LIGHTING FIXTURE. ( INDICATES BRACKET, WALL MOUNTED
FIXTURES). UNDERCASE LETTER INDICATES LIGHTING ZONE.
EXIT LIGHTING FIXTURE. ARROW, WHEN USED, INDICATES
DIRECTION. ( INDICATES BRACKET, WALL MOUNTED FIXTURES).
FILLED IN QUADRANT(s) OF SYMBOL INDICATES NUMBER AND
ORIENTATION OF ILLUMINATED FACES. (SEE LEGEND NOTE 4)
SINGLE POLE SWITCH, 20 A, 120/277 V. MOUNT 48" AFF UON.
HOSPITAL GRADE DUPLEX CONVENIENCE RECEPTACLE, 20 A,
125 VAC, MOUNT +18" AFF UON. "WP" INDICATES
WEATHERPROOF OUTLET. "GFI" INDICATES RECEPTACLE WITH
INTERNAL GROUND FAULT PROTECTION. "TV" INDICATES
RECEPTACLE FOR TELEVISION, MOUNT 60" AFF, UON. "E"
INDICATES RECEPTACLE ON EMERGENCY CIRCUIT,
RECEPTACLE MUST BE COLORED RED. "T" INDICATES TAMPER
RESISTANT.
RECEPTACLE AS NOTED ABOVE BUT, MOUNT 48" AFF OR 6"
ABOVE BACKSPLASH OR COUNTER TOP WHERE COUNTER IS
INDICATED. REFER TO DUPLEX CONVENIENCE RECEPTACLE
DEFINITION ABOVE FOR SUBSCRIPT DEFINITIONS.
DESCRIPTIONSYMBOL
LIGHTINGPROVIDE
LOW VOLTAGE DIMMER SWITCH. SUBSCRIPT INDICATES LIGHTING
ZONE (WATTAGE AS REQUIRED TO CONTROL THE FIXTURE(S)
CONNECTED UON.). MOUNT 48" AFF UON. SEE SHEET EL501 FOR
SWITCH CONFIGURATIONS.
POWER DEVICES
SPECIAL PURPOSE RECEPTACLE, MOUNT 46" AFF, UON. (NEMA
CONFIGURATION AS NOTED)
EQUIPMENT CONNECTIONS
EQUIPMENT CONNECTION. FOR MECHANICAL / PLUMBING
EQUIPMENT: DISCONNECT SWITCHES, STARTERS, VFD'S, AND
OTHER REQUIRED COMPONENTS FOR THE OPERATION OF THE
EQUIPMENT SHALL BE FURNISHED BY THE MECHANICAL /
PLUMBING CONTRACTOR. PROVIDE CONDUIT AND WIRING
FROM THE POWER SOURCE TO THE DISCONNECT SWITCH,
FROM THE DISCONNECT SWITCH TO THE STARTER / VFD, AND
FROM THE STARTER / VFD TO THE FINAL EQUIPMENT
CONNECTION.
JUNCTION BOX
DESCRIPTION
DISTRIBUTION
PANELBOARD - 208Y/120V
DRY TYPE TRANSFORMER, SIZE AS INDICATED.
PANELBOARD - 480Y/277V
WIRE, CONDUIT AND RACEWAY
INDICATES A CONDUIT RUN CONCEALED IN CEILING, WALL,
FLOOR, OR ABOVE SUSPENDED CEILING UON.
CONDUIT TURNED DOWN
CONDUIT TURNED UP
MOTOR CONNECTION AS NOTED.
EQUIPMENT TAG - SEE EQUIPMENT CONNECTION SCHEDULE
SHEET EP501.
QUADRUPLEX CONVENIENCE RECEPTACLE MOUNTED IN TWO-
GANG OUTLET BOX - EACH RATED 20A, 125 VOLTS WITH
SINGLE COVER PLATE, MOUNT 18" AFF, UON. REFER TO
DUPLEX CONVENIENCE RECEPTACLE DEFINITION ABOVE FOR
SUBSCRIPT DEFINITIONS.
LIGHTING FIXTURE TYPE, SEE LIGHTING FIXTURE SCHEDULE
ON SHEET EL501.
A
EMERGENCY LIGHTING FIXTURE ( INDICATES BRACKET,
WALL MOUNTED FIXTURES). UNDERCASE LETTER INDICATES
LIGHTING ZONE.
THREE-WAY SWITCH, 20 A, 120/277 V. MOUNT 48" AFF UON.
KEY OPERATED SWITCH. 20 A, 120/277 V. MOUNT 48" AFF UON.
DUAL TECHNOLOGY OCCUPANCY SENSOR CONTROLLER, CEILING
MOUNTED (IR INDICATES INFRARED ONLY, US INDICATES
ULTRASONIC ONLY).
'IR' OR
'US'
FLUSH FLOOR DUPLEX RECEPTACLE, 20 A, 125 VAC
MOTOR RATED SWITCH
DISCONNECT SWITCH. REFER TO EQUIPMENT CONNECTION
SCHEDULE SHEET EP501 FOR SIZE AND TYPE.
OTHERWISE, PROVIDE 600 V IN NEMA 1 ENCLOSURE UON. 3P =
NO. OF POLES, 60 = SWITCH RATING, 40 = FUSE RATING (NF
INDICATES NON-FUSIBLE) (SEE LEGEND NOTE 5)
DISCONNECT SWITCH PROVIDED INTEGRAL WITH EQUIPMENT.
LVD
K
OS
E
J
M
M
T
3P 60
VARIABLE FREQUENCY CONTROLLER CONNECTION (DRIVE
FURNISHED WITH EQUIPMENT)
VFC
DEMO
LVD
K
OS
E
J
M
M
VFC
T
BRANCH CIRCUIT OR FEEDER WIRING IN CONDUIT. NO
LABEL INDICATES 2 #12 CONDUCTORS & 1 #12 GND IN 3/4"
CONDUIT. CONDUIT LARGER THAN 3/4", CONDUCTOR
QUANTITY MORE THAN 3, OR WIRE LARGER THAN #12 SHALL
BE AS INDICATED. (SEE LEGEND NOTE 1)
HOMERUNS TO PANEL. PANEL AND CIRCUIT
DESIGNATIONS AS INDICATED.
L2A-1,3L2A-1,3
AHU-1
LOW VOLTAGE SWITCH. SUBSCRIPT INDICATES LIGHTING
ZONE (WATTAGE AS REQUIRED TO CONTROL THE FIXTURE(S)
CONNECTED, UON. MOUNT 48" AFF UON. SEE SHEET EL501
FOR SWITCH CONFIGURATIONS
LVLV
EXISTING
LVD
K
OS
E
J
M
M
VFC
AHU-1
LV
SYMBOL
PROVIDEDEMOEXISTING
T
L2A-1,3
DUAL TECHNOLOGY OCCUPANCY SENSOR SWITCH, 20 A,
120/277 V. MOUNT 48" AFF UON.
OSOSOS
GROUND BAR
a a a a
DIMMER SWITCH, 20 A, 120/277 V. MOUNT 48" AFF UON.DDD
TELEPHONE OUTLET, MOUNT 18"AFF UON. 'C' INDICATES TO
MOUNT 48" AFF OR 6" ABOVE BACKSPASH OR COUNTER TOP
WHERE COUNTER IS INDICATED.
TELEPHONE AND DATA SYSTEMS (SEE TELECOM OUTLET
FACEPLATE DETAILS, SHEET TT501.)
DESCRIPTION
COMBINATION OUTLET BOX WITH (4)-8 PIN MODULAR JACKS,
QUANTITY AND NETWORK TYPE (TELEPHONE, DATA) AS INDICATED.
'C' INDICATES TO MOUNT 48" AFF OR 6" ABOVE BACKSPASH OR
COUNTER TOP WHERE COUNTER IS INDICATED.
PROVIDEDEMO
CATV OUTLET WITH ONE COAX CABLE AND F-TYPE JACK,
MOUNT 18" AFF UON.
TVTV
EXISTING
TV
SYMBOL
C
C
NURSE CALL PATIENT STATION, MOUNT 54" AFF, UON.NNN
NURSE CALL EMERGENCY PULL CORD, MOUNT 40" AFF, UON.NNN
EEE
NURSE CALL MASTER STATION, MOUNT 60" AFF, UON.NNN
MMM
NURSE CALL DOME LIGHT. ( INDICATES BRACKET, WALL
MOUNTED FIXTURES).
NNN
NURSE CALL BED STATION WITH (2) 3-WAY SWITCHES AND
DIMMERS, MOUNT 40" AFF, UON.
NNN
BBB
SSTV HEADEND EQUIPMENT.CH
ACCESS CONTROL HEADEND EQUIPMENT.PH
NURSE CALL HEADEND EQUIPMENT.NH
CARD READER.CR
SECURITY CAMERA.
ELECTRIC STRIKE.ES
GENERAL
NOTE REFERENCE - TYPICALLY LOCATED ON SAME SHEET
WHERE SYMBOL IS USED, UON.
POINT OF CONNECTION NEW-TO-EXISTING (SEE LEGEND
NOTE 3).
POINT OF DEMOLITION
ROOM NUMBER.101
DARK AND DASHED, OR CROSS HATCHING INDICATES
REMOVE INDICATED DEVICE OR CIRCUIT. (SEE LEGEND
NOTE 6)
XXX FEEDER DESIGNATION. FOR FEEDER SCHEDULE, SEE SHEET
EP701.
