/4
347/82 3/457 3/411 5/822 3/826 1/42931 1/433 1/8TOTAL FPM464010292970
36135 1/48 1/812 3/823 5/827 7/830 3/43335
3813 1/85 1/28 5/8132529 3/832 1/234 7/837Divided by 202320.0501464.850
4013 1/45 7/8913 5/826 3/83134 1/836 3/439
421 1/83 3/86 1/89 1/214 3/827 5/832 1/235 7/838 5/840 1/8Times Duct Area5.595.592.64
441 1/83 5/86 3/81015293437 5/840 3/842 7/8
461 1/43 3/46 3/410 3/815 3/430 1/435 5/839 1/440 1/444 3/4= Total CFM12959.2808182.330
481 1/44710 7/816 3/831 5/837 1/8414446 3/4
Elevator rooms839838
13798.28373333339020

Page &P of &N

TRAVERSE POINT LAYOUT

6 7 8 9 10 1 2 3 4 5

RET FAN 2 AIR APPARATUS

AIR APPARATUS TEST REPORT
BASEW/O#
SYSTEMBUILDINGDATENAME
TYPE EQUIPMENTAHUSUPPLY FANEXHAUSTRETURN
TYPE OF SYSTEMCVVAVMULITZONEDUAL DUCTREHEAT
FAN DATAMOTOR DATA
MANUFACTURERMANUFACTURERGE
MODEL NUMBERMODEL NUMBER5KS213SAB205
WHEEL TYPEAIR FOILFORWARD CURVENAME PLATE HORSE POWER7 1/2NAME PLATE RPMS1770
BACKWARDS INCLINEOTHEREFFICIENCY91.7POWER FACTOR83.5
BELT SIZEBX-82SHAFT SIZE1 7/16SHAFT SIZE1 3/8AS FOUNDFINAL
PULLEY FAN OD9 3/4MOTOR OD8 1/2RPM1399
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT28 1/4BHP
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT
DESIGNAS FOUNDFINALDESIGNACTUALFINAL
FAN CFM11276VOLTAGE A-B460477
FAN RPM1199VOLTAGE B-C460477
DISCHARGE S.P.VOLTAGE C-A460477
EXTERNAL S.P.AMPERAGE A9.25.2
REMARKSAMPERAGE B9.25.2
Fan operating at 47.1 hzAMPERAGE C9.25.2
Fan and motor pulleys are worn
AIR VOLUMES
DESIGNAS FOUNDFINAL
MAXMINMAXMINMAXMIN
O/A CFM
R/AS/AAFTER CC/AR/A CFM
O/A TEMPR/A TEMPM/A TEMP
STATIC PRESSURE DROPS
COIL NAME AND DESIGN S.P. DROPAS FOUNDFINALAS FOUNDFINALAS FOUNDFINAL

Page &P of &N

AHU 2 RET & OA TRAVERSE

BASE:SYSTEM:LOCATION:
1234567891011121314151617
A133213341351123213721370117917515601243572701435880
B1347136313011283136413541282153254147309344336207107215
C1269118511831323127111721279234312232372423427305259308
D10978441024102611298581103342323352407439428343412414
E631233543615416584935360373436440486444437436438
F41600244249375395315420480494490529541543537
G
HReturn airOutside Air
ITotal FPM =39863Total FPM =17966
JFt per Minute Average =949.119047619Ft per Minute Average =332.7037037037
KArea K (32" X 62") /144 =11.88Area K (34" X 60") /144 =14.166
LCubic Ft. per Minute =11,276Cubic Ft. per Minute =4,713
M
N
O
P335369435500475393269333215
Q275417532520594472410424265
R434560576566583587549472438
S465578585591572624603571456
T578632599579605651658644535
U453650573521643652678676625
V
WReturn airOutside Air
XTotal FPM =0Total FPM =27995
YFt per Minute Average =0Ft per Minute Average =518.4259259259
ZArea K (0" X 0") /144 =11.88Area K (34" X 60") /144 =14.166
Cubic Ft. per Minute =0Cubic Ft. per Minute =7,344

