BB Correct Patient Privacy Deficiencies 2N/2S Lake City, FL Project # 573A4-18-603
Solicitation number
36C24825R0127
Issued by

About this file

This document is a Pre-Bid Request for Information (RFI) dated June 2, 2025, addressing technical drawing and specification questions for a VA Medical Center patient privacy deficiencies correction project. The RFI contains six specific technical inquiries from potential bidders, with corresponding detailed responses from the Architecture/Engineering (A/E) team. Key responses include providing missing technical sheets (AE709, AE503, AE302), clarifying electrical receptacle symbols (specifically the "T" indicating tamper-resistant outlets), and detailing signage specifications for sign types A through F located on Sheet AE709. The document is part of the pre-solicitation process for Project No. 573A4-18-603 at the Lake City VAMC, which involves renovating approximately 30,000 square feet on the facility's second floor.

View the file

Other files

File Type Posted
36C24825R0127_2 Synopsis.pdf PDF
AE709.pdf PDF
2024 01 29 Drawings Architectural.pdf PDF
2024 01 29 Drawings Fire Protection.pdf PDF
2024 01 29 Drawings Mechanical.pdf PDF
AE503.pdf PDF
2024 01 29 Drawings Plumbing.pdf PDF
Specifications Vol 2.pdf PDF
Specifications Vol 1.pdf PDF
AE302.pdf PDF
2024 01 29 Drawings Electrical.pdf PDF
2024 01 29 Drawings Structural.pdf PDF
Show all 12

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Pre-Bid RFIs June 2, 2025 A/E Responses

573A4-18-603

CORRECT PATIENT PRIVACY DEFICIENCIES

Lake City VAMC

1. Sheet AE709 is missing from the drawing set. Will the VA please provide it?

RESPONSE

A PDF copy of Sheet AE709 is provided with this response.

2. Sheet EP-104 in Rooms 308 and 309, a receptacle symbol with a superscript "T". Please indicate the design intent for this symbol.

RESPONSE

Refer to Sheet E001 under “SYMBOL” and “DESCRIPTION”. These are the left-hand columns on the sheet.

The last sentence in the first note under POWER DEVICES reads: “ "T" INDICATES

TAMPER RESISTANT” .

3. Please provide cross-section details 1/A/503, 2/A503, 3/A503, 4/A503, 5/A503 & 6/A503 noted on sheet AE101.

A PDF copy of Sheet AE503 is provided with this response.

4. Please provide cross section detail 4/A302, 8/AE302, 9/AE302, 9A/A302 & 10/A302 noted on sheet AE101 next to the Equipment storage room A213 on the second floor. Sheet A302 is not included in the plans. Please review and advise.

A PDF copy of Sheet AE302 is provided with this response.

5. Sheet A503 is not included in the plans. Please review and advise.

A PDF copy of Sheet AE503 is provided with this response.

6. Please provide Signage specifications for Key notes: A, B, C, D,E & F noted on the signage plans. No information was provided.

RESPONSE

Sign Types A, B, C, D, E, and F are shown on Sheet AE709. Theses are sign type details 1,2,3,4,5 and 6/AE709.