PROVIDEDEMOEXISTING
INDICATES AREA NOT IN SCOPE OF WORK.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
ELECTRICAL LEGEND, NOTES AND
ABBREVIATIONS
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
E001
573A4-18-603
JANUARY 29, 2024
A AMPERE
A/C AIR CONDITIONING
AF AMPERE FRAME
AFCI ARC FAULT CIRCUIT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
ASD ADJUSTABLE SPEED DRIVE
AT AMPERE TRIP
ATC AUTOMATIC TEMPERATURE CONTROL
AWG AMERICAN WIRE GAUGE
B.U.G. BACKLIGHT / UPLIGHT / GLARE
BG BELOW GRADE
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CCT CORRELATED COLOR TEMPERATURE
CKT CIRCUIT
CRI COLOR RENDERING INDEX
DAS DISTRIBUTED ANTENNA SYSTEM
DISC SW DISCONNECT SWITCH
DT DRY TYPE
DVP DOMINION ENERGY
DWG DRAWING
EA EACH
EC EMPTY CONDUIT
EF EXHAUST FAN
ELEC ELECTRICAL
EMT ELECTRICAL METALLIC TUBING
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST EXISTING
EXP EXPLOSION PROOF EQUIPMENT
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FMC FLEXIBLE METAL CONDUIT
FT FEET
GFCI GOVERNMENT FURNISHED,
CONTRACTOR INSTALLED
GFGI GOVERNMENT FURNISHED,
GOVERNMENT INSTALLED
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID METAL CONDUIT
HDPE HIGH DENSITY POLYETHYLENE
CONDUIT
HH HANDHOLE
HID HIGH INTENSITY DISCHARGE
HP HORSEPOWER
HPS HIGH PRESSURE SODIUM
IMC INTERMEDIATE METAL CONDUIT
KAIC THOUSAND AMP CAPACITY, RMS
SYMMETRICAL
KCMIL THOUSAND CIRCULAR MILS
KVA KILOVOLT AMPERE
KWH KILOWATT HOUR
LAN LOCAL AREA NETWORK
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LFMC LIQUIDTIGHT FLEXIBLE METAL CONDUIT
LEGEND NOTES
GENERAL NOTES
A. WIRING IN CONDUIT, MINIMUM SIZE ONE-HALF (1/2) INCH WITH LARGER
SIZES AS INDICATED OR REQUIRED BY NEC.
B. WIRE AND CABLE MUST BE #12 AWG MINIMUM.
C. OPENINGS CREATED IN A FIRE OR SMOKE RATED WALL OR FLOOR BY
PROVISION OF ANY ELECTRICAL DEVICE OR CONDUIT, MUST BE SEALED
AFTER THE WORK IS COMPLETED WITH A UL APPROVED FIRE/SMOKE
SEALANT TO RE-ESTABLISH THE PREVIOUS RATING OF THE WALL OR
FLOOR. SEE ARCHITECTURAL PLANS FOR FIRE RATED WALLS/FLOORS
AND THEIR RATING.
D. COORDINATE EXACT LOCATION OF CEILING MOUNTED LIGHTING
FIXTURES AND SPEAKERS WITH ARCHITECTURAL REFLECTED CEILING
PLANS.
1. WIRE AND CONDUIT FOR MOTOR AND EQUIPMENT LOADS MUST BE
CONTINUOUS IN SIZE AND COUNT FROM SOURCE TO FINAL CONNECTION.
SIZE AND COUNT AS INDICATED ON THE CIRCUIT HOMERUN UNLESS
OTHERWISE NOTED.
2. WHERE BRANCH CIRCUIT HOMERUNS ARE LABELED "SPLIT CIRCUIT" (SC),
THE BRANCH CIRCUIT NUMBER INDICATED HAS BEEN USED ON MORE
THAN ONE HOMERUN INDICATOR. ONE CONDUCTOR PER CIRCUIT
BREAKER POLE WITHIN THE PANELBOARD ENCLOSURE. SPLICES
NECESSARY TO COMPLY WITH THIS REQUIREMENT MUST BE MADE IN A
SEPARATE SPLICE BOX OUTSIDE THE PANELBOARD ENCLOSURE.
3. WHERE A NEW-TO-EXISTING CONNECTION IS INDICATED, PROVIDE
MATERIALS AND LABOR REQUIRED TO MAKE THE CONNECTION.
4. BRANCH CIRCUIT WIRING TO EXIT LIGHT FIXTURES AND TO THE BATTERY
INVERTERS WITHIN FIXTURES WITH INTEGRAL BATTERY UNITS MUST BE
UNSWITCHED, CONNECTED AHEAD OF ANY CONTROL SWITCHES.
5. A (*) IN THE FUSE RATING OR TRIP RATING POSITION FOR THIS SYMBOL
INDICATES TO PROVIDE FUSE OR BREAKER TRIP RATING IN
ACCORDANCE WITH MANUFACTURERS RECOMMENDATION.
6. WHERE EQUIPMENT OR DEVICES ARE NOTED AS "REMOVE", REMOVE
CONDUCTORS ASSOCIATED WITH THESE ITEMS TO THE LAST ACTIVE
ITEM ON THE CIRCUIT, OR TO THE BRANCH CIRCUIT BREAKER IF ALL
ITEMS ON THE CIRCUIT ARE REMOVED. REMOVE CONDUITS FOR THESE
CIRCUITS WHERE THEY RUN EXPOSED OR IN CEILING OR FLOOR
PLENUMS. CONDUITS RUN CONCEALED IN WALLS OR FLOOR SLABS
SHALL BE CUT OFF FLUSH WITH SURFACE AND ABANDONED. VOIDS IN
WALLS OR FLOOR SLABS LEFT BY THE REMOVAL OF ELECTRICAL
EQUIPMENT OR CONDUITS MUST BE FILLED WITH NON-SHRINK GROUT
AND FINISHED TO MATCH ADJACENT SURFACES.
ELECTRICAL ABBREVIATIONS
LTG LIGHTING
LTS LUMINAIRE
MC METAL-CLAD CABLE
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MH MANHOLE
MI MINERAL-INSULATED,
METAL-SHEATHED CABLE
MIN MINIMUM
MLO MAIN LUG ONLY
MOCP MAXIMUM OVERCURRENT PROTECTION
MSB MAIN SWITCHBOARD
MT MOUNT
MTD MOUNTED
MTG HT MOUNTING HEIGHT
MV MEDIUM VOLTAGE
N/C NORMALLY CLOSED
N/O NORMALLY OPEN
NAC NOTIFICATION APPLIANCE CIRCUIT
NEC NATIONAL ELECTRICAL CODE
NESC NATIONAL ELECTRICAL SAFETY CODE
NEU NEUTRAL
NF NON FUSIBLE
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NTS NOT TO SCALE
OBI OUTLET BASE INFEED
OC OCCUPANCY SENSOR
P POLE
PBB PRIMARY BONDING BUSBAR
(FORMERLY TELECOMMUNICATIONS
MAIN GROUNDING BUSBAR - TMGB)
PH PHASE
PNL PANEL
PVC RIGID POLYVINYL CHLORIDE CONDUIT
QTY QUANTITY
RCPT,
RECEPT
RECEPTACLE
REQ'D REQUIRED
RFI RADIO FREQUENCY INTERFERENCE
RM ROOM
RMC RIGID METAL CONDUIT
S.E. SERVICE ENTRANCE
S/N SOLID NEUTRAL
SBB SECONDARY BONDING BUSBAR
(FORMERLY TELECOMMUNICATIONS
GROUND BUSBAR - TGB)
SC SPLIT CIRCUIT (SEE LEGEND NOTE 2)
SF SUPPLY FAN
SPD SURGE PROTECTIVE DEVICE
SSTV SECURITY SURVEILLANCE TELEVISION
SW SWITCH
TEL TELEPHONE
TELECOM TELECOMMUNICATIONS
TTB TELEPHONE TERMINAL
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UON UNLESS OTHERWISE NOTED
UP UNDERGROUND PRIMARY POWER
US UNDERGROUND SECONDARY POWER
V VOLTAGE OR VOLTS
VAC VOLTS ALTERNATING CURRENT
VDC VOLTS DIRECT CURRENT
VFD VARIABLE FREQUENCY DRIVE
W WIRE
WH WATER HEATER
WP WEATHERPROOF
X IN SCHEDULES, ITEM NOT APPLICABLE
XFMR TRANSFORMER
Ø PHASE
5452474644
41'
3527262317
D.42
D.70
D.33
D.34
D.35
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
SECOND FLOOR DEMOLITION
PLAN - LIGHTING
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
ED101
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
GENERAL NOTES
3/32" = 1' - 0" 0 5' 10' 20' 40'
SCALE: 3/32" = 1'-0"
F1
SECOND FLOOR DEMOLITION PLAN - LIGHTING
A. COORDINATE ELECTRICAL DEMOLITION WITH ARCHITECTURAL FLOOR PLANS,
DETAILS, ELEVATIONS, STRUCTURAL, MECHANICAL, PLUMBING AND FIRE
PROTECTION DRAWINGS. THE ELECTRICAL CONTRACTOR IS TO ENSURE
THAT ALL AREAS NOT IN THE SCOPE OF THIS DEMOLITION MUST HAVE
SERVICE MAINTAINED OR RECONNECTED TO AN EXISTING PANELBOARD OR
NEW PANELBOARD AS NECESSARY. ALL AREAS OUTSIDE OF THIS SCOPE OF
WORK MUST STAY IN PROPER WORKING ORDER DURING AND AFTER ALL
DEMOLITION IS COMPLETED.
B. ALL EXISTING CEILINGS, WALLS, AND FLOORS TO REMAIN THAT ARE
DISTURBED OR DISFIGURED BY THE ELECTRICAL RENOVATION MUST BE
PATCHED, MENDED, OR REPLACED BY TRADES ACTIVELY PARTICIPATING IN
THIS TYPE OF WORK. RESPONSIBILITY FOR REPAIRS MUST BE COORDINATED
BETWEEN THE GENERAL CONTRACTOR AND ELECTRICAL SUBCONTRACTOR.
VERIFY ALL WALLS REMAINING WITH ARCHITECTURAL DRAWINGS PRIOR TO
DEMOLITION.
C. WHEN REMOVING BRANCH CIRCUITS, REMOVE ALL CONDUCTORS, CONDUIT,
AND BOXES TO SERVING PANELBOARDS OR EXISTING PORTION OF BRANCH
CIRCUIT TO REMAIN WHERE ACCESSIBLE. WHERE IN-ACCESSIBLE, CUT
CONDUIT FLUSH WITH WALL OR FLOOR AND PATCH TO MATCH
SURROUNDING FINISH. PROVIDE BLANK PAINTABLE STAINLESS-STEEL COVER
PLATES WHERE RECESSED JUNCTION BOXES ARE ABANDONED.
D. THE CONTRACTOR SHALL FIELD VERIFY EXACT ROUTINGS OF EXISTING
RACEWAYS AND LOCATIONS OF ALL EXISTING DEVICES AND EQUIPMENT
BEFORE STARTING ANY WORK AND IS TO NOTIFY THE ARCHITECT OF ANY
KNOWN DISCREPANCIES.