AHU 4 AIR APPARATUS

AIR APPARATUS TEST REPORT
BASEW/O#
SYSTEMAHU 4BUILDINGDATENAME
TYPE EQUIPMENTAHUSUPPLY FANEXHAUSTRETURN
TYPE OF SYSTEMCVVAVMULITZONEDUAL DUCTREHEAT
FAN DATAMOTOR DATA
MANUFACTURERTraneMANUFACTURERBaldor
MODEL NUMBERMCCA050GAM0ACAMODEL NUMBERM4104T
WHEEL TYPEAIR FOILFORWARD CURVENAME PLATE HORSE POWER30NAME PLATE RPMS1760
BACKWARDS INCLINEOTHEREFFICIENCY93.6POWER FACTOR80
BELT SIZEBX-53 4eaSHAFT SIZE2 3/8SHAFT SIZE1 7/8AS FOUNDFINAL
PULLEY FAN OD9 7/8MOTOR OD7 3/4RPM
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT16BHP
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT
DESIGNAS FOUNDFINALDESIGNACTUALFINAL
FAN CFMVOLTAGE A-B460
FAN RPMVOLTAGE B-C
DISCHARGE S.P.VOLTAGE C-A
EXTERNAL S.P.AMPERAGE A38
REMARKSAMPERAGE B
AMPERAGE C
AIR VOLUMES
DESIGNAS FOUNDFINAL
MAXMINMAXMINMAXMIN
O/A CFM
R/AS/AAFTER CC/AR/A CFM
O/A TEMPR/A TEMPM/A TEMP
STATIC PRESSURE DROPS
COIL NAME AND DESIGN S.P. DROPAS FOUNDFINALAS FOUNDFINALAS FOUNDFINAL

Page &P of &N x x X

AHU4 AIR APPARATUS 2ND TRIP

PITOT TUBE TRAVERSE LARGE ROUND DUCT
BASE:JOB NO.:DATE:
LOCATION: BuildingSYSTEM:
LOCATION OF DUCT:AREA SERVED:DUCT TEMP.:DUCT S.P.:
DUCT SIZE:A= 24"B=22"REQUIRED CFM:REQUIRED FPM:PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM
DUCT AREA IN SQ.FT.:ACTUAL CFM:ACTUAL FPM:
TRAVERSE POINTSREADINGS
DUCT A 1st flrDUCT B 2nd flr
FPMFPMFPMFPM
12471295743382213
22549317144382235
32600321744042194
42554315043712209
52620325644942268
63215329344842905
73475312443022944
83665318042753153
93770294642303229
103877273339523267
13525330347002865
23613335947983043
DUCT DIA12345678910
33503342847892985
123/811 3/42 3/44 1/87 7/89 1/410 1/41111 5/8
133/811 7/82 7/84 1/28 1/210 1/811 1/81212 5/843337339847532968
143/81 1/823 1/84 3/49 1/410 7/81212 7/813 5/8
153/81 1/42 1/43 3/85 1/89 7/811 5/812 3/413 3/414 5/853188334446882939
163/81 1/42 3/83 5/85 1/210 1/212 3/813 5/814 3/415 5/8
171/21 3/82 1/23 7/85 3/411 1/413 1/814 1/215 5/816 1/263159323045922775
181/21 1/22 5/84 1/86 1/811 7/814 1/215 3/816 1/217 1/2
191/21 1/22 3/44 1/46 1/212 1/215 3/416 1/417 1/218 1/273262314545302835
201/21 5/82 7/84 1/26 7/813 1/817 1/817 1/818 1/219 1/2
225/81 3/43 1/457 1/214 1/21718 3/420 1/221 3/883347308744872958
245/823 1/25 1/28 1/815 3/418 1/220 1/22223 3/8
265/82 1/83 3/45 7/88 7/817 1/820 1/822 1/423 3/825 3/893255306044692960
283/42 1/44 1/86 3/89 5/818 3/821 5/823 7/825 3/427 1/4
303/42 1/24 3/86 3/410 1/419 3/423 1/425 5/827 1/219 1/4103057268340342879
327/82 5/84 5/87 1/4112124 3/427 3/829 3/831 1/4
347/82 3/457 3/411 5/822 3/826 1/42931 1/433 1/8TOTAL FPM64042630648912855824
36135 1/48 1/812 3/823 5/827 7/830 3/43335
3813 1/85 1/28 5/8132529 3/832 1/234 7/837Divided by 203202.13153.24456.42791.2
4013 1/45 7/8913 5/826 3/83134 1/836 3/439
421 1/83 3/86 1/89 1/214 3/827 5/832 1/235 7/838 5/840 1/8Times Duct Area2.642.643.143.14
441 1/83 5/86 3/81015293437 5/840 3/842 7/8
461 1/43 3/46 3/410 3/815 3/430 1/435 5/839 1/440 1/444 3/4= Total CFM8453.548324.44813993.108769.95
481 1/44710 7/816 3/831 5/837 1/8414446 3/4
11630466313
static9616.5448324.448144599082.95
pitot tube0.93c/l 2.38Max VAV onlyc/l 1.80"

