This architectural drawing (AE302) is a detailed technical document showing wall sections, duct penetration, and rooftop post enclosure details for the VA Medical Center renovation project in Lake City, Florida. The drawing provides precise technical specifications for construction elements including:
Key technical details include wall section configurations for interior and exterior interfaces, duct support framing, window head treatments, rooftop post enclosures, and flashing/membrane installation methods. The drawings specify construction materials such as metal studs, exterior grade plywood, gypsum board, continuous sealant, and metal shrouding. Specific dimensional annotations indicate precise measurements for ceiling heights, clearances, and structural interfaces, supporting the project's comprehensive patient privacy deficiency correction and modernization efforts at the facility.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S502
SECOND OR THIRD FLOOR
THIRD OR FOURTH FLOOR
DUCT SUPPORT
FRAME: SEE STRUCT
DUCT AND
INSULATION SEE
MECHANICAL
DUCT SUPPORT
FRAME: SEE STRUCT
EXIST BRICK WALL
EXIST CLAY TILE WALL
EXIST 5/8" PLASTER
NEW GMS STUDS AND
GWB ONLY AT IDENTIFIED
WINDOW HEAD POCKETS
EXIST CONC FLOOR BEAMS
INTERIOR EXTERIOR
EXIST CONC FLOOR BEAMS
REMOVE AND REPLACE
EXIST BRICK AS REQD.
INFILL WITH MATCHING
BRICK TO A TIGHT FIT.
PROVIDE CLR SEALANT
FOR WATERTIGHT
INSTALLATION (TYP).
REGLET FLASHING, BACKER
ROD AND SEALANT W/
METAL TERMINATION BAR
AND COUNTERFLASHING.
DUCT AND INSULATION
SEE MECHANICAL
PROVDE METAL DUCT
CLOSURE & CONTINUOUS
WATER TIGHT SEAL AS
REQUIRED, 4 SIDES
DRIP EDGE AT BOTTOM SIDE
M A
X D
U C
T C
LE
A
R A
N C
E
1'
4"
8'
" C
E
IL
IN
G
H E
IG
H
T
2"
REGLET FLASHING, BACKER
ROD AND SEALANT W/
METAL TERMINATION BAR
AND COUNTERFLASHING.
M A
X D
U C
T C
LE
A
R A
N C
E
2nd or 3rd FLOOR LINE
DUCT AND INSULATION
SEE MECHANICAL
PROVDE METAL DUCT
CLOSURE & CONTINUOUS
WATER TIGHT SEAL AS
REQUIRED, 4 SIDES
1'
1/
2"
FURRED WALL BEYOND
DRIP EDGE AT BOTTOM SIDE
1'
8"
1'
1/
2"
V
IF
2'
1"
1' - 2"
3"
EXIST STL COPING
OVER EXIST
STONE CAP
CONT MTL CLEAT
FASTENING
5/8" EXT GRADE
PLYWOOD ON 2 1/2"
MTL FRAMING
CONT SEALANT
SS BAND CLAMP MTL SHROUD
STL POST: SEE STRUCT
4" MTL STUDS
5/8" EXT GRADE PLYWOOD
REMOVE EXIST CANT TO
PREFORM NEW WORK
FLASHING MEMBRANE
CUT IN NEW ROOFING TO EXIST
PER MFR RECOMMENDATIONS
1'
1/
2"
M A
X D
U C
T C
LE
A
R A
N C
E
8'-3" TYP WINDOW HD
8'-0" CEILING HEIGHT
PROVIDE 4" CANTS AT
MOD BIT ROOFING
2nd or 3rd FLOOR LINE or TOP/ROOF SLAB
CONT SEALANT
2'-2"
DEMO EXIST CELINGS
WHERE SHOWN ON DEMO
RCP PLANS
2 1/2" GMS FRAMING
4" GMS FRAMING
ACT CEILING:
SEE RCP PLANS EXIST WINDOWS
EXIST BRICK VENEER
SHADED AREAS ARE
ALL EXIST CONSTR
AE302
AE302
AE302
5/8" GWB, TYP
CONT
SEALANT
SS BAND CLAMP
STL POST: SEE STRUCT
4" MTL STUDS
5/8" EXT GRADE PLYWOOD
REMOVE EXIST CANT TO
PREFORM NEW WORK IN
"X" AREA
FLASHING MEMBRANE
CUT IN NEW ROOFING TO
EXIST PER MFR
RECOMMENDATIONS
PROVIDE 4" CANTS AT
MOD BIT ROOFING
EXIST STL
COPING OVER
EXIST STONE
CAP