E. REMOVE EXISTING ELECTRICAL EQUIPMENT IN THE AREA OF WORK UNLESS
SPECIFICALLY NOTED OTHERWISE. ALL ELECTRICAL DEVICES IN WALLS TO
BE REMOVED MUST BE REMOVED OR RELOCATED AS NOTED. IF NOT SHOWN
ON PLAN, DEVICE MUST BE REMOVED AND RELOCATED. COORDINATE NEW
LOCATION WITH ARCHITECT/OWNER.
F. ALL DEVICES AND EQUIPMENT REMOVED DURING DEMOLITION ARE THE
PROPERTY OF THE OWNER AND MUST BE DISPOSED OF OR STORED AS
DIRECTED BY THE OWNER.
G. WHERE WALL BOXES FOR SWITCHES AND OTHER DEVICES ARE REMOVED IN
WALLS TO REMAIN, CONTRACTOR MUST REMOVE BOX AND CONDUIT TO
ALLOW PATCHING UNDER ARCHITECTURAL.
H. REMOVE ALL EXISTING LIGHT FIXTURES, SWITCHES, FACEPLATES AND
ASSOCIATED BRANCH CIRCUITS BACK TO SERVING PANELBOARD OR
EXISTING BRANCH CIRCUIT TO REMAIN WITHIN AREA OF WORK. WHERE
LIGHT FIXTURES ARE BEING REMOVED FROM EXISTING CIRCUITS FEEDING
LIGHT FIXTURES TO REMAIN, SPLICE AND EXTEND CIRCUITS AS REQUIRED TO
MAINTAIN FULL OPERATION. PROVIDE ADDITIONAL CONDUIT AND WIRING AS
REQUIRED.
I. REMOVE EXISTING EXIT SIGNS, EGRESS LIGHT FIXTURES AND ASSOCIATED
BRANCH CIRCUITRY BACK TO SERVING PANELBOARD OR EXISTING BRANCH
CIRCUITRY TO REMAIN.
J. WHERE RECEPTACLES AND DEVICES ARE BEING REMOVED FROM EXISTING
CIRCUITS FEEDING RECEPTACLES TO REMAIN, SPLICE AND EXTEND CIRCUITS
AS REQUIRED TO MAINTAIN FULL OPERATION. PROVIDE ADDITIONAL CONDUIT
AND CONDUCTORS AS REQUIRED.
K. REMOVE ALL EXISTING CABLING AND DATA OUTLETS IN AREAS UNDERGOING
DEMOLITION. ANY CABLING THAT FEEDS THROUGH THIS AREA SHALL
REMAIN. PROTECT ALL EXISTING SYSTEMS CABLING IN AREAS UNDERGOING
DEMOLITION WHERE SYSTEMS ARE TO REMAIN. ALL EXISTING SYSTEMS
MUST BE RESTORED TO PROPER WORKING ORDER UPON COMPLETION OF
PROJECT.
L. PROVIDE BLANK STAINLESS-STEEL COVER PLATES ON ALL JUNCTION BOXES
NOT INTENDED FOR REUSE.
M. PROVIDE CONDUIT AND CABLE SUPPORTS TO BUILDING STRUCTURE FOR ALL
UNSUPPORTED CONDUIT AND CABLE ABOVE ANY CEILING BEING REMOVED.
SUPPORT AS REQUIRED BY THE CURRENT NATIONAL ELECTRICAL CODE.
PROVIDE COVER PLATES FOR ALL EXISTING UNCOVERED JUNCTION BOXES
ABOVE ANY CEILING BEING REMOVED.
N. ALL EXISTING WIRELESS INTERNET SYSTEM EQUIPMENT, CABLING AND
ANTENNAS MUST REMAIN. WHERE EQUIPMENT IS MOUNTED IN EXISTING
CEILINGS TO BE REMOVED, TEMPORARILY SUPPORT EQUIPMENT ABOVE
CEILING AND REINSTALL IN NEW CEILING. FIELD VERIFY LOCATIONS OF
EXISTING EQUIPMENT.
41'
3527262317
D.42
D.70
D.33
D.34
D.35
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
THIRD FLOOR DEMOLITION PLAN -
LIGHTING
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
ED102
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
GENERAL NOTES
3/32" = 1' - 0" 0 5' 10' 20' 40'
SCALE: 3/32" = 1'-0"
F1
THIRD FLOOR DEMOLITION PLAN - LIGHTING
A. REFER TO SHEET ED101 FOR ALL GENERAL DEMOLITION NOTES.
41'
3527262317
D.42
D.70
D.33
D.34
D.35
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
SECOND FLOOR DEMOLITION
PLAN - POWER/TELECOM
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
ED103
573A4-18-603
JANUARY 29, 2024
SCALE: 3/32" = 1'-0"
F1
SECOND FLOOR DEMOLITION PLAN - POWER/TELECOM
GRAPHIC SCALE(S)
GENERAL NOTES
3/32" = 1' - 0" 0 5' 10' 20' 40'
A. REFER TO SHEET ED101 FOR ALL GENERAL DEMOLITION NOTES.
B. DISCONNECT AND REMOVE ALL NURSE CALL DEVICES AND MAINTAIN FOR
REUSE. DEMOLISH ALL ASSOCIATED CONDUIT AND CABLING BACK TO
SOURCE.
41'
3527262317
D.42
D.70
D.33
D.34
D.35
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
THIRD FLOOR DEMOLITION PLAN -
POWER/TELECOM
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
ED104
573A4-18-603
JANUARY 29, 2024
SCALE: 3/32" = 1'-0"
F1
THIRD FLOOR DEMOLITION PLAN - POWER/TELECOM
GRAPHIC SCALE(S)
GENERAL NOTES
3/32" = 1' - 0" 0 5' 10' 20' 40'
A. REFER TO SHEET ED101 FOR ALL GENERAL DEMOLITION NOTES.
B. DISCONNECT AND REMOVE ALL NURSE CALL DEVICES AND MAINTAIN FOR
REUSE. DEMOLISH ALL ASSOCIATED CONDUIT AND CABLING BACK TO
SOURCE.
27262317
D.70
D.33
D.34
D.35
A.I.I.
BEDROOM
2NB-1
A.I.I.
BEDROOM
2NC-1
CORRIDOR
C2-3
PATIENT
ISOLATION
TLT
2NB-3
BARIATRIC
ISOLATION
TLT
2NA-3
A.I.I. ANTE
ROOM
2NB-2
A.I.I.
BARIATRIC
ANTE ROOM
2NA-2
A.I.I. ANTE
ROOM
2ND-2
A.I.I. ANTE
ROOM
2NC-2
PATIENT
ISOLATION
TLT
2NC-3
PATIENT
ISOLATION
TLT
2ND-3
A.I.I.
BEDROOM
2NE-1
STERILE
SUPPLY
MSD
STAIR #1
S1.2
A.I.I.
BARIATRIC
BEDROOM
2NA-1 NURSE
MANAGER
2NN-1
NURSE
STATION-NORTH
2NN-2
CORRIDOR
C2-4
SOILED
UTILITY RM
A.I.I. ANTE
ROOM
2NE-2
PATIENT
ISOLATION
TLT
2NE-3 A.I.I.
BEDROOM
2NF-1
A.I.I.
BEDROOM
2NJ-1
PATIENT
ISOLATION
TLT
2NJ-3
A.I.I. ANTE
ROOM
2NJ-2
A.I.I. ANTE
ROOM
2NF-2
PATIENT
ISOLATION
TLT
2NF-3
PATIENT
ISOLATION
TLT
2NG-3
A.I.I. ANTE
ROOM
2NG-2
A.I.I. ANTE
ROOM
2NH-2
PATIENT
ISOLATION
TLT
2NH-3
A.I.I.
BEDROOM
2NH-1
A.I.I.
BEDROOM
2NG-1
MED. PREP
2NN-5
STAIR #2
S2.2
PUBLIC
ELEVATOR
LOBBY
C2-1
NOURISH
2NN-4
HAND WASH
ALCOVE
2NN-3
CLEAN
UTILITY RM
ALCOVE
C2-4A
MED. GAS
STORAGE
ONCOLOGY
EXAM
EXISTING
INFUSION
CLINIC
TELECOM
ROOM
EQUIPMENT
STORAGE
A213
CORRIDOR
C2-8A
A1
C1
B1 B1
B1
B3 B3
B2 B2 B2 B2
B3
B3
A1 C1B1
B1
B1
B1
B1
F2
F2
HAC
F2
F2
F2
F2
F2 F2
F2
F2
FAM. TLT
F1
F1
F1 F1
F1 F1 F1 F1 F1 F1 F1
F1
F1
F1
F1
F1
F1
F1
F1
H1 H1 H1 H1 H1
H1H1H1
H1
F1 F1 F1
F1
F2 F2
F2
F1
F2
F2
A1C1
B1
B1 B1
B3 B3
B2B2 B2 B2
B3 B3
B1
B1 B1
B1
B1
A1
C1 C1
A1
B1 B1
B1
B1
B2 B2
C1
A1 B1
B1B1
B1 B1
B3
B3
B2
B2
B3
B3
B1
B1
B1
B1
B1
A1
C1
B1
B1
B1
B1
B1
A1
C1
B2
B2B3
B3
B3
B3
B2
B2
B1B1
B1 B1
B1 A1
C1
F2
F2
F2
F2
F2
F2 F2
F2
F2F2F2
J1 J1
J1J1
B1
B1
F1
F1
F1
F1
F1
F1
F1
B1
X1
X1
X1X1
X1
X1
X1
M A
T C
H
LI
N E
B
C2H-2-1
C2H-2-3
LH-2-1 (SC)
NH-2-1 (SC)
NH-2-3
NH-2-5
NH-2-7 (SC)
D1
D1 a abb c a aa a c b a a c b a
B1a B1 c a a a a b b a a a a c c b a a aa aa aa b c aa a a b c a aa a c b a a a a a a a a a
MD OFFICE
A.I.I
BEDROOM
2ND-1
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
SECOND FLOOR PLAN - LIGHTING -
2 NORTH
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EL101
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
# KEY NOTES
GENERAL NOTES
1/8" = 1' - 0" 0 5' 10' 15' 30'
SCALE: 1/8" = 1'-0"
F3
SECOND FLOOR PLAN - LIGHTING - 2 NORTH
1 LIGHT FIXTURE "A1" HAS (2) SEPARATE LIGHT SOURCES (EXAM AND
AMBIENT). BOTH LIGHT SOURCES TO BE SWITCHED FROM HEADWALL UNIT.