TRAVERSE POINT LAYOUT

6 7 8 9 10 1 2 3 4 5

AHU 4 Total Supply Air

PITOT TUBE TRAVERSE LARGE ROUND DUCT
BASE:JOB NO.:DATE:
LOCATION:SYSTEM:
LOCATION OF DUCT:AREA SERVED:DUCT TEMP.:DUCT S.P.:
DUCT SIZE:XREQUIRED CFM:REQUIRED FPM:PERCENT OF DESIGN = ACTUAL CFM/REQUIRED CFM
DUCT AREA IN SQ.FT.:ACTUAL CFM:ACTUAL FPM:
TRAVERSE POINTSREADINGS
DUCT A 1st flrDUCT B 2nd flr
FPMFPMFPMFPM
124714338
225494438
326004404
425544371
526204494
632154484
734754302
836654275
937704230
1038773952
135254700
236134798
DUCT DIA12345678910
335034789
123/811 3/42 3/44 1/87 7/89 1/410 1/41111 5/8
133/811 7/82 7/84 1/28 1/210 1/811 1/81212 5/8433374753
143/81 1/823 1/84 3/49 1/410 7/81212 7/813 5/8
153/81 1/42 1/43 3/85 1/89 7/811 5/812 3/413 3/414 5/8531884688
163/81 1/42 3/83 5/85 1/210 1/212 3/813 5/814 3/415 5/8
171/21 3/82 1/23 7/85 3/411 1/413 1/814 1/215 5/816 1/2631594592
181/21 1/22 5/84 1/86 1/811 7/814 1/215 3/816 1/217 1/2
191/21 1/22 3/44 1/46 1/212 1/215 3/416 1/417 1/218 1/2732624530
201/21 5/82 7/84 1/26 7/813 1/817 1/817 1/818 1/219 1/2
225/81 3/43 1/457 1/214 1/21718 3/420 1/221 3/8833474487
245/823 1/25 1/28 1/815 3/418 1/220 1/22223 3/8
265/82 1/83 3/45 7/88 7/817 1/820 1/822 1/423 3/825 3/8932554469
283/42 1/44 1/86 3/89 5/818 3/821 5/823 7/825 3/427 1/4
303/42 1/24 3/86 3/410 1/419 3/423 1/425 5/827 1/219 1/41030574034
327/82 5/84 5/87 1/4112124 3/427 3/829 3/831 1/4
347/82 3/457 3/411 5/822 3/826 1/42931 1/433 1/8TOTAL FPM640420891280
36135 1/48 1/812 3/823 5/827 7/830 3/43335
3813 1/85 1/28 5/8132529 3/832 1/234 7/837Divided by 203202.104456.40
4013 1/45 7/8913 5/826 3/83134 1/836 3/439
421 1/83 3/86 1/89 1/214 3/827 5/832 1/235 7/838 5/840 1/8Times Duct Area3.1423.1422.642.64
441 1/83 5/86 3/81015293437 5/840 3/842 7/8
461 1/43 3/46 3/410 3/815 3/430 1/435 5/839 1/440 1/444 3/4= Total CFM10061.00011765.580
481 1/44710 7/816 3/831 5/837 1/8414446 3/4
1163466
11223.998212232
Max VAV only