CONT MTL
CLEAT
FASTENING
5/8" EXT GRADE
PLYWOOD ON 2
1/2" MTL
FRAMING
MTL
SHROUD
TOP/ROOF
1'- 4"
EXISTING
PARAPET CONSTR
BEYOND
CONT
SEALANT
SS BAND
CLAMP
TYP POSITION OF
STL POST IN
FOREGROUND:
SEE STRUCT
MTL "L" FLASHING
WELDED TO EXIST
COPING (EA SIDE)
MEMBRANE
FLASHING
OVER
PLYWOOD
CONT MTL
CLEAT
FASTENING
5/8" EXT GRADE
PLYWOOD ON 2
1/2" MTL
FRAMING
MTL
SHROUD
TOP/ROOF
1'- 4"
EXIST PARAPET
CONSTR
2'- 2"
1'
- 4
EXIST MTL COPING
OVER EXIST STONE
COPING
EXIST CANT
BELOW
NEW CANTS
BELOW AT
MOD BIT
ROOFING
MEMBRANE
FLASHING ON 5/8"
EXT GRADE
PLYWOOD
MTL SHROUD
ABV DASHED
FOR CLARITY
EXIST
ROOFING
SURFACE
BELOW
STL POSTS:
SEE STRUCT
AE302
AE302
CONT TERM BAR
CONT SEALANT
SS BAND CLAMP
MTL SHROUD
STL POST: SEE STRUCT
4" MTL STUDS
5/8" EXT GRADE PLYWOOD
REMOVE EXIST CANT TO
PREFORM NEW WORK
FLASHING MEMBRANE
CUT IN NEW ROOFING
TO EXIST PER MFR
RECOMMENDATIONS
PROVIDE 4" CANTS AT
MOD BIT ROOFING
2nd or 3rd FLOOR LINE or TOP/ROOF SLAB
CONT SEALANT
SHADED AREAS
ARE ALL EXIST
CONSTR
CONT MTL CLEAT
FASTENING
AE302
AE302
AE302
CONT
SEALANT
SS BAND CLAMP
STL POST: SEE STRUCT
4" MTL STUDS
5/8" EXT GRADE PLYWOOD
REMOVE EXIST CANT TO
PREFORM NEW WORK IN
"X" AREA
FLASHING MEMBRANE
CUT IN NEW ROOFING TO
EXIST PER MFR
RECOMMENDATIONS
PROVIDE 4" CANTS AT
MOD BIT ROOFING
CONT MTL
CLEAT
FASTENING
5/8" EXT GRADE
PLYWOOD ON 2
1/2" MTL
FRAMING
MTL
SHROUD
TOP/ROOF
1'- 4"
EXISTING WALL
CONSTR BEYOND
CONT
SEALANT
SS BAND
CLAMP
TYP POSITION OF
STL POST IN
FOREGROUND:
SEE STRUCT
MEMBRANE
FLASHING
OVER
PLYWOOD
CONT MTL
CLEAT
FASTENING
5/8" EXT GRADE
PLYWOOD ON 2
1/2" MTL
FRAMING
MTL
SHROUD
TOP/ROOF
REMOVE EXIST
CANT AS REQD TO
PERFORM THE
WORK
EXIST
BLDG WALL
BEYOND
1'
- 4
EXIST WALL
CONSTR
EXIST CANT
BELOW
MEMBRANE
FLASHING ON 5/8"
EXT GRADE
PLYWOOD
MTL SHROUD
ABV DASHED
FOR CLARITY
EXIST
ROOFING
SURFACE
BELOW
STL POSTS:
SEE STRUCT
1'- 2"
CONT TERM BAR
ALL SHADED AREAS
ARE EXIST CONSTR
AE302
AE302
NEW CANTS
BELOW AT
MOD BIT
ROOFING
EXISTING WINDOW
WINDOW SILL PLATE
5/8" GYP. BOARD ON 2-1/2"
STUD FURRING @ 16" O.C.
FURRING WALL
BEYOND
INTERIOR EXTERIOR
7 3/4"
2"
4"
7' - 10"
8' - 0"
EXISTING WALL
EXISTING WALL
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
CRM JD/DB/EO5/
/2
9:
:0
A
M
WALL SECTIONS AND DETAILS CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
AE302
573A4-18-603
JAN. 29, 2024
3/4" = 1'-0"AE302
9 ELEVATION AT DUCT SUPPORT
1 1/2" = 1'-0"AE302
10 DUCT PENETRATION FLASHING DETAIL ABOVE WINDOWS
1 1/2" = 1'-0"AE302
4 WALL SECTION - WINDOW HEAD AND POSTS AT PARAPETS
1 1/2" = 1'-0"AE302
1 ROOFTOP POST ENCLOSURE SECTION 1
1 1/2" = 1'-0"AE302
2 ROOFTOP POST ENCLOSURE SECTION 2
1 1/2" = 1'-0"AE302
3 PLAN DETAIL 1 - SHROUD AND FRAMING AT ROOFTOP POSTS
1 1/2" = 1'-0"AE302
8 WALL SECTION - POSTS AT PERPENDICULAR WALL
1 1/2" = 1'-0"AE302
5 ROOFTOP POST ENCLOSURE SECTION 3
1 1/2" = 1'-0"AE302
6 ROOFTOP POST ENCLOSURE SECTION 4
1 1/2" = 1'-0"AE302
7 PLAN DETAIL 2 - SHROUD AND FRAMING AT ROOFTOP POSTS
0' 4" 8" 1' - 4" 2'
SCALE: 1-1/2" = 1' - 0"
1 1/2" = 1'-0"AE302
9A WALL SECTION AT EXISTING WINDOW