AMBIENT LIGHT SOURCE SHALL BE CONTROLLED AT HEADWALL UNIT AND
DOOR.
2 LIGHT FIXTURE "C1" TO BE CONTROLLED BY HEADWALL UNIT AND AT DOOR.
A. SEE SHEET EL501 FOR LIGHT FIXTURE SCHEDULE AND DETAILS.
41'
D.42
D.70
D.33
D.34
D.35
CLEAN
LINEN
EXISTING
ELECTRICAL
ROOM
MULTI-PURPOSE
ROOM/
STAFF
LOUNGE
CORRIDOR
C2-5
CORRIDOR
C2-8A
FAMILY
LOUNGE
SERVICE
ELEVATOR
LOBBY
C2-2
NOURISH
2SN-4
MED. PREP
2SN-5
NURSE
STATION-SOUTH
2SN-2
CORRIDOR
C2-6
CLEAN
UTILITY RM
MED. GAS
STORAGE
STAFF TLT
204A CORRIDOR
C2-7 SOILED
UTILITY RM
NURSE
ASSIST
MANAGER
2SN-1
STAIR #3
S3.2
STERILE
SUPPLY
MSD
HAC
A.I.I.
BARIATRIC
BEDROOM
2SA-1 BARIATRIC
ISOLATION
TLT
2SA-3
PATIENT
ISOLATION
TLT
2SB-3
A.I.I.
BEDROOM
2SB-1
A.I.I.
BARIATRIC
ANTE ROOM
2SA-2
A.I.I. ANTE
ROOM
2SD-2
PATIENT
ISOLATION
TLT
2SD-3
PATIENT
ISOLATION
TLT
2SC-3
A.I.I. ANTE
ROOM
2SC-2
A.I.I.
BEDROOM
2SC-1
A.I.I.
BEDROOM
2SD-1
A.I.I.
BEDROOM
2SE-1
A.I.I. ANTE
ROOM
2SE-2
PATIENT
ISOLATION
TLT
2SE-3
A.I.I.
BEDROOM
2SH-1 A.I.I.
BEDROOM
2SG-1
PATIENT
ISOLATION
TLT
2SG-3
PATIENT
ISOLATION
TLT
2SF-3
A.I.I.
BEDROOM
2SF-1
A.I.I. ANTE
ROOM
2SF-2
A.I.I. ANTE
ROOM
2SG-2
A.I.I. ANTE
ROOM
2SH-2
A.I.I. ANTE
ROOM
2SJ-2 PATIENT
ISOLATION
TLT
2SJ-3
PATIENT
ISOLATION
TLT
2SH-3
A.I.I.
BEDROOM
2SJ-1
F1
F1
B1
B1
J1
J1
H1
H1 H1
H1
H1H1H1 B1 B1
A.I.I. ANTE
ROOM
2SB-2
A1
C1
B1
B1B1
B3 B3
B2B2B2B2
A1
C1
B3 B3
B1
B1B1
B1 B1
F1
F1
F2
F2
F2
F2
F2F2
F2F2
F1 F1
F1 F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F1
F1
H1H1H1H1
H1
H1H1H1H1
F1F1
F1
F2 F2
F2
F1
F2
F2
A1 C1
B1
B1B1
B3 B3
B2B2B2 B2
A1 C1
B3 B3
B1
B1
B1 B1
B1
A1 C1
B1
B1
B1B1
B3
B3
B2B2
C1
A1
B1 B1
B1
B1 B1
B3
B3
B2
B2
C1
A1
B1B1
B1
B1 B1
B3
B3
B2
B2
C1
A1
B1 B1
B1
B1 B1
B3
B3
B2
B2
C1
A1
B1 B1
B1
B1 B1
B3
B3
B2
B2
B1
F1
F1F1
F1
F1
F1
H1
H1H1
X1
X1
X1
X1
X1
X1
M A
T C
H
LI
N E
A
C2H-2
LH-2
NH-2
C2H-2-2
C2H-2-4
LH-2-1 (SC)NH-2-1 (SC)
NH-2-1 (SC)
NH-2-7 (SC)
FAM. TLT
NH-2-7 (SC) NH-2-9
D1
D1 a a a b c a a a a c b a aa b c a a c ab
B1 a B1 a a a a c b a a c a a b a aa a c b 2 a aa a b c2 a a a a cb2 a a a a a a a a a
NH-2-2
NH-2-4
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
SECOND FLOOR PLAN - LIGHTING -
2 SOUTH
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EL102
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
# KEY NOTES
GENERAL NOTES
1/8" = 1' - 0" 0 5' 10' 15' 30'
SCALE: 1/8" = 1'-0"
F2
SECOND FLOOR PLAN - LIGHTING - 2 SOUTH
1 LIGHT FIXTURE "A1" HAS (2) SEPARATE LIGHT SOURCES (EXAM AND
AMBIENT). BOTH LIGHT SOURCES TO BE SWITCHED FROM HEADWALL UNIT.
AMBIENT LIGHT SOURCE SHALL BE CONTROLLED AT HEADWALL UNIT AND
DOOR.
2 LIGHT FIXTURE "C1" TO BE CONTROLLED BY HEADWALL UNIT AND AT DOOR.
35272623
D.70
EQUIPMENT
STORAGE
STAIR #2
S2.3
TOILET
311A
STAFF
LOUNGE
NURSE
EDUCATOR
SOCIAL
WORKER
TELECOM
ROOM
SERENITY
ROOM
EXISTING
ELECTRICAL
ROOM
LAUNDRY
STAFF
LOUNGE
TOILET
304A
SERVICE
ELEVATOR
LOBBY
C3-2
FAMILY
DINING
ROOM
CORRIDOR
C3-8A
FAMILY TLT.
FAMILY TLT.
H1 H1
H1B1B1
F2
F2
F2
F2
F1
F1
J1
J1
B1 B1
H1H1
H1
F1
F1
B1
B1
B1
B1
F1
F1
F1 F1 F1
F1 F1 F1
F1
F1
F1
F1 F1
F1
F1
F1
F1 F1
F1
X1
X1
X1
NH-3
LH-3
LH-3-1
J1
J1
J1J1
NH-3-1
COORIDOR
C3-8
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
THIRD FLOOR PLAN - LIGHTING CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EL103
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
GENERAL NOTES
1/8" = 1' - 0" 0 5' 10' 15' 30'
SCALE: 1/8" = 1'-0"
F3
THIRD FLOOR PLAN - LIGHTING
CEILING
HANGER
WIRE, TYP.
RECESSED
CAN
LUMINAIRE
ARCHITECTURAL
CEILING GRID
WIRE TIE OR SCREW
BAR HANGER TO
ARCHITECTURAL
CEILING GRID TYP.
LUMINAIRE
BAR
HANGERS
12GA. HANGER WIRE AT
DIAGONAL CORNER
ATTACHED TO
STRUCTURE
ACOUSTICAL
CEILING TILE (TYP)
RECESSED
CAN
LUMINAIRE
ARCHITECUTRAL CEILING GRID
ARCHITECTURAL
CEILING GRID
ARCHITECTURAL
CEILING GRID
ACOUSTICAL
CEILING TILE (TYP)
ARCHITECTURAL
CEILING GRID
CEILING HANGER
WIRE
#12 GA. HANGER WIRE
THROUGH INTEGRAL
GALVANIZED LIPPED STEEL
MOUNTING CHANNEL &
ATTACHED TO STRUCTURE
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING CHANNEL
JUNCTION
BOX
LOCKING
SQUARE
WASHER & NUT
1/4"
SCREW
WIRE TIE THROUGH
MOUNTING CHANNEL
& CROSS BEAM, TYP.
ACOUSTICAL CEILING
TILE (TYP)
ARCHITECTURAL
CEILING GRID
LUMINAIRE. REFER
TO SCHEDULE
FIXTURE WHIP FROM JUNCTION
BOX (6FT. LONG MAX.)
LUMINAIRE. REFER TO
SCHEDULE
LUMINAIRE MANUFACTURER'S EARTHQUAKE
CLIP, (4) PER FIXTURE AT CORNERS. ATTACH
WITH SHEET METAL SCREW
LUMINAIRE SUSPENSION
WIRES (#10 MIN) ATTACHED
TO STRUCTURE (TYP EA.
CORNER)
3 TWIST MINIMUM
(TYP)
EMERGENCY HOT
EMERGENCY NEUTRAL
EMERGENCY LIGHTING LOAD
EMERGENCY
POWER OUT
UL924
TRANSFER
DEVICE
EMERGENCY NEUTRAL
EMERGENCY POWER IN
NORMAL HOT
NORMAL NEUTRAL
NORMAL LIGHTING LOAD
LOCAL CONTROL
DEVICE OR CONTACTOR
NORMAL
POWER SENSE
LEG NORMAL NEUTRAL
NORMAL SWITCH SENSE LEG
NOTE: FOR USE WHERE EMERGENCY
LIGHT FIXTURES ARE CONTROLLED
WITH AND BY A SINGLE NON-
EMERGENCY CONTROL DEVICE.
TO FIRE ALARM ADDRESSABLE RELAY FOR
OCCUPANCY SENSOR OVERRIDE. COORDINATE
WITH FIRE ALARM REQUIREMENTS.
INTEGRAL TO INTERIOR EMERGENCY
LIGHTING FIXTURES AND TO THE CENTRAL
EMERGENCY INVERTER FEEDING EXTERIOR
LIGHTING FIXTURES.
LIGHTING CONTROL SCHEDULE
SPACES DESCRIPTION OF OPERATION
OFFICE/EXAM/CLINIC
LOCAL MANUAL ON WITH DIMMING CONTROL.
AUTO OFF WITHIN 30 MINUTES OF NO OCCUPANCY.
PATIENT ROOM
LOCAL MANUAL ON/OFF WITH DIMMING CONTROL.
LIFE SAFETY OVERRIDE OF EMERGENCY LIGHTS TO FULL OUTPUT ON LOSS OF POWER.
ELECTRICAL/TELECOM LOCAL MANUAL ON/OFF.
CORRIDOR
LOCAL MANUAL ON VIA KEYED SWITCH.