Page &P of &N

TRAVERSE POINT LAYOUT

6 7 8 9 10 1 2 3 4 5

Ret Fan 4 AIR APPARATUS

AIR APPARATUS TEST REPORT
BASEW/O#
SYSTEMReturn Fan 4BUILDINGDATENAME
TYPE EQUIPMENTAHUSUPPLY FANEXHAUSTRETURN
TYPE OF SYSTEMCVVAVMULITZONEDUAL DUCTREHEAT
FAN DATAMOTOR DATA
MANUFACTURERTraneMANUFACTURERBaldor
MODEL NUMBEROFNA4491MODEL NUMBEREM3311T-G
WHEEL TYPEAIR FOILFORWARD CURVENAME PLATE HORSE POWER7 1/2NAME PLATE RPMS1770
BACKWARDS INCLINEOTHEREFFICIENCY91POWER FACTOR79
BELT SIZEB-98SHAFT SIZE1 11/16SHAFT SIZE1 3/8AS FOUNDFINAL
PULLEY FAN OD11 3/8MOTOR OD4 7/8RPM
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT37 1/2BHP
FAN SHAFT TO MOTOR SHAFT C/C MEASUREMENT
DESIGNAS FOUNDFINALDESIGNACTUALFINAL
FAN CFM24000VOLTAGE A-B460
FAN RPM845VOLTAGE B-C
DISCHARGE S.P.VOLTAGE C-A
EXTERNAL S.P.AMPERAGE A9.7
REMARKSAMPERAGE B
Loose beltAMPERAGE C
AIR VOLUMES
DESIGNAS FOUNDFINAL
MAXMINMAXMINMAXMIN
O/A CFM
R/AS/AAFTER CC/AR/A CFM
O/A TEMPR/A TEMPM/A TEMP
STATIC PRESSURE DROPS
COIL NAME AND DESIGN S.P. DROPAS FOUNDFINALAS FOUNDFINALAS FOUNDFINAL

Page &P of &N x

AHU 4 VAV (1)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-300.560.64680270791116%392145%692102%289107%696102%289107%
1340136380111.8%198145.6%345101.5%147108.1%349102.6%147108.1%
2340136411120.9%194142.6%347102.1%142104.4%347102.1%142104.4%
VAV 4-390.650.6680032063579%77397%77397%354111%
2412140016034786.8%420105.0%420105.0%165103.1%
2412240016028872.0%35388.3%35388.3%189118.1%
There is a third diffuser in the space that was not part of the original design. It was delivering 35 cfm.
VAV 4-180.60.62635254672106%355140%00%00.0%672106%305120%
2408120080211105.5%113141.3%0.0%0.0%211105.5%96120.0%
Hall217570181103.4%95135.7%0.0%0.0%181103.4%82117.1%
24123260104280107.7%147141.3%0.0%0.0%280107.7%127122.1%
VAV 4-220.640.93162064886653.5%00%1736107%00%1615100%673104%
2400b140516221252.3%0.0%38093.8%0.0%35587.7%14992.0%
2400b240516219548.1%0.0%533131.6%0.0%485119.8%209129.0%
2400b340516222355.1%0.0%38895.8%0.0%37692.8%15092.6%
2400b440516223658.3%0.0%435107.4%0.0%39998.5%165101.9%
Reheat coil was blocked by duct insulation
VAV 4-200.690.5728011026494%00%00%00%27799%112102%
2409128011026494.3%0.0%0.0%0.0%27798.9%112101.8%

Page &P of &N

AHU 4 VAV (2)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-170.541.0118015022147119%614122%1959109%49599%1847103%49599%
24111417116520124.7%147126.7%462110.8%120103.4%437104.8%120103.4%
2411241711637088.7%10792.2%34783.2%8674.1%32978.9%8674.1%
24113417116560134.3%159137.1%509122.1%125107.8%484116.1%125107.8%
2411427577345125.5%103133.8%328119.3%82106.5%304110.5%82106.5%
2411527577352128.0%98127.3%313113.8%82106.5%293106.5%82106.5%
Changed max from 2097 to 1800 cfm to allow proper balancing. Found minimum at 500 cfm. Left at this value. Room does not require 850 cfm at minimum.
VAV 4-210.350.3233513530992%0%32296%13399%
2412133513530992.2%0.0%32296.1%13398.5%
VAV 4-230.670.6105042095691%37389%00%00.0%1047100%428102%
2408136514634394.0%13391.1%0.0%0.0%368100.8%153104.8%
Hall236514633291.0%12787.0%0.0%0.0%379103.8%153104.8%
2412332012828187.8%11388.3%0.0%0.0%30093.8%12295.3%
VAV 4-2445518238785.1%184101%481106%00%481106%188103%
2400b126510623187.2%110103.8%286107.9%0.0%286107.9%112105.7%
2400b21907615682.1%7497.4%195102.6%0.0%195102.6%76100.0%