LIFE SAFETY OVERRIDE OF EMERGENCY LIGHTS TO FULL OUTPUT ON LOSS OF POWER.
ANTE ROOM/STORAGE/MED
PREP/NOURISH/LOUNGE/DINING
ROOM/BATHROOM/LAUNDRY
ROOM
LOCAL MANUAL ON.
AUTO OFF WITHIN 30 MINUTES OF NO OCCUPANCY.
NURSE STATION
LOCAL MANUAL ON WITH DIMMING CONTROL.
AUTO OFF WITHIN 30 MINUTES OF NO OCCUPANCY.
LIFE SAFETY OVERRIDE OF EMERGENCY LIGHTS TO FULL OUTPUT ON LOSS OF POWER.
GENERAL NOTE:
A. EMERGENCY LIGHTS SHALL BE CONTROLLED WITH NORMAL LIGHTS VIA A UL924 RELAY. REFER TO DETAIL D4, THIS SHEET.
ON/
OFF ON/
OFF
LOWER
RAISE
SLV SLVD
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
LIGHT FIXTURE SCHEDULE AND
DETAILS
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EL501
573A4-18-603
JANUARY 29, 2024
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER MODEL NO. Lamp CCT CRI
LUMEN
OUTPUT VOLTAGE WATTAGE MOUNTING NOTES
A1 2'X2' LED AMBIENT/EXAM MEDICAL TROFFER FAIL-SAFE MAE-G-2-LD4-277-1HI/HI-40-EDC-AM/80 LED 4000 K 80 3200 lm 277 V 45 W RECESSED
B1 6" LED MEDICAL DOWNLIGHT FAIL-SAFE FLD6C-10-D010-FEU6C-1025-80-40-F6LC-M-1-LI LED 4000 K 80 1000 lm 277 V 10 W RECESSED
B2 6" LED MEDICAL SHOWER DOWNLIGHT FAIL-SAFE FLD6CX-10-D010-FEU6C-1025-80-40-F6LCXS-M-1-LI LED 4000 K 80 1000 lm 277 V 10 W RECESSED
B3 6" LED MEDICAL DOWNLIGHT FAIL-SAFE FLD6C-25-D010-FEU6C-1025-80-40-F6LC-M-1-LI LED 4000 K 80 2500 lm 277 V 33 W RECESSED
C1 3' WALL MOUNT MEDICAL LINEAR FAIL-SAFE MPBL-3-LD4-277-1/LO-1/LO-40-EDC LED 4000 K 80 1400 lm 277 V 20 W WALL 1
D1 24" UNDERCABINET LIGHT HALO HU30ADV24 LED 4000 K 90 630 lm 277 V 11 W SURFACE 2
F1 2'X2' LED TROFFER METALUX 22RTC3440 LED 4000 K 80 3400 lm 277 V 29 W RECESSED
F2 2'X2' LED TROFFER METALUX 22RTC4840 LED 4000 K 80 4800 lm 277 V 38 W RECESSED
H1 4' LED LINEAR NEO-RAY S124DR-S-1020D940-4F0-UNV LED 4000 K 80 4080 lm 277 V 36 W RECESSED
J1 4' LED INDUSTRIAL STRIP METALUX 4SNX-41SL-LC-UNV-L940 LED 4000 K 80 4100 lm 277 V 26 W SURFACE
X1 LED EXIT SIGN SURE-LITES APX6R LED 277 V 1 W SURFACE
NOTES:
1. MOUNT FIXTURE 7'-0" AFF, UON.
2. PROVIDE LIGHT FIXTURE WITH INTEGRAL OCCUPANCY SENSOR.
NOT TO SCALE
B4
DOWNLIGHT MOUNTING - LAY IN CEILING
NOT TO SCALE
D1
EXIT LIGHT MOUNTING - LAY IN CEILING
NOT TO SCALE
B1
LUMINARE MOUNTING - LAY IN CEILING
NOT TO SCALE
D4
UL924 DEVICE AS A BYPASS
NOT TO SCALE
E1
LOW VOLTAGE SWITCH DETAILS
D.70D.33D.34D.35
64-DP-CRH2
64-DP-LSH1
64-DP-EQH1
NH-1
64-SWBDHN
SECTION1
SECTION 2
SECTION 3
ELEC ROOM
1A
A186
EES ROOM
A184
NEW
SUBSTATION
A185
CATS2
LATS EATS
D.70
CWP-2
CWP-1
EQH-2-7,9,11
HT-1
EQL-2-25
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
LOWER LEVEL AND FIRST FLOOR
PLANS - POWER
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EP101
573A4-18-603
JANUARY 29, 2024
SCALE: 1/8" = 1'-0"
F3
FIRST FLOOR - POWER
SCALE: 1/8" = 1'-0"
C4
LOWER LEVEL - POWER
GRAPHIC SCALE(S)
1/8" = 1' - 0" 0 5' 10' 15' 30'
272623
A.I.I. ANTE
ROOM
2NE-2
PATIENT
ISOLATION
TLT
2NE-3
A.I.I.
BEDROOM
2NE-1
PATIENT
ISOLATION
TLT
2ND-3
PATIENT
ISOLATION
TLT
2NC-3
A.I.I. ANTE
ROOM
2NC-2
A.I.I. ANTE
ROOM
2ND-2
A.I.I.
BEDROOM
2NC-1
CORRIDOR
C2-3
SOILED
UTILITY RM
A.I.I.
BEDROOM
2NB-1
PATIENT
ISOLATION
TLT
2NB-3
BARIATRIC
ISOLATION
TLT
2NA-3
A.I.I.
BARIATRIC
ANTE ROOM
2NA-2
A.I.I. ANTE
ROOM
2NB-2
A.I.I.
BARIATRIC
BEDROOM
2NA-1
STERILE
SUPPLY
MSD
STAIR #1
S1.2
HAC
NURSE
MANAGER
2NN-1
NURSE
STATION-NORTH
2NN-2
CORRIDOR
C2-4
MED. GAS
STORAGE
CLEAN
UTILITY RM
ONCOLOGY
EXAM
EXISTING
INFUSION
CLINIC
A.I.I.
BEDROOM
2NF-1
A.I.I.
BEDROOM
2NJ-1
PATIENT
ISOLATION
TLT
2NF-3
A.I.I. ANTE
ROOM
2NF-2
A.I.I. ANTE
ROOM
2NJ-2
PATIENT
ISOLATION
TLT
2NJ-3
PATIENT
ISOLATION
TLT
2NH-3
A.I.I. ANTE
ROOM
2NH-2
A.I.I. ANTE
ROOM
2NG-2
PATIENT
ISOLATION
TLT
2NG-3
A.I.I.
BEDROOM
2NG-1
A.I.I.
BEDROOM
2NH-1
MED. PREP
2NN-5
HAND WASH
ALCOVE
2NN-3
NOURISH
2NN-4
STAIR #2
S2.2
EQUIPMENT
STORAGE
A213
PUBLIC
ELEVATOR
LOBBY
C2-1
CORRIDOR
C2-8A
FAM. TLT
TELECOM
ROOM
D.42
D.70
D.33 D.33
D.34 D.34
D.35 D.35
E
E
E
E
GFI
E
E
E
E
GFI GFI
GFI
GFI
E E
GFI
GFI
GFI
E E
GFI
E E
GFI
GFI
GFI
E E
EE
GFI
GFI
E E
EGFI
WP
AHU-1
EF-1
M A
T C
H
LI
N E
B
C2L-2A-1 C2L-2A-3
NL-2A-1
NL-2A-3
NL-2A-5
C2L-2A-5
NL-2A-7
C2L-2A-7
C2L-2A-9
NL-2A-9
NL-2A-11
NL-2A-13
C2L-2A-15
NL-2A-15
NL-2A-17
C2L-2A-17
E
NL-2A-19 NL-2A-21 NL-2A-23
NL-2A-25
C2L-2A-19 E E
E
E
C2L-2A-21
C2L-2A-23
C2L-2A-25C2L-2A-27
NL-2A-27
C2L-2B-21
NL-2A-31
C2L-2A-29
C2L-2A-31
C2L-2A-33
NL-2A-33
NL-2A-20
NL-2A-22
NL-2A-24
NL-2A-26NL-2A-28
NL-2A-30
C2L-2A-20
NL-2A-32
E
NL-2A-34
NL-2A-35 (SC)
E
C2L-2A-22
E
C2L-2A-24
E
C2L-2A-26
E
C2L-2A-28
E
C2L-2A-30
C2L-2A-32
E
C2L-2A-34E
E C2L-2A-35
E C2L-2A-36
E C2L-2B-1
E
E E
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
E C2L-2B-25
E C2L-2B-27
E
C2L-2B-29
1 E C2L-2B-31 E
C2L-2B-33
E
C2L-2B-35
E
C2L-2B-26
E
C2L-2B-28
1 1
E
C2L-2B-30
AHU-3
EQH-2-1,3,5
DOOR
DOOR
C2L-2B-37
DOOR
DOOR DOOR
C2L-2B-39
DOOR DOOR
C2L-2B-41
DOOR DOOR
C2L-2B-43
NL-2B-25 (SC)
NL-2B-25 (SC)
3 3
NL-2B-27 (SC)
NL-2B-27 (SC)
NL-2B-25 (SC)
NL-2B-27 (SC)
NL-2B-29 (SC)
NL-2B-31 (SC)
NL-2B-29 (SC)
NL-2B-31 (SC)
3 3
NL-2B-10 (SC)
NL-2B-8 (SC)
GFI
GFI
GFI
MD OFFICE
C2L-2A-43
C2L-2A-44
C2L-2A-45
C2L-2A-46
NL-2B-14
WP
T
T
T
T T
T
T
T
T
T T
T
T T
T
T T
T
GFI
ACCESS
CONTROL LL-2-1 (SC)
EF-2
GFI
DH-3
DH-1
EF-9
HWP-5
HWP-3EQL-2-9,11
EQH-2-25,27,29
EQL-2-1,3
EQL-2-5,7
EQH-2-31,33,35
64-SWBDHN-A9
64-SWBDHN-A10
T
4 NL-2B-18 (SC)
NL-2B-18 (SC)
HT-2
HT-3
EQH-2-13
EQL-2-27
C2L-2B-46
C2L-2B-47GFI
C2L-2A-11
C2L-2A-13
AC-1 (2)
WP
WP NL-2B-22
A.I.I
BEDROOM
2ND-1
E T
C2L-2A-48
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
SECOND FLOOR PLAN - POWER - 2
NORTH
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EP102
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
# KEY NOTES
1/8" = 1' - 0" 0 5' 10' 15' 30'
SCALE: 1/8" = 1'-0"
F3
SECOND FLOOR PLAN - POWER - 2 NORTH
1 RECEPTACLE FOR PATIENT LIFT CHARGER. COORDINATE MOUNTING
HEIGHT AND LOCATION WITH MANUFACTURERS' REQUIREMENTS.
2 AUTOMATIC FLUSH VALVE. PROVIDE JUNCTION BOX ABOVE CEILING FOR
CONNECTION.
3 AUTOMATIC FAUCET. PROVIDE JUNCTION BOX ABOVE CEILING FOR
CONNECTION.
4 VAV/CAV CONTROL POWER.
5 INDOOR UNIT POWERED BY OUTDOOR UNIT. CONNECT TO OUTDOOR UNIT
PER MANUFACTURER'S REQUIREMENTS.
6 MOUNT RECEPTACLE TO TOP OF TELECOM RACK.
7 RECEPTACLE MOUNTED TO DESK.
54524746
41'
CORRIDOR
C2-8A
FAMILY
LOUNGE
FAM. TLT
SERVICE
ELEVATOR
LOBBY
C2-2
MULTI-PURPOSE
ROOM/
STAFF
LOUNGE
EXISTING
ELECTRICAL
ROOM
CLEAN
LINEN
STAFF TLT
204A
CLEAN
UTILITY RM
CORRIDOR
C2-6
CORRIDOR
C2-5
NURSE
STATION-SOUTH
2SN-2
NURSE
ASSIST
MANAGER
2SN-1
STAIR #3
S3.2
STERILE
SUPPLY
MSD
A.I.I.
BARIATRIC
BEDROOM
2SA-1
HAC
MED. PREP
2SN-5
NOURISH
2SN-4
MED. GAS
STORAGE
A.I.I.
BEDROOM
2SJ-1
A.I.I.
BEDROOM
2SH-1
PATIENT
ISOLATION
TLT
2SH-3
PATIENT
ISOLATION
TLT
2SJ-3
A.I.I. ANTE
ROOM
2SJ-2
A.I.I. ANTE
ROOM
2SH-2
A.I.I.
BEDROOM
2SG-1
PATIENT
ISOLATION
TLT
2SG-3
A.I.I. ANTE
ROOM
2SG-2
A.I.I. ANTE
ROOM
2SF-2
PATIENT
ISOLATION
TLT
2SF-3
A.I.I.
BEDROOM
2SF-1
SOILED
UTILITY RM
PATIENT
ISOLATION
TLT
2SE-3
A.I.I. ANTE
ROOM
2SE-2
A.I.I.
BEDROOM
2SE-1
A.I.I.
BEDROOM
2SD-1
CORRIDOR
C2-6
PATIENT
ISOLATION
TLT
2SD-3
PATIENT
ISOLATION
TLT
2SC-3
A.I.I.
BEDROOM
2SC-1
A.I.I. ANTE
ROOM
2SC-2
A.I.I. ANTE
ROOM
2SD-2
A.I.I.
BEDROOM
2SB-1
PATIENT
ISOLATION
TLT
2SB-3
BARIATRIC
ISOLATION
TLT
2SA-3
A.I.I.
BARIATRIC
ANTE ROOM
2SA-2
A.I.I. ANTE
ROOM
2SB-2
D.42
D.70
D.33 D.33
D.34 D.34
D.35 D.35
E E
GFI
GFI
EE
GFI
GFI
E E
E E
TVTV
GFI
GFI
GFI
GFI
GFI
GFI
GFI
E E
GFI GFI
GFIGFI
E E E
E E E
E E
E E
E
GFI
LL-2
NH-2
LH-2
C2H-2
C2L-2A
NL-2A
N-XF-2
(BELOW)
C2-XF-2
(ABOVE)
M A
T C
H
LI
N E
A
NL-2A-2
C2L-2A-2 C2L-2A-4
NL-2A-4
C2L-2A-6
NL-2A-6
C2L-2A-8
NL-2A-8
NL-2A-10
NL-2A-12
NL-2A-14
C2L-2A-16
NL-2A-16
NL-2A-18
E
NL-2B
NL-2A-35 (SC)
C2L-2B
E
GFI
GFI
C2L-2B-3
GFI
E
C2L-2B-5
E
C2L-2B-7
E
C2L-2B-9
GFI
E
C2L-2B-11
E
C2L-2B-13
E
C2L-2B-15
E
C2L-2B-17
E C2L-2B-19
NL-2A-29
NL-2A-36
E
C2L-2B-23
C2L-2B-2
C2L-2B-4
C2L-2B-6
C2L-2B-8
NL-2B-1
NL-2B-3
E
C2L-2B-10 C2L-2B-12
C2L-2B-14
C2L-2B-16 NL-2B-5
C2L-2B-18
NL-2B-7
NL-2B-9 NL-2B-11
NL-2B-13
CORRIDOR
C2-7
NL-2B-15
NL-2B-17 NL-2B-19
NL-2B-21
C2L-2B-20
E
C2L-2B-22
NL-2B-23
C2L-2B-24
E
GFI GFI
GFI
GFI
NL-2B-2
NL-2B-6
E
C2L-2B-32
E
C2L-2B-34
E
C2L-2B-36
E 1
C2L-2A-37
EC2L-2A-39
E
C2L-2A-41
E
C2L-2A-38
E
C2L-2A-40
E
C2L-2A-42
EQH-2
DOOR
DOOR
C2L-2B-38
DOOR
DOORDOOR
C2L-2B-40
DOOR DOOR
C2L-2B-42
DOOR DOOR
C2L-2B-44
NL-2B-33 (SC)
NL-2B-35 (SC)
NL-2B-33 (SC)
NL-2B-35 (SC)
NL-2B-33 (SC)
NL-2B-35 (SC)
NL-2B-4 (SC)
NL-2B-12 (SC)
NL-2B-12 (SC)
NL-2B-4 (SC)
NL-2B-8 (SC)
NL-2B-10 (SC)
NL-2B-10 (SC)
NL-2B-8 (SC)
E
E
EE
T
T
T
T
T
T
T
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
T
T
T
T
T T
T
T GFI
GFI
C2L-2B-45
ACCESS
CONTROL
LL-2-1 (SC)
NL-2B-16
EXIST
LS-XF-2
(ABOVE)
EQ-XF-2
(BELOW)
EQL-2
AHU-2
AHU-4
DH-4
DH-2
HWP-4
HWP-6
EF-10
EQL-2-13,15
EQH-2-2,4,6
EQH-2-8,10,12
EQL-2-17,19
EQL-2-21,23
64-SWBDHN-A11
64-SWBDHN-A12
NL-2B-20 (SC)
NL-2B-20 (SC)
T
GFI
C2L-2A-10
C2L-2A-12
C2L-2A-18 C2L-2A-14
HP-1 (1)EQL-2-2,4
HP-1 (2)
EQL-2-6,8
HP-1 (3)
EQL-2-10,12
AC-1 (1)
NL-2B-24
E
T
C2L-2B-48
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
SECOND FLOOR PLAN - POWER - 2
SOUTH
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EP103
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
# KEY NOTES
1/8" = 1' - 0" 0 5' 10' 15' 30'
SCALE: 1/8" = 1'-0"
F3
SECOND FLOOR PLAN - POWER - 2 SOUTH
1 RECEPTACLE FOR PATIENT LIFT CHARGER. COORDINATE MOUNTING HEIGHT
AND LOCATION WITH MANUFACTURERS' REQUIREMENTS.
2 AUTOMATIC FLUSH VALVE. PROVIDE JUNCTION BOX ABOVE CEILING FOR
CONNECTION.
3 AUTOMATIC FAUCET. PROVIDE JUNCTION BOX ABOVE CEILING FOR
CONNECTION.
4 MED GAS ALARM PANEL. COORDINATE EXACT LOCATION WITH MECHANICAL
CONTRACTOR.
5 VAV/CAV CONTROL POWER.
6 INDOOR UNIT POWERED BY OUTDOOR UNIT. CONNECT TO OUTDOOR UNIT
PER MANUFACTURER'S REQUIREMENTS.
7 RECEPTACLE MOUNTED TO DESK.
D.70
EQUIPMENT
STORAGE
STAIR #2
S2.3
TOILET
311A
STAFF
LOUNGE
NURSE
EDUCATOR
SOCIAL
WORKER
TELECOM
ROOM
SERENITY
ROOM
EXISTING
ELECTRICAL
ROOM
LAUNDRY
STAFF
LOUNGE
TOILET
304A
SERVICE
ELEVATOR
LOBBY
C3-2
FAMILY
DINING
ROOM
CORRIDOR
C3-8A
FAMILY TLT.
FAMILY TLT.
GFI GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
GFI
NH-3
LH-3 LL-3
NL-3
N-XF-3
(BELOW)
NL-3-1
NL-3-3
NL-3-5
NL-3-7
NL-3-9
NL-3-11
NL-3-13
NL-3-15
NL-3-17
NL-3-2
NL-3-4
NL-3-6
NL-3-8
NL-3-10
GFI
GFI
GFI
NL-3-14 (SC)
NL-3-16 (SC)
NL-3-14 (SC)
NL-3-16 (SC)
NL-3-14 (SC)
NL-3-16 (SC)
NL-3-19
C1H-3 C1L-3
EQH-3
EQL-3
EXIST
LS-XF-3
(ABOVE)
C1-XF-3
(ABOVE)
EQ-XF-3
(BELOW)
C1L-3-1
C1L-3-3
C1L-3-5
C1L-3-7
COORIDOR
C3-8
NL-3-18
NL-3-20,22 3
NL-3-21
NL-3-12
ACCESS
CONTROLS
ACCESS
CONTROLS
LL-3-1
T
T
T
T
T
T T
T
T
T
T
T
T
T
T
5-30R
NL-3-23
AC-1 (3)
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
THIRD FLOOR PLAN - POWER CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EP104
573A4-18-603
JANUARY 29, 2024
GRAPHIC SCALE(S)
# KEY NOTES
1/8" = 1' - 0" 0 5' 10' 15' 30'
SCALE: 1/8" = 1'-0"
F3
THIRD FLOOR PLAN -POWER
1 AUTOMATIC FLUSH VALVE. PROVIDE JUNCTION BOX ABOVE CEILING FOR
CONNECTION.