Page &P of &N

AHU 4 VAV (3)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-190.770.71365545126693%53899%133298%00%2299168%53899%
2400b125010023995.6%9898.0%251100.4%0.0%472188.8%9898.0%
2400b225010022790.8%9595.0%24598.0%0.0%328131.2%9595.0%
2400b325010021586.0%9797.0%252100.8%0.0%515206.0%9797.0%
2400b425010024196.4%104104.0%22991.6%0.0%336134.4%104104.0%
2400b525010023393.2%9999.0%24196.4%0.0%324129.6%9999.0%
2400b61154611196.5%4597.8%11499.1%0.0%324281.7%4597.8%
VAV 4-250.720.8475150490103%13691%0%32268%13389%
240212257521495.1%5877.3%0.0%322143.1%133177.3%
2402225075276110.4%78104.0%0.0%322128.8%133177.3%
Design max air flow was 375 cfm. Increased to 475 cfm (HVAC request) to help satisify the room during cooling mode. Box is at 100% damper
VAV 4-260.540.2544021538988%00%00%00.0%449102%20394%
2401125012221385.2%0.0%0.0%0.0%24296.8%11392.6%
240121909317692.6%0.0%0.0%0.0%207108.9%9096.8%
VAV 4-270.640.57595203625105%20199%59099%00%625105%20199%
24031320109333104.1%10697.2%31397.8%0.0%333104.1%10697.2%
2403227594292106.2%95101.1%277100.7%0.0%292106.2%95101.1%
VAV 4-280.640.5393037289696%00%00%00%92399%35495%
2400137014835595.9%0.0%0.0%0.0%373100.8%14094.6%
2400237014836297.8%0.0%0.0%0.0%370100.0%14598.0%
240031907617994.2%0.0%0.0%0.0%18094.7%6990.8%

Page &P of &N

AHU 4 VAV (4)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-290.540.481205482108090%00%117397%00%117397%501104%
2400a128011227598.2%0.0%320114.3%0.0%320114.3%130116.1%
2400a232513029590.8%0.0%30292.9%0.0%30292.9%135103.8%
2400a330012025986.3%0.0%27190.3%0.0%27190.3%11999.2%
2400a430012025183.7%0.0%28093.3%0.0%28093.3%11797.5%
VAV 4-310.550.5318707481887101%746100%00%00.0%1887101%746100%
Corridor10000.0%00.0%0.0%0.0%00.0%00.0%
Corridor221084217103.3%7285.7%0.0%0.0%217103.3%7285.7%
Corridor321084213101.4%7791.7%0.0%0.0%213101.4%7791.7%
Corridor421084217103.3%7791.7%0.0%0.0%217103.3%7791.7%
Corridor521084217103.3%8297.6%0.0%0.0%217103.3%8297.6%
Corridor62108420597.6%7791.7%0.0%0.0%20597.6%7791.7%
Corridor72108420497.1%7892.9%0.0%0.0%20497.1%7892.9%
Corridor82108419994.8%8398.8%0.0%0.0%19994.8%8398.8%
Ladies920080210105.0%95118.8%0.0%0.0%210105.0%95118.8%
Mens1020080205102.5%105131.3%0.0%0.0%205102.5%105131.3%
Diffuser 1 was never connected due to a beam in the area. Air flow max was found at 1870 by original balancer (???) left at this value
VAV 4-320.550.73300120361120%140117%00%150125%305102%142118%
23131300120361120.3%140116.7%0.0%150125.0%305101.7%142118.3%
Damper closed to 6% open and airflow at 142 cfm, box will not zero or calibrate correctly
VAV 4-330.80.6270108818303%00%00%00%568210%300278%
2308127010825092.6%0.0%0.0%0.0%0.0%0.0%
VAV 4-340.850.7330012028495%00%00%00%28495%150125%
2306130012028494.7%0.0%0.0%0.0%28494.7%150125.0%
Minimum air flow will not calibrate properly nd box will not zero. Possible controller issue. Found flow tubes off as well.