2 AUTOMATIC FAUCET. PROVIDE JUNCTION BOX ABOVE CEILING FOR
CONNECTION.
3 PROVIDE 2#10 AND 1#10 GROUND IN 3/4"C.
4 VAV/CAV CONTROL POWER.
5 INDOOR UNIT POWERED BY OUTDOOR UNIT. CONNECT TO OUTDOOR UNIT
PER MANUFACTURER'S REQUIREMENTS.
6 MOUNT RECEPTACLE TO TOP OF TELECOM RACK.
474644434241'4039
171615131274
D.70
EF-4
EF-8
EF-3
EF-7
EQH-3-1,3,5
EQH-3-13,15,17
EF-5
EQH-3-7,9,11
EF-6
EF-11
EQL-3-1,3
EF-12
EQH-3-19,21,23
HWP-2
HWP-1
EQH-3-25,27,29
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
ROOF PLAN - POWER CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EP105
573A4-18-603
JANUARY 29, 2024
SCALE: 1/8" = 1'-0"
E1
ROOF PLAN - POWER
GRAPHIC SCALE(S)
1/8" = 1' - 0" 0 5' 10' 15' 30'
NOTES:
GROUND-GREEN
BONDING JUMPER CONNECTION
PLASTER RING
DEVICE GROUND
NEUTRAL-WHITE
PHASE B-RED
RACEWAY
4" SQUARE BOX
WIRENUTS (TYPICAL)
STEEL E.M.T. CONNECTOR WITH
NYLON INSULATED THROAT OR
LOCKNUT AS REQUIRED
RACEWAY
PHASE A-BLACK
A. PROVIDE MINIMUM 6" SLACK FOR CONDUCTORS FOR THE PURPOSE OF MAKING UP SPLICES..
B. DO NOT INSTALL WIRES IN BACK OF DEVICE. LOOP AROUND TERMINAL SCREWS.
C. FACE OF PLASTER RING (WHERE UTILIZED) SHALL BE FLUSH WITH WALL.
D. FRONT OF DEVICE SHALL BE WITHIN 1/8" OF FINISHED WALL.
LENGTH
AS
REQUIRED
CONDUIT CLAMP.
SIZE AS
REQUIRED
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
REFER TO PLANS
FOR
QUANTITY & SIZE OF
CONDUITS
NOTES
1. METAL CHANNEL STRUT SUPPORT LONGER THAN THAN 36" SHALL BE
INSTALLED WITH A CENTER SUPPORT ROD.
2. FASTEN THREADED ROD TO STRUCTURE BY APPROVED METHOD PER
SPECIFICATION 26 0533, RACEWAYS AND BOXES FOR ELECTRICAL
SYSTEMS. FIELD VERIFY EXACT CONDITIONS.
3. FOR TRAPEZE INSTALLATIONS IN SEISMIC AREAS COMPLY WITH
SECTION "SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS.
LOCKING SQUARE
WASHER &
LOCKNUT
3/8" MIN
GALVANIZED
THREADED ROD,
TYP.
WASHER
LOCKNUT
INTEGRAL
GALVANIZED
LIPPED STEEL
MOUNTING
CHANNEL
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
EQUIPMENT CONNECTION
SCHEDULE AND DETAILS
CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EP501
573A4-18-603
JANUARY 29, 2024
NOT TO SCALE
F3
RECEPTACLE WIRING DETAIL
NOT TO SCALE
F6
CONDUIT TRAPEZE MOUNTING DETAIL
EQUIPMENT CONNECTION SCHEDULE
EQUIPMENT
DESIGNATION DESCRIPTION
LOAD
RATING (HP,
KW, ETC) FLA MCA MOCP VOLTS PHASE
DISCONNECT SWITCH
FEEDER SIZE NOTES
NO. OF
POLES RATING FUSE SIZE NEMA TYPE
AHU-1 AIR HANDLING UNIT 1 21.5 A 26.9 A 45 A 480 V 3 3 60 A 45 A 3R 3#8, 1#10G, 3/4"C
AHU-2 AIR HANDLING UNIT 2 28.5 A 35.6 A 60 A 480 V 3 3 60 A 60 A 3R 3#6, 1#10G, 3/4"C
AHU-3 AIR HANDLING UNIT 3 21.5 A 26.9 A 45 A 480 V 3 3 60 A 45 A 3R 3#8, 1#10G, 3/4"C
AHU-4 AIR HANDLING UNIT 4 28.5 A 35.6 A 60 A 480 V 3 3 60 A 60 A 3R 3#6, 1#10G, 3/4"C
CWP-1 CHILLED WATER PUMP 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 1 3#6, 1#8G, 3/4"C 1
CWP-2 CHILLED WATER PUMP 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 1 3#6, 1#8G, 3/4"C 1
DH-1 HUMIDIFIER 78 KW 93.8 A 117.3 A 125 A 480 V 3 3 200 A 125 A 3R 3#1, 1#6G, 1 1/2"C
DH-2 HUMIDIFIER 78 KW 93.8 A 117.3 A 125 A 480 V 3 3 200 A 125 A 3R 3#1, 1#6G, 1 1/2"C
DH-3 HUMIDIFIER 78 KW 93.8 A 117.3 A 125 A 480 V 3 3 200 A 125 A 3R 3#1, 1#6G, 1 1/2"C
DH-4 HUMIDIFIER 78 KW 93.8 A 117.3 A 125 A 480 V 3 3 200 A 125 A 3R 3#1, 1#6G, 1 1/2"C
EF-1 EXHAUST FAN 1 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-2 EXHAUST FAN 2 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-3 EXHAUST FAN 3 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-4 EXHAUST FAN 4 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-5 EXHAUST FAN 5 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-6 EXHAUST FAN 6 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-7 EXHAUST FAN 7 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-8 EXHAUST FAN 8 10 HP 14 A 17.5 A 25 A 480 V 3 3 60 A 25 A 3R 3#6, 1#8G, 3/4"C
EF-9 EXHAUST FAN 9 1/2 HP 5.6 A 7.0 A 15 A 208 V 1 2 30 A 15 A 3R 2#12, 1#12G, 1/2"C
EF-10 EXHAUST FAN 10 1/2 HP 5.6 A 7.0 A 15 A 208 V 1 2 30 A 15 A 3R 2#12, 1#12G, 1/2"C
EF-11 EXHAUST FAN 11 1/2 HP 5.6 A 7.0 A 15 A 208 V 1 2 30 A 15 A 3R 2#12, 1#12G, 1/2"C
EF-12 EXHAUST FAN 12 10 HP 14 A 17.5 A 25 A 480 V 3 3 30 A 25 A 3R 3#10, 1#10G, 3/4"C
HP-1 (1) MINI SPLIT SYSTEM 1 11 A 13.8 A 20 A 208 V 1 2 30 A 20 A 3R 2#12, 1#12G, 1/2"C
HP-1 (2) MINI SPLIT SYSTEM 2 11 A 13.8 A 20 A 208 V 1 2 30 A 20 A 3R 2#12, 1#12G, 1/2"C
HP-1 (3) MINI SPLIT SYSTEM 3 11 A 13.8 A 20 A 208 V 1 2 30 A 20 A 3R 2#12, 1#12G, 1/2"C
HT-1 MECHANICAL PIPING HEAT TRACE 1 KW 8.3 A 10.4 A 20 A 120 V 1 1 2#12, 1#12G, 1/2"C
HT-2 MECHANICAL PIPING HEAT TRACE 2.2 KW 7.9 A 9.9 A 20 A 277 V 1 1 2#12, 1#12G, 1/2"C
HT-3 MECHANICAL PIPING HEAT TRACE 0.4 KW 2.9 A 3.6 A 20 A 120 V 1 1 2#12, 1#12G, 1/2"C
HWP-1 HOT WATER PUMP 5 HP 7.6 A 9.5 A 15 A 480 V 3 3 30 A 15 A 1 3#10, 1#10G, 3/4"C 1
HWP-2 HOT WATER PUMP 5 HP 7.6 A 9.5 A 15 A 480 V 3 3 30 A 15 A 1 3#10, 1#10G, 3/4"C 1
HWP-3 HOT WATER PUMP 1 HP 9.2 A 11.5 A 20 A 208 V 1 2 30 A 15 A 3R 3#10, 1#10G, 3/4"C
HWP-4 HOT WATER PUMP 1 HP 9.2 A 11.5 A 20 A 208 V 1 2 30 A 15 A 3R 3#10, 1#10G, 3/4"C
HWP-5 HOT WATER PUMP 1 HP 9.2 A 11.5 A 20 A 208 V 1 2 30 A 15 A 3R 3#10, 1#10G, 3/4"C
HWP-6 HOT WATER PUMP 1 HP 9.2 A 11.5 A 20 A 208 V 1 2 30 A 15 A 3R 3#10, 1#10G, 3/4"C
NOTES:
1. ELECTRICAL CONTRACTOR MUST INSTALL AND MAKE ALL CONNECTIONS TO VFD PROVIDED BY MECHANICAL CONTRACTOR.
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
Date:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
BID DOCUMENTS
590 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 200
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
F ile
P a th
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
Building #64
MBS CMB
PANELBOARD SCHEDULES CORRECT PATIENT PRIVACY
DEFICIENCIES - BLDG 64-UNIT A
LAKE CITY VAMC
Lake City, FL
EP601
573A4-18-603
JANUARY 29, 2024
1. PROVIDE INTERNALLY MOUNTED SPD. 1. LOCATION: RM. 203
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 63.2 B: 63.7 C: 56.3
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: 63.2 B: 63.7 C: 56.3
41 BUSSED SPACE C 15.6 56.3 42
39 BUSSED SPACE B 17.0 61.3 FED VIA XFMR C2-XF-2 (75 KVA) 40
37 BUSSED SPACE A 16.7 60.2 110 * PANEL C2L-2A 38
35 BUSSED SPACE C BUSSED SPACE 36
33 BUSSED SPACE B BUSSED SPACE 34
31 BUSSED SPACE A BUSSED SPACE 32
29 BUSSED SPACE C BUSSED SPACE 30
27 BUSSED SPACE B BUSSED SPACE 28
25 BUSSED SPACE A BUSSED SPACE 26
23 BUSSED SPACE C BUSSED SPACE 24
21 BUSSED SPACE B BUSSED SPACE 22
19 BUSSED SPACE A BUSSED SPACE 20
17 BUSSED SPACE C 20 SPARE 18
15 SPARE 20 B 20 SPARE 16
13 SPARE 20 A 20 SPARE 14
11 SPARE 20 C 20 SPARE 12
9 SPARE 20 B 20 SPARE 10
7 SPARE 20 A 20 SPARE 8
5 SPARE 20 C 20 SPARE 6
3 LTG - NORTHWEST WING 12 20 1.2 0.3 B 0.3 1.2 20 12 LTG - SOUTHWEST WING 4
1 LTG - NORTH WING 12 20 1.5 0.4 A 0.4 1.5 20 12 LTG - SOUTH WING 2
NO. LOAD DESCRIPTION SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE LOAD DESCRIPTION NO.
CKT. WIRE BKR BKR WIRE CKT.
225 AMP MCB 480Y/277 VOLTS 3PH, 4W, 60 HZ MIN. 42 KAIC SURFACE MOUNTED
PANEL C2H-2 SCHEDULE
2. PROVIDE WITH FEED-THRU LUGS.
1. PROVIDE INTERNALLY MOUNTED SPD. 1. LOCATION: RM. 203
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 139.0 B: 141.5 C: 130.0
TOTAL AMPS (FEEDTHRU) A: 74.0 B: 76.5 C: 70.0
TOTAL AMPS (CONN. LOAD) A: 65.0 B: 65.0 C: 60.0
53 SPARE 20 C 20 SPARE 54
51 SPARE 20 B 20 SPARE 52
49 SPARE 20 A 20 SPARE 50
47 SPARE 20 C 0.6 5.0 20 12 COMPUTER REC - RM C2-4 48
45 SERVER RACK REC - RM 201 12 20 5.0 0.6 B 0.6 5.0 20 12 SERVER RACK REC - RM 201 46
43 SERVER RACK REC - RM 201 12 20 5.0 0.6 A 0.6 5.0 20 12 SERVER RACK REC - RM 201 44
41 PATIENT LIFT CHARGER - RM 2SF-1 12 20 1.0 0.1 C 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2SJ-1 42
39 PATIENT LIFT CHARGER - RM 2SE-1 12 20 1.0 0.1 B 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2SH-1 40
37 PATIENT LIFT CHARGER - RM 2SD-1 12 20 1.0 0.1 A 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2SG-1 38
35 COMPUTER REC - RM 2NG-1 12 20 5.0 0.6 C 0.6 5.0 20 12 COMPUTER REC - RM 2NJ-1 36
33 PYXUS MACHINE - RM 2NN-5 12 20 10.0 1.2 B 0.6 5.0 20 12 COMPUTER REC - RM 2NF-1 34
31 REFRIGERATOR - RM 2NN-5 12 20 10.0 1.2 A 0.6 5.0 20 12 COMPUTER REC - RM 2NE-1 32
29 REFRIGERATOR - RM 2NN-4 12 20 10.0 1.2 C 0.6 5.0 20 12 COMPUTER REC - RM 2ND-1 30
27 COMPUTER REC - RM 2NN-2 12 20 5.0 0.6 B 0.6 5.0 20 12 COMPUTER REC - RM 2NA-1 28
25 COMPUTER REC - RM 2NN-2 12 20 5.0 0.6 A 0.6 5.0 20 12 COMPUTER REC - RM 2NC-1 26
23 COMPUTER REC - RM 2NN-2 12 20 5.0 0.6 C 0.6 5.0 20 12 COMPUTER REC - RM 2NB-1 24
21 COMPUTER REC - RM 2NN-2 12 20 5.0 0.6 B 0.6 5.0 20 12 PYXUS MACHINE COMPUTER - RM 2NN-5 22
19 COMPUTER REC - RM 2NN-1 12 20 5.0 0.6 A 0.6 5.0 20 12 COMPUTER REC - RM C2-3 20
17 RECS - RM 2NH-1 12 20 3.0 0.4 C 0.4 3.0 20 12 RECS - RM 2SH-1 18
15 RECS - RM 2NJ-1 12 20 3.0 0.4 B 0.4 3.0 20 12 RECS - RM 2SJ-1 16
13 RECS - RM 2NG-1 12 20 3.0 0.4 A 0.4 3.0 20 12 RECS - RM 2SG-1 14
11 RECS - RM 2NF-1 12 20 3.0 0.4 C 0.4 3.0 20 12 RECS - RM 2SF-1 12
9 RECS - RM 2NE-1 12 20 3.0 0.4 B 0.4 3.0 20 12 RECS - RM 2SE-1 10
7 RECS - RM 2ND-1 12 20 3.0 0.4 A 0.4 3.0 20 12 RECS - RM 2SD-1 8
5 RECS - RM 2NC-1 12 20 3.0 0.4 C 0.4 3.0 20 12 RECS - RM 2SC-1 6
3 RECS - RM 2NA-1 12 20 3.0 0.4 B 0.4 3.0 20 12 RECS - RM 2SA-1 4
1 RECS - RM 2NB-1 12 20 3.0 0.4 A 0.4 3.0 20 12 RECS - RM 2SB-1 2
NO. LOAD DESCRIPTION SIZE TRIP AMPS KVA PH KVA AMPS TRIP SIZE LOAD DESCRIPTION NO.
CKT. WIRE BKR BKR WIRE CKT.
225 AMP MCB 208Y/120 VOLTS 3PH, 4W, 60 HZ MIN. 22 KAIC SURFACE MOUNTED
PANEL C2L-2A SCHEDULE
1. PROVIDE INTERNALLY MOUNTED SPD. 1. LOCATION: RM. 203
PANELBOARD OPTIONS: PANELBOARD NOTES:
TOTAL AMPS (CONN. LOAD + FEED-THRU) A: 74.0 B: 76.5 C: 70.0
TOTAL AMPS (FEEDTHRU) A: B: C:
TOTAL AMPS (CONN. LOAD) A: 74.0 B: 76.5 C: 70.0
53 SPARE 20 C 20 SPARE 54
51 SPARE 20 B 20 SPARE 52
49 SPARE 20 A 20 SPARE 50
47 ACCESS CONTROL HEADEND 12 20 5.0 0.6 C 0.6 5.0 20 12 COMPUTER REC - RM C2-7 48
45 MED GAS ALARM PANEL - RM 2SN-2 12 20 5.0 0.6 B 0.6 5.0 20 12 NURSE CALL HEADEND 46
43 POWERED DOOR - RMS 2NG-1, 2NH-1 12 20 5.0 0.6 A 0.6 5.0 20 12 POWERED DOOR - RMS 2SG-1, 2SH-1 44
41 POWERED DOOR - RMS 2NF-1, 2NJ-1 12 20 5.0 0.6 C 0.6 5.0 20 12 POWERED DOOR - RMS 2SF-1, 2SJ-1 42
39 POWERED DOOR - RMS 2NA-1, 2ND-1, 2NE-1 12 20 7.5 0.9 B 0.9 7.5 20 12 POWERED DOOR - RMS 2SA-1, 2SD-1, 2SE-1 40
37 POWERED DOOR - RMS 2NB-1, 2NC-1 12 20 5.0 0.6 A 0.6 5.0 20 12 POWERED DOOR - RMS 2SB-1, 2SC-1 38
35 PATIENT LIFT CHARGER - RM 2NF-1 12 20 1.0 0.1 C 0.2 1.5 20 12 PATIENT LIFT CHARGER - RM 2SA-1 36
33 PATIENT LIFT CHARGER - RM 2NE-1 12 20 1.0 0.1 B 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2SC-1 34
31 PATIENT LIFT CHARGER - RM 2ND-1 12 20 1.0 0.1 A 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2SB-1 32
29 PATIENT LIFT CHARGER - RM 2NA-1 12 20 1.5 0.2 C 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2NJ-1 30
27 PATIENT LIFT CHARGER - RM 2NC-1 12 20 1.0 0.1 B 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2NH-1 28
25 PATIENT LIFT CHARGER - RM 2NB-1 12 20 1.0 0.1 A 0.1 1.0 20 12 PATIENT LIFT CHARGER - RM 2NG-1 26
23 COMPUTER REC -RM 2SN-1 12 20 5.0 0.6 C 0.6 5.0 20 12 COMPUTER REC - RM C2-6 24
21 RECS - RM 2NN-2 12 20 4.5 0.5 B 1.2 10.0 20 12 REFRIGERATOR - RM 210 22
19 COMPUTER REC - RM 2SJ-1 12 20 5.0 0.6 A 1.2 10.0 20 12 REFRIGERATOR - RM 204 20
17 COMPUTER REC - RM 2SH-1 12 20 5.0 0.6 C 1.2 10.0 20 12 REFRIGERATOR - RM 2SN-4 18
15 COMPUTER REC - RM 2SG-1 12 20 5.0 0.6 B 0.4 3.0 20 12 RECS - RM 2SN-5 16
13 COMPUTER REC - RM 2SF-1 12 20 5.0 0.6 A 1.2 10.0 20 12 REFRIGERATOR - RM 2SN-5 14
11 COMPUTER REC - RM 2SE-1 12 20 5.0 0.6 C 0.6 5.0 20 12 PYXUS MACHINE COMPUTER - RM 2SN-5 12
9 COMPUTER REC - RM 2SD-1 12 20 5.0 0.6 B 1.2 10.0 20 12 PYXUS MACHINE - RM 2SN-5 10
7 COMPUTER REC - RM 2SC-1 12 20 5.0 0.6 A 0.6 5.0 20 12 COMPUTER REC - RM 2SN-2 8
5 COMPUTER REC - RM 2SA-1 12 20 5.0 0.6 C 0.6 5.0 20 12 COMPUTER REC - RM 2SN-2 6
3 COMPUTER REC - RM 2SB-1 12 20 5.0 0.6 B 0.6 5.0 20 12 COMPUTER REC - RM 2SN-2 4
1 COMPUTER REC - RM 2NH-1 12 20 5.0 0.6 A 0.6 5.0 20 12 COMPUTER REC - RM 2SN-2 2
NO. LOAD…