Page &P of &N

AHU 4 VAV (5)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-370.560.4572529059382%00%66692%00%68494%27796%
231111606411873.8%0.0%13886.3%0.0%14188.1%4875.0%
23112160647647.5%0.0%8452.5%0.0%12880.0%5687.5%
230931355412995.6%0.0%144106.7%0.0%135100.0%57105.6%
2305413554135100.0%0.0%150111.1%0.0%140103.7%58107.4%
2303513554135100.0%0.0%150111.1%0.0%140103.7%58107.4%
Box is at 100%
VAV 4-360.540.47410164677165%214130%26765%210128%39797%178109%
2300120582329160.5%105128.0%13163.9%102124.4%19796.1%87106.1%
2300220582348169.8%109132.9%13666.3%108131.7%20097.6%91111.0%
Corrected VAV size from 6" to 8"
VAV 4-380.540.6825510200%00%00%00%00%00%
2301125510200.0%00.0%00.0%00.0%00.0%00.0%
Unable to calibrate possible controller issue
VAV 4-350.550.5613805521445105%49990%00%00%1445105%51193%
Corridor123092236102.6%8289.1%0.0%0.0%236102.6%8592.4%
Corridor223092237103.0%8390.2%0.0%0.0%237103.0%8592.4%
Corridor323092244106.1%8693.5%0.0%0.0%244106.1%8895.7%
Corridor423092240104.3%8188.0%0.0%0.0%240104.3%8592.4%
Corridor523092244106.1%8592.4%0.0%0.0%244106.1%8188.0%
Corridor623092244106.1%8289.1%0.0%0.0%244106.1%8794.6%

Page &P of &N

AHU 4 VAV (6)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-10.72116046400%00%00%00%00%00%
1405158023200.0%0.0%0.0%0.0%0.0%0.0%
1405258023200.0%0.0%0.0%0.0%0.0%0.0%
Damper motor not working
VAV 4-20.640.61130452106394%453100%00%00.0%1129100%453100%
1401132012831899.4%132103.1%0.0%0.0%329102.8%132103.1%
1400a227010824992.2%111102.8%0.0%0.0%284105.2%111102.8%
1400a327010824691.1%10496.3%0.0%0.0%25594.4%10496.3%
1400a427010825092.6%10698.1%0.0%0.0%26196.7%10698.1%
VAV 4-30.920.9116156461790111%655101%1645102%00.0%1645102%00%
14031552270127.3%25113.6%55100.0%0.0%55100.0%0.0%
1400a2520208600115.4%220105.8%560107.7%0.0%560107.7%0.0%
1400a3520208620119.2%225108.2%560107.7%0.0%560107.7%0.0%
1400a452020850096.2%18588.9%47090.4%0.0%47090.4%0.0%
VAV 4-40.330.4272529072399.7%315109%00%00%723100%315109%
1404119076191100.5%90118.4%0.0%0.0%191100.5%90118.4%
Corridor236514636098.6%150102.7%0.0%0.0%36098.6%150102.7%
1402317068172101.2%75110.3%0.0%0.0%172101.2%75110.3%
VAV 4-70.620.5962024861098%23796%00%00%00%23796%
24091310124330106.5%11592.7%0.0%0.0%0.0%11592.7%
2409131012428090.3%12298.4%0.0%0.0%0.0%12298.4%

Page &P of &N

AHU 4 VAV (7)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-5216086400%00%00%00%00%00%
1400a15402160.0%0.0%0.0%0.0%0.0%0.0%
1400a25402160.0%0.0%0.0%0.0%0.0%0.0%
1400a35402160.0%0.0%0.0%0.0%0.0%0.0%
1400a45402160.0%0.0%0.0%0.0%0.0%0.0%
Unable to measure due to furniture and customers
VAV 4-60.510.491400560132094%55399%137898%00.0%137898%55399%
1400132012830294.4%130101.6%326101.9%0.0%326101.9%130101.6%
1400a2270108276102.2%113104.6%281104.1%0.0%281104.1%113104.6%
1400a327010824891.9%10496.3%26297.0%0.0%26297.0%10496.3%
1400a427010824590.7%10294.4%25092.6%0.0%25092.6%10294.4%
1400a427010824992.2%10496.3%25995.9%0.0%25995.9%10496.3%
VAV 4-80.67206082498648%76292%2070100%00.0%203899%79396%
130313001203110.3%11495.0%26488.0%0.0%301100.3%11696.7%
1303230012017658.7%11797.5%24080.0%0.0%306102.0%124103.3%
13033215862310.7%8295.3%262121.9%0.0%21097.7%8194.2%
1303430012016454.7%10385.8%24381.0%0.0%28193.7%10789.2%
1303521586198.8%7688.4%297138.1%0.0%215100.0%8093.0%
130362158614065.1%7890.7%18586.0%0.0%21399.1%8295.3%
1303730012019063.3%10385.8%26688.7%0.0%28294.0%10890.0%
1303821586243113.0%89103.5%313145.6%0.0%230107.0%95110.5%
Found box with 1197 max and 199 min should be 2060 and 824. Changed to correct values
VAV 4-90.540.6961024454489%383157%752123%311127%630103%253104%
Wait130512226887.9%186152.5%395129.5%151123.8%327107.2%132108.2%
Wait130512227690.5%197161.5%357117.0%160131.1%30399.3%12199.2%
Reset VAV … corrected duct size from 10" to 8" heating valve actuator broken

Page &P of &N

AHU 4 VAV (8)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-100.560.451907518999%79105%00%00%18999%79105%
1302110040102102.0%44110.0%0.0%0.0%102102.0%44110.0%
1304290368796.7%3597.2%0.0%0.0%8796.7%3597.2%
Not zeroed check mode
VAV 4-110.550.66375150442118%00%392105%00%392105%00%
13001375150442117.9%392104.5%392104.5%0.0%
minimum air flow was measured at 242 cfm when the program shows the damper at zero. Box sees 144 cfm cannot calibrate until damper is allowed to close fully
VAV 4-120.770.6363025259995%21083%00%21083.3%59995%270107%
Corridor110542118112.4%44104.8%0.0%3992.9%118112.4%54128.6%
Corridor210542107101.9%42100.0%0.0%43102.4%107101.9%43102.4%
Corridor3105429186.7%2764.3%0.0%3583.3%9186.7%43102.4%
Corridor4105429085.7%3173.8%0.0%2764.3%9085.7%42100.0%
Corridor5105429691.4%3173.8%0.0%3583.3%9691.4%42100.0%
Corridor6105429792.4%3583.3%0.0%3173.8%9792.4%46109.5%
(Check mode) Minimum air flow was measured at 210 cfm when the program shows the damper at zero.
VAV 4-130.710.641800720160689.2%63588%00%00%1855103%718100%
Break132513028186.5%11084.6%0.0%0.0%31998.2%12797.7%
Break232513029189.5%11386.9%0.0%0.0%334102.8%130100.0%
Break332513028688.0%11185.4%0.0%0.0%335103.1%130100.0%
Break432513028688.0%11185.4%0.0%0.0%335103.1%12999.2%
Bath Ent510040100100.0%3690.0%0.0%0.0%119119.0%43107.5%
Ladies62008018190.5%7796.3%0.0%0.0%208104.0%7897.5%
Mens72008018190.5%7796.3%0.0%0.0%205102.5%81101.3%
Locked up after attempt to balance

Page &P of &N

AHU 4 VAV (9)

VAV Diffuser and Grill Test Data
BASELOCATIONWORK ORDER0
SYSTEMAHU 4TESTED BYDATE
ROOM T-STATK factorAIR VOLUMES
RoomVAV DiffTEMP S.P.TEMP ACTP/V. OutAS FOUNDFINALDESIGN CFMAS FOUND CFMTEST #1FINAL AIR VOLUMESROOM TEMP
MAXMINMAX%MIN%MAX%MIN%MAX%MIN%
VAV 4-140.540.8513605441740128%598110%00%00%1406103%598110%
Corridor117068199117.1%5580.9%0.0%0.0%14987.6%5580.9%